System Sensor EPS10-1, EPS10-2 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CAUTION
WARNING
HEX ADJUSTMENT SCREW
MAIN ADJUSTMENT WHEEL
4-1/4"
5-1/8"
LOCKING SCREW
1/2" NPT
COM
AB
GROUND SCREW (GREEN)
SWITCH #2
MODEL EPS10-1
MODEL EPS10-2
A
COM
B
SWITCHES AT 0 P.S.I.
SWITCH AT 0 P.S.I.
SWITCH AT 4-8 P.S.I. (HIGH TRIP PT.)
B
COM
A
B
COM
A
B
COM
A
A
COM
B
A
COM
B
SWITCH 1 BOTH SWITCHES ACTIVATE SIMULTANEOUSLY
SW1 SW2
SW1 SW2
SWITCHES AT 4-8 P.S.I. (HIGH TRIP PT.)
I56-0551-009R
EPS10 Series Alarm Pressure Switches
SPECIFICATIONS
Contact Ratings: 10 A, 1/2 HP @ 125/250 VAC 8 A, 125/250 VAC (LPCB only)
2.5A @ 6/12/24 VDC Overall Dimensions: See Figure 1 Operating Temperature Range: –40° to +160°F Maximum Service Pressure: 300 PSI Maximum Adjustment Range: 4 – 20 PSI Enclosure Rating: UL 4x — Indoor or Outdoor Use NEMA 4 — Indoor or Outdoor Use IP54 Approximate Differential: 3 PSI throughout range
FIGURE 1. PRESSURE SWITCH BASIC DIMENSIONS:
OPERATION
As pressure changes, a diaphragm actuates 1 or 2 snap action switches. The pressure switch actuation is determined by adjustment settings.
INSTALLATION
1. Remove Cover Cover is held on by two tamper resistant screws. (Removal key is en-
closed with pressure switch.)
2. Mounting the Switch
The device is designed to be mounted in the upright or horizontal posi-
tion; side mounting is also acceptable. Locate it where vibration, shock, and mechanical loading are minimal. Refer to piping diagram (Figure 2 on page 2).
a. Mount the device directly to the line via the 1⁄2
nection. The use of teflon pipe sealant tape is recommended. Be sure the fitting is tight enough to prevent leaks.
b. Apply tightening torque to the black plastic hex portion of device.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
NPT pressure con-
IMPORTANT
Please Read Carefully and Save
Read all instructions carefully before installation, following only those instruc­tions that apply to the model you are installing.
Before installing any alarm device, be thoroughly familiar with:
NFPA 72: Installation, Maintenance, and Use of Protective Signaling Systems
NFPA 13: Installation of Sprinkler Systems
NFPA 13A: Inspection, Testing, and Maintenance of Sprinkler Systems
Other applicable NFPA standards, local codes, and the requirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm condition. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
Do not use in potentially explosive atmospheres.Do not leave unused wires exposed.
D770-08-00 1 I56-0551-009R
W0170-00
High voltage. Electrocution hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury or death. When utilizing switches at voltages greater than 74 VDC or 49 VAC , means to provide all-pole disconnection must be incorporated in the field wiring, such as a circuit breaker.
3. Wire the device in accordance with the National Electrical Code. Two
7
8
diameter conduit connection holes have been provided in the
mounting plate to accept standard 1⁄2
conduit fittings (one is remov­able knock-out type). If a NEMA 4/UL 4x (waterproof unit) is re­quired, waterproof flexible metallic conduit and appropriate conduit fittings must be used. Recommended connectors are Thomas and Betts PN 5332 (180° coupling), PN 5352 (90° coupling), and PN 5262 seal ring.
4. Connect wiring to terminals (see Figure 3 and Table 1).
TABLE 1. ELECTRICAL CONNECTIONS (REFERENCED AT FACTORY SETTINGS):
WET SYSTEM ALARM CHECK VALVE
WET SYSTEM WET SYSTEM DRY SYSTEM
WIRE TO ALARM
WIRE TO ALARM
WIRE TO ALARM
FIGURE 2. TYPICAL PIPING DIAGRAM FOR EPS10-1, EPS10-2
COMMON
LOOP WIRES.
