System Sensor WFD Series, WFD20, WFD25, WFD30, WFD35 Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
WFD Vane-type Waterflow
3825 Ohio Avenue, St. Charles, Illinois 60174
Detectors
Specifications
Contact Ratings: 10 A @ 125/250 VAC
2.5 A @ 24 VDC Triggering Threshold Bandwidth (Flow Rate): 4 to 10 gpm Static Pressure Rating: 250 PSI (Max) 2" – 8" Dimensions, Installed: 3.5"H x 3.0"W x 6.7"D Operating Temperature Range: 32°F to 120°F (0°C to 49°C) Compatible Pipe: Steel water pipe, schedule 10 or 40. Shipping Weight: 4 to 7 lb., according to size. Enclosure Rating: NEMA 4, as tested by Underwriters Laboratories, Inc. (requires optional Outdoor Cover Gasket Model WFDN4 and cover part #C58-164-01)
Important
This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detectors for use by oth­ers must leave this manual or a copy of it with the user.
Read all instructions carefully before beginning. Follow only those instructions that apply to the model you are in­stalling.
Principles Of Operation
Vane-type waterflow detectors mount to water-filled pipes in sprinkler systems. Waterflow in the pipe deflects a vane, which produces a switched output–usually after a specified delay. All waterflow detectors have a pneumatically con­trolled mechanical delay mechanism. Delays do NOT accu­mulate; they reset if the flow of water stops before the entire delay has elapsed. All switches actuate when the wa­ter flow rate is 10 gallons per minute or greater, but will not actuate if the flow rate is less than 4 gallons per minute.
1-800-SENSOR2, FAX: 630-377-6495
A Division of Pittway
CAUTION
Use vane-type waterflow detectors in wet-pipe systems only. Do NOT use them in dry pipe, deluge, or preaction systems. The sudden inrush of water in such systems may break the vane or damage the mechanism. Do not use in potentially explosive atmospheres. Do not al­low unused wires to remain exposed.
This System Sensor installation manual covers the follow­ing waterflow detectors for sprinkler/fire alarm applica­tions.
Models
WFD20 Waterflow detector, Schedule 10/40, 2" WFD25 Waterflow detector, Schedule 10/40, 2-1/2" WFD30 Waterflow detector, Schedule 10/40, 3" WFD35 Waterflow detector, Schedule 10/40, 3-1/2" WFD40 Waterflow detector. Schedule 10/40, 4" WFD50 Waterflow detector, Schedule 10/40, 5" WFD60 Waterflow detector, Schedule 10/40, 6" WFD80 Waterflow detector, Schedule 10/40, 8"
D770-01-00 1 I56-459-07
Technical Manuals Online! - http://www.tech-man.com
CAUTION
Do NOT use any of the WFD models on copper pipe. The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from functioning properly. Do NOT install steel or iron pipe sections in copper piping for mounting a waterflow detector. Incompatibility be­tween the dissimilar metals causes bimetallic corrosion.
Installation Guidelines
Before installing any waterflow alarm device, be thor­oughly familiar with:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems, Section 3.17 NFPA 25: Inspection, Testing and Maintenance of Sprin-
kler Systems
Other applicable NFPA standards, local codes, and the re­quirements of the authority having jurisdiction
Failure to follow these directions may prevent the device from reporting the flow of water in the event the associated sprinkler system is activated by a fire. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
Figure 1. Mounting dimensions:
3-3/4"
3"
U-bolt nut
Pipe saddle
U-bolt
Overall width = pipe diameter + 3"
Pipe diameter
plus 5-1/4"
Pipe
Plastic vane
A78-1609-00
1. Mount the detector where there is adequate clearance for installation and removal and a clear view of it for inspec­tions. See Figure 1 for mounting dimensions.
2. Locate to protect from damage–6 to 7 feet above the floor.
3. On horizontal runs, position the detector on the top or side of the pipe. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector. For vertical flow applications, mount the detector on pipe through which water flows upward. Otherwise, the unit may not operate properly.
4. Mount the detector at least 6 inches from a fitting that changes the direction of water flow and no less than 24 inches from a valve or drain.
5. Be sure the direction-of-flow arrow matches the direction of flow in the pipe.
Mounting Instructions
1. Drain the pipe.
2. Cut a hole at the desired location. Center the hole in the pipe, as shown in Figure 2, and be sure the hole is per­pendicular to the center of the pipe. Before drilling, use a punch or scribe to mark the drill site to prevent the bit from slipping. If the hole is off center, the vane will bind against the inside wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See Table 1 for hole size.
Figure 2. Mounting hole location:
Wrong
Right
Remove burrs from edge of hole. Clean out scale and foreign matter for one pipe diameter on each side of hole.
A78-1496-01
D770-01-00 2 I56-459-07
Technical Manuals Online! - http://www.tech-man.com
Table 2:Table 1:
WFD SIZE Hole Size
2" - 3-1/2
4" - 8
When drilling the hole with a hole saw, make certain that the center of the cut does not remain in the pipe.
3. Remove burrs and sharp edges from the hole. Clean and
remove all scale and foreign matter from the inside of the pipe for one diameter on each side of the hole to en­sure free movement of the vane. Clean the outside of the pipe to remove dirt, metal chips, and cutting lubricant.
4. Seat the O-ring or gasket against the saddle and mount
the detector directly to the pipe. Carefully roll the vane opposite the direction of flow and insert it through the hole. Seat the saddle firmly against the pipe so that the locating boss goes into the hole.
5. Install the U-bolt, tightening the nuts alternately to en-
sure a uniform seal. See Table 2 for torque values.
6. Remove the metal cover with the tamper-proof wrench
provided. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the cause before proceeding.
Be sure the direction-of-flow arrow points in the right direc­tion or else water flow will go unreported. See Figure 3.
Preoperation Testing
1. Fill the sprinkler system and check for leaks around the
waterflow detector. If it leaks, first check for the proper torque on the U-bolt nuts. If the leak persists, drain the system and remove the detector (refer to Maintenance. page 6). Check for dirt or foreign objects under the gas­ket, and make sure that the pipe surface is not dented. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped.
2. Connect an ohmmeter or continuity tester across the
COM and B switch terminals. The ohmmeter should in­dicate an open circuit.
3. Deflect the actuator lever and hold it until the pneumatic
delay shaft releases the switch buttons. The ohmmeter or continuity tester should show a short circuit after the delay has elapsed. If there is no delay, check the setting of the delay adjustment dial.
"
"
CAUTION
1-1/4
2
"
"
CAUTION
Wiring
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in injury or death.
1. All models have two SPDT switches. Switch contacts COM and B are closed when water is flowing and open when it is not. Connect the switches, as shown in Figure 4 on page 5, depending on the application.
2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be nonsilenceable.
3. A ground screw is provided with all waterflow detectors. When grounding is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 5A, page 5.
4. If a second conduit entry is required, remove the knock­out plug using a flat blade screwdriver as shown on Fig­ure 5B, page 5. Strike sharply with a hammer to pierce the wall of the knockout plug. Move to an adjacent wall section and repeat until the plug falls out. Make sure that the waterflow detector is supported adequately dur­ing this operation to avoid injury.
WFD SIZE Torque
2" - 3-1/2
4" - 8
"
"
WARNING
30 - 35 ft-lb 55 - 60 ft-lb
D770-01-00 3 I56-459-07
Technical Manuals Online! - http://www.tech-man.com
Figure 3. Assembly diagram:
Cover Tamper proof wrench (P/N WFDW)
Switch enclosure (Replacement P/N A77-01-02)
Delay mechanism (Replacement P/N A3008-00)
Mounting plate
Pipe saddle
Roll paddle opposite of flow arrow while inserting
Saddle gasket
Plastic vane
Conduit entrance 
Direction-of-flow arrow
U-bolt nut
Pipe
Waterflow
WFD Size
"
– 3-1/2"
2
4
"
– 8
D770-01-00 4 I56-459-07
"
Hole Size
1-1/4"
2
"
U-bolt
Technical Manuals Online! - http://www.tech-man.com
A78-1914-00
Figure 4. WFD wiring:
WFD Switch
Assembly
Top View
to nonsilenceable initiating 
zone of listed FACP
to power source
compatible
with bell
Switch 1
COM
ABBA
WFD
B
B
COM
COM
Typical FACP Connection
(Multiple Detectors)
B
COM
Typical Local Bell Connection
COM
local
bell
COM
B
NOTE: Common and B connections will
close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector.
Switch 2
CONTACT RATINGS
125/250 VAC
24 VDC
WFD
B
end-of-line resistor
COM
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. Do NOT loop wires.
10 AMPS
2.5 AMPS
Figure 5A. Ground screw location: Figure 5B. Knockout plug removal:
GROUND SCREW (GREEN)
MOUNTING PLATE
A78-1586-00
A78-1914-03A78-2063-00
D770-01-00 5 I56-459-07
Technical Manuals Online! - http://www.tech-man.com
Mechanical Delay Adjustment
The pneumatic delay is preset at the factory to dial setting
2. To adjust the setting, turn the adjustment dial clockwise to increase the delay, counterclockwise to decrease it. The delay is adjustable from 0 to 70 seconds. See Figure 6.
NOTE: Set the delay to the minimum required to prevent
false alarms from flow surges.
Maintenance
To prevent accidental water damage, control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced.
Inspect detectors monthly for leaks and replace if a leak occurs. Test detectors at least monthly, as described under Operational Testing, to ensure proper operation. Test more often if required by the authority having jurisdiction.
After extended service, parts of the detector may become worn, reducing the delay time and causing false alarms. If this happens, increase the delay. If the delay is already at the maximum, replace the mechanical delay assembly. Re­fer to Maintenance for ordering replacement parts.
Operational Testing
Always notify a central station monitoring waterflow alarms before repairing, maintaining, or testing waterflow alarm devices.
1. Replace the cover and tighten the tamper proof screws with the tamper proof wrench. Store the wrench in a se­cure place.
2. Open the inspector’s test valve and time how long it takes for the detector to indicate a flow condition. The detector should remain activated until the inspector’s test valve is closed. Air pockets in the sprinkler system may increase the apparent delay.
