The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
VoltageRegulated SupplyRectified Unfiltered Supply
Range
Average PeakInrushAveragePeakInrush
Operating Current Current OperatingCurrentCurrent
Current(mA)(Amps) Current(mA)(Amps)
(mA)20/30(mArms)20/30
VrmsVrms
The MA12/24D sounder is suitable for outdoor applications (-35° to 66° C) when it is used with a WBB Weatherproof Back Box. The signaling strobe is rated for 0° to 49°
C and is NOT suitable for outdoor use.
installer be familiar with these requirements, with local
codes, and any special requirements of the local fire authority having jurisdiction.
The UL-rated light output of the SS2415ADAS,
SS241575ADAS, MASS2415ADAS, and MASS241575ADAS
is 15 cd (See Figure 1).
The Multi-Alert™ sounder and signaling strobe are intended
to be connected to the alarm indicating circuit of a UL-
NOTE: The light output at 0° viewing angle for
listed fire alarm control panel and is compatible with DC
line supervision. The electronic sounder can be connected
to either 12 or 24 VDC panels. Models SS2415ADAS,
SS241575ADAS, and combination models incorporating
Any one of eight sounds can be selected on the electronic
sounder, as indicated in Table 2.
these strobes, require 24 volt panels. Panels may have fullwave rectified, unfiltered power supplies. The strobes are
NOTE: SS24ADAS, MASS24ADAS AND MAEH24ADAS SEsynchronized and flash at a rate of one flash per second
with continuous voltage applied. SS24ADAS, SS24ADA,
MASS24ADAS, and MASS24ADA series devices may be
combined in the same zone.
Table 2. Sound output and current ratings for the MA12/24D:
RIES DEVICES OPERATING IN THE SAME ZONE
WILL NOT BE SYNCHRONIZED IF ENERGIZED AT
DIFFERENT TIMES (I.E., IF MORE THAN ONE CONTROLLER IS CONTROLLING THE SAME ZONE.)
UL (dBA)
Ratings
UL (dBA)
w/MDL Module
Note 1:See Figure 2 for tab clip removal & storage.
Note 2:All models can be powered using full wave rectified unfiltered sup-
plies. Under no circumstances can SS24ADAS or MASS24ADAS series devices input voltage exceed 33 VDC or be less than 16 VDC
(18-33Vrms for full-wave rectified, unfiltered supplies).
D900-06-001I56-750-58
Note 3:Measured at 10 feet in an anechoic chamber.
Note 4:Measured in a UL reverberant room.
Note 5: Only continuous tones (800Hz, 2400 Hz) can be temporally
coded per UL. Strobes cannot be used on an MDL module providing temporal coding to Multi-Alert™ horns.
The sound selected determines the maximum current and
sound power output per device. SeeTable 2 for these values.
Independent Sounder/Strobe Operation
There may be applications where it is desirable to drive the
sounder and strobe as independent devices. The System
Sensor MASS12/24ADA series sounder/strobes are easily
configured for this capability. The terminal connection for
this application is shown in Figure 6. Independent strobe
operation in a coded system requires a separate uncoded
power supply for the strobe.
Installation - For Strobe Placement, See NFPA 72,
Chapter 6
A. General: Slotted head screws are used to attach each de-
vice or combination of devices to the electrical outlet
box. Phillips head screws are used to attach accessories
to the horn. Refer to Figures 3,4,5, and 6 for wiring
methods.
B. Sounder/Strobe combination mounting:
1. Surface Mount: (See Fig. 10)
2. Semi Flush Mount: (See Fig. 11 and 14)
C. Sounder mounting:
1. Surface Mount : (See Fig. 7)
2. Semi Flush Mount: (See Fig. 11 and 14)
3. Flush Mount (See Fig. 13)
Flush mounting requires the use of the deep box (Part
# BB-D) or equivalent. Determine which of the two
device holes will be used to attach the device to the
box. Mount the flush plate to the sounder using the
other two holes with two 1-inch phillips head screws
and two square nuts.
D. Strobe mounting:
1. Surface Mount: (See Fig. 9)
2. Semi Flush Mount (See Fig.12)
Installation procedures must conform to all applicable codes
and the requirements of the authority having jurisdiction.
NOTES: Do not loop wires under the terminal screw. Wires
connecting the device to the panel must be broken
at the device terminal connection in order to
maintain electrical supervision.
NOTE: The rated output of the sounder is specified at 10
feet. It cannot be assumed that the output will
meet the NFPA standard of 15 dB over ambient
noise at all locations within a room. Additional
sounders may be needed to ensure sound output
Strobe and strobe/horn combination are de-
level complies with NFPA requirements.
signed for wall mounting ONLY.
The sounder is 1-1/4" deep. Back boxes must be 4"
square by at least 1-1/2" deep – 2-1/8" deep box is recommended.
All strobes must be mounted so that the top of the lens is
24 inches (61 cm) below ceilings or as required by the
authority having jurisdiction.
WARNING
The Limitations of Sounder/Strobes
The Sounder and/or Strobe will not work without power. The sounder/
strobe gets its power from the fire/security panel monitoring the alarm
system. If power is cut off for any reason, the sounder/strobe will not provide the desired audio or visual warning.
