TAC
1354 Clifford Avenue
P. O. Box 2940
Loves Park, IL 61132-2940
www.tac.com
Application
The 2211 Series Pneumatic Room Thermostat is
designed for proportional control of pneumatic devices
and actuators in environmental control systems. These
one-pipe thermostats are force-balanced and utilize an
external restrictor in the supply line. Their design
incorporates a highly sensitive bimetal thermostatic
element and a ball valve for pneumatic feedback, which
ensures accuracy and stability over the entire
operating range.
These thermostats have a serrated thumb wheel for
setpoint adjustment. Models are also available with
preassembled internal dial stops. Thermostat covers
are available in various styles to meet particular
requirements. Cover options include models with a
setpoint scale and a thermometer, a setpoint scale
only, a thermometer only, or blank. An external setpoint
adjustment cover is available on some models, or can
be field-installed on covers where desired.
2211 Series
One-Pipe Pneumatic Room Thermostats
General Instructions
Full Dial Cover Shown
(Covers must be ordered
separately except as noted.)
SPECIFICATIONS
Features
• Factory-calibrated, stainless steel ball-in-seat
provides pneumatic feedback for stable, linear
operation.
• Easy-to-use throttling range adjustment and
recalibration.
• Adjustable (patented) bimetal shows actual
throttling range in both °F and °C. Adjustable 2 to
12 °F (1 to 6.7 °C)
• Leak-proof, self-closing branch gauge tap.
Action: Proportional.
Setpoint Range: 55 to 85 °F (13 to 29 °C).
Throttling Range: 2 to 12 °F adjustable.
Supply Air Pressure: 20 psig.
Maximum Air Pressure: 30 psig.
Main Air Consumption: 30 scim.
Calibration Point: 9 psig branch line pressure when
ambient equals setpoint.
Setpoint Adjustment: Serrated thumbwheel.
Construction:
Mechanical Components, Die cast aluminum, stainless
steel, and glass-filled nylon.
Diaphragm, Fabric-reinforced Neoprene.
Air Lines, Connect to thermostat nipples with
spring-reinforced plastic tubes.
Branch Connections, Equipped with internal fiters.
Environment
Humidity: 5 to 95% relative humidity, non-condensing.
Locations: NEMA Type 1.
Printed in U.S.A. 8/06 © Copyright 2006 TAC All Rights Reserved. F-24574-2
ORDERING DATA
Table-1 Model Chart — Thermostats.
Wholesale
Number
2211-012 T12-301
2211-112
2211-013 T13-301
2211-113
a
These models have factory-installed 20-712 dial stop kits.
Replaces
a
T12-3011
a
T13-3011
Model
Action Description
Direct
Includes (1) 1/4" x 3/16"
barbed coupling, 20-693
tubing, 20-714 wall plate,
20-711 mounting plate, and
Reverse
mounting screws.
Table-2 Model Chart — Thermostat Replacement Kits.
Wholesale
Number
2211-411 T12-301 Direct
2211-412 T13-301 Reverse
Replaces
Model
Action Description
Includes thermostat, 20-714
wall plate, 20-042 mounting
plate, mounting screws,
20-693 tubing and 2890-011
convertible cover.
Table-3 Model Chart — Uni-Kits®.
Wholesale
Number
2211-512
2211-513
Replaces
Model
a
T12-3011 Direct
a
T13-3011 Reverse
Action Description
Includes thermostat with
stops, 21-933 full dial cover
with blank cover conversion,
and 22-022 Conversion Kit.
2211-612 T12-301 Direct
2211-613 T13-301 Reverse
a
These models include factory-installed 20-712 dial stop kits.
Table-4 Covers.