Under normal conditions, System Sensor waterflow detec­tors should provide years of trouble-free service. However, if the delay mechanism or switch enclosure becomes faulty, replace it. To replace the delay mechanism or switch enclosure, use a phillips head screwdriver to re­move the three screws that hold it in place. Either mecha­nism can be easily replaced without removing the detector from the pipe or draining the pipe. Do not repair or replace any other waterflow detector components. If any other part of the detector does not perform properly, replace the entire detector. Failure to to follow this in­struction may result in failure of the detector to report the flow of water. To replace the delay mechanism, request Part No. A3008-00. For switch enclosure, request Part No. A77-01-02.
Figure 6. Delay adjustment dial:
Table of dial settings embossed here. See below. 
ON
ER
DIAL
MB
NU
2
3
Delay adjustment dial
0
APP
0
ROX
IMA
1
15
TE
1
2
30
TIME
4
45
55
DEL
0
5
AY
70
(SE
CON
DS)
5
4
3
Dial setting
Seconds (±50%)
D770-01-00 6 I56-459-07
0 0
15
1
23
30
45
55
5
4
70
Technical Manuals Online! - http://www.tech-man.com
A78-1496-05
To remove a detector:
1. Drain the pipe.
2. Turn off electrical power to the detector and disconnect
the wiring.
3. Loosen the nuts and remove the U-bolts.
4. Gently lift the saddle far enough to get your fingers un-
der it. Then, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle.
5. Lift the detector clear of the pipe.
CAUTION
If a vane breaks in a pipe, find and remove it. If it is not re­moved, the vane may restrict the flow of water to all or part of the sprinkler system.
D770-01-00 7 I56-459-07
Technical Manuals Online! - http://www.tech-man.com
The Limitations of Waterflow Alarm Devices
1. Waterflow detectors may not work or operate properly if sprinkler piping being monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be checked regularly for such blocking material, following the instructions in Chapter 5 of NFPA Standard 13A.
2. Alarms generated by the activation of waterflow detec­tors may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open.
3. Vane-type waterflow detectors have a normal service life
Three-Year Limited Warranty
System Sensor warrants its enclosed waterflow detector to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this waterflow detector. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the waterflow detector which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
WARNING
of 10-15 years. Hard water systems, however, may re­duce waterflow detector service life to 4 or 5 years.
4. Waterflow detectors are not a substitute for insurance. Building owners should always insure property and lives being protected by sprinkler systems.
5. If valves controlling the water supply to a sprinkler sys­tem are closed, vane-type waterflow detectors will not work. All valves controlling a sprinkler water supply should be sealed or locked in the normally open posi­tion. The normally open position should be monitored by a sprinkler supervisory switch.
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D770-01-00 8 I56-459-07
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
WFDT/WFDTH Vane-type Waterflow Detectors
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
A Division of Pittway
Specifications
Contact Ratings: Two sets of SPDT (Form C)
10 A @ 125/250 VAC; 2.5 A @ 24 VDC Triggering Threshold Bandwidth (Flow Rate): 4 - 10 GPM Service Pressure Rating: 250 PSI (Max.) Overall Dimensions, Installed: WFDT– 45/16
WFDTH– 45/16
H × 3
H × 3
3
/4
9
/16
W × 6
W × 6
3
/4″D
3
/4″D
Operating Temperature Ranges: 32°F - 120°F (0°C - 49°C) Shipping Weight: 2.6 lbs. The WFDT is U.L. listed for indoor and outdoor installations The WFDTH is U.L. listed for indoor use only. The WFDTH can be installed between 2×4 stud wall construction.
Important
This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detectors for use by others must leave this manual or a copy of it with the user. Read all instructions carefully before beginning.
Tee Depth Threaded Sweat Poly B CPVC
1 × 1 × 1 11/4 × 11/4 × 1 11/2 × 11/2 × 1
2 × 2 × 1"
Approximate Tee Depth Requirements
(See Figure 1)
21/8″ 21/2″ 23/4″
13/4″ N/A 21/4″ 21/6″ N/A 21/4″
21/2″
N/A 23/4″
N/A N/A N/AN/A
CAUTION
Use vane-type waterflow detectors in wet-pipe systems only. DO NOT USE IN DRY-PIPE, DELUGE, OR PRE-AC­TION SYSTEMS. The sudden inrush of water in such sys­tems may break the vane off or damage the mechanism. Do not use in potentially explosive atmospheres. Do not leave unused wires exposed.
Principles Of Operation
Vane-type waterflow detectors mount to water filled pipes in sprinkler systems. Water flow in the pipe deflects a vane. Deflection of the vane produces a switched output, usually after a specified delay.
All WFDTs have a pneumatically controlled mechanical delay mechanism. Delays are noncumulative; they reset if the flow of water stops before the entire delay has elapsed. All detectors will activate on a sustained flow of water greater than 10 gallons per minute (gpm) but will not activate if the flow rate is less than 4 gpm.
Compatible Pipe Tees
The WFDT and WFDTH fit 1″ to 11/2″ NPT threaded ferrous and brass, 1″ to 2″ sweat brass, 11/2″ polybutylene plastic and 1″ pvc plastic tees having a 1″ threaded NPT branch (see Figure 1 and chart for recommended tee depths).
Figure 1. Mounting dimensions:
33/4″
(WFDT)
39/16″
(WFDTH)
3
45/16″
Tee Adapter
Tee Depth
Refer to
Tee Depth
Table
Gage (End of Paddle Tree) Must Fit Between Top of Tee and Bottom of Flange
Tee Fitting
Plastic Vane
A78-1939-00
Installation Guidelines
Before installing any waterflow alarm device, be thoroughly familiar with: NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems NFPA 25: Inspection, Testing, and Maintenance of
Water-based Fire Protection Systems
NFPA 13D: Standard for 1 and 2 Family Dwellings and
Manufactured Homes
NFPA 13R: Standard for Multi-family Dwellings
N770-05-00 1 I56-480-03
Technical Manuals Online! - http://www.tech-man.com
Figure 2. Assembly diagram:
COVER
TAMPER PROOF WRENCH (P/N WFDW)
DELAY MECHANISM (REPLACEMENT P/N A3008-00)
WATERFLOW
FLOW
FILLISTER HEAD SCREW
1 NPT THREAD
ACTUATOR LEVER
SWITCH ENCLOSURE (REPLACEMENT P/N A77-01-02)
GROUND SCREW (GREEN)
MOUNTING PLATE
PADDLE (PADDLE REPLACEMENT KIT (P/N PRK9)
A78-2134-01
(Cover tamper option is available.)
Also, follow other applicable NFPA standards, local codes and the requirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report a waterflow condition. System Sensor is not responsible for devices that have been improperly installed, tested or maintained.
1. Mount the detector where there is adequate clearance for installation and removal and a clear view of it for in­spection. See Figure 1 for mounting dimensions.
2. Locate to protect from damage, 6-7 feet above the floor.
3. On horizontal runs, position the detector on top of the pipe or on the side of it. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector. For vertical flow applications, mount detector on pipe where upflow conditions exist. Failure to do so may pre­vent unit from operating properly.
4. Mount detector at least 6 inches from a fitting which changes the direction of the water flow, or no closer than 24 inches from a valve or drain.
5. BE SURE DIRECTION-OF-FLOW ARROW MATCHES AC­TUAL DIRECTION OF FLOW IN THE PIPE.
Mounting Instructions
1. The WFDT and WFDTH waterflow detectors are de­signed to fit only the appropriate tee fitting.
2. WFDT and WFDTH units are shipped without paddles mounted to the actuator. Select the correct size paddle for the type of tee being used. Align hole on stem of paddle with hole on actuator lever. Fasten together using a #4-40 x 1/4" fillister head screw supplied in bag as­sembly. See Figure 2. Use only the screw provided with the unit. Drive screw head through hole in paddle until it seats to actuator lever surface. No washer is required. For paddle replacement refer to Maintenance section.
3. Carefully roll the vane opposite the direction of flow and insert through tee. Thread detector onto tee fitting and tighten with wrench. Use of thread sealant or tape is rec­ommended. Use height gage (located at end of paddle tee) to ensure proper depth of detector on tee fitting. See Figure 1. Height gage must fit between top of tee fitting and under side of hex tee adapter. A gap between gage and tee adapter is acceptable. When correctly installed, the detector must face in the proper direction of waterflow and be aligned with the pipe.
4. Remove the metal cover. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the problem before proceeding.
CAUTION
Be sure the direction-of-flow arrow points in the right direc­tion, otherwise a waterflow condition will go unreported. See Figure 2.
Preoperation Testing
1. Fill the sprinkler system with water and check for leaks around the WFDT or WFDTH. If there is a leak, check to see that the fittings are tight. If leak persists, drain the system and remove the detector (see removal instruc­tions under Maintenance). Check for damaged threads or cracked fitting. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped.
2. Connect an ohmmeter or continuity tester across (COM and B) terminal switch contacts. The ohmmeter should show an open circuit, no continuity.
3. Deflect the actuator lever and hold it until the pneumatic delay shaft releases the switch buttons. The ohmmeter or continuity tester should show a short circuit after the delay has elapsed. If there is no delay, check the setting of the delay adjustment dial.
NOTE: Leg of tee perpendicular to flow of water must
have a 1" NPT thread. Do not use a reducer to achieve the correct thread size. Failure to follow this instruction will result in failure of the detector to report a waterflow condition.
N770-05-00 2 I56-480-03
Technical Manuals Online! - http://www.tech-man.com
Figure 3. Field wiring:
Switch 1
COM
Top Vie w
NOTE: Common and B connections will
close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector.
COM
ABBA
WFDTH
WFDT
BB
to nonsilenceable initiating
zone of listed FACP
to power source
compatible
with bell
COM COM
Typical FACP Connection
B
COM
Typical Local Bell Connection
Field Wiring
WARNING
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
Switch 2
WFDTH
WFDT
BB
COM COM
local
bell
WFDT and WFDTH
switch assembly
CONTACT RATINGS
125/250 VA C
24 VDC
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
10 AMPS
2.5 AMPS
end-of-line resistor
A78-1992-00
After extended service, parts of the detector may become worn reducing the delay time and causing false alarms. If this happens, increase the delay. If the delay is already at maximum, replace the mechanical delay assembly. Refer to Maintenance section for ordering replacement parts.
1. The WFDT and WFDTH have two SPDT switches. Switch contacts (COM and B) are closed when water is flowing and open when water is not flowing. Connect the switches as shown in Figure 3 depending on the application.
2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be non-silenceable.
