System Sensor FAAST 7100X, FAAST 7100XA Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
WARNING
I56-6006-001
FAAST 7100X and 7100XA Fire Alarm Aspiration Sensing Technology
SPECIFICATIONS
Electrical Characteristics
External Supply Voltage 18 – 30 VDC Remote Reset Time External monitor must be pulled low for a minimum of 100 msec Power Reset 1 sec Relay Contact Ratings 3.0A @ 30VDC, 0.5A @125VAC
Environmental Ratings
The purpose of this document is to provide practical information for mount­ing and connecting to FAAST XS. For full product information, which includes installation guidelines, instructions for safe use, and warranty and safety information, refer to the FAAST XS Comprehensive User Guide available at systemsensor.com/7100Xuserguide or by scanning the QR code.
ITEMS INCLUDED WITH UNIT
• FAAST XS (7100X or 7100XA) device
• Mounting bracket and hardware
• Installation and Maintenance Instructions
• USB interface cable
• PipeIQ® software, comprehensive manual, and other helpful documents are available at systemsensor.com/faast
CONNECTING TO FAAST XS
FAAST XS requires a valid configuration from PipeIQ in order to initialize. The device must be connected to a PC running PipeIQ with either the USB port, or the Ethernet port located inside the wiring cabinet.
CONNECTING TO FAAST XS VIA USB
NOTE: In order to connect your computer to the FAAST XS using a USB con­nection, a USB driver must first be installed. The driver installation occurs during the installation of PipeIQ version 2.2 or later. Once the driver is in­stalled, connect to the device using the following steps.
1. Launch PipeIQ. (Download from www.systemsensor.com/faast.)
2. Create a new project and select FAAST XS device, or open an existing project
3. Expand the tree view in the left side navigation pane to reveal the device
4. Right click on the device and select ‘Connect Device’
5. Select USB, The USB combo box should already be populated with FAAST XS (COM Port Number).
6. Select ‘Admin’ and enter the password – the default password is ‘password’ – then hit ‘Connect’
CONNECTING TO FAAST XS VIA ETHERNET
Default Device IP Configuration
IP Address: 192.168.1.10
Subnet Mask: 255.255.255.0
Default Gateway: 192.168.1.1
Primary DNS: 0.0.0.0
Secondary DNS: 0.0.0.0
CONFIGURE YOUR PC
Your PC will need to be sitting on the same local area network as the FAAST XS device in order to establish communication. Change your PC’s IP address to
192.168.1.15 by:
1. Accessing your network setting in your PC’s control panel
2. Open ‘Local Area Connection’ settings and select ‘Properties’
3. Select ‘Internet Protocol Version 4 (TCP/IPv4) and then select ‘Properties’
4. Select ‘Use the following IP address and enter 192.168.1.15. If the sub-
5. Hit OK and close out of the network menus.
Important Note: Before changing your PC’s IP address, be sure to take note of whether your IP is currently dynamically set, or is a static IP address. If your PC is assigned a static IP address, make note of all IP address and settings so that you can change back to the proper settings after the FAAST has been configured.
CONNECT USING PIPEIQ
1. Launch PipeIQ. (Download from systemsensor.com/faast)
2. Create and save a new project, or open an existing project
3. Expand the tree view in the left side navigation pane to reveal the device
4. Right click on the device and select ‘Connect Device’
5. Select Host/IP and type in the device’s IP address - default is
6. Select ‘Admin’ and enter the password – the default password is
7. Upon connection, a green dot will appear on the device icon in the
INSTALLATION
This equipment must be installed in accordance with all local and national codes and regulations.
PIPE INSTALLATION
The pipe layout is designed using the PipeIQ software package. Refer to the Comprehensive Instruction Manual to design the pipe network. All pipe must be installed in accordance with local and national codes and regulations. The pipe network should be complete before proceeding with the physical and electrical system installation.
