1354 Clifford Avenue
P. O. Box 2940
Loves Park, IL 61132-2940
www.tac.com
Application
These sensors provide electronic sensing of room
temperature at wall locations for use with
microprocessor-based energy management systems,
including TAC NETWORK 8000
InspectionInspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
Requirements• Job wiring diagrams
• Tools (not provided):
– Digital Volt-ohm Meter (DVM)
– Room temperature thermometer in °F or °C
– Appropriate screwdriver(s) for cover, terminals and mounting screws
– Appropriate drill and drill bit for mounting screws
– Diagonal wire cutters for removing mounting tabs
• Appropriate screws for mounting to European 1/4 DIN standard electrical box or for
mullion mounting (not provided)
• TS-5711-770, TS-5711-850, TS-57011-770, and TS-57011-850, two mounting screws
provided for mounting to a 2" x 4" conduit box
• Training: Installer must be a qualified, experienced technician.
• Appropriate accessories
Warning:
• Electrical shock hazard! Disconnect power before installation to prevent electrical shock
or equipment damage.
• Make all connections in accordance with the electrical wiring diagram and in
accordance with national and local electrical codes. Use copper conductors only.
Location
Caution:
• Do not locate the temperature sensor near sources of heat or cold, such as lamps,
motors, sunlight, or concealed ducts or pipes. The accuracy of the system may be
affected by the presence of a room temperature gradient or sources of radiant energy.
• Avoid locations where excessive moisture, corrosive fumes, explosive vapors, or
vibration is present.
• NEMA Type 1 devices are intended for indoor use. Conformance to the NEMA Type 1
requirements primarily provides a degree of protection against contact with the
enclosed components.
Locate the temperature sensor on an inside wall, in a position which represents the average
temperature in the room or space. At this location, the sensor should be exposed to
unrestricted air circulation of 30 ft. per minute (9.2 m per minute), minimum. The selected
location should be out of direct sunlight, away from sources of heat or cold, and away from
concealed ducts or pipes. Locate the sensor in accordance with local building codes and
architectural specifications, as required. Typically, temperature sensors are located 4 to 6 ft.
(1.2 to 1.8 m) from floor level.
MountingThe TS-5711-770 and TS-5711-850 series sensors are designed to be mounted only on
American Standard 2" x 4" electrical boxes. The TS-57011-770 and TS-57011-850 series
sensors may be mounted on either American Standard 2" x 4" electrical boxes or European
DIN Standard electrical boxes. The TS-57031 and TS-57031-850 sensors are mullion
mounted. Refer to the mounting dimensions shown in Figure-2 , Figure-3 , Figure-4 , and
Figure-5 , and mount the sensor according to the applicable procedure that follows.
Figure-5 Dimensions for Mullion Mounting TS-57031 and TS-57031-850.
Mounting TS-5711-770 and TS-5711-850 Sensor on American Standard
2" x 4" Electrical Box
1. Remove the cover screw and remove the sensor cover from the base plate (see Figure-
6).
Tab
Mounting Screws (2)
(furnished)
Cover
American Standard
Sensor
Base Plate
Cover
Screw
Electrical Box
Figure-6 Mounting of TS-5711-770 or TS-5711-850 on American Standard 2" x 4"
Electrical Box.
2. Identify the two wires that are to be connected to the sensor. Route these wires to the
electrical box.
3. Strip 1/4" (6mm) of insulation from the ends of the wires.
4. Connect the wires to the screw terminals on the back of the base plate. See the wiring
diagrams in Figure-1 .
5. Using the two mounting screws (#6-32 flathead screws) provided, mount the base plate
onto the electrical box.
Caution:
mounting the sensor base plate onto the electrical box.
6. Dress the wires down and inside the perimeter of the base plate.
7. Reinstall the cover by inserting its top inside edge over the tab of the base plate and
rotating the cover downward. Secure the cover with the cover screw.
To prevent damage to the components, do not use excessive force when
Mounting TS-57011-770 or TS-57011-850 Series Sensor on American
Standard 2" x 4" Electrical Box
1. Remove the sensor cover from the base plate, according to the following:
a. Insert the blade of a small-bladed screwdriver into the cover latch slot in the bottom
of the sensor cover (see Figure-7 ).
Cover Latch Slot
(Insert Screwdriver Blade Here)
Bottom View
Figure-7 Removing Sensor Cover.
b. Gently push upward on the screwdriver to release the cover latch.
c. Rotate the cover away from the base plate while removing the screwdriver from the
cover latch slot.
2. Separate the wall plate from the base plate (see Figure-8 ). The wall plate is snapped
onto the base plate.
3. Identify the two wires that are to be connected to the sensor. Route these wires from
the electrical box and through the wire feedthrough opening near the top of the base
plate.
4. Using the two mounting screws (#6-32 x 5/8" flat head screws) provided, mount the
base plate onto the electrical box.
Note:
No more than 6" (152 mm) of wire should remain under the cover.
5. Strip 1/4" (6 mm) of insulation from the ends of the wires.
Figure-8 Mounting of TS-57011-770 or TS-57011-850 Series on 2" x 4" Electrical Box.
6. Connect the wires to the terminal block on the base plate. See the wiring diagrams in
Figure-1 . When installing a wire in the terminal block, insert the wire from the top side
of the terminal and secure it by tightening the screw located on the front side of the
terminal block.
Caution:
To prevent damage to the components, do not use excessive force when
mounting the sensor base plate onto the electrical box.
