System Sensor EPS10EXP User Manual

COVER
4.9"
9.5"
LOCKING SCREW
HEX ADJUST SCREW 1/4" HEX HEAD
COVER TAMPER SET SCREW (WRENCH PROVIDED)
ADJUSTMENT WHEEL COVER (WRENCH PROVIDED)
MAIN ADJUSTMENT WHEEL (TURN COUNTERCLOSKWISE TO INCREASE PRESSURE)
1/2" NPT
D770-25-00 1 I56-1427-001R
EPS10EXP Explosion Proof Alarm Pressure Switch
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Important
Please Read Carefully and Save
This instruction manual contains important information about the installation and operation of alarm pressure switches. Purchasers who install switches for use by others must leave this manual or a copy of it with the user.
Read all instructions carefully before installation, following only those instructions that apply to the model you are installing.
Before installing any alarm device, be thoroughly familiar with: NFPA 72: Installation, Maintenance, and Use of
Protective Signaling Systems
NFPA 13: Installation of Sprinkler Systems
Other applicable NFPA standards, local codes, and the requirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm condition. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
Operation
As pressure changes, a diaphragm actuates 2 snap action switches. The pressure switch actuation is determined by adjustment settings.
Specifications
Contact Ratings: 10 A, 1/2 HP @ 125/250 VAC
2.5 A @ 6/12/24 VDC Operating Temperature Range: –40° F to +160°F Maximum Service Pressure: 250 PSI Maximum Adjustment Range: 4 – 20 PSI Enclosure Rating: NEMA Type 4 — Indoor or/Outdoor Use Hazardous Atmospheres Classification: Class I, Groups B, C, D, Div. 1
Class II, Groups E, F, G, Div. 1 Class III, Div. 1
Approximate Differential: 3 PSI throughout range
Installation
1.
Back out cover tamper set screw and remove cover (Fig. 1).
2. Mounting the Switch The device is designed to be mounted in the upright or horizontal position; side mounting is also acceptable.
Figure 1. Pressure switch basic dimensions:
WARNING
To prevent ignition of hazardous atmospheres, disconnect circuits before removing cover. Keep cover closed while cir­cuits are live. Conduit runs must have sealing fittings con­nected within 18” of the enclosure.
D770-25-00 2 I56-1427-001R
Locate it where vibration, shock, and mechanical loading are minimal. Refer to piping diagram (Figure 2 on page 2).
a. Mount the device directly to the line via the 1/2" NPT
pressure connection. The use of teflon pipe sealant tape is recommended. Be sure the fitting is tight enough to prevent leaks.
b. Apply tightening torque to the brass hex portion of
device.
High voltage. Electrocution hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death.
3. Wire the device in accordance with the National Electrical Code. Two 1/2” NPT conduit entry holes have been provided in the mounting base to accept explosion proof conduit fittings. If necessary, remove conduit entry plug with 3/8” square wrench.
4. Connect wiring to terminals (see Figure 3 and Table 1).
Adjustments To Factory Settings
CAUTION
WET SYSTEM ALARM CHECK VALVE
OS & Y VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
RETARD
WATER MOTOR GONG
EPS10EXP
WET SYSTEM ALARM CHECK VALVE
OS & Y VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
RETARD
WATER MOTOR GONG
EPS10EXP
DRY SYSTEM ALARM CHECK VALVE
OS & Y VALVE
WATER
BY-PASS
VALVE
LOCAL ALARM
SHUT OFF
VALVE
WATER MOTOR GONG
CHECK VALVE
EPS10EXP
WET SYSTEM WET SYSTEM DRY SYSTEM
WIRE TO ALARM INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
WIRE TO ALARM INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
WIRE TO ALARM INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
TO SPRINKLER SYSTEM
TO SPRINKLER SYSTEM
TO SPRINKLER SYSTEM
Figure 2. Typical piping diagram for EPS10EXP
A78-2398-00
Figure 3. Switch terminals:
Table 1. Electrical connections (referenced at facto­ry settings):
COMMON TERMINALS
TERMINAL “A”
SWITCH #2
TERMINAL “B”
GROUND SCREW (GREEN)
SWITCH #1
A78-2346-02
BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION. DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING. DO NOT LOOP WIRES.
SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)
SWITCHES AT 0 P.S.I.
SW1 SW2
MODEL EPS10EXP
SW1 SW2
B
COM
A
B
COM
A
A
COM
B
A
COM
B
BOTH SWITCHES ACTIVATE SIMULTANEOUSLY
Loading...
+ 2 hidden pages