System Sensor DH400ACDCP User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH400ACDCP Air Duct Smoke Detector
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use of Smoke Detectors in Duct Applications
(A05-1004), which provides detailed information on de­tector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available online at www.systemsensor.com or via System Sensor’s toll free fax-back service, Documents on Demand at 800/736-7672. NFPA Standards 72 and 90A should also be referenced for
detailed information.
NOTICE: This manual should be left with the owner/user of this equipment.
Table of Contents Page
[1] General Description 1 [2] Exploded View of Duct Detector Components 2 [3] Contents of the Duct Detector Kit 2 [4] Limitations of Duct Detectors 2 [5] Installation Sequence 2 [6] Duct Detector Maintenance and Test Procedures 8 [7] Detector Cleaning Procedures 10 [8] Specifications 12 Warranty 13 Detector Test log 16
List of Tables and Figures Page
Fig. 1: Duct Detector Exploded View 2 Fig. 2: Installation of Sampling Tube Gaskets 3 Fig. 3: Mounting Location of Speed Nuts 3 Table 1: Inlet Sampling Tube Selection 3 Fig. 4: Inlet Sampling Tube 4 Fig. 5: Sampling Tube Mounting Configurations 4 Fig. 6: Wiring Diagram 6 Fig. 7: Wiring Diagram – No Control Panel 7 Fig. 8: Wiring Diagram – Accessories 8 Fig. 9: Sampling Tube Filter Installation 8 Fig. 10: Testing Detector Alarm 9 Fig. 11: Detector Head Removal 9 Fig. 12: RTS451/RTS451KEY Test Coil Installation 10 Fig. 13: Photo Head Exploded View 11
[1] General Description
An HVAC system supplies conditioned air to virtually ev­ery area of a building. Smoke introduced into this air duct system will be distributed to the entire building. Smoke detectors designed for use in air duct systems are used to sense the presence of smoke in the duct.
Model DH400ACDCP Air Duct Smoke Detector utilizes photoelectric technology for the detection of smoke. This smoke detection method, when combined with an efficient housing design, samples air passing through the duct and allows detection of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is initi­ated at the fire control panel monitoring the detector, and appropriate action can be taken to shut off fans and blow­ers, change over air handling systems, etc. These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system.
For testing, the alarm can be enabled by a magnet activated test switch, by insertion of a calibrated test card into the sensing chamber (photoelectronic version only), or by the optional remote test station. The duct smoke detectors latch into alarm state when alarm occurs. LEDs on each detector illuminate to provide local alarm indication, and optional accessories offer a variety of annunciation capabilities.
The detector can be reset by a momentary power inter­ruption, by the magnet activated reset switch, or by the optional remote test station.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsenor.com
D400-13-00 1 I56-555-09R
WARNING
WARNING
WARNING
CAUTION
[2] Figure 1. Exploded view of duct detector components:
SAMPLING TUBE
FILTERS
CONDUIT HOLES
DUCT DETECTOR
HOUSING
TERMINAL STRIP
PC BOARD INSULATOR
DUCT DETECTOR
COVER
SAMPLING TUBE
MOUNTING
SCREWS
DETECTOR HEAD
EXHAUST
FILTER ADAPTER
DETECTOR BASE
INLET SAMPLING TUBE
(SUPPLIED SEPARATELY)
O-RINGS
FOAM
GASKETS
HOUSING
MOUNTING SCREWS
TEST MAGNET
TUBE
END
PLUG
[3] Contents Of The Duct Detector Kit
1. Complete housing base and cover assembly
2. Two #10 sheet metal mounting screws
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two 5/16 O-rings
7. Two rubber tube bushing seals
8. Four #6 self-tapping mounting screws for the sampling and optional exhaust tube extension
9. One filter adapter
10.One inlet tube end plug
11.Two #10 speed nuts
NOTE: The inlet sampling tube must be ordered sepa-
rately. It must be the correct length for the width of the duct where it will be installed. See Table 1 on page 4 to determine the inlet tube required for different duct widths.