7. Dress the wires down and inside the perimeter of the base plate.
8. Snap the wall plate onto the base plate.
9. Reinstall the cover by inserting its top inside edge over the tab on the base plate and
rotating the cover downward. Press the cover to snap it in place.
Mounting TS-57011-770 or TS-57011-850 Series Sensor on European 1/4 DIN
Standard Electrical Box
1. Remove the sensor cover from the base plate, according to the following:
a. Insert the blade of a small-bladed screwdriver into the cover latch slot in the bottom
of the sensor cover (see Figure-7 ).
b. Gently push upward on the screwdriver to release the cover latch.
c. Rotate the cover away from the base plate while removing the screwdriver from the
cover latch slot.
2. Separate the wall plate from the base plate (see Figure-8 ). The wall plate is snapped
onto the base plate. The wall plate may be discarded or used as a cover plate.
3. Using diagonal wire cutters, cut the mounting tabs from the top and bottom of the base
plate (see Figure-9 ).
l
o
o
T
n
D
a
c
i
i
a
r
g
e
o
m
n
a
A
l
C
u
t
t
e
r
s
Diagonal Wire
Cutters
Cut Mounting
Tab Here
Sensing Element
Cut Mounting
Tab Here
Figure-9 Removing Mounting Tabs.
4. Identify the two wires that are to be connected to the sensor. Route these wires from
the electrical box and through the wire feedthrough opening near the top of the base
plate (see Figure-10 ).
Figure-10 Mounting Procedure for European 1/4 DIN Electrical Box.
5. Using two appropriately sized mounting screws (not provided), mount the base plate
onto the 1/4 DIN electrical box.
Note:
No more than 6" (152 mm) of wire should remain under the cover.
6. Strip 1/4" (6 mm) of insulation from the ends of the wires.
7. Connect the wires to the terminal block on the base plate. See the wiring diagrams in
Figure-1 . When installing a wire in the terminal block, insert the wire from the top side
of the terminal and secure it by tightening the screw located on the front side of the
terminal block.
Caution:
To prevent damage to the components, do not use excessive force when
mounting the sensor base plate onto the electrical box.
8. Dress the wires down and inside the perimeter of the base plate.
9. If the wall plate is to be used, snap it onto the base plate.
10. Reinstall the cover by inserting its top inside edge over the tab on the base plate and
rotating the cover downward. Press the cover to snap it in place.
1. Using a 0.062" Allen wrench (tool number N2-4), turn the cover set screw clockwise into
the base plate, to release the sensor cover. Remove the sensor cover. Refer to Figure11 .
Cover
Printed Circuit
Terminal
Block
#6 Mounting Screws (2)
(not furnished)
Board
Hex Nuts (2)
Note: The sensor is provided with the printed circuit
board alread
Sensing
Element
assembled to the base plate.
Base Plate
Cover Setscrew
Figure-11 Mounting Procedure for TS-57031 and TS-57031-850.
Note:
The sensor is provided with the printed circuit board assembled to the base plate.
Sufficient room is provided between the printed circuit board and the base plate, so that
removal of the printed circuit board is not necessary when routing the system wires for
connection to the terminal block.
2. Identify the two wires that are to be connected to the sensor. Route these wires through
the base plate, then around the printed circuit board.
3. Strip 1/4” (6 mm) of insulation from the ends of the wires.
4. Connect the wires to the terminal block on the printed circuit board. Refer to the wiring
diagram in Figure-1.
5. Dress the wires down and into the mounting location.
6. Secure the base plate to the mounting location, using two #6 screws (not provided).
7. Position the tabs of the cover into the corresponding holes on the top of the base plate.
Use a 0.062" Allen wrench (tool number N2-4) to turn the cover set screw
counterclockwise, to secure the sensor cover to the base plate.
• Do not use unshielded sensor cable in the same conduit with 120/240 Vac power
wiring, or in areas with high RFI/EMI generating devices.
• Shielded cable must be used when it is necessary to install the sensor leads in the same
conduit with power wiring, or when it is known that devices generating high RFI/EMI are
near. Ground the shield according to the controller or controlled device manufacturer's
specification.
• For TAC NETWORK 8000 applications, follow the recommended shielding and wiring
practices in the TAC NETWORK 8000 Hardware Installation Practices Manual, F-
23061.
• Do not use the inside of the sensor cover or electrical box as a termination location for
other control circuits.
Wiring connections to the temperature sensor are made during the mounting process. Be
sure to observe the following wiring guidelines:
• Two-conductor twisted pair wires (six turns per foot), Class II, low voltage, are suitable
for the sensor leads.
Use copper conductors only.
• Restrict wiring leads to the shortest practical length. For recommended wiring lengths,
refer to Table-3, below.
Table-3 Typical Sensor Wiring Lengths.
CHECKOUT
MAINTENANCE
FIELD REPAIR
Wire Gage
22150 (46)
181,000 (305)
162,250 (686)
144,000 (1219)
Length of Run (Total Wiring in Loop)
ft. (m)
Use a Digital Volt-ohm Meter (DVM) to measure the resistance between the two field
connection terminals on the temperature sensor (see Figure-1 for terminal identification).
The temperature sensor requires no maintenance. However, the sensor should be
periodically inspected for dirt and for any blockage of the airflow over the elements.
Regular maintenance of the total system is recommended to assure sustained, optimum
performance.
None.
Copyright 2006, TAC
All brand names, trad emarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
F-23837-5
TAC
1354 Clifford Avenue
P.O. Box 2940
Loves Park, IL 61132-2940
www.tac.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.