TA CMI User Manual

TA-CMI
307 161-50
2004.xx
User Manual
1
TA-CMI Contents
FCC Notification and ETL markings 2
General 3
Unpacking 4
Important information 5
Radio frequency communication 5 Storage recommendations 5 Charging of batteries 5
Keyboard and display 6
Keyboard 6 Symbols 6
Valve setting 7
Starting the instrument 8
Starting the instrument for the first time 8 Normal start of the instrument 9
Connection to measuring points 10
Disconnection from measuring points 12
Measure Valve 14
Entering the valve factor (Kv value) for other valve types 18 Define media 20 Freezing measurements 23
Measure Temperature 24
Save as media temperature 25
Handwheel Setting calculation 26
Calculation of the valve factor (Kv value) for other valve types 29
Instrument Setup and Information 30
Instrument Setup 30 Information 31
Clearing faults, service and calibration 32
Clearing faults 32 Service 3 2 Calibration 32
Technical data 33
Accessories 34
Contents
3
TA-CMI
2
TA-CMI
TA-CMI is a computer programmed measuring instrument. It is a handheld instrument for measuring differential pressure, temperature, and flow through balancing valves in hydronic systems. It consists of a sensor unit and a instrument unit that has been programmed with the TA valve characteristics, which makes it possible to take a direct reading of flow and differen­tial pressures.
The TA-CMI has two main components:
• A sensor unit which contains a piezoresistive pressure sensor, one measurement valve, connections and rechargeable NiMH batteries. The measurement valve has a safety function which protects the sensor from too high differential pressures.
• An instrument unit which contains a micro computer, input touch pad, LCD display and rechargeable NiMH batteries.
The instrument and the sensor units communicate wirelessly or by cable.
= Warning – read the manual.
The TA-CMI can be cleansed with a damped cloth and a lenient cleaning-agent.
General
General
Guarantee
TA-CMI is guaranteed to be free of material or performance defects in normal use and service. The guarantee period is five years, starting from and including the day of delivery. A guarantee period of 180 days applies for repairs and service. This guarantee applies only for the original purchaser and does not include consumable materials or measuring instruments which, in TA´s opinion, have been used incorrectly, have been neglected or have been damaged as a result of accident or abnormal use or handling. Tour & Andersson AB guarantees that its software operates in all significant respects in accordance with its performance specification. TA does not guarantee that its software is fault-free or that it will operate without crashing. TA´s obligations in respect of its guarantee are restricted to full replacement of the purchase cost or cost-free repair or replacement of defective products delivered to a Tour&Andersson AB authorised service centre during the guarantee period, at Tour&Andersson AB's discretion. To claim service under guarantee, either contact the nearest TA authorised service centre or send the product, carriage-paid (FOB) and insured, to the nearest Tour & Andersson AB authorised service centre with a description of the problem. TA does not accept the risk of damage to the product during transport. After repair under guarantee, the product will be returned carriage-paid (FOB) to the purchaser. If TA is of the opinion that the fault has been caused by incorrect use, modifications, accident or abnormal use or handling, we will submit an estimate for the cost of repairs and await approval of this estimate before starting work. After repair, the product will be returned carriage-paid to the customer, after which the customer will be invoiced for the cost of repair and of returning the product (FOB). Note! If the warranty seal is broken or tampered with, this guarantee is null and void.
Guarantee
FCC Notification and ETL markings
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Caution: Changes or modifications of the equipment, not expressly approved by the party responsible for compliance, could void the user´s authority to operate the equipment. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protections against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help. ETL LISTED: Conforms to UL std. 61010B-1: Certified to CAN/CSA std. C22.2 No.1010.1-92
5
TA-CMI
4
TA-CMI
Important information
Important information
Charging of batteries
Radio frequency communication
TA-CMI uses radio frequency to communicate wirelessly between the instrument and sensor units. Always turn off radio communication when there is risk that
TA-CMI disturbs other vital electronic devices, i.e. near medical equipment and implanted cardiac pacemakers, in health care facilities, aircrafts, blasting areas, areas with potentially explosive atmosperes and other areas posted “turn off two-way radio”! You turn off radio communication by setting the radio
channel to “OFF” in the Instrument setup menu (see page 30).