[4] Limitations Of Duct Detectors
The National Fire Protection Association has established that DUCT DETECTORS MUST NOT BE USED AS A SUB­STITUTE FOR OPEN AREA DETECTOR PROTECTION as a means of providing life safety. Nor are they a substitute for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recom­mends that the user read NFPA Standards 90A, 72, and 101. The DH400ACDCP Air Duct Smoke Detectors are listed per UL 268A.
H0249-00
This device does not sense smoke unless the ventilation system is operating.
[5] Installation Sequence
Step Page
[5.1] Verify duct air flow direction and velocity 2 [5.2] Drill the mounting holes 3 [5.3] Secure the detector housing to the duct 3 [5.4] Install the sampling tube 3 [5.5] Complete the field wiring 5 [5.6] Install the filters and check pressure differential 8 [5.7] Perform detector check 8 [5.8] Install the cover 8
[5.1] Verify Duct Air Flow Direction And Velocity
D400-13-00 2 I56-555-09R
feet per minute. Be sure to check engineering specifications
SCREW HOLES FOR ATTACHING DETECTOR HOUSING TO DUCT
FOAM GASKETS
EXHAUST TUBE
(EXTENSION BUSHING)
DUCT DETECTOR
HOUSING
O-RINGS
MOUNTING
SCREWS
INLET SAMPLING
TUBE BUSHING
HOLE B
HOLE A
DUCT WALL
SPEED
NUT
[5.2] Drill The Mounting Holes
[5.3] Secure The Detector Housing To The Duct
Remove the duct housing cover. Slide the foam gaskets over the tube bushings as shown in Figure 2. Make sure the two small holes in the gaskets line up with the two base mount­ing holes. Put one 5/16-inch O-ring over each of the two #10 sheet metal screws. Use the two sheet metal screws to screw the detector housing to the duct. CAUTION: Do not overtighten the screws.
Figure 2. Installation of foam gaskets over sampling tube bushings:
[5.4] Install The Inlet
The inlet tube (shown in Figure 4) is identified by a series of air inlet holes on the tube. This tube must be purchased separately. Order the correct length, as specified in Table 1, for width of the duct where it will be installed. The exhaust tube is molded into the base of the duct housing, and the A2440-00 Exhaust Tube Extension is available as an ac­cessory in those cases where the molded exhaust port does not extend at least 2 inches into the duct.
The inlet tube is always installed in the centermost hous­ing bushing, with air inlet holes facing into the air flow. To assist proper installation, the tube’s mounting flange is marked with arrows. Make sure the inlet tube is mounted so that the arrows point into the air flow. Figure 5 shows the various combinations of tube mounting configurations with respect to air flow.
Table 1. Inlet tubes required for different duct widths:
Outside Duct Width Inlet Tube Required
1 to 2 ft. ST-1.5 2 to 4 ft. ST-3 4 to 8 ft. ST-5 8 to 12 ft. ST-10
H0238-00
Figure 3. Speed nut mounting location:
D400-13-00 3 I56-555-09R
H0116-00
Figure 4. Air duct detector inlet sampling tube:
INLET TUBE END PLUG
AIR HOLES
ARROWS
MUST FACE
INTO AIR FLOW
AIR FLOW DIRECTION
FLANGE
AIR FLOW
DIRECTION
DETECTOR
HOUSING
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DETECTOR
HOUSING
INLET TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
EXHAUST
TUBE
INLET TUBE
INLET TUBE
EXHAUST
TUBE
DETECTOR
HOUSING
AIR FLOW
DIRECTION
EXHAUST
TUBE
INLET TUBE
DETECTOR
HOUSING
A.
B.
C.
D.
HORIZONTAL MOUNTING OF HOUSING
VERTICAL MOUNTING OF HOUSING
WARNING
Figure 5. Tube mounting configurations with varying air flow direction:
H0108-00
H0109-00
[5.4.1] Installation For Ducts Less Than 8 Feet Wide
outside the duct. Plug this end with the end plug and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in the tube ex­posed to the air stream.
