System Sensor FSB-200, FSB-200S Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
FSB-200, FSB-200S Single-ended Reflected Type Projected Beam Smoke Detector
Range: 16 to 230 Feet (5 to 70m) 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK Sensitivity: 25% to 50% Total Obscuration in 6 levels Level 1 = 25% Level 2 = 30% Level 3 = 40% Level 4 = 50% Level 5 = 30% to 50% (Acclimate) Level 6 = 40% to 50% (Acclimate) Spacing: 30 to 60 Feet (9.1 to 18.3m) Response Time: Alarm: 20 seconds typical Trouble: 30 seconds typical Trouble Conditions: Beam Blockage (96% or More Obscuration) Improper Initial Alignment Self-compensation limit reached (service needed) In Alignment mode Test/Reset Features: Integral Sensitivity Test Filter (FSB-200S only, requires additional external power supply) Sensitivity Filter (Incremental scale on reflector) Local Alarm Test Switch Local Alarm Reset Switch Remote Test and Reset Switch Capability (compatible with RTS451/RTS451KEY) Indicators: Alarm: Remote Output, Local LED (red) Trouble: Remote Output, Local LED (yellow) Blink Pattern Indicates Trouble Diagnostics Normal Operation: Local LED (flashing green with communication) Alignment Aids: Optical Gunsight (coarse adjustment) 00 to 99 Digital Display (fine adjustment) Sensitivity: Digital Display Readout in Percent Obscuration Style 7 Operation: On-board isolators provide style 7 operation. (may be disabled via shunts on circuit board)
12 Clintonville Rd.
Northford, CT 06472-1653
Phone: 203/484-7161
Environmental
Temperature: –22°F to 131°F (–30°C to 55°C) Note: for applications below 32°F (0°C) see Special Applications section of this manual. Humidity: 10% to 93% RH Noncondensing
Mechanical
Shipping Weight: 3.9 lbs. (1.77 kg) Shipping Size: 15 × 10.5 × 6.5 (381mm × 267mm × 165mm) Mounting: Wall only without optional accessories Wiring: Plug-in Terminal Blocks (12 to 22AWG) Adjustment Angle: ±10° Horizontal and Vertical Paintable Trim Ring: May be painted using enamel or acrylic type paints
N200-25-00 1 I56-2424-04R
Specifications (continued) Electrical
Voltage: 15 to 32 VDC Standby Current: Avg. Standby: 2mA Max. (1 communication every 5 sec., LED flashing, SLC @ 24 V) Max. Alarm (LED on): 8.5mA Max. Max. Trouble (LED on): 4.5mA Max. Max. Alignment: 20mA Max. External Supply (FSB-200S only): Voltage: 15 to 32 VDC Current: 0.5A Max. Remote Output: Voltage: 15 to 32 VDC (alarm) Note: Output voltage same as device input voltage. Current: 15mA maximum 6mA minimum Note: Output current is limited by 2.2Kohm resistor
General Description
Model FSB-200/FSB-200S is a long range projected beam smoke detector designed to provide open area protection. It is to be used with UL-listed compatible control panels only. The detector consists of a transmitter/receiver unit and a reflector. Smoke entering the area between the transmitter/ receiver and reflector causes a reduction in signal. When the obscuration reaches alarm thresholds (chosen at the transmitter/receiver unit), the detector generates an alarm signal. Complete blockage of the beam causes a trouble signal. Slow changes in obscuration due to a build up of dirt or dust on the lens of the detector are compensated for by a microcontroller that continuously monitors the signal
Special Applications
Due to the inherent capabilities of projected type beam detectors they are often installed in locations where spot­type detection is impractical. Projected type beam smoke detectors are ideally suited for environmental conditions that might include high ceilings, dusty and dirty envi­ronments, or environments that experience temperature extremes. Often these conditions present special problems for the installation of spot-type detectors and even greater problems for their proper maintenance. Due to the inherent flexibility of mounting locations and large coverage area of projected type beam detectors often the conditions above
can be addressed or minimized. strength and periodically updates the alarm and trouble thresholds. When the self-compensation circuit reaches its limit, the detector generates a trouble signal, indicating the need for service.
Some examples of applications for beam detectors might
include freezers, aircraft hangars, cold storage warehouses,
shipping warehouses, enclosed parking facilities, sporting
arenas and stadiums, concert halls, barns, or stables. Some Three LEDs on the detector indicate the current status: a red LED for alarm, a yellow LED for trouble, and a blinking green LED for standby operation. Note: The panel controls the status of the red and green LEDs. The local reset but-
of these environments might be considered too hostile for
spot-type smoke detectors. If the environment is consid-
ered to be hostile then the colder alarm threshold settings
should be used. ton is accessible by removing the outer paintable trim ring. The yellow LED will blink in specific patterns to provide a diagnostic aid when diagnosing the cause of a trouble sig­nal. It will also blink the amount of drift compensation that has been used at the conclusion of the local test. Trouble signals automatically reset upon removing the cause of trouble. Red and yellow LEDs can be remotely connected to the remote Alarm and Trouble outputs. These outputs mimic the functions of the detector’s red and yellow LEDs. In addition to these indicators, there is a dual digital display that reads 00 to 99. This display is used to indicate the sig­nal strength of the beam in alignment mode and to indicate the sensitivity setting of the detector in percent obscuration when setting the sensitivity of the detector. No additional equipment is needed for alignment of the beam.