3. A ground screw is provided with all units. When ground­ing is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 2.
Mechanical Delay Adjustment
The pneumatic delay is preset at dial setting 2 at the factory. To adjust the delay, turn the adjustment dial on the delay mechanism. Turn clockwise to increase the delay, counterclockwise to decrease the delay. Delay can be adjusted over a range from 0-70 seconds. See Figure 4.
NOTE: Set the delay to the minimum required to prevent
false alarms due to flow surges.
N770-05-00 3 I56-480-03
Technical Manuals Online! - http://www.tech-man.com
Figure 4. Delay adjustment dial:
Table of dial settings
3
2
45
1
30
0
15
0
1
0
2
3
Delay adjustment dial
Dial setting
Seconds (±50%)
001152303454555
embossed here.
See below.
4
55
5
70
5
4
70
A78-1596-05
Operational Testing
Always notify a central station monitoring waterflow alarms before repairing, maintaining or testing waterflow alarm devices.
1. Replace the cover and tighten the security screws with the tamper proof wrench. Store the wrench in a secure place.
2. Open the inspector’s test valve and time how long it takes for the detector to indicate a flow condition. The detector should remain activated until the inspector’s test valve is closed. Air pockets in the sprinkler system may increase the apparent time delay.
Maintenance
To prevent accidental water damage, control valves should be shut tightly and the system completely drained before waterflow detectors are removed or replaced.
Inspect detectors monthly for leaks. Test detectors at least monthly as described under Operational Testing above to insure proper operation. This device is not designed for use on “dry pipe” systems. Test more often if required by the authority having jurisdiction.
replacement kits are available. To replace the delay mechanism, request Part No. A3008-00; for switch enclosure, request Part No. A77-01-02. Complete instructions are enclosed with each. Either mechanism can be easily replaced without removing the detector from the pipe or draining the pipe. If damage occurs to paddle, order replacement kit PRK9. Refer to procedure below for removal of detector on pipe. Do not repair or replace any other waterflow detector components in the field. If any other part of the detector does not perform properly, replace the entire detector. Failure to follow this
instruction may result in failure of the detector to report a waterflow condition.
Proceed as follows to remove a detector.
1. Drain the pipe.
2. Turn off electrical power to the detector, and then dis­connect wiring.
3. Unscrew WFDT or WFDTH from tee fitting.
4. Lift detector clear of pipe.
CAUTION
Under normal conditions System Sensor waterflow detectors should provide years of trouble-free service. If, however, the delay mechanism becomes faulty,
WARNING
The Limitations of Waterflow Alarm Devices
1. Waterflow detectors may not work or operate properly if sprinkler piping being monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be checked regularly for such blocking material, following the instructions in NFPA Standard 25.
2. Alarms generated by the activation of waterflow detec­tors may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open.
Three-Year Limited Warranty
System Sensor warrants its enclosed waterflow detector to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this waterflow detector. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the waterflow detector which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
If a vane breaks off in a pipe, find and remove it. Failure to do so may restrict the proper flow of water to part of the sprinkler system.
3. Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water systems, however, may re­duce waterflow detector service life to 4 or 5 years.
4. If valves controlling the water supply to a sprinkler sys­tem are closed, vane-type waterflow detectors will not work. All valves controlling a sprinkler water supply should be sealed or locked in the normally open posi­tion. The normally open position should be monitored by a sprinkler supervisory switch.
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
N770-05-00 4 I56-480-03
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
WFDTNR Vane-type Waterflow Detector
Specifications
Contact Ratings: 10 A @ 125/250 VAC
2.5 A @ 24 VDC Triggering Threshold Bandwidth (Flow Rate): 4 - 10 GPM Static Pressure Rating: 250 PSI (Max.) Overall Dimensions, Installed: 3.25" x 4.25" cover dia.
3.25" above pipe tee Operating Temperature Range: 32°F - 120°F (0°C - 49°C) Shipping Weight: 1.5 lbs.
Important
This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detectors for use by oth­ers must leave this manual or a copy of it with the user. Read all instructions carefully before beginning.
CAUTION
Tee Depth Threaded Sweat Poly B CPVC
1 × 1 × 1 11/4 × 11/4 × 1 11/2 × 11/2 × 1
2 × 2 × 1"
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Approximate Tee Depth Requirements
(See Figure 1)
21/8″ 21/2″ 23/4″
13/4″ N/A 21/4″ 21/6″ N/A 21/4″
21/2″
N/A 23/4″
N/A N/A N/AN/A
Use vane-type waterflow detectors in wet-pipe systems only. DO NOT USE IN DRY-PIPE, DELUGE, OR PRE-AC­TION SYSTEMS. The sudden inrush of water in such sys­tems may break the vane off or damage the mechanism. Do not use in potentially explosive atmospheres. Do not leave unused wires exposed.
Principles Of Operation
Vane-type waterflow detectors mount to wet-pipe systems only. Water flow in the pipe deflects a vane. Deflection of the vane produces a switched output. All detectors will ac­tivate on a sustained flow of water greater than 10 gallons per minute (gpm) but will not activate if the flow rate is less than 4 gpm.
Compatible Pipe Tees
Model WFDTNR fits 1"–11/2" NPT threaded ferrous and brass, 1" - 2" sweat brass, 11/2" polybutylene plastic and 1" pvc plastic tees having a 1" threaded NPT branch (see Fig­ure 1 and chart for recommended tee depths).
Installation Guidelines
Before installing any waterflow alarm device, be thor­oughly familiar with: NFPA 72: Installation, Maintenance and Use of Local
Protective Signalling Systems
Figure 1. Mounting dimensions:
3 1/4"
1 3/4"
3 1/4"
"TEE DEPTH"
REFER TO
TEE DEPTH
TABLE
PIPE TEE FITTING
PLASTIC VANE
HEX TEE ADAPTOR
INSTALLATION GAGE (END OF PADDLE TREE) MUST FIT BETWEEN TOP OF TEE AND BOTTOM OF HEX TEE ADAPTOR FLANGE.
A78-2110-00
NFPA 13: Installation of Sprinkler Systems, specifically
Section 3.17
NFPA 25: Inspection, Testing and Maintenance of Sprin-
kler Systems, specifically Chapters 4 and 5
NFPA 13D: Standard for Residential Dwellings NFPA 13R: Standard for Multifamily Dwellings Other applicable NFPA standards, local codes and the re­quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report a waterflow condition. System Sensor is
N770-06-00 1 I56-509-01
Technical Manuals Online! - http://www.tech-man.com
Figure 2. Assembly diagram:
COVER
TAMPER PROOF WRENCH (P/N WFDW)
PADDLE
A78-2111-00
ACTUATOR LEVER
FLOW
ACTUATOR ASSEMBLY
HEAD SCREW
WATER FLOW
FILLISTER
1" NPT THREAD
GROUND SCREW (GREEN)
MOUNTING PLATE
not responsible for devices that have been improperly in­stalled, tested or maintained.
1. Mount the detector where there is adequate clearance for installation and removal and a clear view of it for in­spection. See Figure 1 for mounting dimensions.
2. Locate to protect from damage, 6-7 feet above the floor.
3. On horizontal runs, position the detector on top of the pipe or on the side. Do not mount it upside down.
4. Mount detector at least 6 inches from a fitting which changes the direction of the water flow.
5. BE SURE DIRECTION-OF-FLOW ARROW MATCHES AC­TUAL DIRECTION OF FLOW IN THE PIPE.
Mounting Instructions
1. This WFDTNR waterflow detector is designed to fit only the appropriate tee fitting.
NOTE: Leg of tee perpendicular to flow of water must
have a 1" NPT thread. Do not use a reducer to achieve the correct thread size. Failure to follow this instruction will result in failure of the detector to report a waterflow condition.
2. WFDT units are shipped without the paddles mounted to the actuator. Select the correct size paddle for the tee be­ing used the appropriate nominal pipe diameter size is molded on the surface of the paddles). Align hole on stem of paddle with hole on actuator lever. Fasten to­gether using a #4-40 x 1/4" fillister head screw supplied in bag assembly. See Figure 2. Use only the screw pro­vided with the WFDTNR. Drive screw head through hole in paddle until it seats firmly to actuator lever surface. No washer is required. For paddle replacement refer to Maintenance section.
3. Thread detector onto tee fitting and tighten with
wrench. Use of thread sealant or tape is recommended. Use height gage (located at end of paddle tee) to ensure proper depth of detector on tee fitting. See Figure 1. Height gage must fit between top of tee fitting and under side of hex tee adapter. A gap between gage and tee adapter is acceptable. When correctly installed, the de­tector must face in the proper direction of waterflow and be aligned with the pipe.
4. Remove the plastic cover with the tamper proof wrench provided. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the problem before proceeding.
CAUTION
Be sure the direction-of-flow arrow points in the correct di­rection, otherwise a waterflow condition will go unre­ported. See Figure 2.
Operational Testing
Always notify a central station monitoring waterflow alarms before repairing, maintaining, or testing waterflow alarm devices.
1. Fill the sprinkler and check for leaks around the WFDTNR. If it leaks, check to see that the fittings are tight. If leak persists, drain the system and remove the detector (see removal instructions under Maintenance). Check for damaged threads or cracked fitting. Reinstall detector and check again for leaks. Do not proceed until all leaks have been stopped.
2. With cover removed, connect an ohmmeter or continu­ity tester across (COM and B) terminal switch contacts. The ohmmeter should show an open circuit, no continu­ity (when the red switch buttons are depressed).
3. Deflect the actuator lever to release the switch buttons. The ohmmeter or continuity tester should show a short circuit when the switch buttons are released.
4. Open the inspector's test valve to allow the detector to indicate a flow condition. The detector should remain activated until the inspector's test valve is closed. Air pockets in the sprinkler system may prevent the detector from firing immediately.
5. Replace the cover and tighten the security screws with the tamper proof wrench. Store wrench is a secure place.
Field Wiring
1. The WFDT has two SPDT switches. Switch contacts (COM and B) are closed when water is flowing and open when water is not flowing. Connect the switches as shown in Figure 3 depending on the application.
2. When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be non-silenceable.
N770-06-00 2 I56-509-01
Technical Manuals Online! - http://www.tech-man.com
Figure 3. Field wiring:
Switch 1
COM
COM
NOTE: Common and B connections will
close when vane is deflected, i.e., when water is flowing. Dual switches permit applications to be combined on a single detector.