2. Slide the tube into the centermost housing bushing. Po­sition the tube so that the arrows point into the air flow.
4. For tubes longer than the width of the air duct, the tube should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube extending out of the duct, select a different length using Table 1. Otherwise, trim the end of the tube protruding through the duct so that 1 to 2 inches of the tube extend
D400-13-00 4 I56-555-09R
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install inlet tubes in ducts more than 8 feet
wide, work must be performed inside the air duct. Sampling of air in ducts wider than 8 feet is accomplished by using the ST-10 inlet sampling tube. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4 and support the end opposite the duct detector.
Install the inlet tube as follows:
1. Drill a 3/4-inch hole in the duct directly opposite the
hole already drilled for the inlet tube.
2. Slide the inlet tube with the flange into the centermost
housing bushing. Position the tube so that the arrows point into the air flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
3. From inside the duct, couple the other section of the
inlet tube to the section already installed using the 1/2­inch conduit fitting supplied. Make sure that the holes on both of the air inlet tubes are lined up and facing into the air flow.
4. Trim the end of the tube protruding through the duct so
that 1 to 2 inches of the tube extend outside the duct. Plug this end with the end plug and tape closed any holes in the protruding section of the tube. Be sure to seal the duct when the tube protrudes.
NOTE: An alternate method to using the ST-10 is to use
two ST-5 inlet tubes. Remove the flange from one of the tubes and install as described above. After the installation, use electrical tape to close off some of the sampling holes so that there is a to­tal of 10 to 12 holes spaced as evenly as possible across the width of the duct.
Air currents inside the duct may cause excessive vibration, especially when the longer sampling tubes are used. In these cases a 3 inch floor flange (available at most plumb­ing supply stores) may be used to fasten the sampling tube to the other side of the duct. When using the flange/con­nector mounting technique, drill a 1 inch to 1-1/4-inch hole where the flange will be used.
[5.4.3] Modifications Of Inlet Sampling Tubes
There may be applications where duct widths are not what is specified for the installation. In such cases, it is permis­sible to modify an inlet sampling tube that is longer than necessary to span the duct width.
[5.5] Field Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction. Proper wire gauges should be used. The conductors used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding properly in the event of a fire.
For signal wiring, (the wiring between interconnected de­tectors or from detectors to auxiliary devices), it is usually recommended that single-conductor wire be no smaller than 18 gauge. The duct detector terminals accommodate wire sizes up to 14 gauge. The last foot of conduit should be flexible steel conduit (available in electrical supply houses), which facilitates installation and puts less strain on the conduit holes in the housing. Solid conduit connec­tions may be used, if desired.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loop.
Wiring Instructions
The DH400ACDCP duct detector is designed to operate from 24 VDC, 24 VAC, 120 VAC, or 240 VAC.
The detector may be wired for interconnection to UL listed control panels, or for stand alone service per NFPA 90A. Refer to the wiring diagrams of Figures 6, 7, and 8 to select the appropriate circuit for your application.
Use a 0.193-inch diameter (#11) drill and add the appro­priate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12. Space the additional holes as evenly as possible over the length of the tube.
D400-13-00 5 I56-555-09R
24V
120
VAC
220/240
VAC
1
2 1
2
13 14
AVAILABLE POWER INPUTS
ALARM AUXILIARY CONTACTS
FOR FAN SHUTDOWN, ETC.
15
16
17 18
19 20
N.C.C.
N.O.
N.O.
C.
N.C.
ALARM AUXILIARY CONTACTS SHOWN IN
STANDBY. CONTACTS TRANSFER DURING
ALARM AS INDICATED BY THE ARROWS.
TROUBLE CONTACTS
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.
CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS
REMOVED, AND DURING RESET. OPEN CONTACTS
SIGNAL TROUBLE CONDITION TO PANEL.
24V
120
VAC
220/240
VAC
1 2
12
13
14
AVAILABLE POWER INPUTS
ALARM AUXILIARY CONTACTS
FOR FAN SHUTDOWN, ETC.
