System Sensor WFD20A, WFD30-2A, WFD25A, WFD60A, WFD80A Installation Instruction

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
CAUTION
CAUTION
CAUTION
WFDA Vane-type Waterflow Detectors
SPECIFICATIONS
Contact Ratings: 10 A @ 125/250 VAC ; 2.5 A @ 24 VDC Cover Tamper Switch Ratings: 5 A @ 125/250 VAC; 2.5 A @ 24 VDC Triggering Threshold Bandwidth (Flow Rate): 4 to 10 gpm Static Pressure Rating: See models listed below Dimensions, Installed: 3.5 in H × 3.0 in W × 6.7 in D Operating Temperature Range: 0°C to 49°C (32°F to 120°F) Compatible Pipe: Steel water pipe, schedule 10 through 40 Shipping Weight: 4 to 7 lbs, according to size All WFDA waterflow detectors are ULC approved. U.S. Patent Numbers: 5,213,205
I56-2338-004R
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, Fax: 630-377-6495
www.systemsenor.com
IMPORTANT
Please Read Carefully And Save
This instruction manual contains important information about the installation and operation of waterflow detectors. Purchasers who install waterflow detec­tors for use by others must leave this manual or a copy of it with the user.
Use vane-type waterflow detectors in wet-pipe systems only. Do NOT use them in dry pipe, deluge, or pre action systems. The sudden inrush of water in such systems may break the vane or damage the mechanism.
Do not use in potentially explosive atmospheres. Do not allow unused wires to remain exposed.
PRINCIPLES OF OPERATION
Model
WFD20A 2 (50 mm) 10 thru 40 450
WFD25A 2.5 (65 mm) 10 thru 40 450
WFD30-2A 3 (80 mm) 10 thru 40 450
WFD40A 4 (100 mm) 10 thru 40 450
WFD50A 5 (130 mm) 10 thru 40 450
WFD60A 6 (150 mm) 10 thru 40 450*
WFD80A 8 (200 mm) 10 thru 40 450*
*Max Pressure Rating 400 psig as Approved by Factory Mutual Research.
Do NOT use any of the WFDA models on copper pipe. The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from functioning properly.
Do NOT install steel or iron pipe sections in copper piping for mounting a waterflow detector. Incompatibility between the dissimilar metals causes bi­metallic corrosion.
D770-44-00 1 I56-2338-004R
Pipe Size
(inches)
Pipe
Schedule
Max. Pressure
Rating (psig)
INSTALLATION GUIDELINES
Before installing any waterflow alarm device, be thoroughly familiar with:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems NFPA 25: Inspection, Testing and Maintenance of Sprinkler Systems,
Section 5.3.3.2
CAN/ULC S524 Other applicable NFPA standards, local codes, and the requirements of the
authority having jurisdiction
NOTE: Installation methods other than those listed in this installation manual may prevent the device from reporting the flow of water in the event the asso­ciated sprinkler system is activated by a fire. System Sensor is not responsible for devices that have been improperly installed, tested or maintained.
1. Mount the detector where there is adequate clearance for installation and
removal and a clear view of it for inspections. See Figure 1 for mounting dimensions.
2. Locate the detector 6 to 7 ft. above the floor to protect from acciden­tal damage.
3. On horizontal runs, position the detector on the top or side of the pipe. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector.
For vertical flow applications, mount the detector on pipe through which
water flows upward. Otherwise, the unit may not operate properly.
4. Mount the detector at least 6 inches from a fitting that changes the direc­tion of water flow and no less than 24 inches from a valve or drain.
5. Be sure the direction-of-flow arrow matches the direction of flow in the pipe.
MOUNTING INSTRUCTIONS
1. Drain the pipe.
2. Cut a hole at the desired location. Center the hole in the pipe, as shown in Figure 2, and be sure the hole is perpendicular to the center of the pipe. Before drilling, use a punch or scribe to mark the drill site to pre­vent the bit from slipping. If the hole is off center, the vane will bind against the inside wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See Table 1 for hole size.