Before installing the transmitter/receiver unit or reflector
in these types of applications special consideration should
be given to insure proper operation of the beam detector.
The beam detector should not be installed in environments
where there is no temperature control and condensation or
icing is likely. Condensation or icing of the reflector surface
or the outer surface of the transmitter/receiver unit will
obscure the light beam resulting in a false alarm. If elevated
humidity levels and rapidly changing temperatures can be
expected then condensation will likely form and the appli-
cation should not be considered acceptable for the beam
detector. The beam detector should not be installed in
locations where the transmitter/receiver unit, the reflector,
or the optical pathway between them may be exposed to
outdoor conditions such as rain, snow, sleet, or fog. These
N200-25-00 2 I56-2424-04R
conditions will impair the proper operation of the detector and must be avoided.
Approved Accessories
The following accessories can be purchased separately for use with this beam detector.
BEAMLRK
The BEAMLRK allows System Sensor reflected beam detec­tors to be installed at separations between 230 and 328 feet (70 to 100 meters). At these distances, four 8″×8 reflectors must be used to provide enough reflected infrared light. This kit includes 3 additional reflectors with new test scale legends. The reflector included with the transmitter/ receiver unit is the fourth reflector to be used. This kit is not compatible with the multi-mount kit (BEAMMMK).
BEAMMMK
The BEAMMMK allows System Sensor reflected beam detec­tors and reflectors to be mounted to either a vertical wall or the ceiling. The kit allows for additional alignment range in cases where the detector and reflector cannot be mounted within 10° of each other. The kit includes the hardware necessary to mount either a single transmitter/receiver unit or a single reflector. (To mount the transmitter/receiver the surface mount kit, BEAMSMK, must also be used). If the transmitter/receiver and the reflector require additional alignment range two kits are required. The kit is not com­patible with the long-range reflector kit (BEAMLRK).
BEAMSMK
The BEAMSMK allows System Sensor reflected beam detec­tors to be mounted when surface wiring is used. This kit must be used when mounting the transmitter/receiver unit with the multi-mount kit (BEAMMMK).
BEAMHK
The BEAMHK allows the transmitter/receiver unit to oper­ate in environments prone to the formation of condensa­tion. Condensation forming on the beam detector unit may result in trouble or false alarm conditions. BEAMHK will lessen the likelihood of condensation by maintaining the unit at a temperature that is slightly higher than the surrounding air. Please refer to the BEAMHK installation manual for operation instructions.
BEAMHKR
The BEAMHKR allows the reflector to operate in environ­ments prone to the formation of condensation. Condensation forming on the reflector may result in trouble or false alarm conditions. BEAMHKR will lessen the likelihood of conden­sation by maintaining the reflector at a temperature that is slightly higher than surrounding air. The kit requires a 24V power supply. When used with the long-range reflector kit (BEAMLRK), it is necessary to purchase and install four BEAMHKR kits. Please refer to the BEAMHKR installation manual for operation instructions.
RTS451/KEY
The remote test accessory, RTS451/KEY allows for the beam detector to be tested remotely. The test accessory provides test and reset functions and green and red LED’s that mimic the LED’s on the detector.
Parts List
Description Quantity
Transmitter/Receiver Unit . . . . . . . . . . . . . . . . . . . .1
Paintable Trim Ring . . . . . . . . . . . . . . . . . . . . . . . . .1
Reflector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Plug-in Terminal Blocks . . . . . . . . . . . . . . . . . . . . . .3
Isolator Shunts . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Instruction Manual . . . . . . . . . . . . . . . . . . . . . . . . .1
Orange Sticky Paper . . . . . . . . . . . . . . . . . . . . . . . . .1
Parts Diagram (not to scale)
Terminal Block
Isolator Shunt
Paintable Trim Ring
C0306-00
Detector Placement
This section of the manual discusses the placement of pro­jected beam detectors. Though this information is based upon industry expertise, it is intended to be used only as a technical guide. Always comply with the requirements of applicable codes and standards such as, NFPA 72, National Fire Alarm Code, as well as directives of the Authority Having Jurisdiction (AHJ).
Projected beam detectors are usually located with their beams parallel to the ceiling. However, they can be mount­ed vertically or at any angle to protect the area involved. Since beam detectors sense the smoke buildup over a dis­tance, they are ideal for locations with high ceilings. They can also be mounted on a wall or ceiling below the level of a spot type detector, reducing the effects of air stratifica­tion. Some typical locations would include large areas with high ceilings such as atriums, warehouses, and factories.
NOTE: Projected beam smoke detectors should always
be mounted to stable mounting surfaces. See the MOUNTING LOCATION section for details.
N200-25-00 3 I56-2424-04R
Some fire codes specify spacing on a given center-to-center
1/2 S S
12-18 in.