Strip Gauge
to nonsilenceable initiating
zone of listed FACP
to power source
compatible
with bell
ABBA
WFDTNR
BB
COM COM
Typical FACP Connection
B
Typical Local Bell Connection
Switch 2
COM
3. A ground screw is provided with all WFDT units. When grounding is required, clamp wire with screw in hole lo­cated between conduit entrance holes. See Figure 2.
WARNING
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
Maintenance
To prevent accidental water damage, control valves should be shut tightly and the system completely drained before waterflow detectors are removed or replaced.
Inspect detectors monthly for leaks. Test detectors at least monthly as described under Operational Testing to insure proper operation. This device is not designed for use on “dry pipe” systems. Test more often if required by the au­thority having jurisdiction.
CONTACT RATINGS
WFDTNR
BB
COM COM
local
bell
125/250 VAC
24 VDC
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
10 AMPS
2.5 AMPS
end-of-line resistor
Under normal conditions System Sensor waterflow detec­tors should provide years of trouble-free service. If, how­ever, the switch enclosure becomes faulty, request Part No. A77-01-08. If damage occurs to paddle, order replacement kit PRK9. Refer to procedure below for removal of detector on pipe. Do not repair or replace any other waterflow de­tector components in the field. If any other part of the de­tector does not perform properly, replace the entire detector. Failure to follow this instruction may result in
failure of the detector to report a waterflow condition.
Proceed as follows to remove a detector:
1. Drain the pipe
2. Turn off electrical power to the detector, and then dis­connect wiring
3. Unscrew WFDTNR from tee fitting
N770-06-00 3 I56-509-01
Technical Manuals Online! - http://www.tech-man.com
WARNING
The Limitations of Waterflow Alarm Devices
1. Waterflow detectors may not work or operate properly if sprinkler piping being monitored is plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be checked regularly for such blocking material, following the instructions in Chapter 5 of NFPA Standard 13A.
2. Alarms generated by the activation of waterflow detec­tors may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open.
3. Vane-type waterflow detectors have a normal service life
Three-Year Limited Warranty
System Sensor warrants its enclosed waterflow detector to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this waterflow detector. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the waterflow detector which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
of 10-15 years. Hard water systems, however, may re­duce waterflow detector service life to 4 or 5 years.
4. Waterflow detectors are not a substitute for insurance. Building owners should always insure property and lives being protected by sprinkler systems.
5. If valves controlling the water supply to a sprinkler sys­tem are closed, vane-type waterflow detectors will not work. All valves controlling a sprinkler water supply should be sealed or locked in the normally open posi­tion. The normally open position should be monitored by a sprinkler supervisory switch.
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
N770-06-00 4 I56-509-01
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
OSY2 Gate Valve Supervisory Switch
Specifications
Contact Ratings: 10 A @ 125/250 VAC
2.5 A @ 24 VDC Dimensions: 53/4"H X 31/2"W X 31/4"L Maximum Stem Extension: 25/8" Minimum Stem Extension: Bracket Span: 63/4" Operating Temperature Range: 32° - 120°F (0° - 49°C) Shipping Weight: 23/4 lb.
Important
This manual contains important information about the in­stallation and operation of supervisory switches. These in­structions apply to System Sensor switches for outside screw and yoke valves only. Read all instructions carefully before beginning installation.
WARNING
Do NOT use this switch in explosive or potentially explo­sive atmospheres. Do NOT leave unused wires exposed.
5
/8"
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Figure 1:
ACTUATOR
VERTICAL (DOWN)
ACTUATOR
HORIZONTAL
ment. If this is the case, the bolts can be positioned on the outside of the yoke.
All supervisory switch installations must comply with local codes and ordinances and the requirements of the authority having jurisdiction. Additional information is available in National Fire Protection Association standards NFPA 13, 13D, 13R, 71, and 72.
General Installation Considerations
The OSY2 Supervisory Switch can be mounted on open yoke valves between 1/2" and 12" in diameter in the posi­tions shown in Figure 1 only. If the switch is installed with the actuator pointing upward, water may leak into the inte­rior of the switch. Therefore, do NOT install the OSY2
with its actuating lever pointing upward.
All OSY2 models are equipped with a ground screw inside the switch housing near the conduit exit hole for those ap­plications where grounding is required.
Narrow Yoke Valves
As Figure 2 suggests, installing the valve with mounting bolts inside the yoke is recommended. However, some valves may have yokes that are too narrow for this arrange-
Limited Clearance Valves
The OSY2 mounting bracket fits most of the open yoke valves used in fire protection systems. However, some of these valves, especially those less than 11/2" in diameter, have irregularly shaped yokes or such limited clearances that the clamping bar cannot be installed properly and/or it causes the valve to bind. If this is the case, the use of the supplied J-bolts is required to attach the OSY2 to the valve (see J-Bolt Detail, Figure 2).
Installation Procedure
See Figures 2 and 3, as required, while performing the pro­cedure that follows.
Perform step 1 on valves 11/2" in diameter and smaller only. Proceed directly to step 2 if the switch is being in­stalled on a valve larger than 11/2" in diameter.
1. Remove and discard the two C-clips and roller from the actuating lever.
2. Set the valve to its fully open position. Remove the OSY2 Supervisory Switch from the carton and adjust the posi­tion of the retaining washers to provide sufficient bolt length for the yoke thickness of the valve.
N770-04-00 1 I56-393-05
Technical Manuals Online! - http://www.tech-man.com
Figure 2:
Actuating Cam
Actuating lever
set screw
Wrench for
tamper-resistant
screws
(P/N WFDW)
Cover
Spring
Mounting screws
Terminal block
Tamper-resistant screws
Seal
Base housing
Mounting Bracket
"C" clip
Actuating lever roller (2 thru 12"only)
Valve Stem
Carriage Bolt
Yoke
Clamping Bar
J-Bolt Detail
Hex wrench (P/N HEXW)
SLIDE CLAMPING BAR TO REMOVE OR INSTALL.
NOTE: LARGER GATE VALVE SHOWN (2" THRU 12"). WHEN INSTALLING SUPERVISORY SWITCH TO SMALLER GATE VALVES (1/2" THRU 1 1/2") CARRIAGE BOLTS ARE TO BE LOCATED ON OUTBOARD SIDE OF YOKE. ON SMALL VALVES WITH LIMITED CLEARANCE THE USE OF J-BOLTS MAY BE REQUIRED.
Retaining Washer
Nut
N770-04-00 2 I56-393-05
Technical Manuals Online! - http://www.tech-man.com
Figure 3: the valve, slide the open end of the clamping bar onto
the bolts and under the retaining washers, as indicated in Figure 2.
7. Ensure that the actuating lever does not hit the inside
of the cover or the clamping bar at any point in its travel. If it does, adjust the length of the lever by loos­ening the set screw, sliding the lever in or out, as needed, and retightening the set screw.
8. Adjust the supervisory switch position on the valve so
that both switches are depressed (COM to B circuit
VALVE
STEM
GLAND
THREADED VALVE
STEM HEX
YOKE
CLAMPING BAR NOT SHOWN
GROOVE
GLAND HEX NUT
OR BOLT
open) when the actuating lever is in the groove with the valve in the full open position. The COM to B circuit should close when the valve is closed 1/5 of its
Position the switch on the valve with the bolts on the inside
(preferably) or outside of the yoke, depending on clear­ances. Adjust the position of the OSY2 as far as possible from the valve gland and in a location where the actuat­ing lever contacts the unthreaded section of the valve stem (if the valve stem is already grooved, proceed di­rectly to step 6).
3. When the switch is in position on the valve, slide the open end of the clamping bar onto the bolts and under the retaining washers. If necessary, adjust the length of the actuating lever by loosening the set screw on the cam, sliding the lever in or out, as appropriate, and re­tightening the set screw. The lever is properly adjusted when it clears the clamping bar. Tighten the nuts by hand and slide the OSY2 until the second switch trip points are found as the lever rests on the valve stem. This approximates the final position of the OSY2 after the valve stem is grooved. Carefully check all clearances
travel or 2 full turns of the handle, whichever is less. The switch produces an audible “click” when it closes. The switch closure can also be tested electrically by using an ohmmeter to test for continuity between its terminals.
9. Tighten the nuts securely with a wrench and check the operation of the OSY2 as in step 8. If necessary, reposi­tion the OSY2 and test it again.
10. Wire the supervisory switch as shown in Figure 4.
11. Replace the OSY2 cover and tighten the tamper-resistant cover screws with the special wrench provided. Store this wrench in a secure location.
12. Test the operation of the OSY2 by closing the valve the
1
/5 of its travel distance or two full turns, whichever is less. The circuit between COM and B should indicate a closure during this procedure. If it does not, readjust the supervisory switch and actuator positions until the switch closes when the valve is operated.
of the bolts, actuator, mounting bracket, clamping bar, and OSY2 cover. Adjust the position as necessary. If clearance is a problem, refer to the Limited Clearance Valves (page 1) section of this manual.
4. Mark the point on the valve stem where the actuating le-
Testing
Test the operation of all supervisory switches before they are placed into service and at least semiannually, or as re­quired by the authority having jurisdiction.
ver contacts the valve stem.
5. Remove the OSY2 by loosening the nuts and sliding the clamping bar from beneath the retaining washers. Re­move the OSY2 from the valve and set it aside. (a) Valves 11/2" in diameter and smaller only.
Use a 1/4" untapered round file to file a groove 3/32"
NOTE: Notify the proper authorities that the supervisory
switch(es) is (are) undergoing maintenance and, therefore, will be temporarily out of service. Dis­able the system or zone undergoing testing to pre-
vent unwanted alarms. deep in the valve stem at the mark that was made in step 4. Be sure to remove any burrs resulting from the filing to avoid damaging the valve stem packing gland.
(b) Valves larger than 11/2" inches in diameter only.
Use a 3/8" untapered round file to file a groove 1/8"
Test the operation of the OSY2 by closing the valve the 1/5 of its total travel distance or two full turns, whichever is less. A contact closure must occur during this procedure. If it does not, readjust the supervisory switch and actuator
positions until the switch closes when the valve operated. deep in the valve stem at the mark that was made in step 4. Be sure to remove any burrs resulting from the filing to avoid damaging the valve stem packing gland.