PHYSICAL UNIT INSTALLATION
Make sure that there are no pipes or electrical wires within the wall before drilling any mounting holes
SECURING THE MOUNTING BRACKET
The typical mounting location for the FAAST XS unit is on the wall. The unit is mounted to the wall using the enclosed mounting bracket. Figure 1 shows the wall mounting bracket. For easier access to the FAAST XS unit, it is preferred to position the mounting bracket in an easily accessible location.
1. Place the mounting bracket on the wall in the desired location and use
2. Mark the hole locations and remove the bracket. It is recommended to
3. Using a drill and the proper size bit for your mounting hardware, drill
4. Use appropriate fasteners to accommodate the mounting surface and
5. Secure the bracket to the wall.
®
net mask does not automatically populate, enter 255.255.255.0 into the subnet mask field.
192.168.1.10
‘pass word’ – then hit ‘Connect’
navigation tree
it as a template to locate the necessary mounting holes.
secure the bracket using both mounting holes.
the necessary holes.
FAAST XS device weight.
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495 www.systemsensor.com
SS-600-012 1 I56-6006-001
FIGURE 1: WALL MOUNTING BRACKET
ATTENTION
WARNING
CONNECTING THE AIR SAMPLING PIPE
5.800
3.500
2.500
3.860
.300, 1/4 in., 20 TPI Mounting Stud
.300
ASP127-00
MOUNTING THE DETECTOR TO THE BRACKET
Once the mounting bracket is attached, the unit is ready to be secured onto the bracket. Perform the following procedure to mount the unit.
1. Before installing the unit onto the bracket, remove the appropriate conduit caps from the top or left side of the unit to match the orienta­tion of the wiring.
2. Align the unit with the three mounting clips and the mounting stud on the left side. Locate the conduit openings around the wiring access door.
3. Push the unit down onto the mounting clips and secure it with the supplied washer and nut on the mounting stud protruding through the mounting slot shown in Figure 1.
FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS
4.680
2.500
10.310
Detailed pipe network information and best practices can be found in the
Pipe Installation Guide, available for download at systemsensor.com/faast
The input and output ports are designed to accept nominal one inch pipe (25mm). The input and output ports are tapered to provide fast, easy, pushfit connection of the sampling pipe to the unit. Perform the following procedure to connect the air sampling pipe to the unit.
1. Square off and de-burr the end of the sampling pipe. Ensure that the pipe is free from any particles that might interfere with the pipe con­nection.
2. Remove the input plug from the input port being used (either the top or bottom of the unit).
3. Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT glue these pipes.
EXHAUST PIPE
The device should always be exhausted into the space that it is monitoring. There are some circumstances where it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit. Adding as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensur­ing quieter operation. Perform the following procedure to connect the exhaust pipe to the unit.
1. Square off and de-burr the end of the exhaust pipe. Ensure that the pipe is free from any particles that might interfere with the pipe con­nection.
2. Remove the plug from the exhaust port being used (either the top or bottom of the unit).
3. Inset the air exhaust pipe into the port, ensuring a snug fit. DO NOT glue these pipes.
WIRING
Before working on the FAAST XS system, notify all required authorities that the system will be temporarily out of service. Make sure all power is removed from the system before opening the unit. All wiring must be in accordance with local codes.
POWER CABLES
Use the power ratings of the unit and any other connected products to deter­mine the required wire sizes for each connection.
CONDUIT USAGE
If electrical conduit has been used for system wiring, terminate the conduits at the cable entry ports on the top of the unit, using the appropriate conduit connectors.
1. Run all wiring, both power and alarm, through the conduit and into the left side of the unit enclosure.
2. Attach the appropriate wires to the supplied Euro connectors. Follow appropriate local codes and electrical standards for all cabling.
3. Plug the appropriate connector into the mating connector on the unit. Refer to Table 1.
9.000
SS-600-012 2 I56-6006-001
6.415
ASP126-00
Loading...
+ 2 hidden pages