(0.3-0.46m)
WALL
16 ft. (5m) Minimum
328 ft. (100m) Maximum
Tx/Rx Reflector
S
Tx/Rx Reflector
1/2 S Maximum
1/4 S
Max.
S
3 ft. (0.
9m
)
Max.
S
1/2 S MAX.
Tx/Rx
Reflector
distance between detectors under ideal conditions. This spacing is based on rooms with smooth ceilings and no physical obstructions between the contents being protected and the detectors. Moreover, they are also based on a maxi­mum ceiling height, and on the assumption that the value and the combustible nature of the contents of the room being protected do not warrant greater protection or closer spacing.
In a room with a smooth ceiling, detectors should be spaced between 30 and 60 feet (9.1 to 18.3m). One-half that spacing between the beam and the sidewall may be used as a guide. See Figure 1. The beam detector can be mounted with the transmitter/receiver on one wall and the reflector on the opposite wall, or both suspended from the ceiling, or any wall/ceiling combination. In the case of the ceiling mount, the distance from the end walls should not exceed one-quarter of the selected spacing (7.5 ft. [2.3m] maximum if the spacing is 30 ft. [9.1m]). See Figure 2.
Figure 1. Spacing for smooth ceiling (side view):
Figure 2. Spacing for smooth ceiling (top view):
C0255-00
In the case of peaked or sloped ceilings, codes may specify
spacing of detectors by using horizontal spacing from the
peak of the roof or ceiling. Figures 3 and 4 show the spacing
for both the shed type and peaked type sloped ceilings.
On smooth ceilings, beam smoke detectors should gener-
ally be mounted between 12 and 18 inches (0.3 to 0.46m)
from the ceiling. In many cases, however, the location and
sensitivity of the detectors shall be the result of an engi-
neering evaluation that includes the following: structural
features, size and shape of the room and bays, occupancy
and uses of the area, ceiling height, ceiling shape, surface
and obstructions, ventilation, ambient environment, burn-
ing characteristics of the combustible materials present,
and the configuration of the contents in the area to be
protected.
Figure 3. Sloped ceiling (shed type):
C0254-00
C0256-00
N200-25-00 4 I56-2424-04R
Figure 4. Sloped ceiling (peaked type):
1/2
S
S
S
1/2
S
3 ft. (0.9m)
Max.
3 ft. (0.9m
)
Max.
Mount Detector
Anywhere in This Area
Tx/Rx
Reflector
WA
L
L
REFLE
CTOR
Acceptable mounting locations for reflector
10ϒ
10ϒ
C0257-00
Mounting Locations
Beam detectors require a stable mounting surface for proper operation. A surface that moves, shifts, vibrates, or warps over time will cause false alarm or trouble condi­tions. Initial selection of a proper mounting surface will eliminate false alarms and nuisance trouble signals.
Mount the detector on a stable mounting surface, such as brick, concrete, a sturdy load-bearing wall, support col­umn, structural beam, or other surface that is not expected to experience vibration or movement over time. DO NOT MOUNT the beam detector on corrugated metal walls, sheet metal walls, external building sheathing, external siding, suspended ceilings, steel web trusses, rafters, non­structural beam, joists, or other such surfaces.
the supplied drilling template (see Appendix II). The detec­tor base has 4 primary mounting keyholes, one in each corner of the base. All four hole locations should be used to provide a secure mounting. The outer housing of the beam detector is held to the base using four screws. In order to mount the detector you must remove the outer housing first.
The reflector can be mounted to the wall using the sup­plied drilling template (see Appendix III). The reflector has 4 mounting holes, one in each corner. All four hole locations should be used to provide a secure mounting. The reflector must be mounted such that it is within 10° in both the X and Y planes of the transmitter/receiver unit. See Figure 5a. The reflector must also be mounted such that plane of the reflector is perpendicular to the optical line of sight to the transmitter/receiver unit. The maximum tolerance for non-perpendicular mounting locations is 10°. See Figure 5b. If the reflector cannot be mounted within 10° of the transmitter/receiver unit then the multi-mount kit (BEAMMMK) may be used to provide greater angular adjustment of the transmitter/receiver unit. If the perpen­dicular plane of the reflector cannot be mounted within 10° of the optical line of sight then the multi-mount kit can be used for the reflector. See BEAMMMK instructions.
To aid in locating the reflector in the alignment mirror at long distances a bright orange sticky backed piece of paper is provided. Remove the protective backing from the orange sticker. Temporarily affix the orange paper next to the reflector using the sticky backing of the paper. The location of the sticky paper is not critical. It may be placed anywhere near the reflector as long as it not covering the reflective surface of the reflector. This sticky paper should be removed once the installation is completed.
