System Sensor WMSOU-RR-P01, WMSOU-WW-P01, WMSOU-WW-P02, WMSOU-RR-P02, IBSOU-DD-P01 Installation Instructions Manual

...
Terminal Description
Table 1
BASES
Low Profile Base
Deep Base
Waterproof Base
INSTALLATION
If the waterproof option is required then the wall gasket must be fitted behind the deep base, and the sealing o ring fitted after attaching the low profile base.
CONTINUITY SPRING
The sounder base incorporates a continuity spring between terminals 2 and 3. This allows the continuity of the field wiring to be checked without the need for the sounder to be present. Inserting the sounder will disengage the spring. Removing the sounder will close the loop.
ANTI TAMPER LOCK
The sounder base also includes a tamper resistance feature that when activated prevents removal of the unit without the use of a tool.
To activate this feature, carefully, using a pair of small pliers or similar remove the tab section in the wall of the sounder (as shown). Asprung section of the base will now snap into this cavity upon installation of the device. This prevents the device being turned to enable its release. To remove the device once the tamper resistance feature has been activated, place a small bladed screwdriver into the small hole on the side of the unit and push the plastic lever into the hole, away from the sounder. This will allow the sounder to be rotated free of the plastic arm. This feature is non­reversible.
INSTALLATION INSTRUCTIONS FOR WMSOU WALL MOUNTED LOOP POWERED ADDRESSABLE SOUNDERS.
MODELS
Non Isolation - WMSOU-RR-P01 and WMSOU-WW-P01. With Isolation - WMSOU-RR-P02 and WMSOU-WW-P02.
GENERAL
The WMSOU range of sounders is designed to be connected to analogue addressable fire alarm systems. These sounders must only be connected to control panels that use a compatible proprietary analogue addressable communication protocol. These devices receive their power from the loop, and can be controlled via the communication protocol(s). The sounders have three volume levels and 32 tone sets. Models WMSOU­RR-P02 and WMSOU-WW-P02 include in built isolation providing short circuit protection of the loop.
Up to 159 addresses are available. These are selected via the two rotary selector switches. The 'tens' digits go from 0 to 150 (0 to F) and the 'units' from 0 to 9. See address settings on reverse.
Volume setting is selected by SW6 and SW7 of the 8 way DIP switch (see table 1). The appropriate tone set is selected by SW1 to 5 of the 8 way DIP switch (see table 2). The 2nd stage tone (related to the 1st stage tone) is controlled by the fire panel via the protocol.
SPECIFICATIONS
Signalling Line Supply Voltage (non isolation) 15 to 32VDC (24VDC typical) Signalling Line Supply Voltage (isolation) 15 to 28VDC (24VDC typical)
Max current consumption (High Volume Tone 24 @24V) <6.81mA Max Output Power (High Volume Tone1 @24V) 100dB(A) +/- 3dB
Operating temperature range -25 to +70
o
C
Relative humidity up to 95% - non condensing Terminal Connections (See table)
Terminal Size 2.5mm2- maximum IP Rating
With Low profile base IP24 With Waterproof base IP65
SW6 SW7 Volume setting
OFF OFF HIGH OFF ON MEDIUM
ON OFF LOW ON ON LOW
Terminal
Function
T1 Negative T2 Positive in T3 Positive out T4 N/C T5 Shield
Gasket
O-Ring
D800 issue 8
Optional Earth Continuity Link
O-Ring
System Sensor Europe, Units 15-19 Trescott Road, Redditch, Worcestershire, England. B98 7AH.
Sounder Tone Select DIP Switch configuration Table 2
DIMENSIONS
ADDRESS SETTING
To set one of the 159 available addresses for the device use the two rotary selectors located alongside the dip switch unit. The 'tens' digits go from 0 to 15 (0 to F) and the 'units' from 0 to 9.
A= 10 B = 11 C = 12 D = 13 E = 14 F = 15
System Sensor Europe, Units 15-19 Trescott Road, Redditch, Worcestershire, England. B98 7AH.
115mm
109mm
68mm
Sounder Output data, in accordance with EN54-3, is available on Document Ref: D 535.