6. Mount the switch loosely with the actuating lever cen­tered in the groove. When the switch is in position on
N770-04-00 3 I56-393-05
Technical Manuals Online! - http://www.tech-man.com
Figure 4. Supervisory switch wiring diagram:
Top View
Switch 1
Strip Gage
to nonsilenceable initiating
zone of listed FACP
to power source
compatible
with bell
COM
ABBA
COM
Sup. Switch
BB
COM COM
Typical FACP Connection
B
COM
Typical Local Bell Connection
Switch 2
Sup. Switch
BB
COM COM
local
bell
CONTACT RATINGS
125/250 VAC
24 VDC
10 AMPS
2.5 AMPS
end-of-line resistor
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
WARNING
The Limitations of Supervisory Switch Alarm Devices
1. Alarms generated by the actuation of the activating lever may not be received by a central station if telephone or other communication lines to the detector are out of ser­vice, disabled, or open.
2. Supervisory switch alarm devices have a normal service life of 10-15 years.
Three-Year Limited Warranty
System Sensor warrants its enclosed supervisory switch to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this supervisory switch. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the supervisory switch which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
A78-1639-00
3. Supervisory switches are not a substitute for insurance. Building owners should always insure property and lives being protected.
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
N770-04-00 4 I56-393-05
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Cover
Tamper screws
Tamper proof wrench (P/N WFDW)
Actuating cam
Actuating lever
set screw
Nipple set screws
Threaded nipple
Base housing
Actuating lever
Retaining nut
Switch Enclosure
Mounting screws
Spring
Hex wrench (P/N HEXW)
4-1/4" H
(Assembled)
3-1/4" D
3-1/2" W
PIBV2 Post Indicator and Butterfly Valve Supervisory Switch
Specifications
Contact Ratings: 10A @ 125/250 VAC
2.5 A @ 24 VDC
Overall Dimensions: 81/4 H X 31/2 W X 31/4" D Operating Temperature Range: 32°F to 120°F (0°C to 49°C) Maximum Stem Extension: 2 5/32" Shipping Weight 2 lbs.
Important
Please Read Carefully and Save
This instruction manual contains important information on the installation and operation of supervisory switches. Purchasers who install supervisory switches for use by oth­ers must leave this manual or a copy of it with the user. These instructions apply to System Sensor switches for post indicator and butterfly type valves. Read all instructions carefully before beginning. Follow only those instructions that apply to the model being installed.
Figure 1:
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
CAUTION
Do NOT use in potentially explosive atmospheres. Do NOT leave unused wires exposed.
Before installing any supervisory switches in sprinkler sys­tems, be thoroughly familiar with: NFPA 72: Installation, Maintenance and Use of Local
Protective Signalling Systems
NFPA 13: Installation of Sprinkler Systems, specifi
cally, Section 3.17
NFPA 25: Inspection, Testing and Maintenance of
Sprinkler Systems, specifically Chapters 4 and 5
General Information for Post Indicator Valves and Butterfly Valves
1. Model PIBV2 is designed for installation in a 1/2" NPT tapped hole and located so that the actuating lever of the switch engages the target or flag of the valve . The switch actuating lever is spring loaded against the flag or target of the valve and is released when the valve moves toward the closed position from the fully open position. The switch is factory set to indicate an alarm condition
Technical Manuals Online! - http://www.tech-man.com
when the target and lever move in the direction toward the conduit entry hole when the valve closes, but can be reversed if the installation demands (refer to Section 4).
2. Model PIBV2 is equipped with a removable 1/2" NPT
N770-03-00 1 I56-394-05
A78-1587-00
pipe nipple which is locked in place with two set screws. These models also include an adjustable length actuat­ing lever which eliminates any need for alteration of the length of the lever. A hex key is furnished for both of these features.
3. The cover is secured with two tamper resistant screws which require a special key to remove. One key is in­cluded with each supervisory switch. Replacement and additional keys are available (Part No. WFDW).
Figures 2A and 2B:
Rising Flag
A78-1629-00 A78-1630-00
Falling flag
HEAD
TARGET
Section 1
Installation Instructions For Post Indicator Valves
1. There are two types of post indicator valves - rising flag and falling flag. In a rising flag installation, the PIBV2 mounts below the target assembly, as shown in Figure 2A. Closing the valve raises the target assembly and re­leases the actuating lever on the PIBV2. In a falling flag installation, the PIBV2 mounts above the target assem­bly (Figure 2B). Closing the valve lowers the target as­sembly and releases the actuating lever on the PIBV2.
The PIBV2 is set for falling flag installation. If a ris­ing flag operation is desired, it is necessary to re­verse the action of the switch (See Section 4).
2. If the post indicator valve is predrilled with 1/2" NPT mounting hole, remove the plug and go to step 6. If the post indicator valve is NOT equipped with a 1/2" NPT mounting hole, it will be necessary to drill and tap the hole.
3. Position the valve in the fully open position ("OPEN" should appear in the window) and remove the head and target assembly. In doing so, ensure that the as­sembly can be reinstalled with its original adjustment.
4. (a)In a falling flag installation (flag lowers as valve is
closed), measure the distance from the bottom of the head to the upper surface of the target that will con­tact the actuating lever of the PIBV2. Add 3/32" to this measurement and mark the outside of the housing at that location. Drill with a 23/32" drill bit and tap a 1/2" NPT thread.
(b)In a rising flag installation (flag rises as valve is
closed), measure the distance from the bottom of the head to the lower surface of the target that will con­tact the actuating lever. Subtract 3/32" to this measure­ment and mark the outside of the housing at that
location. Drill with a 23/32" drill bit and tap a 1/2" NPT thread.
5. Replace the head and target assembly.
6. Screw the locknut onto the threaded nipple which is supplied with the PIBV2.
7. Screw the nipple hand tight into the 1/2" hole in the valve and tighten the locknut against the housing to se­cure the nipple in position.
8. Insert a probe into the hole through the nipple to mea­sure the distance from the open end of the nipple to the to the desired position on the target assembly. Subtract
5
/8" from the distance and set the length of the actuat­ing lever of the PIBV2 from the end of the enclosure to this distance. Tighten the set screw which holds the ac­tuating lever.
9. Close the valve 3 to 4 revolutions.
10. Install the PIBV2 onto the nipple and orient the conduit entry down (See Figure 4). Apply pressure to the PIBV2 and lock the set screws to secure the nipple to the PIBV2.
11. Slowly open the valve to its fully open position. The switch should trip as the valve opens, but not force the actuating lever against the nipple when fully open. To check for this condition, open the valve fully and de­press the top of the actuating cam to stretch the actuat­ing spring further. There should be some additional movement available. If no movement is available, dam­age may occur to the PIBV2 actuator lever. It will be necessary to adjust the flag location by removing the head and turning the handle while the valve stem is disengaged (refer to the valve manufacturer.)
12. After checking the fully open position to ensure ad­equate clearance, close the valve slowly until the PIBV2 contacts trip. The switches must trip within 1/5 of the full travel distance of the valve.
13. If the PIBV2 does not change states within 1/5 of the length of travel, it may be necessary to adjust the flag up or down by removing the head and turning the handle (refer to the valve manufacturer.)
Section 2
Installation Instructions For Butterfly Valves
(See Figure 3)
1. Remove the 1/2" NPT plug from the gear housing.
2. Loosen 2 set screws that hold the nipple on the PIBV2
and remove the nipple.
3. Screw the locknut onto the nipple.
4. Screw the nipple into the 1/2" NPT hole and hand
tighten. Tighten the locknut firmly to the housing to se­cure the nipple.
5. Open the valve fully and close the valve approximately 3
revolutions, noting which direction the target moves.
6. Retract the actuating arm and install PIBV2 onto the
N770-03-00 2 I56-394-05
Technical Manuals Online! - http://www.tech-man.com
Figure 3:
Conduit Entry
Phillips
Screw
Spring in final
position
Actuating Lever
Switch Enclosure
Spring in initial position
Slide in
this direction
CLOSE
A78-1633-00
N
E
P
O
O
T
CLOSE
nipple, orienting the PIBV2 to trip the switch as the valve closes. If the conduit entry is on the wrong side, it will be necessary to reverse the action of the switch (see Section 4). Apply pressure to PIBV2 and tighten set screws to secure the assembly.
7. Slide the actuating arm into the valve until it bottoms on the flag, but do not tighten set screw.
8. Open the valve to the full open position and tighten set screw to hold actuating arm in position. (Actuating arm length will adjust slightly as valve is opened.) Check to ensure that in the full open position the actuating arm is not resting on the nipple. Do this by depressing the actu­ating cam to further stretch the spring, ensuring that more travel is available when the valve is open. If there is no travel, damage may occur to PIBV2 actuating arm. Some slight alteration of the valve stop setting may be necessary to ensure that no damage occurs.
9. Carefully close valve and note the number of handle revolutions until the switch trips. The switch must trip within 1/5 of the total travel range of the valve.
Actuator Vertical (Pointing Up)
2. Ground Screw — A ground screw is provided with all
supervisory switch models. When grounding is required, clamp wire with the screw in hole located near conduit entrance.
3. Wiring — See Figure 6, Page 4.
Section 4
Reversing The Action Of Pibv2
1. Loosen the 3 phillips screws on the top of the black switch enclosure so that the switch enclosure is loose and free to move (see Figure 5).
2. Slide the switch enclosure away from the conduit entry toward the actuating pivot arm as far as possible and tighten the 3 screws to secure the enclosure. (Ensure that switch enclosure remains oriented away from the conduit entry as screws are tightened.)
3. Grasp the spring at the center and lift it over the actuat­ing cam so that it seats on the opposite side of the actua­tor (see Figure 5).
Figure 5:
Section 3
General Installation Instructions
1. Installation Positions
Figure 4:
The following are examples of acceptable mounting positions:
Actuator Vertical (Down) Actuator Horizontal
The following mounting position is not acceptable:
N770-03-00 3 I56-394-05
Technical Manuals Online! - http://www.tech-man.com
A78-1631-00
Figure 6:
Switch 1
Top View
NOTE: Common and B connections will
close when valve moves 1/5 of its total travel distance.
Strip Gage
to nonsilenceable initiating
zone of listed FACP
to power source
compatible
with bell
COM
ABBA
COM
Sup. Switch
BB
COM COM
Typical FACP Connection
B
COM
Typical Local Bell Connection
Switch 2
Sup. Switch
BB
COM COM
local
bell
CONTACT RATINGS
125/250 VAC
24 VDC
10 AMPS
2.5 AMPS
end-of-line resistor
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
The Limitations of Supervisory Switch Alarm Devices
1. Alarms generated by the activation of the actuating lever may not be received by a central station if telephone or other communication lines to the alarm device are out of service, disabled, or open.