In cases where only one stable mounting surface as defined above can be used, the transmitter/receiver unit should be mounted to the stable surface and the reflector should be mounted to the less stable surface. The reflector has
tions defined above.
a much greater tolerance for the unstable mounting loca-
Mounting Instructions
The transmitter/receiver unit may be mounted over a recessed junction box. The cavity behind the detector is then used for routing of the wiring from the junction box to the terminal blocks on the detector. The transmitter/ receiver unit should be mounted to the wall such that unit covers the recessed junction box in the wall completely. If the junction box is not recessed then you may use the surface mount kit (BEAMSMK). See the BEAMSMK instal­lation instructions for surface mounting instructions. The transmitter/receiver unit can be mounted to the wall using
N200-25-00 5 I56-2424-04R
Figure 5a. Reflector Mounting Guidelines
C0258-00
Figure 5b. Reflector Mounting Guidelines
10ϒ maximum
optical line of sight
REFLECTOR
C0259-00
between the detector and the reflector, (A minimum of 10°
off perpendicular should be considered), and make certain
that the glass is smooth, clear and mounted securely. The
complete reflector blockage test can be used to determine if
the installation is acceptable. See Testing and Maintenance
Section of this manual.
Where high ceilings (in excess of 30 feet or 9.1 meters) are
present additional beams may be required to detect smoke
at lower levels.
Mounting Considerations for Single Ended Beam Detectors
There must be a permanent clear line of vision between the detector and the reflector. Reflective objects must not be near the line of vision between the detector and reflector. Reflective objects too near to the line of sight can reflect the light beam from the transmitter to the receiver. If this occurs, the detector will not be able to distinguish these reflections from those of the reflector and the protected space will be compromised. Reflective objects should be
Wiring Installation Guidelines
Always install all wiring in compliance with the National
Electrical Code, and/or the applicable local codes, and any
special requirements of the local authority having jurisdic-
tion. Proper wire gauges and suitable means for strain relief
should be used. The conductors used to connect beam
smoke detectors to control panels and accessory devices
should be color-coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from
responding properly in the event of a fire. a minimum of 15 inches (38.1cm) from the line of sight between the detector and reflector. In cases where reflective objects cannot be avoided, the complete reflector blockage test can be used to determine if the installation is accept­able. See Testing and Maintenance Section of this manual.
Installation wire used for the beam detector shall be no
smaller than 22 AWG (1.0 mm2). For best system perfor-
mance, all wiring should be twisted pair and installed in
separate grounded conduit. Do NOT mix fire system wiring
in the same conduit as any other electrical wiring. Shielded Light sources of extreme intensity such as sunlight and hal­ogen lamps, if directed at the receiver, can cause a dramatic
cable may be used to provide additional protection against
electrical interference. signal change resulting in fault and alarm signals. To prevent this problem direct sunlight into the transmitter/receiver unit should be avoided. There should be a minimum of 10° between the pathway of the light source and detector and the line of sight between detector and reflector.
When installing the beam smoke detector in applications
where the head unit will be mounted to either a wall or
the ceiling using the multi-mount kit (BEAMMMK) flexible
conduit will be used. The surface mount kit (BEAMSMK)
and multi-mount kit (BEAMMMK) must be installed with Operation of the detector through panes of glass should be avoided. Since single ended beam detectors operate on
the cable before wiring the unit, according to the instruc-
tions supplied with the kit. a reflection principle, a pane of glass perpendicular to the line of sight between the detector and the reflector can reflect the light beam from the transmitter to the receiver. If this occurs, the detector will not be able to distinguish these reflections from those of the reflector and the pro­tected space will be compromised.
When the detector has been mounted over a recessed junc-
tion box, all wiring should be routed out of the box and
behind the detector to the bottom of the detector where
the terminal blocks are located. When installing the wir-
ing in the junction box be sure to leave enough wire in the
box to connect to the terminal blocks. (Approximately 9 Panes of glass will also absorb some of the light as it passes through it. This absorption of light will reduce the acceptable installed distance between the detector and the reflector.
(23cm) of wire outside of the junction box will be required
for proper installation). All wiring to the detector is done
via pluggable terminal blocks. In order to properly make
electrical connections strip approximately 1/4″ (6mm) of
insulation from the end of the wire, sliding the bare end of In cases where operation through panes of glass cannot be avoided some specific installation practices can help to minimize the effects of the glass. These practices include: avoid penetration of multiple panes of glass, position the glass so that it is not perpendicular to the line of sight
the wire under the clamping plate screw.
Figure 6 shows all the wiring connections to the transmitter/
receiver unit. Figure 7 shows the proper wiring diagram for
either class A or class B operation. Figure 8 shows the con-
nections that are necessary when using one of the optional
N200-25-00 6 I56-2424-04R
remote test stations (RTS451 or RTS451KEY). Figure 9
SLC (–)
SLC (+)
SLC (–)
SLC (+)
RESET I NPUT
TEST INPUT
AUX (–)
REMOTE ALARM OUT
Not used
REMOTE TROUBLE OUT
TEST OPTION (–)
TEST OPTION (+)
T3 T2 T1
+ –
+ –
+
+
TO NEXT
DEVICE
FROM PANEL OR
PREVIOUS DEVICE
LISTED
REMOTE
POWER
SOURCE
* Only used for FSB-200S. See electrical ratings.