15 16
17 18 19
20
N.C.
C.
N.O.N.O.
C.N.C.
ALARM AUXILIARY CONTACTS SHOWN IN
STANDBY. CONTACTS TRANSFER DURING
ALARM AS INDICATED BY THE ARROWS.
TROUBLE CONTACTS
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.
CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS
REMOVED, AND DURING RESET. OPEN CONTACTS
SIGNAL TROUBLE CONDITION TO PANEL.
11
10
11
10
8
9
ALARM
INITIATION
CONTACTS
CONTACTS SHOWN
OPEN IN STANDBY.
CONTACTS CLOSE
IN ALARM.
8
9
ALARM
INITIATION
CONTACTS
CONTACTS SHOWN
OPEN IN STANDBY.
CONTACTS CLOSE
IN ALARM.
ALARM
INITIATION
LOOP
UL LISTED
CONTROL PANEL
FIRST DETECTOR IN THE LOOP
DH400ACDCP
LAST DETECTOR IN THE LOOP
DH400ACDCP
EOL RESISTOR
SPECIFIED BY
PANEL MANUFACTURER
CONNECT POWER SOURCE
TO APPROPRIATE TERMINALS
OF EACH DETECTOR. SEE
SPECIFICATIONS FOR
ADDITIONAL POWER SUPPLY
INFORMATION.
FOR WIRING OF AUXILIARY
DEVICES, REFER TO
MANUFACTURER'S
INSTALLATION INSTRUCTIONS
OR CONTACT MANUFACTURER.
POWER INPUTS ACCEPT
24 VDC, 24 VAC 50-60 HZ,
120 VAC 50-60 HZ, OR
220/240 VAC 50-60 HZ.
CONNECT POWER SOURCE
TO APPROPRIATE TERMINALS
OF EACH DETECTOR.
AUX. CONTACT RATINGS
10A @ 30 VDC
10A @ 250 VAC
500mA MINIMUM @ 24 VDC
NOT INTENDED FOR
CONNECTION TO CONTROL
PANELS.
TROUBLE CONTACT RATING
0.3 A @ 32 VAC/DC
CAUTION
Figure 6. System wiring diagram for duct detectors using a UL listed control panel (see Figure 8 for wiring of optional accessories):
Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.
D400-13-00 6 I56-555-09R
H0252-00
24V
120
VAC
220/240
VAC
1
2 12
13 14
AVAILABLE POWER INPUTS
ALARM AUXILIARY CONTACTS
FOR FAN SHUTDOWN, ETC.
15
16 17 18
19 20
N.C.C.N.O.
N.O.C.
N.C.
ALARM AUXILIARY CONTACTS SHOWN IN
STANDBY. CONTACTS TRANSFER DURING
ALARM AS INDICATED BY THE ARROWS.
ALARM INITIATION CONTACTS
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY.
CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS
REMOVED, AND DURING RESET. OPEN CONTACTS
SIGNAL TROUBLE CONDITION TO PANEL.
9
8
5
(+) ALARM SIGNAL
AUDIBLE PIEZO ALERT WITH ALARM AND POWER (TROUBLE) LEDS. FOR STAND ALONE APPLICATIONS ONLY. APA451 RECOMMENDED FOR COMPLIANCE TO NFPA 90A. LOCATE IN NORMALLY OCCUPIED AREA OF PREMISES.
DH400ACDCP DUCT DETECTOR
SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION.
FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER’S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER.
TROUBLE CONTACT RATING
0.3A @ 32 VAC/DC
POWER INPUTS ACCEPT 24 VDC, 24 VAC 50-60 HZ, 120 VAC 50-60 HZ, OR 220/240 VAC 50-60 HZ. CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR.
ALARM AUXILIARY CONTACT RATINGS 10A @ 30 VDC 10A @ 250 VAC 500mA MINIMUM @ 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS.