2. Supervisory switch alarm devices have a normal service life of 10-15 years.
Three-Year Limited Warranty
System Sensor warrants its enclosed supervisory switch to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this supervisory switch. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the supervisory switch which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
A78-1639-00
WARNING
3. Supervisory switches are not a substitute for insurance. Building owners should always insure property and lives being protected.
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
N770-03-00 4 I56-394-05
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS

Cover Tamper Switch

Specifications
Contact Ratings: 5.0A @ 125/250 VAC
2.5A @ 24 VDC
Overall Dimensions: 11/4˝H x 2˝W x 3/4˝D Operating Temperature Range: 32° to 120°F (0° to 49°C) Shipping Weight: 0.025 lb.
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user of this equipment.
CAUTION
Do not leave unused wires exposed. Do not use in poten­tially explosive atmospheres.
General Information
This cover tamper switch mounts to all System Sensor WFD, WFDT, OSY2 and PIBV2 terminal block units. Cover removal produces a switch output. The unit will reset when the product cover is reinstalled.
Installation Guidelines
Before installing any cover tamper switch, be thoroughly familiar with:
Figure 1. Assembly Diagram:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems, specifically
section 3.17.
NFPA 25: Inspection, Testing and Maintenance of Sprin-
kler Systems, specifically chapters 4 and 5. Other applicable NFPA standards, local codes and the re­quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm or trouble condition. System Sen­sor is not responsible for devices that have been improperly installed, tested or maintained.
Mounting Instructions
1. Install switch mounting bracket onto terminal block us-
ing the 2 screws provided, shown in Figure 1.
2. Snap the switch onto the switch mounting bracket in po-
sition shown in Figure 1.
D770-05-00 1 I56-403-03
Technical Manuals Online! - http://www.tech-man.com
A78-1661-00
WARNING
High voltage. Electrocution hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury of death.
Field Wiring
1) Wire as required per wiring diagram (Figure 2), placing the stripped wire lead under the correct terminal plate. Extra wire lead should be clipped and terminated with a wire nut to avoid shorting to housing.
Figure 2. Field Wiring:
Blue
Wire Nut
to nonsilenceable initiating zone of listed FACP
Red
COM COM
NC NO COM
BB
Typical Fire Alarm Control Panel Connection
Red
Wire Nut
BlackBlueBlack
COM COM
BB
AAAA
NC NO COM
NOTE: Where one wire already exists under the terminal
plate, connect the cover tamper wire under the op­posite side of the terminal plate.
2) When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be non-silenceable.
Wire Code:
Cover Tamper Switch:
(Non Alarm Condition)
(Cover Off)
end-of-line resistor
Waterflow or Supervisory Switch:
Com to B = Open Circuit Com to A = Closed Circuit
Black / Blue: Open Black / Red: Closed
Cover Tamper Switch
to power source compatible with bell
NC NO
COM
Red
B
Blue
Black
A
COM
Wire Nut
local
bell
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
Typical Local Bell Connection
NOTE: Local bell will activate when cover is removed.
Operational Testing
Always notify a central station monitoring waterflow or su­pervisory switch alarms before repairing, maintaining, or testing cover tamper switch devices.
Three-Year Limited Warranty
System Sensor warrants its enclosed cover tamper switch to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this cover tamper switch. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the cover tamper switch which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
D770-05-00 2 I56-403-03
Technical Manuals Online! - http://www.tech-man.com
1) Replace the cover and tighten the security screws with the security wrench. Store the wrench in a secure place.
2) Verify that circuit has reset by checking FACP.
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
© System Sensor 1996
A78-1662-01
INSTALLATION AND MAINTENANCE INSTRUCTIONS

546-8000 Cover Tamper Switch

For use with System Sensor Pressure Switches: EPS10-1, EPS10-2, EPS40-1, EPS40-2, EPS120-1, EPS120-2
Specifications
Contact Ratings: 5A @ 125/250 VAC
2.5A @ 6/12/24 VAC
Operating Temperature Range: -40° to +160°F (-40° to +71°C) Shipping Weight: 0.115 lbs.
NOTICE: This manual should be left with the owner/user of this equipment.
General Information
The System Sensor 546-8000 cover tamper switch mounts to EPS series pressure switches to monitor removal of the cover. Cover removal produces a switch output. The unit will reset when the product cover is reinstalled.
Wiring Instructions
1. Remove the pressure switch cover using the security wrench provided with the pressure switch.
2. Attach the cover switch with the two screws provided (see Figure 1).
3. Route wires away from the pressure switch mechanism.
4. Wire the circuit as shown in Figures 2, 3, or 4, or as re­quired by the installation requirements and as approved by the authority having jurisdiction. Clip the unused wire from the tamper switch and use the wire nut to pro­tect from shorting.
5. Perform the required system tests and include the cover tamper switch in the test by alternately replacing and re­moving the cover to produce the desired circuit effects.
6. After testing, secure the cover with the security wrench.
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Figure 1. Wire routing inside EPS Series pressure switch:
C
A
SWITCH
B
SCREWS
SWITCH ARM
NORMALLY CLOSED
NORMALLY OPEN
COM
A78-2616-01
D770-14-00 1 I56-919-02
Technical Manuals Online! - http://www.tech-man.com
Figure 2. Class B initiating circuit with single device:
COVER TAMPER SWITCH
1
CONTROL PANEL
2
END OF LINE DEVICE
INITIATING DEVICE
A78-2617-00
Figure 3. Class B initiating circuit with multiple devices:
1
CONTROL PANEL
2
Figure 4. Class A 4-wire initiating circuit with multiple devices:
INITIATING DEVICES
COVER TAMPER SWITCHES
END OF LINE DEVICE
A78-2618-00
COVER TAMPER
SUPERVISORY ZONE
CONTROL PANEL
SWITCHES
Three-Year Limited Warranty
System Sensor warrants its enclosed cover tamper switch to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this cover tamper switch. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the cover tamper switch which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
END OF LINE DEVICE
INITIATING DEVICES
A78-2619-00
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D770-14-00 2 I56-919-02
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
EPS10 Series Alarm Pressure Switches
Specifications
Contact Ratings: 10 A, 1/2 HP @ 125/250 VAC
2.5A @ 6/12/24 VDC
Overall Dimensions: See Figure 1 Operating Temperature Range: –40° to +160°F Maximum Service Pressure: 175 PSI Maximum Adjustment Range: 4 – 20 PSI Enclosure Rating: UL 4x — Indoor or Outdoor Use
NEMA 4 — Indoor or Outdoor Use
Approximate Differential: 3 PSI throughout range
Important
Please Read Carefully and Save
This instruction manual contains important information about the installation and operation of alarm pressure switches. Purchasers who install switches for use by others must leave this manual or a copy of it with the user.
Read all instructions carefully before installation, following only those instructions that apply to the model you are in­stalling.
Before installing any alarm device, be thoroughly familiar with:
NFPA 72: Installation, Maintenance, and Use of Protec-
tive Signaling Systems
NFPA 13: Installation of Sprinkler Systems NFPA 13A: Inspection, Testing, and Maintenance of Sprin-
kler Systems
Operation
As pressure changes, a diaphragm actuates 1 or 2 snap ac­tion switches. The pressure switch actuation is determined by adjustment settings.
Installation
1. Remove Cover Cover is held on by two tamper resistant screws. (Re­moval key is enclosed with pressure switch.)
2. Mounting the Switch The device is designed to be mounted in the upright or horizontal position; side mounting is also acceptable. Locate it where vibration, shock, and mechanical load­ing are minimal. Refer to piping diagram (Figure 2 on page 2).
Figure 1. Pressure switch basic dimensions:
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
4-1/4"
Other applicable NFPA standards, local codes, and the re­quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm condition. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
CAUTION
Do not use in potentially explosive atmospheres. Do not
leave unused wires exposed.
D770-08-00 1 I56-551-02
Technical Manuals Online! - http://www.tech-man.com
5-1/8"
LOCKING SCREW
GROUND SCREW (GREEN)
COM
AB
SWITCH #1
HEX ADJUSTMENT SCREW
MAIN ADJUSTMENT WHEEL
1/2" NPT
A78-2345-00
Figure 2. Typical piping diagram for EPS10-1, EPS10-2
WIRE TO ALARM INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
LOCAL ALARM
SHUT OFF
VALVE
WATER MOTOR GONG
RETARD
WET SYSTEM ALARM CHECK VALVE
OS & Y VALVE
TO SPRINKLER SYSTEM
WATER
BY-PASS
VALVE
WET SYSTEM ALARM CHECK VALVE
OS & Y VALVE
EPS10
TO SPRINKLER SYSTEM
WATER
BY-PASS
VALVE
WET SYSTEM WET SYSTEM DRY SYSTEM
a. Mount the device directly to the line via the 1/2" NPT
pressure connection. The use of teflon pipe sealant tape is recommended. Be sure the fitting is tight enough to prevent leaks.
b. Apply tightening torque to the black plastic hex por-
tion of device.
CAUTION
High voltage. Electrocution hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
WIRE TO ALARM
WATER MOTOR GONG
LOCAL ALARM
SHUT OFF
VALVE
RETARD
EPS10
INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
DRY SYSTEM ALARM CHECK VALVE
OS & Y VALVE
TO SPRINKLER SYSTEM
CHECK VALVE
WATER
BY-PASS
VALVE
EPS10
LOCAL ALARM
SHUT OFF
VALVE
Table 1. Electrical connections (referenced at factory settings):
MODEL EPS10-1
SWITCH AT 0 P.S.I.
B
COM
A
SWITCH AT 4-8 P.S.I. (HIGH TRIP PT.)
B
COM
A
SWITCH 1 BOTH SWITCHES ACTIVATE SIMULTANEOUSLY
COM
SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)
COM
MODEL EPS10-2
SWITCHES AT 0 P.S.I.
B
A
SW1 SW2
B
A
SW1 SW2
COM
COM
B A
B A
WIRE TO ALARM INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
WATER MOTOR GONG
A78-2398-00
3. Wire the device in accordance with the National Electri­cal Code. Two 7/8" diameter conduit connection holes have been provided in the mounting plate to accept stan­dard 1/2" conduit fittings (one is removable knock-out type). If a NEMA 4/UL 4x (waterproof unit) is required, waterproof flexible metallic conduit and appropriate conduit fittings must be used. Recommended connectors are Thomas and Betts PN 5332 (180° coupling), PN 5352 (90° coupling), and PN 5262 seal ring.