COMMUNICATION LINE
32 VDC MAX. TWISTED PAIR IS RECOMMENDED.
+
T3 T2 T1
RTS451/KEY
FSB-200/FSB-200S
Pin 1
Remote Alarm Out
T2-1
T2-2
T2-4
T2-3
AUX (–)
Power In +T1-1
T1-2
T1-3
T1-4Power In –
Power Out +
Power Out –
Reset Input
Test Input
T3-3
Remote Trouble Output
Optional Yellow LED
Pin 2
Pin 4
Pin 3
Pin 5
FSB-200S
Alarm Signal Circuit
(Note 1)
T2-1
T2-2
Note 1: See electrical ratings section of this manual for circuit output ratings.
SLC (+)
SLC (–)
Red
shows the remote output for alarm indication.
WARNING: Disable the zone or system before applying
power to the beam detector to prevent unwant­ed alarms. When applying power to the beam detector before the alignment procedure has been completed the detector may enter alarm or fault.
Figure 6. Wiring Connections at Detector
Figure 7. Wiring Diagram
C0335-00
Figure 8. Wiring Diagram (RTS451)
C0260-01
C0336-01
Figure 9. Wiring Diagram (RTS451)
N200-25-00 7 I56-2424-04R
C0326-00
Installation / Alignment
Reference Figures 10 through 14 for installation, alignment,
brightly colored object on the wall near the reflector to aide in seeing the reflector in the alignment mirror.
and maintenance.
3. Once the reflector has been located, begin to adjust both The alignment of the FSB-200/FSB-200S is divided into four steps: coarse alignment, fine adjustment, final gain adjust­ment, and final verification. It is necessary for all four steps to be executed properly to ensure proper alignment of the product. If the detector and reflector are mounted per
the horizontal and vertical alignment knobs so that the reflector becomes centered in the alignment mirror. Take care in this step. If the optics are incorrectly aligned in this step, it will not be possible to proceed with the fine
adjustment step. Mounting Locations and Mounting Instructions sections of this manual and the alignment procedures are executed properly, false alarms and nuisance trouble signals will be
Step 2. Fine Adjustment
Refer to Figures 10 through 12 for this step.
minimized.
In this step you will be fine-tuning the optics to the reflec-
Pre-Alignment Checklist
• Insure that both the detector and reflector are mounted
securely to stable surfaces.
• Insure that all wiring is correct.
• Insure that terminal blocks are fully seated into their
receptacles on the detector.
• Complete any wiring dressing to minimize movement
to the detector once the alignment procedure is com­pleted.
• Insure that the appropriate number of reflectors are
used for the installed distance. Distances between 230 & 328 Feet (70 - 100m) require additional reflectors (4 total). The BEAMLRK accessory should be used in these cases.
tor. To provide feedback of the signal level coming from the reflector the dual digital display readout will be used. Due to the large distance range that the detector can operate over it is necessary that the detector operate with many dif­ferent settings of “electronic amplifier gain”. The detector is capable of determining the appropriate gain setting and then setting it itself via on-board processing algorithms. There are no external gain settings on the detector that must be set by the operator. Periodically throughout the fine adjustment step the detector will need to re-adjust its “electronic amplifier gain” setting. When this occurs it will be indicated by the dual digital readout as “- -”. When this occurs, cease any further adjustment until the display again reads a number value.
• Insure that the line of sight between the detector and
reflector is clear and that reflective objects are not too near. See Mounting Instructions for more details.
1. Insure that neither you nor any other objects are in the line of sight between the detector and the reflector.
• Insure that both the detector and reflector are mounted within their operational parameters for off axis angles. See Mounting Instructions for more details.
• Disable the zone or system to prevent unwanted alarms before applying power.
• Insure power to the detector is “ON”.
• Insure that the appropriate address is set on the code wheels.
2. Depress the Alignment switch once. Both the digital dis­play and the yellow LED should turn on indicating that alignment mode has been entered. The display should begin reading “- -” signifying an electronic gain adjust­ment. After a few moments the display will indicate a numeric value near 20. If the display reads “Lo” then the detector is not receiving enough light from the reflec­tor. Go back and repeat the course alignment step and
You are now ready to begin the alignment procedure.
verify that the proper number of reflectors is used for the installed distance.
Step 1. Coarse Alignment
Refer to Figures 11 and 12 for this step.
NOTE: The display will continue to read “Lo” until the
detector receives enough light from the reflector to
1. Insure that both of the optics lock-down screws are loos-
continue with the fine adjustment step.
ened so that the optics will move freely.
NOTE: In alignment mode (indicated by the yellow LED
2. Looking through the alignment mirror at both the align­ment sight and reflector simultaneously locate the posi-
and the numeric display) the sensitivity select and
test switches are disabled. tion of the reflector in the optical sight. This step will require some practice. It is necessary to train your eyes to shift focus between the reflector and the mirror in order to locate the reflector. If the distance between the reflector and the detector is large it is helpful to place a
N200-25-00 8 I56-2424-04R
3. With the display reading a numeric value, begin adjust­ing the horizontal and vertical alignment knobs one at a time in the direction that increases the numeric signal level on the display. Continue adjusting each axis one
at a time going back and forth between them until a peak value is indicated. If a value of 90 is achieved, the detector will re-adjust the electronic gain once again. This will be indicated by a “- -” reading on the display. When this happens halt any further adjustment until the display again reads a numeric value. This process may occur more than once during the fine adjustment step.
