INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-6006-001
FAAST 7100X and 7100XA
Fire Alarm Aspiration Sensing Technology
SPECIFICATIONS
Electrical Characteristics
External Supply Voltage 18 – 30 VDC
Remote Reset Time External monitor must be pulled low for a minimum of 100 msec
Power Reset 1 sec
Relay Contact Ratings 3.0A @ 30VDC, 0.5A @125VAC
Environmental Ratings
Operating Temperature 32°F (0°C) to 100°F (38°C) – Factory tested to 131°F (55°C)
Sampled Air Temperature -4°F (-20°C) to 140°F (60°C)
Humidity 10 to 95% non-condensing
The purpose of this document is to provide practical information for mounting and connecting to FAAST XS. For full product information, which includes
installation guidelines, instructions for safe use, and warranty and safety
information, refer to the FAAST XS Comprehensive User Guide available at
systemsensor.com/7100Xuserguide or by scanning the QR code.
ITEMS INCLUDED WITH UNIT
• FAAST XS (7100X or 7100XA) device
• Mounting bracket and hardware
• Installation and Maintenance Instructions
• USB interface cable
• PipeIQ® software, comprehensive manual, and other helpful documents
are available at systemsensor.com/faast
CONNECTING TO FAAST XS
FAAST XS requires a valid configuration from PipeIQ in order to initialize. The
device must be connected to a PC running PipeIQ with either the USB port, or
the Ethernet port located inside the wiring cabinet.
CONNECTING TO FAAST XS VIA USB
NOTE: In order to connect your computer to the FAAST XS using a USB connection, a USB driver must first be installed. The driver installation occurs
during the installation of PipeIQ version 2.2 or later. Once the driver is installed, connect to the device using the following steps.
1. Launch PipeIQ. (Download from www.systemsensor.com/faast.)
2. Create a new project and select FAAST XS device, or open an existing project
3. Expand the tree view in the left side navigation pane to reveal the device
4. Right click on the device and select ‘Connect Device’
5. Select USB, The USB combo box should already be populated with FAAST
XS (COM Port Number).
6. Select ‘Admin’ and enter the password – the default password is ‘password’
– then hit ‘Connect’
CONNECTING TO FAAST XS VIA ETHERNET
Default Device IP Configuration
IP Address: 192.168.1.10
Subnet Mask: 255.255.255.0
Default Gateway: 192.168.1.1
Primary DNS: 0.0.0.0
Secondary DNS: 0.0.0.0
CONFIGURE YOUR PC
Your PC will need to be sitting on the same local area network as the FAAST
XS device in order to establish communication. Change your PC’s IP address to
192.168.1.15 by:
1. Accessing your network setting in your PC’s control panel
2. Open ‘Local Area Connection’ settings and select ‘Properties’
3. Select ‘Internet Protocol Version 4 (TCP/IPv4) and then select ‘Properties’
4. Select ‘Use the following IP address and enter 192.168.1.15. If the sub-
5. Hit OK and close out of the network menus.
Important Note: Before changing your PC’s IP address, be sure to take note of
whether your IP is currently dynamically set, or is a static IP address. If your PC
is assigned a static IP address, make note of all IP address and settings so that
you can change back to the proper settings after the FAAST has been configured.
CONNECT USING PIPEIQ
1. Launch PipeIQ. (Download from systemsensor.com/faast)
2. Create and save a new project, or open an existing project
3. Expand the tree view in the left side navigation pane to reveal the device
4. Right click on the device and select ‘Connect Device’
5. Select Host/IP and type in the device’s IP address - default is
6. Select ‘Admin’ and enter the password – the default password is
7. Upon connection, a green dot will appear on the device icon in the
INSTALLATION
This equipment must be installed in accordance with all local and national
codes and regulations.
PIPE INSTALLATION
The pipe layout is designed using the PipeIQ software package. Refer to the
Comprehensive Instruction Manual to design the pipe network. All pipe must
be installed in accordance with local and national codes and regulations. The
pipe network should be complete before proceeding with the physical and
electrical system installation.