4. Connect wiring to terminals (see Figure 3 and Table 1).
Figure 3. Switch terminals:
SWITCH #1
COM
A
SWITCH #2
B
GROUND SCREW
LOCKING SCREW
COMMON TERMINALS
TERMINAL “A”
BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION. DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING. DO NOT LOOP WIRES.
SWITCH #2
TERMINAL “B”
A78-2346-00
D770-08-00 2 I56-551-02
Technical Manuals Online! - http://www.tech-man.com
Adjustments To Factory Settings
Both EPS10-1 and EPS10-2 devices are pre-adjusted at the factory to alarm at 4–8 PSI on rising pressure (see Table 2). Pressure switch settings may be adjusted in the field to ob­tain a different pressure alarm response from 4 PSI to 20 PSI. The switch has an override feature on the adjustment mechanism to prevent exceeding the 20 PSI max. setting of the switch. This override feature carries with it a tolerance band that may limit the upper adjustment to 16–20 PSI. Care must be used when setting the switch to ensure that the lower limit of 4 PSI is not exceeded. This will allow the switch to reset within the 3 PSI differential stated.
1. Install pressure switch as stated in “INSTALLATION”
portion of instruction manual. Attach pressure test source to system.
2. Back off locking screw (see Figure 1) to allow main ad-
justment wheel to rotate freely.
3. Test set point by slowly introducing pressure from the
pressure test source. When set point is found, reduce pressure to zero. Rotate main adjustment wheel (coun­terclockwise to increase pressure) and retest until switch trip point is at the desired pressure setting (4–20 PSI range). The approximate sensitivity of the adjustment wheel: 1 turn = 2.5 PSI. A reset differential of approxi­mately 3 PSI is typical throughout the entire adjustment range of switch.
4. Retest the set point several times to ensure accuracy of
setting.
5. Re-seat locking screw.
Table 2.
FACTORY SETTINGS (PSI)
MODEL
EPS10-1 EPS10-2
Fall
(Low Switch)
–– ––
Approx.
Reset
––––
Rise
(Hi Switch)
4– 8
Approx.
Reset 3 PSI Diff.4– 8 3 PSI Diff.
NOTE: The sensor assembly is not field replaceable. Do
not attempt to disassemble these parts. If you have any questions, consult System Sensor. System Sen­sor recommends careful consideration of the fol­lowing factors when specifying and installing Alarm Pressure Switches. Always refer to the In­stallation and Maintenance Instruction for spe­cific recommendations on individual devices before installing the unit.
• Electrical ratings stated in literature and on name­plates should not be exceeded.
• Overload on switch can cause failure on the first cycle. Always wire devices according to national and local electrical codes.
• Install units away from shock and vibration. Proper electrical fittings should be used to prevent moisture from entering the enclosure via the conduit.
• Test all devices for proper operation after initial instal­lation. Perform preventive maintenance and periodic testing as required by the applicable NFPA standards but not less than bi-monthly.
• Install a back-up control for all critical applications where control failure could endanger life or property. A backup control to serve as a high or low limit con­trol is especially recommended for applications where a runaway condition could result.
• Do not mount unit where ambient temperatures will exceed published limits.
• Avoid impact or mechanical loading.
D770-08-00 3 I56-551-02
Technical Manuals Online! - http://www.tech-man.com
Three-Year Limited Warranty
System Sensor warrants its enclosed pressure switch to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this pressure switch. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the pressure switch which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D770-08-00 4 I56-551-02
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
EPS40 Series and EPS120 Series Supervisory Pressure Switches
Specifications
Contact Ratings: 10 A, 1/2 HP @ 125/250 VAC
2.5A @ 6/12/24 VDC
Overall Dimensions: See Figure 1 Operating Temperature Range: –40°F to +160°F Maximum Service Pressure: EPS40-1, EPS40-2: 250 PSI
EPS120-1, EPS120-2: 250 PSI
Maximum Adjustment Range: EPS40-1, EPS40-2: 10 – 100 PSI
EPS120-1, EPS120-2: 10 – 200 PSI
Enclosure Rating: UL 4x — Indoor or Outdoor Use
NEMA 4 — Indoor or Outdoor Use
Approximate Differential: EPS40-1, EPS40-2: 3 PSI at 10 PSI
6 PSI at 100 PSI
EPS120-1, EPS120-2: 3 PSI at 10 PSI
9 PSI at 200 PSI
Important
Please Read Carefully and Save
This instruction manual contains important information about the installation and operation of supervisory pres­sure switches. Purchasers who install switches for use by others must leave this manual or a copy of it with the user.
Read all instructions carefully before installation, following only those instructions that apply to the model you are in­stalling.
Do not use in potentially explosive atmospheres. Do not
Operation
As pressure changes, a diaphragm actuates 1 or 2 snap ac­tion switches. The pressure switch actuation is determined by adjustment settings.
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
CAUTION
leave unused wires exposed.
Before installing any alarm device, be thoroughly familiar with:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems NFPA 25: Inspection, Testing, and Maintenance of Water-
based Fire Protection Systems
NFPA 13D: Standard for 1 and 2 Family Dwellings and
Manufactured Homes
NFPA 13R: Standard for Multi-family Dwellings
Other applicable NFPA standards, local codes, and the re­quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm condition. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
D770-17-00 1 I56-986-00
Technical Manuals Online! - http://www.tech-man.com
Figure 1. Pressure switch basic dimensions:
4-1/4"
COM
AB
SWITCH #1
MAIN ADJUSTMENT WHEEL
1/2" NPT
5-1/8"
LOCKING SCREW
GROUND SCREW (GREEN)
HEX ADJUSTMENT SCREW
A78-2345-00
Figure 2. Typical piping diagram for EPS40-1, EPS40-2
Figure 3. Typical piping diagram for EPS120-1, EPS120-2
EPS10
WIRE TO ALARM INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
WATER MOTOR GONG
LOCAL ALARM
SHUT OFF
VALVE
AIR LINE SHUT-OFF VALVE
CHECK VALVE
EPS40
WIRE TO SUPERVISORY CIRCUIT OF FIRE ALARM CONTROL PANEL
INSTALL BLEEDER VALVE FOR TESTING
DRY PIPE VALVE
OS & Y VALVE
TO SPRINKLER SYSTEM
CHECK VALVE
WATER
BY-PASS
TEST
VALVE
DRY SYSTEM
A78-2397-00
Installation
1. Remove Cover Cover is held on by two tamper resistant screws. (Re­moval key is enclosed with pressure switch.)
2. Mounting the Switch The device is designed to be mounted in the upright po­sition; side mounting is also acceptable. Locate it where vibration, shock, and mechanical loading are minimal. Refer to piping diagram above (Figures 2 and 3). a. Mount the device directly to the line via the 1/2" NPT
pressure connection. The use of teflon pipe sealant tape is recommended. Be sure the fitting is tight enough to prevent leaks.
b. Apply tightening torque to the black plastic hex por-
tion of the device.
TEST
OS & Y VALVE
EPS120
WET SYSTEM ALARM CHECK VALVE
OS & Y VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
WATER MOTOR GONG
RETARD
A78-2398-02
AIR
PRESSURE
SUPPLY
BLEEDER
VALVE
CAUTION
High voltage. Electrocution hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
3. Wire the device in accordance with the National Electri­cal Code. Two 7/8" diameter conduit connection holes have been provided in the mounting plate to accept stan­dard 1/2" conduit fittings (one is removable knock-out type). If a NEMA 4/UL 4x (waterproof unit) is required, waterproof flexible metallic conduit and appropriate conduit fittings must be used. Recommended connectors are Thomas and Betts PN 5332 (180° coupling), PN 5352 (90° coupling), and PN 5262 seal ring.
4. Connect wiring to terminals (see Figure 4 and Table 1).
Figure 4. Switch location:
SWITCH #1
A
SWITCH #2
B
GROUND SCREW
LOCKING SCREW
COMMON TERMINALS
TERMINAL “A”
COM
BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION. DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING. DO NOT LOOP WIRES.
SWITCH #2
TERMINAL “B”
A78-2346-00
Table 1. Electrical connections (referenced at factory settings):
MODELS EPS40-1, EPS120-1
SWITCH AT NORMAL SYSTEM PRESSURE
B
COM
A
SWITCH AT TRIP POINT
B
COM
A
SWITCH 1
MODELS EPS40-2, EPS120-2
SWITCHES AT LOW TRIP POINT
B
COM
A
SW1 SW2
SWITCHES AT NORMAL SYSTEM PRESSURE
B
COM
A
SWITCHES AT HIGH TRIP POINT
B
COM
A
SW1 SW2
COM
COM
COM
B
A
B
A
B
A
D770-17-00 2 I56-986-00
Technical Manuals Online! - http://www.tech-man.com
SW2SW1
Adjustments To Factory Settings
Figure 5. Adjustments (Dual-switch model shown):
Table 2.
FACTORY SETTINGS (PSI)
MODEL
EPS40-1 EPS40-2
EPS120-1 EPS120-2
Fall
(Low Switch)
30± 1.5 30± 1.5
105 - 110
Rise
(Hi Switch)
––
50± 2.5
––
105 - 110 120 - 125
Table 3.
FIELD SETTINGS (PSI)MODEL
EPS40-1 EPS40-2
EPS120-1 EPS120-2
10-100 10-100 10-200
10-200
Single-switch Model — EPS40-1 and EPS120-1
1. Install pressure switch as stated in “INSTALLATION” portion of instruction manual. Attach pressure test source to system.
2. Back off locking screw (see Figure 1) to allow main ad­justment wheel to rotate freely.
3. Test the switch for the set point by introducing 40 PSI pressure from the pressure test source for the EPS40-1 (115 PSI for the EPS120-1). Decrease pressure slowly un­til the switch trips. Rotate adjustment wheel (counter­clockwise to increase pressure) and retest by first introducing a higher pressure than desired and slowly reducing pressure until the switch trips. Repeat process until switch trip point is at desired pressure setting. The approximate sensitivity of the adjustment wheel: 1/2 turn = 11 PSI for the EPS40-1; 1/2 turn = 40 PSI for the EPS120-1.