Storage recommendations
• Never leave water in the sensor unit when there is a risk of freezing (i.e. in a car during winter)!
• Storage above 40°C reduces battery life.
Unpacking
Check that these items are delivered.
Unpacking
T
A
-C
M
I
D
o
k
n
r-0
1
/ 2
0
0
3
.0
6
G
B
M
a
n
u
a
l
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
........................
1
S
E
M
a
n
u
a
l
..........................................................
x
x
TA-CMI
1
2
3
4
5
6
7
8
9
10
11
12
1. Instrument unit
2. Sensor unit
3. Case
4. Connection cable
5. Temperature sensor Pt 1000
6. Charger Mascot 9725, 5.0 V
7. Measuring hose, 400 mm red with shut off valve
8. Measuring hose, 400 mm blue
9. Measuring needles
10. Chain for mounting
11. User Manual
12. Calibration certificate
5 hours!
Note! Both the sensor unit and the instrument unit contains batteries that need to be charged. For best charging performance keep the connector clean. The supplied charger from TA must be used!
Following batteries must be used (user not allowed to change batteries): Instrument unit: 3 pcs NiMh type AA/R6 Sensor unit: 2 pcs NiMh type AAA/R03
Warning! Do not open the instrument as this could damage the warranty seal and void your guarantee! See page 2 for further information.
!
TA-CMI
7
TA-CMI
6
Keyboard and display
Keyboard and display
Radio communication between the instrument and sensor unit is on.
Sensor unit battery capacity
Instrument battery capacity
Valve type
Valve setting (number of turns, see next page)
Media
Temperature
Radio communication between the instrument and sensor unit is off.
The sensor unit is connected to the instrument via the cable.
Symbols
These symbols are used in the instrument:
Valve setting
Valve setting
This section shows how you set or determine the number of valve turns on a TA valve.
The valve’s opening position can be read on the digital handwheel.
Closed valve
Valve open to 2.3 turns
Keyboard
(two keys) Functions according to text in display (see picture)
Navigating up/increasing digit or character/changing unit
Navigating down/decreasing digit or character/changing unit
Selecting digit, character or unit to change/go to selected function
Selecting digit, character or unit to change/go to selected function
Go to selected function/confirming settings (Enter)
Turning power to the instrument on and off. Press the start key for at least 2 seconds.
Returning to previous menu (Escape)
TA-CMI
9
TA-CMI
8
5. Press OK.
When the “radio on” symbol is displayed at the top of the LCD, you can disconnect the cable.
6. Select Functions. The main function menu of
the TA-CMI is displayed.
You select different functions from the main function menu by pressing the down (or up) key repeatedly and then pressing Enter on the desired selection.
1. Start the instrument by pressing the start key
for at least 2 seconds.
Normal start of the instrument
Normally you start the instrument according to below.
2. Select Functions. The main function menu of
the TA-CMI is displayed.
You select different functions from the main function menu by pressing the down (or up) key repeatedly and then pressing Enter on the desired selection.
Starting the instrument
1. Start the instrument by pressing the start key
for at least 2 seconds.
2. Navigate to the line corresponding to your language by repeatedly pressing the down (or up) key.
3. Press Enter on the desired selection, e.g. desired selection English.
4. Connect the cable.
Starting the instrument
Starting the instrument for the first time
The first time you use the instrument and after the radio channel has been in “Sleeping” (see page 30), you start the instrument according to below.
Starting the instrument
TA-CMI
11
TA-CMI
10
3. Connect the measuring needles to the measuring points.
Note! The shut off valve on the red measuring hose must be open when measuring.
Connection to measuring points
Risk of burn if the media is hot! Always connect the measuring needles and the measuring hoses to the sensor unit (1 – 2) before connecting the measuring needles to the measuring points (3).
Connection to measuring points
2. Connect the measuring needles to the measuring hoses.
Connection to measuring points
1. Connect the measuring hoses to the sensor unit.
Note! The connections with the red markings on the sensor unit and the measuring hose shall be connected to the pressure test point with the red marking (the test point with the highest pressure). The connections with the blue markings on the sensor unit and the measuring hose shall be connected to the pressure test point with the blue marking (the test point with the lowest pressure).
!