ALARM INITIATION CONTACT RATING
2.0A @ 30 VAC/DC (0.6 POWER FACTOR)
TROUBLE CONTACTS CLOSED IN STANDBY AND ALARM. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS REMOVED, AND DURING RESET. OPEN CONTACTS EXTINGUISH OPTIONAL APA451 GREEN “POWER” LED TO INDICATE TROUBLE CONDITION.
(–) AUX POWER
(+) AUX POWER
TROUBLE CONTACTS
APA451
N.O.
6
7
10
11
COMMON
FIELD INSTALLED JUMPER
POWER3
GRN.
RED
1
2 ALARM
Figure 7. Wiring diagram for duct detector systems equipped without a control panel (see Figure 8 for wiring of additional optional accessories):
H0253-00
D400-13-00 7 I56-555-09R
SAMPLING TUBE
FILTERS
SAMPLING TUBE
MOUNTING
SCREWS
DETECTOR HEAD
EXHAUST
FILTER ADAPTER
DETECTOR BASE
INLET SAMPLING TUBE
FOAM GASKET
CAUTION
Figure 8. Wiring diagrams for optional accessories (see Figure 7 for APA451 wiring diagram):
ALARM SIGNAL (+)
AUX POWER (–)
5
6
(+)
(–)
DUCT DETECTOR DH400ACDCP
PA400 (OPTIONAL) AUDIBLE ALERT
ALARM SIGNAL (+)
AUX POWER (–)
5
6
(+)
(–)
DUCT DETECTOR DH400ACDCP
RA400Z (OPTIONAL) REMOTE (LED) ANNUNCIATOR
RED
ALARM SIGNAL (+)
AUX POWER (–)
5
6
1
2
DUCT DETECTOR DH400ACDCP
RTS451/RTS451KEY (OPTIONAL) REMOTE TEST STATION
R E D
5
3
4
3
RESET
TEST
4
FIELD INSTALLED JUMPER
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA451
PA400
RA400Z
RTS451/RTS451KEY
STANDBY
12mA MAX
0mA
0mA
0mA*
ALARM
30mA MAX
15mA MAX
10mA MAX
10mA MAX*
ANY COMBINATION OF ACCESSORIES MAY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL:
RESET (–)
TEST (–)
*NOTE: WHEN INITIATING AN ALARM, THE RTS451/RTS451KEY REQUIRES 95mA MAXIMUM
IN PRE-ALARM AND 103mA MAXIMUM IN ALARM. NOMINAL STANDBY CURRENT IS 0mA. ALARM CURRENT IS 10mA MAXIMUM WHEN TEST MAGNET IS REMOVED.
100mA OR LESS IN THE STANDBY STATE, 150mA OR LESS IN THE ALARM STATE.
H0254-00
[5.6] Install The Filters
To install the sampling tube filters, simply push the filter adapter into the exhaust tube, and push the filter onto the adapter tube on the left, as shown in Figure 9. Install the other filter over the end of the inlet sampling tube.
Figure 9. Sampling tube filter installation:
Filters require periodic cleaning or replacement, depending on the amount of dust and dirt accumulated. Visually in­spect the filters at least quarterly; inspect them more often if the dust accumulation warrants it. See Section [6] for more information. Replacement filters can be ordered from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. (Ex­haust tube/intake tube filter P/N F36-05-00).
D400-13-00 8 I56-555-09R
H0239-00
[5.7] Perform Detector Check
2. Perform the MAGNET TEST per Section [6.2.2.1]. The RTS451 test of Section [6.2.2.2] may substitute for this requirement.
3. Perform the AIR FLOW TEST per Section [6.1.1].
4. Perform the SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform the SENSITIVITY TEST per Section [6.2.3].
6. Record all test results in the Detector Test Log at the end of this manual.
[5.8] Install The Cover
Install the cover using the four screws that are fixed in the housing cover. Be certain filters are installed as specified in Section [5.6]. Make sure that the cover fits into the base groove and that all gaskets are in their proper positions. Tighten the four screws to 10 in-lbs.
[6] Duct Detector Maintenance And Test Procedures
Test and maintain duct detectors as recommended in NFPA
72. The tests contained in this manual were devised to
assist maintenance personnel in verification of proper de­tector operation.
