System Sensor WFD User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CAUTION
CAUTION
CAUTION
CAUTION
3825 Ohio Avenue, St. Charles, Illinois 60174
WFDE Vane-type Waterflow Detector
SPECIFICATIONS
Contact Ratings: 10 A @ 125/250 VAC~; 2.5 A @ 24 VDC EC–certificate Number: 0786-CPD-40151 Triggering Flow Rate: Refer to Table 1 EN12259–5 Static Pressure Rating (maximum): 17.25 bar (250 psi) (1725 KPa); 16 bar (VdS) Operating Temperature Ranges: 0°C to 68°C (32°F to 155°F) Compatible Pipe: Steel Water Pipe (Refer to Table 1) Shipping Weight: 1.8 – 3.2 Kilograms Enclosure Rating: Nema4/IP54
IMPORTANT
Please Read Carefully And Save
Read all instructions carefully before beginning. Follow only those instruc­tions that apply to the model you are installing.
Use vane-type waterflow detectors in wet-pipe systems only. DO NOT USE IN DRY-PIPE, DELUGE, OR PRE-ACTION SYSTEMS. The sudden inrush of water in such systems may break the vane or damage the mechanism.
Do not use in potentially explosive atmospheres. Do not leave unused wires exposed.
PRINCIPLES OF OPERATION
Vane type waterflow detectors mount to water-filled pipes in sprinkler sys­tems. Waterflow in the pipe deflects a vane. Deflection of the vane produces a switched output, usually after a specified delay. All WFDEs have a pneumati­cally controlled mechanical delay mechanism. Delays are noncumulative; they reset if the flow of water stops or drops below minimum triggering flow rate before the entire delay has elapsed. All detectors will activate on a sustained flow of water greater than the maximum specified in Table 1, but will not acti­vate if the flow rate is less than the minimum specified in Table 1.
This System Sensor installation manual covers the following waterflow detec­tors for sprinkler/fire alarm applications.
TABLE 1:
VdS LPCB
Model
Number
WFD20E 50 (2) 60.3 2.3/2.9 WFD25E 66 (2,5) 76.1 2.6/2.9 76.0 3.6
WFD30-2E 80 (3) 88.9 2.9/3.2 88.8 4.0
WFD40E 100 (4) 114.3 3.2/3.6 114.1 4.5 WFD60E 150 (6) 168.3 4.0/4.5 165.1 5.0 WFD80E 200 (8) 219.1 4.5/5.9 219.1 6.3
DN Ref.
Pipe Size
mm (in)
Nominal
Pipe O.D.
(mm)
Wall
Thickness
(mm)
Triggering Flow Rate (liters/min)
30-57
Nominal
Pipe O.D.
(mm)
60.3 3.6
Wall
Thickness
(mm)
STEEL PIPE COMPATIBILITY
DO NOT USE THE ABOVE MODELS ON COPPER PIPE. The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from functioning properly.
DO NOT INSTALL STEEL OR IRON PIPE SECTIONS IN COPPER PIPING FOR MOUNTING A WATERFLOW DETECTOR. Incompatibility between the dis­similar metals will cause bimetallic corrosion.
INSTALLATION GUIDELINES
Before installing any waterflow alarm device, be thoroughly familiar with national codes of practice and the requirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report a waterflow condition. System Sensor is not responsible for devices that have been improperly installed, tested or maintained.
D770-53-00 1 I56-2617-004R
1. Mount the detector where there is adequate clearance for installation and removal and a clear view of it for inspections. See Figure 1 for mounting dimensions.
2. Locate the unit 1.8 – 2.1 meters above the floor to protect from damage.
3. On horizontal runs, position the detector on top or on the side of the pipe. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector. For vertical flow ap­plications, mount detector on pipe where upflow conditions exist. Failure to do so may prevent unit from operating properly.
4. Mount detector at least 15 cm from a fitting which changes the direction of the water flow, or no closer than 61 cm from a valve or drain.
5. BE SURE DIRECTION-OF-FLOW ARROW MATCHES ACTUAL DIREC­TION OF FLOW IN THE PIPE.
MOUNTING INSTRUCTIONS
1. Drain the pipe.
2. Cut a hole in the desired location. Center the hole in the pipe as shown in Figure 2, and be sure the hole is perpendicular to the center of the pipe. If the hole is off center, the vane will bind against the inside wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See Table 2 for hole size. Before drilling, use a punch or scribe to mark the drill site to keep the bit from slipping.
When drilling out hole, make certain that center of hole saw cut does not remain in pipe.
TABLE 2:
MODEL NUMBER HOLE DIAMETER TORQUE SETTING
WFD20E
WFD25E
31.8 mm +1.6 mm 11/4 in +1/16 in
WFD30-2E
WFD40E
50.8 mm + 1.6 mm
WFD60E
WFD80E
3. Remove burrs and sharp edges from hole. Clean out scale and foreign mat­ter from inside wall of pipe to ensure free movement of the vane. Clean the outside of the pipe to remove dirt, metal chips, and cutting lubricant.
