INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
M500S Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.5mA (LED On)
Operating Current: 350 µA max., 1 communication every 5 seconds 47k EOL resistor; 485 µA max. (Communicating, NAC Shorted)
Maximum NAC Line Loss: 4 VDC
External Supply Voltage (between Terminals T10 and T11)
Maximum (NAC): Regulated 24VDC
Maximum (Speakers): 70.07 V RMS, 50 W
Max. NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4.675˝ H x 4.275˝ W x 1.4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box; CB500 Barrier
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
I56-3850-005
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
M500S Supervised Control Modules are intended for use in intelligent, twowire systems, where the individual address of each module is selected using
the built-in rotary decade switches. This module is used to switch an external
power supply, which can be a DC power supply or an audio amplifier (up
to 80 VRMS), to notification appliances. It also supervises the wiring to the
connected loads and reports their status to the panel as NORMAL, OPEN,
or SHORT CIRCUIT. The M500S has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator. This
module can be used to replace an M500C module that has been configured for
supervised wiring operation.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed compatible system control panels only.
FIGURE 1. CONTROLS AND INDICATORS:
C0909-01
MOUNTING
The M500S mounts directly to 4-inch square electrical boxes (see Figure 2A).
The box must have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500) are available from System Sensor. The module can also
mount to the DNR(W) duct housing.
FIGURE 2A. MODULE MOUNTING FIGURE 2B:
WITH BARRIER:
ISOLATED
QUADRANT
C1050-00
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. When using control modules in nonpower limited applications, the
System Sensor CB500 Module Barrier must be used to meet UL requirements
for the separation of power-limited and nonpower-limited terminals and wiring. The barrier must be inserted into a 4˝×4˝×21/8˝ junction box, and the
control module must be placed into the barrier and attached to the junction
box (Figure 2A). The power-limited wiring must be placed into the isolated
quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in
Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is 1/4“ to 3/8”). Exposed conductor should be secured under the clamping plate
and should not protrude beyond the terminal block area. Caution: Do not loop
wire under terminals. Break wire run to provide supervision of connections.
SS-460-001 1 I56-3850-005

FIGURE 3. TYPICAL NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Y:
DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF CONNECTIONS.
24 VDC POWER SUPPLY
ISOLATED, REGULATED,
POWER LIMITED PER NFPA 70.
CONTROL
MODULE
LISTED FOR FIRE PROTECTION
WITH BATTERY BACKUP.
MODULE POLARITIES ARE
SHOWN IN ALARM
(−)
(+)
(−)
(+)
(−)(−)
47K EOL
RESISTOR
ALL WIRING SHOWN IS SUPERVISED
ELR-47K
UL LISTED EOL RELAY
SHOWN ENERGIZED
24 VDC COIL EOLR-1
(+)
TO NEXT CONTROL MODULE OR END-OF-LINE
RELAY. ONE RELAY REQUIRED FOR EACH
CIRCUIT. SOME CONTROL PANELS HAVE RELAY
BUILT IN AND DO NOT REQUIRE EXTERNAL
(+)
*NOTE: ANY FAULT IN THE POWER SUPPLY IS
LIMITED TO THAT ZONE AND DOES NOT
RESULT IN A FAULT IN A SEPARATE ZONE.
WIRING. REFER TO PANEL MANUAL.
FIGURE 4. TYPICAL FAULT TOLERANT NOTIFICATION APPLIANCE CIRCUIT CONFIGURATION, NFPA STYLE Z:
24 VDC POWER SUPPLY
ISOLATED, REGULATED, POWER
LIMITED PER NFPA 70. LISTED
FOR FIRE PROTECTION WITH
BATTERY BACKUP.
DO NOT LOOP WIRE ON TERMINALS 10 & 11.
BREAK WIRE RUN TO PROVIDE SUPERVISION
(–)
(+)
24 VDC CIRCUIT
OF CONNECTIONS.
CONTROL
MODULE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
LISTED COMPATIBLE
CONTROL PANELS ONLY
(−)
PANEL OR
(+)
PREVIOUS
FROM
DEVICE
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
AND POWER LIMITED
(−)
(+)
(–)
(+)
TO NEXT
DEVICE
FROM
PANEL OR
PREVIOUS
DEVICE
C0913-05
EOL RESISTOR
IS INTERNAL AT
TERMINALS
8 & 9
UL LISTED EOL
RELAY SHOWN
ENERGIZED
24 VDC COIL
EOLR-1
MODULE POLARITIES ARE
SHOWN IN ALARM
(–)
(+)
TO NEXT CONTROL MODULE OR
END-OF-LINE RELAY. ONE RELAY
REQUIRED FOR EACH CIRCUIT.
SOME CONTROL PANELS HAVE
RELAY BUILT IN AND DO NOT
REQUIRE EXTERNAL WIRING.
REFER TO PANEL MANUAL.
(–)
(+)
(–)
(+)
ALL WIRING SHOWN IS SUPERVISED
*NOTE: ANY FAULT IN THE POWER SUPPLY
IS LIMITED TO THAT ZONE AND DOES NOT
RESULT IN A FAULT IN A SEPARATE ZONE.
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX. TWISTED PAIR
IS RECOMMENDED
AND POWER LIMITED
(–)
(+)
DEVICE
TO
NEXT
C0914-05
SS-460-001 2 I56-3850-005