When drilling the hole with a hole saw, make certain that the center of the cut does not remain in the pipe.
3. Remove burrs and sharp edges from the hole. Clean and remove all scale and foreign matter from the inside of the pipe for one diameter on each side of the hole to ensure free movement of the vane. Clean the outside of the pipe to remove dirt, metal chips, and cutting lubricant.
4. Seat the gasket against the saddle and mount the detector directly to the pipe. Carefully roll the vane opposite the direction of flow and insert it through the hole. Seat the saddle firmly against the pipe so that the locat­ing boss goes into the hole.
5. Install the U-bolt, tightening the nuts alternately to ensure a uniform seal. See Table 1 for torque values.
COVER
WATERFLOW
PIPE
U-BOLT
TAMPER PROOF
WRENCH
(P/N WFDW)
DELAY
MECHANISM
(REPLACEMENT
(P/N A3008-00)
MOUNTING PLATE
PIPE SADDLE
PLASTIC VANE
ROLL PADDLE OPPOSITE OF FLOW ARROW
WHILE INSERTING
SADDLE GASKET
REFER TO
TABLE 1
ELECTRICAL
CONDUIT
ENTRANCE
U-BOLT
NUT
TERMINAL BLOCK
(REPLACEMENT
P/N A77-01-02)
COVER TAMPER SWITCH
WARNING
6. Remove the metal cover with the tamper-proof wrench provided. Move
CAUTION
U-BOLT
NUT
PIPE
SADDLE
U-BOLT
WIDTH: SEE TABLE
PLASTIC
VANE
PIPE
1.70˝
3.73˝ MODEL
WFD20A
WFD25A
WFD30-2A
WFD40A
WFD60A
WFD80A
WIDTH
4.60˝
4.60˝
5.20˝
6.77˝
9.06˝
10.75˝
WRONG
RIGHT
REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE
AND FOREIGN MATTER FROM INSIDE WALL OF PIPE.
the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the cause before proceeding.
Be sure the direction-of-flow arrow points in the right direction or else water flow will go unreported, see Figure 3.
FIGURE 1. MOUNTING DIMENSIONS:
PRE OPERATION TESTING
1. Fill the sprinkler system and check for leaks around the waterflow detec­tor. If it leaks, first check for the proper torque on the U-bolt nuts. If the leak persists, drain the system and remove the detector (refer to Mainte­nance). Check for dirt or foreign objects under the gasket, and make sure that the pipe surface is not dented. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped.
2. Connect an ohmmeter or continuity tester across the COM and B-NO switch terminals. The ohmmeter should indicate an open circuit.
3. Deflect the actuator lever and hold it until the pneumatic delay shaft releases the switch buttons. The ohmmeter or continuity tester should show a short circuit after the delay has elapsed. If there is no delay, check the setting of the delay adjustment dial.
FIGURE 3. ASSEMBLY DIAGRAM:
FIGURE 2. MOUNTING HOLE LOCATION:
TABLE 1:
30-2, 40, 50, 60, 80 55-60 ft.-lb.
W0151-00
WFD MODEL HOLE SIZE TORQUE
20,25 1
1
/4˝ 30-35ft-lb.
W0106-00
W0373-00
WIRING
1. All models have two SPDT switches. Switch contacts COM and B-NO are closed when water is flowing and open when it is not. Connect the switches, as shown in Figure 4, depending on the application.
2. When connected to a listed sprinkler/fire alarm control panel, the initiat­ing circuit must be nonsilenceable.
3. A ground screw is provided with all waterflow detectors. When ground­ing is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 5A.
4. If a second conduit entry is required, remove the knockout plug using a flat blade screwdriver as shown on Figure 5B. Strike sharply with a ham­mer to pierce the wall of the knockout plug. Move to an adjacent wall section and repeat until the plug falls out. Make sure that the waterflow detector is supported adequately during this operation to avoid injury.
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in injury or death.