4. Retest the set point several times to ensure accuracy of setting.
5. Re-seat locking screw.
SWITCH 2
ADJUSTING SCREW 1/4" HEX HEAD (NOT PRESENT IN SINGLE SWITCH MODELS)
(LOW SWITCH
EPS40-2 AND
EPS120-2)
SWITCH 1 (HIGH SWITCH EPS40-2 AND EPS120-2; LOW SWITCH EPS40-1)
MAIN ADJUSTING WHEEL (TURN COUNTERCLOCKWISE TO INCREASE PRESSURE)
A78-2347-00
for the EPS40-2; 1/2 turn = 40 PSI for the EPS120-2.
Option 2: To adjust the pressure window size and the nominal setting of the pressure window, adjust the main adjustment wheel until the high switch (SW1) trips at the desired pressure using the pressure test source. De­crease the pressure until the low switch (SW2) trips. Note pressure and determine how much change is de­sired on the low switch. Adjust the 1/4" hex screw to ei- ther increase (counterclockwise) or decrease (clockwise) the window size. (The low switch will be af­fected.) The approximate sensitivity of the hex screw ad­justment: 1/2 turn = 5 PSI. An approximate maximum window size of 30 PSI is obtainable within the differen­tial limits stated on page 1. Retest the high switch after adjusting the low switch.
4. Retest the set points several times to ensure the accuracy of the settings.
5. Re-seat locking screw.
NOTE: The sensor assembly is not field replaceable. Do
not attempt to disassemble these parts. If you have any questions, consult System Sensor. System Sen­sor recommends careful consideration of the fol­lowing factors when specifying and installing Alarm and Supervisory Pressure Switches. Always refer to the Installation and Maintenance Instruc­tion for specific recommendations on individual devices before installing the unit.
Dual-switch Model — EPS40-2 and EPS120-2
1. Install pressure switch as stated in “INSTALLATION” portion of instruction manual. Attach pressure test source to system.
2. Back off locking screw (see Figure 1) to allow main ad­justment wheel to rotate freely.
3. Option 1: To adjust the nominal setting of the pressure window (low switch setting to high switch setting) with­out affecting the size of the window, adjust the main ad­justment wheel to the desired setting using the pressure source to verify each switch setting. The approximate sensitivity of the adjustment wheel: 1/2 turn = 11 PSI
D770-17-00 3 I56-986-00
Technical Manuals Online! - http://www.tech-man.com
• Electrical ratings stated in literature and on name­plates should not be exceeded.
• Overload on switch can cause failure on the first cycle. Always wire devices according to national and local electrical codes.
• Install units away from shock and vibration. Proper electrical fittings should be used to prevent moisture from entering the enclosure via the conduit.
• Test all devices for proper operation after initial instal­lation. Perform preventive maintenance and periodic testing as required by the applicable NFPA standards but not less than bi-monthly.
• Install a back-up control for all critical applications where control failure could endanger life or property. A backup control to serve as a high or low limit con­trol is especially recommended for applications where a runaway condition could result.
• Do not mount unit where ambient temperatures will exceed published limits.
• Avoid impact or mechanical loading.
Three-Year Limited Warranty
System Sensor warrants its enclosed pressure switch to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this pressure switch. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the pressure switch which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D770-17-00 4 I56-986-00
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
Three-Year Limited Warranty
System Sensor warrants its enclosed pressure switch to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this pressure switch. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the pressure switch which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D770-08-00 4 I56-551-02
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SSM and SSV BELL Series
Specifications
SSM Series:
Starting Voltage: 12 VDC Rated Voltage: 24 VDC Operating Voltage Range: 19.2 - 26.4 VDC Average Current (at rated voltage): 0.03 A Operating Temperature: -31° to 150°F (-35° to +66°C)
SSV Series:
Starting Voltage: 96 VAC Rated Voltage: 120 VAC Operating Voltage Range: 96 - 132 VAC Average Current (at rated voltage: 0.047 A Operating Temperature: -31° to 150°F (-35° to +66°C)
UL Reverberant Room
Sound Output per UL 464 (dBA)
24 VDC SSM
SSM24-6 (6˝, 24 VDC, P, S) 85 SSM24-8 (8˝, 24 VDC, P, S) 85 SSM24-10 (10˝, 24 VDC, P, S) 85
120 VAC SSV
SSV120-6 (6˝, 120 VAC) 82 SSV120-8 (8˝, 120 VAC) 85 SSV120-10 (10˝, 120 VAC) 82 P = Polarized S = Suppressed
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Important
Please Read Carefully and Save
This instruction manual contains important information about the installation and operation of bells. Purchasers who install bells for use by others must leave this manual or a copy of it with the user.
System Sensor supplies bells for nearly all sprinkler/fire alarm/burglar applications.
These instructions apply to all System Sensor bells in the series. Read all instructions carefully before beginning. Fol­low only those instructions that apply to the model you are installing.
CAUTION
Do not use in potentially explosive atmospheres.
Do not leave any unused wires exposed.
D770-11-00 1 I56-674-04
Technical Manuals Online! - http://www.tech-man.com
General Description
The National Fire Protection Association has published codes, standards, and recommended practices for the in­stallation and use of the above appliances. It is recom­mended that the installer be familiar with these requirements, with local codes, and any special require­ments of the authority having jurisdiction.
These bells are intended to be connected to alarm indicat­ing circuits of UL listed fire alarm control panels. The SSM series is polarized to enable supervision of the installation wiring. The SSM bells require 24 VDC and the SSV bells re­quire 120 VAC.
Before installing any alarm device, be thoroughly familiar with:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems NFPA 25: Inspection, Testing, and Maintenance of Water-
Based Fire Protection Systems
Other applicable NFPA standards, local codes, and the re­quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm condition. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
Installation
WARNING
High voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
Operational Testing
Always notify a central station monitoring the system be­fore repairing, maintaining, or testing alarm devices.
Upon completion of initial installation, all bells shall be tested per NFPA 72. Periodic testing should be performed at least annually. Test more often if required by the authority having jurisdiction. Under normal conditions, System Sen­sor bells should provide years of trouble-free service; how­ever, after extended service, parts of the bell may become worn. In this case, bell should be replaced.
Do not repair or replace any bell components in the field. If bell does not perform properly, replace the entire unit. Failure to follow this instruction may result in fail­ure of the bell to report an alarm condition.
1. Remove the gong.
2. Wire the bell in the circuit. See Figure 1, page 3.
3. Mount the bell mechanism on a 4˝ square electrical box with the striker facing down. See Figures 2–4, page 3.
4. Replace the gong.
5. The top of the bell must be mounted a minimum of 90˝ above the floor, or within 6˝ of the ceiling.
CAUTION
Do not loop wire under terminals. Break wire runs to pro­vide supervision of connections.
Audibility Rating Measurement
Sound level measurements are made in accordance with UL Standard 464. The sound power output is measured in a re­verberant room.
D770-11-00 2 I56-674-04
Technical Manuals Online! - http://www.tech-man.com
Figure 1. Typical SSM and SSV bell wiring diagrams:
WIRING (REAR VIEW) OBSERVE POLARITY ON SSMA MODELS
USE BOTH LEADS FOR CONNECTION. BREAK WIRE RUN TO PROVIDE ELECTRICAL SUPERVISION.
RED
RED
BLACK
BLACK
WIRE NUTS
FROM
CONTROL
PANEL
– +
(User supplied)
24VDC WIRING DIAGRAM
– +
Figure 2. Basic mechanism and gongs:
3-1/8" 10", 8" BELLS 2-19/32" 6" BELLS
10"
8"
6"
TO NEXT BELL OR END-OF-LINE RESISTOR
A78-2390-01 A78-2390-02
RED
RED
WIRE NUTS
FROM
(User supplied)
CONTROL
PANEL OR
PRECEDING BELL
120VAC WIRING DIAGRAM
Figure 3. Surface installation:
8-32 SCREW
USE BOTH LEADS FOR CONNECTION. BREAK WIRE RUN TO PROVIDE ELECTRICAL SUPERVISION.
BLACK
BLACK
TO NEXT BELL OR TERMINATE SEPARATELY IF LAST BELL
4" SQUARE ELECTRICAL BOX (NOT INCLUDED)
STRIKER LOCATED ON BOTTOM
3-3/8"
(HOLES ARE LOCATED TO MOUNT TO A
STANDARD 4" SQUARE OUTLET BOX)
3-3/8" SQUARE
MOUNTING HOLE PATTERN
OF BELL (VISIBLE FROM REAR)
Figure 4. Weatherproof installation:
8-32 SCREW
A78-1562-02
4" SQUARE WEATHERPROOF BACKBOX MODEL WBB (NOT INCLUDED
8-32 SCREW
A78-2387-01
8-32 SCREW (4 TOTAL)
D770-11-00 3 I56-674-04
Technical Manuals Online! - http://www.tech-man.com
A78-2388-01
WARNING
The Limitations of Alarm Devices
System Sensor bells are designed to provide fire and security hazard warning.
Bells may not work or operate properly if sprinkler piping being monitored for water flow is plugged with pipe scale, mud, stones, or other foreign material. Sprinkler systems should be checked regularly for such blocking material following the instructions in Chapter 10 of NFPA 25.
BELLS WILL NOT WORK WITHOUT POWER. Bells get their power from the fire or security panel monitoring the alarm system or AC circuit. If power is cut for any reason, the device will not provide the desired audible warning.
Alarms generated by the activation of waterflow detectors or supervisory switches may not be received by a central station if telephone or other communication lines to the detector are out of service, disabled, or open.
Three-Year Limited Warranty
System Sensor warrants its enclosed SSM or SSV bell to be free from de­fects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this SSM or SSV bell. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the SSM or SSV bell which is found to be defective in materials or work­manship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
BELLS MAY NOT BE HEARD. The loudness of the alarm device meets or exceeds current Underwriters Laboratories’ standards. However, the bell may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. The bell may not be heard on a differ­ent floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machinery, or mu­sic appliances that may prevent alert persons from hearing the alarm. THE
BELL MAY NOT BE HEARD BY PERSONS WHO ARE HEARING IM­PAIRED.
If valves controlling the water supply to a sprinkler system are closed, vane-type waterflow detectors will not work and bells will not sound. All valves controlling a sprinkler water supply should be sealed or locked in the normally open position. The normally open position of the valve should be monitored by a valve supervisory switch.
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
D770-11-00 4 I56-674-04
Technical Manuals Online! - http://www.tech-man.com
© System Sensor 1996
Loading...