System Sensor ZC20 User Manual

D770-32-00 1 I56-0053-003R
Zonecheck Flow Switch Tester
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Important
This instruction manual contains important information about the instal­lation and operation of a Zonecheck Flow Switch Tester. Purchasers who install waterflow detectors for use by others must leave this manual or a copy of it with the user. Read all instructions carefully before beginning. Follow only those instruc­tions that apply to the model you are installing.
Use Zonecheck Flow Switch Testers in wet-pipe systems only. Do NOT use them in dry pipe, deluge, or preaction systems.
Do not use in potentially explosive atmospheres. Do not allow unused wires to remain exposed.
Principles Of Operation
Retrofit Model
Zonecheck Flow Switch Tester shall mount on any clear steel pipe span of the appropriate nominal size, either in a vertical upflow or horizontal run, between 6and 12from the flow switch. Flow Switch Tester shall consist of a recirculating pump, operating at nominal 110V or 220V as appropriate, two (2) sets of valves and elbows to facilitate the circulation of the water, a System Sensor vane-type waterflow detector, and a key switch to activate the recirculating pump. When activated, the pump shall circulate the water within the sprinkler riser around the waterflow detector vane to simulate the flow of one sprinkler head in operation. The activating key switch shall provide the means to be wired locally to one Flow Switch Tester, or inter­connected with other key switches for group activation. Flow Switch Tester shall be available for manifold and retrofit installation applications.
Manifold Model Specifications
Zonecheck Flow Switch Tester manifold models shall consist of a sched­ule 10 pipe assembly of the appropriate nominal size. Manifold assembly
CAUTION
Specifications
Static Pressure Rating: 175 PSI Operating Temperature Range: 32°F–120°F (0°C–49°C) Compatible Pipe
(Manifold Models): Schedule 10, 2″–4″ diameter
Compatible Pipe
(Retrofit Models): Schedule 10 and 40, 2″–8″ diameter
(50 mm through 200 mm)
Service Use: Inspection, Testing and
Maintenance of Water-Based Fire Protection Systems: NFPA 25; National Fire Alarm Code: NFPA 72
Manifold Assembly Length
(Manifold Models): 25.6(65 cm)
Component Connections:
Manifold Models: Retrofit Models: 2 ea. - 1NPT/25mm 2 ea. - 1NPT/25mm British Standard
British Standard Thread elbows Thread elbows 2 ea. - 25mm British Standard
Thread elbows
Valves: Red: Standard valve
Green: Contains check valve
Warranty: 3 years
shall provide grooved ends for accepting the appropriate grooved connec­tion fittings. Manifold assembly shall include no less than two drain ports with the appropriate drain plugs. Manifold Zonecheck models shall come with the pump, valves, elbows, pipe assembly, drain plugs, and System Sensor waterflow detector pre-assembled.
Manifold Models
Domestic Models with 1
10 V Pump Canadian Models with 110 V Pump
ZC20, ZC25, ZC30, ZC40 ZC20A, ZC25A, ZC30A, ZC40A
Retrofit Models
Domestic Models Canadian Models International Models with 110 V Pump with 110 V Pump with 220 V Pump ZCR20 ZCR20A ZCR20E ZCR25 ZCR25A ZCR25E ZCR30 ZCR30A ZCR30E ZCR40 ZCR40A ZCR40E ZCR60 ZCR60A ZCR60E ZCR80 ZCR80A ZCR80E
Replacement Parts
ZCK-1 Zonecheck 110V Keyswitch ZCK-1E Zonecheck 220V Keyswitch ZCP-110 Zonecheck 110V Pump ZCP-220 Zonecheck 220V Pump
Do NOT install Zonecheck on copper piping.
General Installation Recommendations
Before installing any waterflow-related device, be thoroughly familiar with: NFPA 72: National Fire Alarm Code
NFPA 13: Installation of Sprinkler Systems, Section 3.17 NFPA 25: Inspection, Testing and Maintenance of Sprinkler Systems
CAUTION
Electrical Specifications
Pump Operating Voltages: Domestic/Canadian models:
1.63A@110 V, 60 Hz
International models: .88A@220 V, 50Hz Key Switch Operating Voltage: ZCK-1 110V, 60Hz; ZCK-1E: 220V, 50Hz Key Switch Mounting Options: Includes back box for surface or flush
mounting. For pre-wiring, use a
411/16″ x 411/16″ back box Key Switch Operation Modes: Self-test: Wired locally
Group test: Interconnected Key Switch LED Operation: Ready state: No LED
Test Initiation: Green LED
Flow switch activation: Red LED
Zonecheck pump) on the other. IMPORTANT: There are two Zonecheck valves enclosed with each Retrofit kit: 1.) A ‘Red’-handled valve, which is a standard valve that serves as an inlet valve; and, 2.) A ‘Green’-handled valve, which is an outlet valve that contains a check valve. The valves must be oriented properly for Zonecheck to work correctly. If mounting Zonecheck to a vertical riser, attach the Red valve so that it will be above the pump, as the assembly would appear after installion (See Figure 1 for illustration). If mounting Zonecheck to a horizontal run of pipe, attach the red valve so that it will be down­stream, in relation to the sprinkler system waterflow, from the Zonecheck pump (See Figure 1 also). Attach the mechanical tees (sup­plied by others), ensuring that both tees are parallel to each other and perpendicular to the Zonecheck assembly. Ensure that all joints are tight and set the entire assembly aside.