The Sounder may not be heard. The loudness of the sounder meets (or
exceeds) current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The Sounder may not be heard
if it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from
hearing the alarm. The Sounder may not be heard by persons who are
hearing impaired.
The Signal Strobe may not be seen. The electronic visual warning signal
that flashes at least once every three seconds meets or exceeds current Underwriters Laboratories’ standard 1971 and uses an extremely reliable xenon flash tube. The visual warning signal is suitable for direct viewing and
must be installed within an area where it can be seen by building occu-
D900-06-002I56-750-58
pants. The strobe must not be installed in direct sunlight or areas of high
light intensity (over 60 foot candles) where the visual flash might be disregarded or not seen. The strobe may not be seen by the visually impaired.
The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should
avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated.
System Sensor recommends that the Multi-Alert Sounder and Signal
Strobe always be used in combination so that the risks from any of the
above limitations are minimized.
The signal strobe cannot operate from coded power supplies. Coded
power supplies produce interrupted power. The strobe must have an uninterrupted source of dc power in order to operate correctly.
Synchronized strobes may not prevent photosensitive reactions to signal
strobes in alarm condition.
y
Figure 1. Vertical and horizontal light distribution:
0˚
45˚
90˚–90˚
–45˚
LIGHT
NOTE: ALL STROBES THAT ARE TO BE IN SYNC MUST BE ON THE SAME POWER CIRCUIT.
Figure 2:Figure 3. Multi-alert sounder:
COVER SLOT
SLIDE COVER
FOR CLIP STORAGE
TONE
SELECTION TABS
TAB A
TAB B
TAB C
To Next
Device
or EOL
DegreesRating
0100
5 - 2590
30 - 4575
5055
5545
6040
6535
7035
7530
8030
8525
9025
Percent of
- VDC
+ VDC
USE A
CLIP
STORAGE
FOR STORING UNUSED CLIPS:
SLIDE COVER BACK TO ALIGN COVER SLOT
WITH CLIP STORAGE POST.
CLIPS REMOVED OR
ADDED TO SELECT
DESIRED TONE.
SMALL BLADED
SCREWDRIVER
TO REMOVE
CLIPS
A78-2167-00
Figure 4. Multi-alert sounder and strobe operating in
Figure 5. Strobe:
(-)
IN OUT
STROBE
ONLY
(-)
IN OUT
(+)
IN OUT
STROBE
ONLY
(+)
IN OUT
From
panel or
previous
device
A78-1137-00
tandem:
To Next
Device
– VDC
+ VDC
or EOL
From
panel or
(–)
IN OUT
STROBE
ONLY
(–)
IN OUT
(+)
IN OUT
STROBE
ONLY
(+)
IN OUT
previous
device
Figure 7. Sounder surface mount:
Note: Use uncoded suppl
Figure 6. Multi-alert sounder and strobe operating
only.
A78-1137-29
BB-STD
MA12/24D
independently:
A
B
A78-1137-03
To Next
Device
or EOL
Caution: Break off P.C.B. Tabs
– VDC
STROBE
+ VDC
– VDC
SOUNDER
+ VDC
NonCoded
Supply
Can Be
Coded
Supply
Screw types used in
Figures 9 to 15
A = 8-32x1-7/16" Slot
B
A
B = #8 Sheet Metal Phillips
From
panel or
(–)
(–)
(+)
IN OUT
STROBE
ONLY
IN OUT
IN OUT
STROBE
ONLY
(+)
IN OUT
D900-06-003I56-750-58
previous
device
A78-1137-01
C = 8-32x1" Phillips
D = #8 Square Nut
E = 8-32x5/8" Slot
F = 8-32x2-3/4" Slot
G = 6-32x5/8" Slot
Figure 9. Strobe surface mount:
MA-12/24D
A
B
B
A
Signal Strobe
Standard
Backbox
1. Complete field wiring.
2. Screw strobe to box with screw A.
3. Fill remaining holes with Screw B.
Standard
Backbox
TOP
A
A
Signal Strobe
B
B
A78-2514-00
Figure 10. Sounder/strobe surface mount:
1. Complete field wiring.
2. Screw sounder/strobe to box
with screw A.
3. Fill remaining screw holes with
screw B.
A78-2515-00
Figure 11. Sounder or sounder/strobe semi-flush
mount:
STANDARD
BACKBOX
MP-SF
E
E
1. Screw plate to box with screw E.
2. Complete field wiring. (See Fig. 3,
4, 5, and 6)
3. Screw sounder or sounder/strobe
MA-12/24D
A
B
B
A
to plate with screw A.
4. Fill remaining holes with screw B.
A78-2517-01
Figure 13. Sounder flush mount (deep box required):
Figure 12. Strobe semi-flush mount:
STANDARD
BACKBOX
MP-SF
Signal Strobe
TOP
1. Screw strobe to plate with
C
screw C.
2. Complete field wiring.
3. Screw strobe plate to box with
A
C
A78-2516-00
screw A.
Figure 14. Sounder or sounder/strobe semi-flush
mount with plaster ring:
A
1. Plaster ring should be properly mounted to electrical box
with screws supplied with box.