OS & Y VALVE
TO SPRINKLER SYSTEM
WATER
BY-PASS
VALVE
EPS10
EPS10EXP
INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
LOCAL ALARM
SHUT OFF
VALVE
WATER MOTOR GONG
RETARD
FIGURE 3. SWITCH TERMINALS:
SWITCH #1
A
B
GROUND SCREW
LOCKING SCREW
COM
SWITCH #2
TERMINALS
TERMINAL “A”
TERMINAL “B”
SWITCH #2
WET SYSTEM ALARM CHECK VALVE
OS & Y VALVE
TO SPRINKLER SYSTEM
WATER
BY-PASS
VALVE
WATER MOTOR GONG
LOCAL ALARM
SHUT OFF
VALVE
RETARD
EPS10
EPS10EXP
INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
DRY SYSTEM ALARM CHECK VALVE
OS & Y VALVE
TO SPRINKLER SYSTEM
CHECK VALVE
WATER
BY-PASS
VALVE
EPS10
LOCAL ALARM
Each number represents an approximate trip point change of 0.2 PSI. One full rotation changes the trip point setting by approximately 2.5 PSI. A reset differential of approximately 3 PSI is typical throughout the entire adjustment range of switch.
4. Retest the set point several times to ensure accuracy of setting.
5. Re-seat locking screw.
TABLE 2.
FACTORY SETTINGS (PSI)
MODEL
Fall
(Low Switch)
Approx.
Reset
Rise
(High Switch)
EPS10-1 4 – 8 3 PSI diff.
EPS10-2 4 – 8 3 PSI diff.
INDICATING CIRCUIT OF FIRE ALARM CONTROL PANEL
WATER MOTOR GONG
SHUT OFF
VALVE
W0171-01
Approx.
Reset
NOTE: The sensor assembly is not field replaceable. Do not attempt to disas-
BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION. DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING. DO NOT
W0173-00
semble these parts. If you have any questions, consult System Sensor. System Sensor recommends careful consideration of the following fac­tors when specifying and installing Alarm Pressure Switches. Always refer to the Installation and Maintenance Instruction for specific rec­ommendations on individual devices before installing the unit.
ADJUSTMENTS TO FACTORY SETTINGS
Both EPS10-1 and EPS10-2 devices are pre-adjusted at the factory to alarm at 4–8 PSI on rising pressure (see Table 2). Pressure switch settings may be adjusted in the field to obtain a different pressure alarm response from 4 PSI to 20 PSI. The switch has an override feature on the adjustment mechanism to prevent exceeding the 20 PSI max. setting of the switch. This override feature carries with it a tolerance band that may limit the upper adjustment to 16–20 PSI. Care must be used when setting the switch to ensure that the lower limit of 4 PSI is not exceeded. This will allow the switch to reset within the 3 PSI differential stated.
1. Install pressure switch as stated in “INSTALLATION” portion of instruc­tion manual. Attach pressure test source to system.
2. Back off locking screw (see Figure 1) to allow main adjustment wheel to rotate freely.
3. Test trip point by slowly introducing pressure from the pressure test source. When trip point is found, reduce pressure to zero. Rotate main adjustment wheel (counterclockwise to increase pressure) and retest un­til switch trip point is at the desired pressure setting (4–20 PSI range).
• Electrical ratings stated in literature and on nameplates should not be exceeded.
• Overload on switch can cause failure on the first cycle. Always wire devices according to national and local electrical codes.
• Install units away from shock and vibration. Proper electrical fittings should be used to prevent moisture from entering the enclosure via the conduit.
• Test all devices for proper operation after initial installation. Perform pre­ventive maintenance and periodic testing as required by the applicable NFPA standards but not less than bimonthly.
• Install a back-up control for all critical applications where control failure could endanger life or property. A backup control to serve as a high or low limit control is especially recommended for applications where a runaway condition could result.
• Do not mount unit where ambient temperatures will exceed published limits.
• Avoid impact or mechanical loading.
Please refer to insert for the Limitations of Fire Alarm Systems
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed pressure switch to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this pressure switch. No agent, representative, dealer, or employee of the Company has the authority to in­crease or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the pressure switch which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Return
D770-08-00 2 I56-0551-009R
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
© System Sensor 2014