NOTE: Each time the display reads a value of 90 or greater
the detector will reduce the electronic gain. Each time the display reads a value of 10 or less the detector will increase the electronic gain.
4. Once satisfied that it is not possible to achieve a higher reading on the display depress the alignment switch to complete the fine adjustment step. The digital display readout will turn “OFF” and the yellow LED will remain “ON”.
NOTE: It may not be possible to achieve a value near 90
on the display during the last adjustment iteration. The final value of the display will not likely be near 90. This is normal. It is due to the detector reducing its electronic gain each time a value of 90 is achieved. When this occurs the detector resumes with less electronic gain than previously when 90 was achieved. Less gain makes it more difficult to achieve higher values. Final values anywhere between 20 and 90 are acceptable if no further increase can be achieved.
NOTE: The housing contains a gasket seal that protects
the detector circuitry from corrosion and moisture sources. To insure that the gasket seal performs correctly it is necessary to fully tighten all four of the screws that hold the outer housing in place.
3. Remove the protective film from the front surface of the outer housing.
4. To initiate the final electronic gain adjustment, the reset switch must be depressed. Once depressed the yellow LED will begin to blink. This indicates that the detector is adjusting the electronic gain setting. Once complete, the yellow LED will stop blinking and the green LED will begin blinking. This indicates that the gain adjustment was successful.
NOTE: Use caution not to block the line of sight between
the detector and reflector in this step.
5. Install the outer aesthetic ring by snapping it onto the outer housing.
NOTE: If the outer aesthetic ring has been painted insure
that the paint is completely dry before proceeding with this step.
Step 4. Final Verification
This step is required to insure the detector has been setup cor­rectly and will detect smoke at the proper sensitivity level.
NOTE: The alignment procedure is not complete yet.
At this time it is possible to set the sensitivity of the detec­tor using the sensitivity switch and digital display. See the Sensitivity Selection section of this manual for further details.
Step 3. Final Gain Adjustment
Refer to Figure 13 for this step.
In this step, the detector will electronically adjust its inter­nal gain one final time. It is necessary to complete this step with the outer housing installed since the housing will change the amount of light received from the reflector.
1. Tighten the optics lock down screws so the optics are secure.
2. Install the outer housing of the detector. The housing is installed by tightening four screws, one in each corner of the housing. The screws are captivated in the plastic of the housing and cannot fall out during assembly.
1. With the detector functioning (indicated by the green LED blinking), completely block the reflector with an opaque material. (Due to the high optical efficiency of the reflector the selection of the opaque material used to block the reflector is not critical. Acceptable mate­rials include, but aren’t limited to, this manual or the cardboard packaging inserts.) See Figure 14. The detec­tor should enter the fault condition (indicated by the fault relay and the yellow LED (see Appendix I). If the detector does not enter the trouble condition there is a problem with the installation refer to the troubleshoot­ing section in Appendix I for further assistance.
2. Complete a sensitivity test of the detector. Refer to the Sensitivity Testing section of this manual for the appro­priate procedure.
3. If the orange sticky paper was used to aid in the loca-
tion of the reflector in the alignment mirror it should be removed now. It is no longer necessary.
Congratulations. You have completed the final installation and alignment procedure.
N200-25-00 9 I56-2424-04R
Figure 10. Switch Locations
ALIGNMENT
SENSITIVITY
TEST
RESET
STYLE 7 ISOLATOR SHUNTS (SHOWN DISABLED)
CODE SWITCH
TENS
ONES
ALIGNMENT MIRROR
ALIGNMENT GUNSIGHT
DIGITAL SIGNAL STRENGTH READOUT
HORIZONTAL ADJUSTMENT
VERTICAL ADJUSTMENT
OPTICS LOCK-DOWN SCREWS
ALIGNMENT POSITION INDICATOR
EYE
REFLECTOR
SCREW
LOCATIONS
SCREW
LOCATIONS
RESET
SWITCH
Figure 11. Alignment Adjustment Locations
Figure 12. Coarse Alignment Procedure
C0265-00
Figure 13. Housing Screw Locations
C0263-00
N200-25-00 10 I56-2424-04R
C0264-00
C0266-00
Short Circuit Isolation
The detector includes an on-board circuit isolator that allows for NFPA72 style 7 operation. In cases where style 7 operation is not desired the isolator can be disabled using the two shunts on the circuit board. See Figure 10 for jump­er locations. When the jumpers are present the isolator is disabled. This is the default state.