Wholesale
Number
21-923 C1-42
22-923 C1-46
22-1023 C1-48 Euro-white 10 to 30 °C
a
21-928
a
22-928
a
22-1028
21-933 C3-42
22-933 C3-46
22-1033 C3-48 Euro-white 10 to 30 °C
a
21-939
a
22-939
a
22-1039
21-943 C5-42
22-943 C5-46
22-1043 C5-48 Euro-white
21-948 C6-42
22-948 C6-46
22-1048 C6-48 Euro-white
a
21-957
a
22-957
a
22-1057
Replaces
Model
Color Material
Satin Chrome
Markings
Metal
55 to 85 °F
Plastic22-823 C1-47 Beige
C2-42
C2-46
Satin Chrome
C2-47 Beige
a
C2-48 Euro-white
Satin Chrome
Metal
Plastic22-828
Metal
55 to 85 °F
Plastic22-833 C3-47 Beige
C4-42
C4-46
Satin Chrome
C4-47 Beige
a
C4-48 Euro-white 10 to 30 °C
Satin Chrome
Metal
55 to 85 °F
Plastic22-839
Metal
Plastic22-843 C5-47 Beige
Cooler - Warmer Yes No
Satin Chrome
Metal
Plastic22-848 C6-47 Beige
C11-42
C11-46
Satin Chrome
C11-47 Beige
a
C11-48 Euro-white
Metal
Plastic22-857
Dial
Setpoint
Adjustment
Yes
Blank Concealed
Yes
Concealed
None Concealed
Includes thermostat, 22-1033
full dial cover with blank cover
conversion, and 22-023
conversion kit.
Thermometer
No
Yes
(External)
Yes
(External)
2 © Copyright 2006 TAC All Rights Reserved. F-24574-2
Table-4 Covers. (Continued)
Wholesale
Number
a
21-960
a
22-960
a
22-1060
2890-010
2890-011
2890-012
2890-013
a
Thermostat covers with concealed setpoint adjustment, and thermostat cover kits inlude setpoint adjustment cover 21-800 (black) or 21-801 (Euro-white).
Replaces
Model
C14-42
C14-46
C14-47 Beige
a
a
a
a
a
C14-48 Euro-white
Kit
Kit
Kit Beige
Kit Euro-white
Color Material
Satin Chrome
Satin Chrome
Metal
Plastic22-860
Metal
Plastic
Dial
Markings
Blank Concealed
55 to 85 °F
or Blank
10 to 30 °C
or Blank
Setpoint
Adjustment
Yes
or
Concealed
Thermometer
(Internal)
Yes
No
Table-5 Accessories.
Wholesale
Number
20-660 6-441 Cover screw
20-707 10-53 Metal thermostat guard
20-712 10-59 Internal stop kit
20-715 10-62 Clear cover thermostat guard
20-850 — Thermostat mounting plate
20-881 N2-4 Thermostat calibration wrench
20-944 N4-32 1.0 SCFH restrictor tee, copper tubing
21-038 N100-0010
21-039 N100-0005
21-153 N100-2501 In-line 1.0 SCFH restrictor, polyethylene
21-800 10-72 Setpoint adjustment cover (black)
21-801 10-81-48 Setpoint adjustment cover (Euro-white)
21-876 10-76 Opaque cover thermostat guard
22-022 — Thermostat conversion kit
22-023 — Thermostat conversion kit
22-138 MCS-GA Branch tap gauge adaptor
900-002 — Thermostat calibration kit
Replaces
Model
Description
1.0 SCFH restrictor tee, polyethylene
tubing
0.5 SCFH restrictor tee, polyethylene
tubing
TYPICAL APPLICATIONS
(Piping Diagram)
20 psig (nominal)
M
INSTALLATION
Inspection
Inspect the package for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the
package and inspect the device for obvious damage. Return
damaged products.
Requirements
• Tools (not provided):
– Appropriate screwdriver for mounting the thermostat
– 20-881 Thermostat calibration and cover screw
wrench (or 1/16” and 1/4” hex wrenches)
• Training: Installer must be a qualified, experienced
technician
• Appropriate accessories
• Piping diagrams
Location
Caution:
• Do not locate the thermostat near sources of heat or
cold, such as lamps, motors, sunlight, or concealed
ducts or pipes. Doing so will affect the accuracy of the
thermostat.
• Avoid installing the thermostat on outside walls. If such a
location is necessary, mount the thermostat on an
insulated back plate (accessory item).
• Mount thermostats
been finished.
only after the wall surfaces have
M
21-038 Restrictor
2211 Series
One-Pipe Pneumatic
Room Thermostat
Control Valve
Locate the thermostat where it will be exposed to an
unrestricted circulation of air, which represents the average
temperature of the controlled space.
Figure-1 Typical Application.
F-24574-2 © Copyright 2006 TAC All Rights Reserved. 3