System Sensor WTP, WTPW User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
SpectrAlert Advance Weatherproof Plate
For use with models WTP and WTPW
SPECIFICATIONS
Operating Temperature: -40° F to 151° F (-40° C to 66° C) Enclosure Rating: Meets NEMA 3R, IP22 rating requirements
WALL PRODUCT LENGTH WIDTH DEPTH FROM WALL
Horn Strobe 6.90˝ 5.90˝ 2.8˝ Including Strobe Lens
Horn 6.90˝ 5.90˝ 1.6˝ Including Horn
Note: This product may only be installed in conjunction with an outdoor SpectrAlert Advance Horn, Strobe or Horn Strobe Models: HRK-R, SRK-R, SRHK-R, SWK-R, SWHK-R, P2RK-R, P2RHK-R, P2WK-R, P2WHK-R, P4RK-R, HRK, SRK, SRK-P, SRHK, SRHK-P, SWK, SWK-P, SWHK, SWHK-P, P2RK, P2RK-P, P2RHK, P2RHK-P, P2WK, P2WK-P, P2WHK, P2WHK-P, P4RK, P4WK (-R models ship minus the outdoor back box, stan-
dard outdoor and -P models ship with an outdoor back box which is not needed when using the weatherproof plate).
Notice: This manual shall be left with the owner/user of this equipment. Note: This product meets NEMA 3R for indoor or outdoor use to provide a
degree of protection against falling dirt, rain, sleet, or snow; and that will be undamaged by the external formation of ice on the enclosure.
GENERAL DESCRIPTION
For installation with SpectrAlert Advance outdoor or outdoor replacement (-R) horns, strobes and horn strobes. This accessory plate allows an outdoor unit to be flush mounted on a number of different surfaces including brick, ce­ramic tile, concrete and masonry brick.. The weatherproof plate is offered in red and white. The weatherproof plate is sold separately from the device.
INSTALLATION:
1. The WTP series of products may be used indoors or outdoors. They must be installed using the proper SpectrAlert Advance K series product. Do not attempt to use weatherproof plates with devices other than those specified for use with this product.
2. Attach device mounting plate to WTP. The WTP is compatible with 4x4x1-1/4” and 2x4x1-1/2” back boxes.
a. Place the device mounting plate on the WTP (See Fig. 1) and secure
using the four #6-32 x 3/8” pan head screws (A).
b. Secure the WTP and device mounting plate assembly to the back box
(See Fig 2) using the two #8-32x2” pan head screws when using a 4x4” back box (B). When using the 2x4” back box (See Fig 3), secure the WTP assembly using the two #6-32x2” pan head screws (C).
c. Tighten screws until the WTP assembly contacts the wall surface
evenly.
3. It is the responsibility of the installer to make sure that all openings and connections are sealed properly. An outdoor rated silicon caulk (not supplied) may be applied around the WTP to fill in around grout tiles or uneven surfaces.
4. Connect field wiring to terminals. Please follow instruction manual sup­plied with the device.
5. Attach the device to the mounting plate by hooking the tabs on the de­vice housing into the grooves on the mounting plate. Then, swing prod­uct into position to engage the pins on the device with the terminals on the mounting plate. Make sure that the tabs on the back are fully engaged with the mounting plate.
6. Secure the device to the WTP (See Fig. 4) by tightening the single mount­ing screw(D) attached to the front of the device housing. For tamper resistance, the captivated screw may be replaced with the Torx screw supplied with the device.
FIGURE 1: WTP AND DEVICE MOUNTING PLATE ASSEMBLY.
A0425-00
I56-3386-002R
SS-110-003 1 I56-3386-002R
FIGURE 2: ASSEMBLY ATTACHMENT TO 4X4” BACK BOX
A0426-00
FIGURE 3: ASSEMBLY ATTACHMENT TO 2X4” BACK BOX
A0427-00
FIGURE 4: INSTALLED DEVICE AND WTP
A0428-00
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed product to be free from defects in materials and
THREE-YEAR LIMITED WARRANTY
workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this product. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defec­tive in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defec­tive units postage prepaid to: System Sensor, Returns Department, RA #__________, 3825
SS-110-003 2 I56-3386-002R ©2009 System Sensor
Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or altera­tions occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Loading...