TC-5231 Series, TC-5232, TC-5241 Series
Low Temperature Thermostats
The TC-5231, TC-5232, and TC-5241 low temperature
thermostats are used to control temperature in air
conditioning or refrigeration systems.
Features:
• 20 ft. (6.1 m) element senses temperature over a large area.
Control responds to coldest one-foot section of the sendor.
• Adjustable setpoint with 5 F degrees (3 C degrees) fixed
differential.
• SPST, SPDT and DPST versions.
• Capillary mounting clips provided.
Model Chart
Model No. Setpoint Range Device Type
TC-5231
Low temp auto
reset
TC-5232 DPST
TC-5241
TC-5242
a
Do not exceed pilot duty rating on one side of switch.
b
Less than 0.5 Amp is not recommended.
c
Full load and locked rotor ratings are suitable for hermetic compressors only.
d
Limit two separate circuit loads with common return to <5885 VA. Only one load may be a motor load.
e
Reset cannot be accomplished until the sensed temperature is at least 5°F above setpoint.
35 to 60qF
(1.7 to 1.5qC)
15 to 55qF
(-9.4 to 12.8qC)
Low tem p manual
reset
e
Electrical
Switch
SPDT
SPDT
1-SPST
Main
N.C.
1-SPST Aux
N.O.
a
d
a
Voltage Vac
b
24
120
c
240
277 ———7.2
b
24
120
c
240
277 ———7.2
b
24
120
c
240
277 ———7.2
120 16 96
c
240
277
120 6 36
208 3.4 20.4
c
240
277
Full Load
Amps
100 16
17 102 720 24208
——10016
24 144 125 24208
100 16
17 102 720 24208
848
—
318
——
Locked
Rotor Amps
—7.2
Pilot
Duty (VA)
125
Non-
Inductive
Amps
—208 9.2 55.2
6
263

TC-5231 Series, TC-5232, TC-5241 Series
DC Ratings for TX-5232 Only.
Volts
120 4.6 46 3 57.5
240 2.3 23 0.5 57.5
600 — — — 57.5
a
FLA — Full Load Amps.
LRA — Locked Rotor Amps.
NIA — Non-Inductive Amps.
PDVA — Pilot Duty VA.
FLA
a
Specifications
Setpoint dial range Dual marked 35 to 60°F (1.7 to 15.5°C). TC-5242: 15 to 55qF (-9.4 to 12.8qC).
Sensing element Vapor pressure type, copper construction.
Response
Differential 5 F degrees (3 C degrees) fixed.
Electrical switch Refer to Model Chart.
Ratings Refer to Model Chart.
Connections Coded screw terminals.
Mounting In any position on
Housing
Environment
Ambient temperature limits
Humidity
Locations NEMA Type 1.
Dimensions
Case
Element 3/32 in. O.D. x 20 ft. length (2.4 mm x 6.1 m). TC-5242 1/8 in. O.D. x 20 ft. length. (3.2 mm x 6.1 m).
Agency Listings
UL 873
CSA Certified for use in Canada by Underwriters Laboratorie
General Instructions Refer to F-25911.
To lowest temperature sensed by any one-foot section of its element. Altitude causes the control to
operate approximately 1°F colder per 1000 ft. of elevation.
any surface not subject to excessive vibration.
Molded gray PVC plastic cover with a zinc-plated steel main enclosure with a 1/2 in. conduit opening.
TC-5242: painted steel housing.
Shipping: -40 to 150qF (-40 to 66qC).
Operating: Must be 5qF (3qC) above setpoint to a maximum of 150qF (66qC) at case.
Thermal sensing element: 300qF (149q
Enclosure: 5 to 95% RH, non-condensing.
Thermal sensing element: 0 to 100% RH.
2-45/64 H x 3-1/2 max. W x 2 max. D in. (69 x 89 x 51 mm). TC-5242: 3-1/4 H x 4 L x 2 D in. (83 x
101 x 51 mm)
Underwriters Laboratories Inc. listed (File # E9429 Category Temperature-indicating and Regulating
Equipment).
LRA
a
C).
a
NIA
s. Canadian standards C22.2 No. 24-93.
PD VA
a
Typical Applications
Figure 1 TC-5231 or TC-5241 Switch Action and Terminal Identification.
264
AC Supply
Earth Ground
Fan
Motor
1
(2)
1 Terminals (2) and (1) close on temperature drop.
(3)
(1)
Temp
Drop
Indication
Circuit

TC-5231 Series, TC-5232, TC-5241 Series
AC Supply
1
L
T
L
T
Indication
Circuit
1 Terminals L-T open on temperature drop.
Fan
Motor
Figure 2 TC-5232 Switch Action and Terminal Identification.
AC Supply
Line 2
Line 1
Indication
Circuit
1 Action on temperature drop.
1
L
L
T
T
M2 Main
M1 Aux
Fan
Motor
Figure 3 TC-5242 Switch Action and Terminal Idenfication Manual Reset.
265