3. Place the aluminum angle template on the pipe (leg ends contacting pipe surface) locating one edge of the leg where the mechanical tee holes will be drilled. Scribe or draw a pencil line on the pipe the full length of the template. Note: Ensure that both legs of the aluminum template are in complete contact along their entire length with the pipe surface to ensure that the scribed line will run along the center line of the pipe. Failure to follow this step may cause damage to the Zonecheck product or leakage.
4. Measure the center-to-center distance between the mechanical tees and transfer that measured dis­tance to the scribed line on the pipe sur­face. IMPORTANT: Ensure that the markings on the pipe are located so that the stripes on the Zonecheck pump housing will be parallel to the floor after installation (See Figure 1 for installation). Failure to follow this step may result in pump seizure.
5. The Waterflow detector will typically mount to the pipe 90 degrees from the location of the pump, as space permits. To determine the location of the flow switch, scribe a second line parallel to the line made in Step 3 and mark the midpoint between the mechanical tees This intersection line will locate the hole for the waterflow device. Ensure that this location will permit access to both the detector and the Zonecheck assembly. If located on horizontal pipe, ensure that the waterflow detector, once mounted, will be located on the topside of the pipe. Ensure that the intended location does not result in the detector being mounted upside­down, as condensation may collect in the housing and impair the oper­ation of the detector. See Figure 1 for illustration.
6. Refer to the suggested hole size requirements from the mechanical tee manufacturer and the waterflow manufacturer and drill the three holes where marked in Steps 4 & 5. IMPORTANT: Before drilling, verify that the stripes on the Zonecheck pump housing will be parallel to the floor after installation, as noted in Step 4 (See Figure 1 for illustration). When drilling the holes with a hole saw, make certain that the center of the cut does not remain in the pipe. Clean the outside of the pipe to remove dirt, metal chips, and cutting lubricant.
7. Mount the completed Zonecheck assembly to the sprinkler pipe. Secure the U-bolts of the mechanical tees and tighten to manufactur­er’s recommended torque.
8. Remove the waterflow detector from the carton and install on pipe. The direction-of-flow arrow shown on the saddle must match the direction of the waterflow in the pipe. Refer to the manufacturer’s instructions for mounting the waterflow detectors.
9. Refer to the wiring diagram (see Figure 2.) for proper electrical con­nections for stand-alone or multiple unit keyswitch installation.
Other applicable NFPA standards, local codes, and the requirements of the authority having jurisdiction also apply. Failure to follow these directions may prevent the device from reporting the flow of water in the event the associated sprinkler system is activated by a fire. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
1. Mount the Zonecheck Flow Switch Tester where there is adequate clearance for installation and removal and a clear view of it for inspec­tions.
2. When installing a manifold model, locate 6 to 7 feet above the floor to protect from possible damage. When installing a retrofit model, mount between 6and 12from the flow switch.
3. On horizontal runs, orient the Zonecheck Flow Switch Tester on the side of the pipe only. Failure to do so may impair the operation of the Zonecheck pump (see Figure 1). For vertical flow applications, mount the Zonecheck Flow Switch Tester on pipe through which water flows upward. Otherwise, the unit may not operate properly.
4. Mount the Zonecheck Flow Switch Tester at least 6 inches from a fit­ting that changes the direction of water flow and no less than 24 inch­es from a valve or drain.
5. Be sure the direction-of-flow arrow shown on the saddle matches the direction of the waterflow in the pipe.
Before installing a Zonecheck Flow Switch Tester:
1. Contact central monitoring station or appropriate fire safety personnel before installing the Zonecheck Flow Switch Tester.
2. Identify and close tightly the sprinkler system’s zone valve.
3. Close both (Red & Green) Zonecheck valves.
4. Drain the sprinkler zone.
Installation Guidelines
Manifold Model
1. Remove the assembled manifold unit from the carton.
2. Prepare to install the manifold unit to the riser. If mounting the mani­fold unit to a vertical riser, orient the assembly with the red valve above the Zonecheck pump. If mounting the manifold to a horizontal waterflow pipe, orient the assembly with the red valve on the down­stream end of the waterflow pipe (see Figure 1). Verify that the stripes on the Zonecheck pump housing will be parallel to the floor after installation. If Zonecheck will be located on a horizontal pipe, ensure that the waterflow detector, once mounted, will be located on the top­side of the pipe (see Figure 1 for illustration). Ensure that the intend­ed location does not result in the detector being mounted upside down, as water may collect in the housing and impair the operation of the detector.
3. Mount the Schedule 10 pipe (to which the Zonecheck pump and Waterflow Detector are mounted) to the riser using industry-accepted practices in conjunction with applicable NFPA standards, local codes, and the authority having jurisdiction.
4. Refer to the wiring schematic for proper electrical connections for stand-alone or multiple unit keyswitch installation.
Retrofit Model
1. Remove contents from the carton.
2. Assemble the Zonecheck unit. If the mechanical tees used to attach the Zonecheck unit to the sprinkler pipe have a British Standard Pipe Thread (BSPT) outlet, select the elbows contained within the bag marked ‘BSPT/BSPT’. If the mechanical tees have an NPT thread out­let, select the elbows contained within the bag marked ‘NPT/BSPT’ (Note: the embossed ‘A’ on the elbow designates the NPT thread). Choose the appropriate elbows. Connect the BSPT threaded end of the 90-degree elbows to each of the Zonecheck valves, insert the gasket into the valve, and connect each valve to the correct side of the Zonecheck pump. Each valve has a female BSPT threaded end (con­nected to the elbow) on one side and a male union (connected to the
CAUTION
D770-32-00 2 I56-0053-003R
Loading...
+ 2 hidden pages