Before conducting these tests, notify the proper authorities that the smoke detection system will be temporarily out of service. Disable the zone or system under test to prevent unwanted alarms.
After conducting these tests, record the appropriate infor­mation in the Detector Test Log at the end of this manual.
Figure 10. Testing detector alarm: Figure 11. Detector head removal:
TEST LOCATOR
TEST MAGNET
PAINTED SIDE
TOWARD HOUSING
DUCT HOUSING
DETECTOR
HEAD
RESET LOCATOR
TWIST COUNTERCLOCKWISE TO REMOVE
DUCT HOUSING
TWIST CLOCKWISE TO INSTALL
DETECTOR HEAD
H0250-00 H0251-00
[6.1] Smoke Entry Tests [6.1.1] Air Flow
To verify sufficient sampling of ducted air, use a manometer to measure the differential pressure created from air flow across the sampling tubes. The pressure should measure
Trouble- If the detector LEDs do not blink or if the APA451
Power LED is not illuminated, the detector lacks power (check wiring, panel, or power supply), the head is missing (install), or the unit is defec-
tive (return for repair). no less than 0.01 inches of water and no greater than 1.20 inches of water.
Test- The trouble condition can be caused
intentionally to verify correct operation of the
[6.1.2] Smoke Response
To determine if smoke is capable of entering the sensing chamber, visually identify any obstructions. Plug the ex­haust and inlet tube holes to prevent ducted air from car­rying smoke away from the detector head, then blow smoke such as cigarette, cotton wick, or punk directly at the head
system. Remove power to the unit, remove the
detector head (see Figure 11), or place the M02-
04-00 magnet into the Reset locator, as shown in
Figure 10. These actions should cause a trouble
condition locally and at the system control
panel. to cause an alarm. REMOVE THE PLUGS AFTER TESTING OR THE DETECTOR WILL NOT FUNCTION PROPERLY.
[6.2.2] Alarm Tests [6.2.2.1] M02-04-00 Magnet Test
[6.1.3] Filter Replacement
The filters do not substantially affect smoke behavior even when they are up to 90% clogged. Quarterly visual inspection is usually often enough to determine if filters should be replace because only a high percentage of con­tamination affects duct detector performance.
1. Place the painted surface of the magnet into the Test locator molded into the side of the housing (see Figure
10).
2. The red alarm LEDs on the detector should latch on, as should any accessories (PA400, RA400Z, RTS451, APA451). Verify auxiliary functions (such as fan shut­down) and system control panel alarm status.
[6.2] Standby, Alarm, And Sensitivity Tests [6.2.1] Standby And Trouble
Standby- Check for the presence of the blinking red LEDs
(blinks about every 10 seconds) through the transparent housing cover. If the APA451 ac-
3. Place the painted surface of the magnet into the Reset locator molded into the side of the housing (see Figure
10). This should clear the latched alarm condition at the detector. If a system control panel is used, the panel may also require resetting.
cessory is used, its green Power LED should be illuminated continuously.
D400-13-00 9 I56-555-09R
[6.2.2.2] RTS451/RTS451KEY Remote Test Station
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm capability of the duct detector as indicated in
DETECTOR
HEAD
TEST COIL
Figure 12. RTS451/RTS451KEY test coil installation:
H0245-00
the RTS451/RTS451KEY manual. The DH400ACDCP duct detector can be reset by the RTS451/RTS451KEY. If a sys­tem control panel is used, the panel itself may also require resetting.
To install the RTS451/RTS451KEY, connect the device as shown in Figure 8; wire runs must be limited to 25 ohms or less per interconnecting wire. Place the coil in the detector housing with the arrow facing up and pointing toward the detector as in Figure 12. Attach the coil leads to the hous­ing terminals as shown; polarity is not important. Firmly screw the bracket in place over the test coil.
[6.2.3] Sensitivity Tests [6.2.3.1] MOD400R Sensitivity Test
After verification of alarm capability, use the MOD400R test module with a voltmeter to check detector sensitivity as described in the test module’s manual. The housing cover must be removed to perform this test.