DIP setting O=Off/1=On SW 1,2,3,4,5
No Pattern
Nominal
Frequency
Switching
Frequency
Description Standard
2nd
Stage
Tone
0,0,0,0,0 1 Alternating 554/440
2Hz
(100mS/400mS)
French Fire Sound
AFNOR
NFS 32-001 7
1,0,0,0,0 2 Alternating 800/970 1Hz BS5839 Pt1 8
0,1,0,0,0 3 Alternating 800/970 2Hz
Alternating tone
telecoms
BS5839 Pt1
FP1063.1 Telecoms
8
1,1,0,0,0 4 Alternating 2400/2900 3Hz 10
0,0,1,0,0 5 Alternating 2500/3100 2Hz 10
1,0,1,0,0 6 Alternating 988/645 2Hz 8
0,1,1,0,0 7 Continuous 660 All Clear 1
1,1,1,0,0 8 Continuous 970 BS5839 Pt1 2
0,0,0,1,0 9 Continuous 1200 2
1,0,0,1,0 10 Continuous 2850
Banshee/Bedlam HF
Continuous
4
0,1,0,1,0 11 Continuous 4000 5
1,1,0,1,0 12 Intermittent 660
0.05Hz 6.5s on, 13s off
7
0,0,1,1,0 13 Intermittent 660
0.277Hz 1.8s on,
1.8s off
7
1,0,1,1,0 14 Intermittent 660
3.33Hz 150mS on, 150mS off
Swedish Alarm Tone 7
0,1,1,1,0 15 Intermittent 970
0.8Hz 0.25s on, 1s
off
intermittent Tone BS5839 Pt1 8
1,1,1,1,0 16 Intermittent 970 1Hz 1s on, 1s off
Backup alarm HF &
BS5839 Pt1
BS5839 Pt1 8
DIP setting O=Off/1=On SW 1,2,3,4,5
No Pattern
Nominal
Frequency
Switching
Frequency
Description Standard
2nd
Stage
Tone
0,0,0,0,1 17 Intermittent 2850 1Hz
Backup alarm HF &
BS5839 Pt1 2nd Tone
BS5839 Pt1 10
1,0,0,0,1 18 Intermittent 970
1Hz 500mS on,
500mS off
ISO 8201 LF &
BS5839 Pt1
BS5839 Pt1, ISO
8201
8
0,1,0,0,1 19 Intermittent 950
0.22Hz (0.5s on,
0.5s off)*3, 1.5s off
8
1,1,0,0,1 20 Intermittent 2850
4Hz 150mS on,
100mS off
Pelican Crossing 10
0,0,1,0,1 21 Sweep 400-1200
(0.5s on, 0.5s off)*3, 1.5s off
9
1,0,1,0,1 22 Sweep 1200 - 500
0.99Hz 1s on,
0.01s off
Evacuate, DIN tone &
PFEER
DIN, PFEER 8
0,1,1,0,1 23 Sweep 2400 - 2850 7Hz Fast Sweep Vds Vds 10
1,1,1,0,1 24 Sweep 500 - 1200
0.5sec off
3.5sec on
Slow whoop evacuate
Netherlands NEN 2575
8
0,0,0,1,1 25 Sweep 800 - 970 50Hz LF buzz BS5839 Pt1 BS5839 Pt1 8
1,0,0,1,1 26 Sweep 800 - 970 7Hz
Fast sweep LF BS5839
Pt1
BS5839 Pt1 8
0,1,0,1,1 27 Sweep 800 - 970 1Hz
Medium sweep LF
buzz BS5839 Pt1 Vds
BS5839 Pt1 8
1,1,0,1,1 28 Sweep 2400 - 2850 50Hz 10
0,0,1,1,1 29 Sweep 500 - 1000 7Hz 8
1,0,1,1,1 30 Sweep
500 - 1200 -
500
0.166Hz rise 1s, stable 4s, fall 1s
8
0,1,1,1,1 31 Sweep 800 - 1000 2Hz 8
1,1,1,1,1 32 Sweep 2400 - 2850 1Hz 10
Loading...