4. Seat the saddle gasket against the saddle and mount detector directly to pipe. Carefully roll the vane opposite the direction of flow and insert it through the hole (see Figure 5). Seat the saddle firmly against the pipe so that the locating boss goes into the hole.
5.
Install the U-bolt around the pipe. Thread both nuts onto the U-bolt and tighten them alternately to ensure a uniform seal. See Table 2 for torque values.
6. Remove the metal cover with the tamper proof wrench provided. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the problem before proceeding.
Be sure the direction-of-flow arrow points in the correct direction, otherwise a waterflow condition will go unreported. See Figure 5.
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
40.7 - 47.5 NT-M 30 - 35 FT-LBS
74.6 - 81.3 NT-M
2 in +1/16 in
55 - 60 FT-LBS
I56-2617-004R
FIGURE 1. MOUNTING DIMENSIONS:
9.5 CM
OVERALL WIDTH = PIPE DIAMETER + 7.6 CM (3˝)
WRONG
AND FOREIGN MATTER FROM INSIDE WALL OF PIPE.
WARNING
(33/4˝)
7.6 CM (3˝)
PIPE DIAMETER
PLUS 13.3 CM
1
/4˝)
U-BOLT
(5
NUT
PIPE
SADDLE
PIPE
PIPE
VANE
U-BOLT
W0105-00
FIGURE 2. LOCATION OF MOUNTING HOLE:
RIGHT
REMOVE BURRS FROM EDGE OF HOLE. CLEAN OUT SCALE
W0106-00
PREOPERATION TESTING
1. Fill the sprinkler system and check for leaks around the WFDE. If it leaks, first check for proper torque on U-bolt nuts. If leak persists, drain the system and remove the detector (see removal instructions under Maintenance). Check for dirt or foreign objects under the gasket. Check that pipe surface is not dented. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped.
2. Connect an ohmmeter or continuity tester across (COM and B-NO) termi­nal switch contacts (see Figure 3). The ohmmeter should show an open circuit, no continuity.
3. Deflect the actuator lever and hold it until the pneumatic delay shaft releases the switch buttons. The ohmmeter or continuity tester should show a short circuit after the delay has elapsed. If there is no delay, check the setting of the delay adjustment dial.
FIELD WIRING
1. All models have two SPDT switches. Switch contacts (COM and B-NO) are closed when water is flowing and open when water is not flowing. Con­nect the switches as shown in Figure 3 depending on the application.
2. When connected to a listed sprinkler/fire alarm control panel, the initiat­ing circuit must be non-silenceable.
3. A ground screw is provided with all WFDE units. When grounding is re­quired, clamp wire with screw in hole located between conduit entrance holes, see Figure 6.
4. Use proper waterproof conduit fittings where required.
5. A 22.2 mm conduit hole is provided for electrical connection. An additional
22.2 mm diameter knockout is provided for multiple line connections.
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a de­vice to which AC power is applied. Doing so may result in severe injury or death.
When utilizing switches at voltages greater than 74VDC or 49VAC~means to provide all–pole disconnection must be incorporated in the field wiring, such as a circuit breaker.
FIGURE 3. FIELD WIRING:
UL-LISTED COMPATIBLE CONTROL PANEL
LOOP
+
+
POWER 24VDC OR 120VAC
INITIATING
SSV120-X
SUGGESTED EOL
RESISTOR
SSM24-X
NOTE: COMMON AND B-NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFLECTED, I.E., WHEN WATER IS FLOWING. DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR.
CONTACT RATINGS
125/250 VAC
24 VDC
SCHEMATIC OF INDIVIDUAL SWITCH IN “NO WATERFLOW” CONDITION
BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION. DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING. DO NOT LOOP WIRES.
10 AMPS
2.5 AMPS
A-NC
COM
B-NO
W0356-01
MECHANICAL DELAY ADJUSTMENT
The pneumatic delay is preset at dial setting 25 at the factory. To adjust the delay, turn the adjustment dial on the delay mechanism. Turn clockwise to increase the delay, counterclockwise to decrease the delay. Delay can be ad­justed over a range from 0 to 30 seconds maximum, see Figure 4.
NOTE: Set the delay to the minimum required to prevent false alarms due to flow surges.
After extended service, parts of the detector may become worn reducing the delay time and causing false alarms. If this happens, increase the delay.
FIGURE 4. DELAY ADJUSTMENT DIAL:
DELAY
ADJUSTMENT
DIAL
0
5
10
25
20
15
DIAL SETTING
0
DIAL SETTING EQUALS DELAY IN SECONDS REFERENCE ONLY.
10 15 25
5
20
W0102-04
D770-53-00 2 I56-2617-004R
Loading...
+ 2 hidden pages