If test module readings indicate that the detector head is outside of the acceptable range that is printed on the back of the detector head, the detector head requires cleaning per Section [7].
[6.2.3.2] R59-18-00 CALIBRATED TEST CARD (photo­electronic units only)
After verification of alarm capability, the R59-18-00 test card may be used to verify correct sensitivity of the de­tector head.
1. Remove the duct housing cover.
2. Remove the detector head from the housing as shown in Figure 11.
3. Remove the detector head cover by placing a small blade screwdriver in the side slot of the detector cover, twisting it slightly until the cover can be turned counter­clockwise.
4. Carefully reinsert the detector head into the duct hous-
ing and wait 50 seconds for power up. Do not hold the swirl chamber to twist the detector head.
5. Insert the NO ALARM end of the test card into the test slot (see Figure 13) and slide it counterclockwise until it stops. The detector should not alarm after 20 seconds.
6. Remove the card and then insert the ALARM end into the slot and slide it counterclockwise until it stops. The LEDs should latch on within 20 seconds. Remove card and reset detector.
7. Put the cover back by gently rotating it clockwise until it locks in place. Secure the duct housing cover using the 4 cover screws.
[7] Detector Cleaning Procedures
Notify the proper authorities that the smoke detector sys­tem is undergoing maintenance, and that the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department.
[7.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect the sampling tube filters.
3. If the filters are heavily coated with dirt, replace them with new filters. If they are not heavily coated, use a vacuum cleaner or compressed air nozzle to remove dust, then reinstall the filters.
[7.2] Photo Heads
1. Remove the detector cover by inserting a small bladed screwdriver into the slot located 90 degrees from the field test port. Rotate the cover counterclockwise to re­move (see Figure 13).
2. Lift the screen from the photo chamber. Vacuum the screen and cover before using clean, compressed air to loosen and blow out any remaining debris. Replacement screens (RS24) are available.
D400-13-00 10 I56-555-09R
REMOVABLE HEAD COVER
CLEANABLE SCREEN
HEAD COVER REMOVAL SLOT
TEST SLOT
VANED CHAMBER
P/N RS24 (W/O THERMAL)
Figure 13. Photo head exploded view:
H0261-00
3. Vacuum the photo chamber. Use clean compressed air to blow it clean.
4. Replace the screen by aligning the arrow on top with the field test port on the detector. Press the screen into place. It should fit tightly on the chamber.
[7.4] Reinstallation
1. Reinstall the detector in its housing.
2. Restore system power.
3. Perform Detector Check, Section [5.7].
D400-13-00 11 I56-555-09R
[8] Model DH400ACDCP Air Duct Smoke Detector Specifications
Description
HVAC air duct mounted ionization or photoelectronic smoke detector for separately powered systems or stand alone sys­tems. Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke.
Environmental Limits
Temperature: 32°F to 120°F 0°C to 49°C Humidity: 10% to 93% R.H. non-condensing Air Velocity: 500 to 4000 Ft/min.
2.54 to 20.3 m/sec.
Test Features
Magnetic test switch, magnetic reset switch, MOD400R test module (optional), RTS451 Remote Test Station (optional).
Mechanical Specifications
Length: 14.5 inches 37 cm Width: 5 inches 13 cm Depth (installed): 4 inches 10 cm Weight: 4 pounds 1.8 kg
Terminals
Captive universal terminal screws with sems plates accept wire sizes of 14 gauge or smaller. The screws can withstand 10 in-lbs of tightening torque without damage.
