System Sensor SSM Series, SSV Series Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SSM and SSV BELL Series
Specifications
SSM Series:
Starting Voltage: 12 VDC Rated Voltage: 24 VDC Operating Voltage Range: 19.2 - 26.4 VDC Average Current (at rated voltage): 0.03 A Operating Temperature: -31° to 150°F (-35° to +66°C)
SSV Series:
Starting Voltage: 96 VAC Rated Voltage: 120 VAC Operating Voltage Range: 96 - 132 VAC Average Current (at rated voltage: 0.047 A Operating Temperature: -31° to 150°F (-35° to +66°C)
UL Reverberant Room
Sound Output per UL 464 (dBA)
24 VDC SSM
SSM24-6 (6˝, 24 VDC, P, S) 85 SSM24-8 (8˝, 24 VDC, P, S) 85 SSM24-10 (10˝, 24 VDC, P, S) 85
120 VAC SSV
SSV120-6 (6˝, 120 VAC) 82 SSV120-8 (8˝, 120 VAC) 85 SSV120-10 (10˝, 120 VAC) 82 P = Polarized S = Suppressed
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Important
Please Read Carefully and Save
General Description
The National Fire Protection Association has published codes, standards, and recommended practices for the in­stallation and use of the above appliances. It is recom­mended that the installer be familiar with these requirements, with local codes, and any special require-
ments of the authority having jurisdiction. System Sensor supplies bells for nearly all sprinkler/fire alarm/burglar applications.
These bells are intended to be connected to alarm indicat-
ing circuits of UL listed fire alarm control panels. The SSM These instructions apply to all System Sensor bells in the series. Read all instructions carefully before beginning. Fol­low only those instructions that apply to the model you are
series is polarized to enable supervision of the installation
wiring. The SSM bells require 24 VDC and the SSV bells re-
quire 120 VAC. installing.
CAUTION
Do not use in potentially explosive atmospheres.
Do not leave any unused wires exposed.
D770-11-00 1 I56-674-04
Before installing any alarm device, be thoroughly familiar with:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems NFPA 25: Inspection, Testing, and Maintenance of Water-
Based Fire Protection Systems
Other applicable NFPA standards, local codes, and the re­quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm condition. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
Installation
WARNING
High voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
Operational Testing
Always notify a central station monitoring the system be­fore repairing, maintaining, or testing alarm devices.
Upon completion of initial installation, all bells shall be tested per NFPA 72. Periodic testing should be performed at least annually. Test more often if required by the authority having jurisdiction. Under normal conditions, System Sen­sor bells should provide years of trouble-free service; how­ever, after extended service, parts of the bell may become worn. In this case, bell should be replaced.
Do not repair or replace any bell components in the field. If bell does not perform properly, replace the entire unit. Failure to follow this instruction may result in fail­ure of the bell to report an alarm condition.
1. Remove the gong.
2. Wire the bell in the circuit. See Figure 1, page 3.
3. Mount the bell mechanism on a 4˝ square electrical box with the striker facing down. See Figures 2–4, page 3.
4. Replace the gong.
5. The top of the bell must be mounted a minimum of 90˝ above the floor, or within 6˝ of the ceiling.
CAUTION
Do not loop wire under terminals. Break wire runs to pro­vide supervision of connections.
Audibility Rating Measurement
Sound level measurements are made in accordance with UL Standard 464. The sound power output is measured in a re­verberant room.
D770-11-00 2 I56-674-04
Loading...
+ 2 hidden pages