System Sensor EBR User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
3
I56-3741-001R
EBR Plug-in Relay Detector Base
SPECIFICATIONS
Base Diameter: 6.85 in (17.4 cm) Base Height (less sensor): 1.61 in (4.1 cm) Operating Temperature Range: Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com Operating Humidity Range: 10% to 93% Relative Humidity (Non-condensing)
Electrical Ratings
Operating Voltage: 15 to 32 VDC Standby Current: 170 µA
Relay Characteristics
Coil: 2 coil latching Contact Type: Form C Contact Relay Ratings
CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION
2 A 25 VAC PF = 0.35 Non-coded
3 A 30 VDC Resistive Non-coded
2 A 30 VDC Resistive Coded
0.46 A 30 VDC (L/R = 20ms) Non-coded
0.7 A 70.7 VAC PF = 0.35 Non-coded
0.9 A 125 VDC Resistive Non-coded
0.5 A 125 VAC Resistive Non-coded
0.3 A 125 VAC PF = 0.35 Non-coded
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Set Time: 20 msec Reset Time: 250 msec
BEFORE INSTALLING
NOTICE: This manual should be left with the owner/user of this equipment. IMPORTANT: The detector used with this base must be tested and maintained
regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.
GENERAL DESCRIPTION
The relay base is intended for use with intelligent systems. Refer to the panel manual for maximum allowable number of units per loop.
Form C latching relay contacts are included for the control of an auxiliary function.
BASE TERMINALS NO. FUNCTION
1. Normal Close
2. Common
3. Normal Open
4. Comm. (–)
5. Comm. (+) In/Out
6. Comm. (+) Out/In
FIGURE 1. TERMINAL LAYOUT:
2
1
4
5
6
CO471-04
SS-450-006 1 I56-3741-001R
MOUNTING
WARNING
Mount the mounting plate directly to an electrical box. The plate will mount directly to 4-inch square, 4-inch octagon, 3 ½-inch octagon, single gang and double gang junction boxes.
1. Connect field wiring to terminals, as shown in Figure 3.
2. Attach the mounting plate to the junction box as shown in Figure 2.
3. To mount the base, hook the tab on the base to the groove on the mounting plate.
4. Then, swing the base into position to engage the pins on the product with the terminals on the mounting plate.
5. Secure the base by tightening the mounting screws.
6. Install a compatible smoke detector as described in the installation manual for the detector.
INSTALLATION AND WIRING GUIDELINES
All wiring must be installed in compliance with all applicable local codes and any special requirements of the local authority having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recom­mended that the wire be no smaller than 18 AWG (0.823 square mm). Wire sizes up to 12 AWG (3.31 square mm) may be used with the base. The base will be shipped with the screw terminals set for 14 AWG wiring. If 12 AWG wire is used, back out the screws to allow the wire to fit beneath the clamp­ing plates.
Make electrical connections by stripping about 3/8 inch (10 mm) of insulation from the end of the wire (use strip gauge molded in base). Then slide the wire under the clamping plate and tighten the clamping plate screw. Do not loop the wire under the clamping plate. (See Figure 4)
Wire the normally open (NO) line to terminal 3 (see Figure 3). Insert the nor­mally closed (NC) line of the relay to terminal 1 and the relay common line to terminal 2. Wire the communication lines in (–) and out (–)to terminal 4. Insert the communication line in (+) and out (+) to terminal 5.
Check the zone wiring of all bases in the system before installing the detec­tors. This includes checking the wiring for continuity, correct polarity,
ground fault testing and performing a dielectric test.
The base includes an area for recording the zone, address, and type of detec­tor being installed. This information is useful for setting the detector head address and for verification of the detector type required for that location.
Once all detector bases have been wired and mounted, and the loop wiring has been checked, the detector heads may be installed in the bases.
Alarm system control panels have specifications for allowable loop resistance. Consult the control panel specifications for the total loop resistance allowed before wiring the detector loops.
FIGURE 2. MOUNTING THE BASE TO AN ELECTRICAL BOX:
SCREWS
(NOT SUPPLIED)
BOX
(NOT SUPPLIED)
MOUNTING PLATE
C0148-03
The base uses a latching relay that can change states if it is subjected to me­chanical shocks or jarring. As a result, even though relay contacts are in the open state when the base is shipped from the factory, the contacts may have closed during shipment.
Connecting an auxiliary control circuit to closed relay contacts can cause an unexpected, and possibly dangerous, activation of that circuit. Therefore, do NOT connect an auxiliary control circuit to the relay contacts (terminals 1, 2, and 3) before ensuring that the relay contacts are in their open state. Ensure that the contacts are open by applying power to the bases WITHOUT the de­tector heads installed.
SS-450-006 2 I56-3741-001R
Loading...
+ 2 hidden pages