Accessories
MOD400R Sensitivity Test Module RA400Z Remote Annunciator RTS451/RTS451KEY Remote Test Station, test & reset switch with alarm LED PA400 Piezo Sounder APA451 Annunciator with piezo, alarm & power LEDs F36-05-00 Replacement Air Filter (two per package) M02-04-00 Replacement Test Magnet P48-21-00 Replacement End Plug for inlet sampling tube R59-18-00 Replacement Calibrated Test Card (For photo units only) RS24 Replacement Screen, Photo A2650-01 Replacement Installation Kit (mounting hardware)
Sampling (Inlet) Tubes
TUBE OUTSIDE DUCT WIDTH ST-1.5 1 to 2 feet (0.3 to 0.6 m) ST-3 2 to 4 feet (0.6 to 1.2 m) ST-5 4 to 8 feet (1.2 to 2.4 m) ST-10 8 to 12 feet (2.4 to 3.7 m)
Exhaust Tube Extension
A2440-00 5.75 in. (14.6 cm.) additional
D400-13-00 12 I56-555-09R
Electrical Specifications
Power Supply Voltage 20 - 29 VDC 24 VAC 50 - 60 Hz 120 VAC 50 - 60 Hz 220/240 VAC 50 - 60 Hz
CURRENT REQUIREMENTS (USING NO ACCESSORIES)
Max. standby current 25 mA 35 mA AC avg. 20 mA AC avg. 20 mA AC avg.
Max. alarm current
95 mA
55 mA AC avg. 55 mA AC avg. 30 mA AC avg.
CONTACT RATINGS
Alarm initiation contacts (SPST) 2.0A @ 30 VAC/DC (0.6 power factor)
Alarm auxiliary contacts (DPDT) 10A @ 30 VDC
10A @ 250 VAC
Trouble contacts (SPST) 0.3A @ 32 VDC (resistive)
Note: Alarm auxiliary contacts must switch 500 mA minimum at 24VDC. Alarm auxiliary contacts shall not be
connected to inititaing circuits of control panels. Use the alarm initiation contact for this purpose.
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE
APA451
PA400
RA400Z
RTS451/ RTS451KEY
STANDBY
12mA MAX
0mA
0mA
0mA*
ALARM
30mA MAX
15mA MAX
10mA MAX
10mA MAX*
ANY COMBINATION OF ACCESSORIES MAY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL:
100mA OR LESS IN THE STANDBY STATE, 150mA OR LESS IN THE ALARM STATE.
*NOTE: WHEN INITIATING AN ALARM, THE RTS451/
RTS451KEY REQUIRES 95 mA MAXIMUM IN PRE-ALARM AND 103 mA MAXIMUM IN ALARM. NOMINAL STANDBY CURRENT IS 0mA. ALARM CURRENT IS 10 mA MAXIMUM WHEN TEST MAGNET IS REMOVED.
Power supply voltage: 20-29 VDC 24 VAC 50-60-Hz 120 VAC 50-60 Hz 220/240 VAC 50-60 Hz Input capacitance: 270 µF max. 270 µF max. N/A N/A Reset voltage: 3.0 VDC min. 2.0 VAC min. 10 VAC min. 20 VAC min. Reset time (with RTS451): .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time (by power down): 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time: 34 sec.max. 34 sec. max. 34 sec. max. 34 sec. max. Alarm response time: 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. 2 to 17 sec. Sensitivity Test: See head label See head label See head label See head label
Electrical Ratings
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this air duct smoke detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization num ber, send defective units postage prepaid to: System Sensor, Repair Department,
D400-13-00 13 I56-555-09R
Three-Year Limited Warranty
RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or inci dental damages for breach of this or any other Warranty, expressed or implied what soever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty
-
gives you specific legal rights, and you may also have other rights which vary from state to state.
-
-
NOTES
D400-13-00 14 I56-555-09R
NOTES
D400-13-00 15 I56-555-09R
DETECTOR TEST LOG
Detector Identification Information
Manufacturer and Serial Date Detector Model: ______________________ Number: ______________________ Installed: ___________________
Description of Detector Location:
________________________________________________________________________________________________
________________________________________________________________________________________________
________________________________________________________________________________________________
Test Results and Maintenance Data
Date Test Test Maintenance Tested Description Results Performed Comments
________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________ ________ ________ ___________ _______ ______________ ___________________________
D400-13-00 16 I56-555-09R © System Sensor 1997
Loading...