Sensitivity Selection
The detector has six sensitivity selections. Each of these selections is only acceptable over a specific distance sepa­ration between the detector and the reflector per UL268. The chart below is used to determine which selections are
acceptable for your installed distance. The sensitivity of
2.0
1.5
1.0
0.5
0.0 0
25% Setting
30% Setting
40% Setting
50% Setting
50 100 150 200 250 300 350
Sensitivity in %/Ft. vs. Distance
(assumes uniform smoke distribution)
Distance in Feet
Obscuration (%/Ft.)
the detector can be set only when the housing is removed and the detector is not in the fine adjustment step of the alignment mode, indicated by the illumination of the dual digital display. To set the sensitivity depress the sensitivity button one time. See Figure 10. Once the switch is pressed the digital display will illuminate and read the current sensitivity setting in percent obscuration. To change the sensitivity continue to depress the sensitivity switch until the desired setting is achieved. The digital display will turn off automatically if no further switch presses occur.
Sensitivity
Setting% Obscuration
Level 1 25 25 16.4 to 120 5.0 to 36.6
Level 2 30 30 25 to 150 7.6 to 45.7
Level 3 40 40 60 to 220 18.3 to 67
Level 4 50 50 80 to 328 24.4 to 100
Acclimate
Level 1
Acclimate
Level 2
30 to 50 A1 80 to 150 24.4 to 45.7
40 to 50 A2 80 to 220 24.4 to 67
Display
Reading
Acceptable
Distance Between Detector
and
Reflector
(Feet)
Acceptable
Distance Between Detector
and
Reflector
(meters)
Sensitivity Testing
NOTE: Before testing, notify the proper authorities that the
smoke detector system is undergoing maintenance, and therefore the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
Detectors must be tested after installation and following periodic maintenance. The sensitivity of the FSB-200/FSB­200S may be tested as follows:
NOTE: Before testing the detector, check for the presence
of the flashing green LED at the receiver, making sure not to disturb or block the beam. If it does not flash and the detector is not in trouble or alarm, power has been lost to the detector (check the wir­ing).
A. Calibrated Test Filter
The sensitivity of the detector can be tested using an opaque material to cover the reflector by an amount indi­cated by the graduated scale on the reflector. (Due to the high optical efficiency of the reflector the selection of the opaque material used to block the reflector is not critical. Acceptable materials include, but aren’t limited to, this manual or the cardboard packaging inserts.)
In addition to the four standard sensitivity selections the detector has two Acclimate settings. When either of these settings is chosen the detector will automatically adjust its sensitivity using advanced software algorithms to select the optimum sensitivity for the environment. The sensitivity will be continuously adjusted within the ranges specified in the chart above.
Sensitivity
Total obscuration can be converted to percent per foot, assuming uniform smoke density for the entire length of the beam. The charts below converts total obscuration to percent per foot for all acceptable sensitivity settings.
N200-25-00 11 I56-2424-04R
Refer to Figure 14 for this procedure.
1. Verify the sensitivity setting of the detector in % obscura­tion. See the Sensitivity Selection section of this manual for sensitivity determination if sensitivity is unknown.
2. Place the blocking material over the reflector, lining it up with the graduated marks that are 10 less than the detector’s setting in % obscuration. The detector should not alarm or fault. Keep the material in place for a mini­mum of 1 minute.
3. Place the blocking material over the reflector lining it up with the graduated marks that are 10 more than the detectors setting in % obscuration. The detector should enter alarm within 1 minute.
C0268-00
Figure 14. Reflector Test Card Procedure
LINE UP EDGE OF TEST CARD WITH APPROPRIATE OBSCURATION LEVEL
MOVE TEST CARD
TO DESIRED AMOUNT
OF OBSCURATION
B. Test Switch
The detector can be tested using the local test switch on the transmitter/receiver unit or remotely using the remote test station.
The remote test station, RTS451 or RTS451KEY, can be used with the FSB-200/FSB-200S beam smoke detector. Follow instructions included with the test station for proper use. See Figure 8 (Remote Test Station) for wiring diagram.
The FSB-200S is equipped with an integral sensitivity test feature that consists of a calibrated test filter attached to a servo motor inside the detector optics. When a test is initiated using the remote test station or local test switch the test filter is moved in the pathway of the light beam. The on-board microprocessor then determines if the proper level of signal reduction is received at the receiver. If the proper level of signal reduction is received the detector will enter alarm. If the proper level of signal reduction was not achieved, indicating that the sensitivity of the detector is out of tolerance, the detector will enter the trouble condi­tion.
C0267-00
4. The detector can be reset with the reset switch on the detector unit or remote reset.
5. Notify the proper authorities that the system is back on line.
If the detector fails this test several steps should be taken to determine if the detector is faulty or simply needs to be re-adjusted before returning the unit. These steps include:
1. Verify all wiring connections and appropriate power is applied to the detector.
2. Verify that the optical line of sight is free from obstruc­tions and reflective objects.
3. Apply the maintenance procedure in this manual. Repeat the test procedure. If the detector still fails the test procedure proceed with step 4.
4. Repeat the alignment procedure in this manual. If the alignment procedure is successful repeat the test pro­cedure. If the detector still fails the test it should be returned.
Always perform a complete reflector blockage test as in step 4 of the Installation/Alignment procedure to insure that the pathway between the detector and reflector is clear.