PHYSICAL UNIT INSTALLATION
Make sure that there are no pipes or electrical wires within the wall before
drilling any mounting holes
SECURING THE MOUNTING BRACKET
The typical mounting location for the FAAST XS unit is on the wall. The unit is
mounted to the wall using the enclosed mounting bracket. Figure 1 shows the
wall mounting bracket. For easier access to the FAAST XS unit, it is preferred
to position the mounting bracket in an easily accessible location.
1. Place the mounting bracket on the wall in the desired location and use
2. Mark the hole locations and remove the bracket. It is recommended to
3. Using a drill and the proper size bit for your mounting hardware, drill
4. Use appropriate fasteners to accommodate the mounting surface and
5. Secure the bracket to the wall.
®
net mask does not automatically populate, enter 255.255.255.0 into
the subnet mask field.
192.168.1.10
‘pass word’ – then hit ‘Connect’
navigation tree
it as a template to locate the necessary mounting holes.
secure the bracket using both mounting holes.
the necessary holes.
FAAST XS device weight.
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
SS-600-012 1 I56-6006-001
FIGURE 1: WALL MOUNTING BRACKET
CONNECTING THE AIR SAMPLING PIPE
5.800
3.500
2.500
3.860
.300, 1/4 in.,
20 TPI Mounting Stud
.300
ASP127-00
MOUNTING THE DETECTOR TO THE BRACKET
Once the mounting bracket is attached, the unit is ready to be secured onto
the bracket. Perform the following procedure to mount the unit.
1. Before installing the unit onto the bracket, remove the appropriate
conduit caps from the top or left side of the unit to match the orientation of the wiring.
2. Align the unit with the three mounting clips and the mounting stud
on the left side. Locate the conduit openings around the wiring access
door.
3. Push the unit down onto the mounting clips and secure it with the
supplied washer and nut on the mounting stud protruding through the
mounting slot shown in Figure 1.
FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS
4.680
2.500
10.310
Detailed pipe network information and best practices can be found in the
Pipe Installation Guide, available for download at systemsensor.com/faast
The input and output ports are designed to accept nominal one inch pipe
(25mm). The input and output ports are tapered to provide fast, easy, pushfit
connection of the sampling pipe to the unit. Perform the following procedure
to connect the air sampling pipe to the unit.
1. Square off and de-burr the end of the sampling pipe. Ensure that the
pipe is free from any particles that might interfere with the pipe connection.
2. Remove the input plug from the input port being used (either the top
or bottom of the unit).
3. Inset the air sampling pipe into the port, ensuring a snug fit. DO NOT
glue these pipes.
EXHAUST PIPE
The device should always be exhausted into the space that it is monitoring.
There are some circumstances where it may be necessary to connect a pipe
to the exhaust port to divert the exhaust away from the location of the unit.
Adding as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensuring quieter operation. Perform the following procedure to connect the exhaust
pipe to the unit.
1. Square off and de-burr the end of the exhaust pipe. Ensure that the
pipe is free from any particles that might interfere with the pipe connection.
2. Remove the plug from the exhaust port being used (either the top or
bottom of the unit).
3. Inset the air exhaust pipe into the port, ensuring a snug fit. DO NOT
glue these pipes.
WIRING
Before working on the FAAST XS system, notify all required authorities that
the system will be temporarily out of service. Make sure all power is removed
from the system before opening the unit. All wiring must be in accordance
with local codes.
POWER CABLES
Use the power ratings of the unit and any other connected products to determine the required wire sizes for each connection.
CONDUIT USAGE
If electrical conduit has been used for system wiring, terminate the conduits
at the cable entry ports on the top of the unit, using the appropriate conduit
connectors.
1. Run all wiring, both power and alarm, through the conduit and into
the left side of the unit enclosure.
2. Attach the appropriate wires to the supplied Euro connectors. Follow
appropriate local codes and electrical standards for all cabling.
3. Plug the appropriate connector into the mating connector on the unit.
Refer to Table 1.
9.000
SS-600-012 2 I56-6006-001
6.415
ASP126-00