NOTE: For the FSB-200 this test does not satisfy the
requirements of NFPA72 for periodic maintenance and sensitivity verification of beam type detectors. For the FSB-200S this test in conjunction with the complete reflector blockage test (see step 4 of the Installation/Alignment procedure in this manual) does satisfy the requirements of NFPA72 for peri­odic maintenance and sensitivity verification of beam type detectors.
If the detector fails this test several steps should be taken to determine if the detector is faulty or simply needs to be re-adjusted before returning the unit. These steps include:
1. Verify all wiring connections and appropriate power is applied to the detector.
2. Verify that the optical line of sight is free from obstruc­tions and reflective objects.
3. Apply the maintenance procedure in this manual. Repeat the test procedure. If the detector still fails the test procedure proceed with step 4.
NOTE: For the FSB-200S the external power supply must
be connected for the test switch to work.
N200-25-00 12 I56-2424-04R
4. Repeat the alignment procedure in this manual. If the alignment procedure is successful repeat the test pro-
cedure. If the detector still fails the test it should be returned for repair.
NOTE: For the FSB-200S, the external power supply must
be connected for the test switch to work.
Maintenance
NOTE: Before cleaning the detector, notify the proper authorities that the smoke detector system is undergoing maintenance, and therefore the system will be temporar­ily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1. Carefully clean the outer housing lens face. A damp soft cloth with a mild soap may be used. Avoid products with solvents or ammonia.
2. Carefully clean the reflector. A damp soft cloth with a mild soap may be used. Avoid products with solvents or ammonia.
3. Notify the proper authorities that the system is back on line.
Painting
The outer aesthetic ring may be painted using a spray or brush type paint of appropriate type. See specification sec­tion of this manual for paint types.
NOTE: Never paint the flat lens surface of the outer
housing.
Special Note Regarding Smoke Detector Guards
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suit­able for that purpose.
N200-25-00 13 I56-2424-04R
Appendix I. Operation Modes and Troubleshooting Guide
• Sunlight into detector or reflector.
• Re-Align detector.
initialization or detector reset
Alignment Switch
Test Stations
Out of Range
• Clean detector and reflector.
Out of Range
reflector for reflective objects in the pathway.
• Faulty unit.
• Faulty unit.
discharged state.
Remains in fault until reset or time-out
after alignment
Blinks output by Yellow LED and Remote Trouble Output once the device has passed a local remote test:
Percent the
detector has
drifted
Remains in fault until reset or time-out
<100% 9
input
input
Number
of blinks
output
<10% None
<20% 1
<30% 2
<40% 3
<50% 4
<60% 5
<70% 6
<80% 7
<90% 8
Dual Digital Display Initiating means Comments & Troubleshooting Tips
Output
Remote Alarm
*Green
See Note Below
Trouble Output
Yellow and Remote
Below
See Note
0-99, or – if automatic gain
resetting, or Lo if signal is
too low
Off 3 Quick Blinks Blink Blink Off Long Term Drift Reference
Off 2 Quick Blinks Blink Blink Off Long Term Drift Reference
Off On Off Panel or RTS451/KEY Remains in alarm until reset or time-out
drift used
Off 2 Quick Blinks Blink Blink Off Increase of Reflected Signal • Inspect line of sight between detector and
Off 4 Quick Blinks Blink Blink Off Beam Blockage • Remove blockage.
On 4 Quick Blinks Blink On Off Beam Blockage • Remove blockage.
Off Blink until complete Blink Blink Off Apply Power from
Off Blink until complete Blink Blink Off Depressing RESET switch
On Blinks out amount of
Blink Blink Off Panel or RTS451/KEY test
Blink Blink Off Panel or RTS451/KEY test
time-out
time-out
Off On until reset or
Off On until reset or
Off On Off Panel or RTS451/KEY Remains in alarm until reset or time-out
drift used
On Blinks out amount of
Modes *Red
Normal Off Off Blink Blink Off Successful completion of
Alignment Off On Blink Blink On, Relative amount of signal
Alarm On Off Off On Off Smoke, Test Filter, RTS451
Trouble-Drift Comp
Elevated Signal
Trouble-Drift Comp
Reduced Signal
N200-25-00 14 I56-2424-04R
Trouble-Signal
Over Range
Trouble-Beam
Blockage Initial
Response
Trouble-Beam
Blockage Long
Term Response
Initialization-
Power on
Initialization-
alignment exit
Local Test
(FSB-200S)
Pass Result
Local Test
(FSB-200S)
Fail Result
Local Test
(FSB-200)
Fail
Local Test
(FSB-200)
Pass Result
Note: Green and Red LEDs are controlled by the control panel.
Appendix II. Detector Drilling Template
4.345
6.190
Scale = 1:1
N200-25-00 15 I56-2424-04R
N200-25-00 16 I56-2424-04R
5.512
(140mm)
8.465
(215mm)
Appendix III. Reflector Drilling Template
Scale = 1:1
N200-25-00 17 I56-2424-04R
Please refer to insert for the Limitations of Fire Alarm Systems
This projected beam smoke detector has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
N200-25-00 18 I56-2424-04R
FCC Statement
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communica­tions. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
©2004 System Sensor
Loading...