Please thoroughly read the System Sensor Guide for Proper
Use of Smoke Detectors in Duct Applications (I56-473),
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor. NFPA
Standards 72 and 90A should also be referenced for detailed information.
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.
Table of ContentsPage
[1]General Description1
[2]Exploded View of Duct Detector Components2
[3]Contents of the Duct Detector Kit2
[4]Limitations of Duct Detectors2
[5]Installation Sequence2
[6]Duct Detector Maintenance and Test Procedures8
[7]Detector Cleaning Procedures10
[8]Specifications12
Warranty13
Detector Test log16
List of Tables and FiguresPage
Fig. 1: Duct Detector Exploded View2
Fig. 2: Installation of Sampling Tube Gaskets3
Fig. 3: Mounting Location of Speed Nuts3
Table 1: Inlet Sampling Tube Selection3
Fig. 4: Inlet Sampling Tube4
Fig. 5: Sampling Tube Mounting Configurations4
Fig. 6: Wiring Diagram6
Fig. 7: Wiring Diagram – No Control Panel7
Fig. 8: Wiring Diagram – Accessories8
Fig. 9: Sampling Tube Filter Installation8
Fig. 10: Testing Detector Alarm9
Fig. 11: Detector Head Removal9
Fig. 12: RTS451/RTS451KEY Test Coil Installation10
Fig. 13: Photo Head Exploded View11
Fig. 14: Ion Head Exploded View11
[1] General Description
An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct system will be distributed to the entire building. Smoke detectors designed for use in air duct systems are used to sense
the presence of smoke in the duct.
Model DH400ACDC Air Duct Smoke Detectors are supplied
with model 1451DH ionization detector heads or model
2451 photoelectronic detector heads. These two smoke detection methods are combined with an efficient housing design that samples air passing through a duct and allows
detection of a developing hazardous condition. When sufficient smoke is sensed, an alarm signal is initiated at the fire
control panel monitoring the detector, and appropriate action can be taken to shut off fans and blowers, change over
air handling systems, etc. These actions can facilitate the
management of toxic smoke and fire gases throughout the
areas served by the duct system.
DH400ACDC detectors are designed to operate from 24
VDC, 24 VAC, 120 VAC, or 240 VAC. Alarm and supervisory
relay contacts are available for control panel interface
(alarm initiation), HVAC control, and other auxiliary functions. These detectors are not designed for 2-wire application.
For testing, the alarm can be enabled by a magnet activated
test switch, by insertion of a calibrated test card into the
sensing chamber (photoelectronic version only), or by the
optional remote test station. The duct smoke detectors
latch into alarm state when alarm occurs. LEDs on each detector illuminate to provide local alarm indication, and optional accessories offer a variety of annunciation
capabilities.
The detector can be reset by a momentary power interruption, by the magnet activated reset switch, or by the optional remote test station.
D400-13-001I56-555-08
[2] Figure 1. Exploded view of duct detector components:
CONDUIT HOLES
FOAM
GASKETS
TUBE
PLUG
DETECTOR BASE
HOUSING
MOUNTING SCREWS
FILTER ADAPTER
TEST MAGNET
END
INLET SAMPLING TUBE
(SUPPLIED SEPARATELY)
EXHAUST
DETECTOR HEAD
O-RINGS
SAMPLING TUBE
FILTERS
[3] Contents Of The Duct Detector Kit
1. Complete housing base and cover assembly
2. Two #10 sheet metal mounting screws
3. Two sampling tube filters
4. One test magnet
5. Drilling template
6. Two 5/16 O-rings
7. Two rubber tube bushing seals
8. Four #6 self-tapping mounting screws for the sampling
and optional exhaust tube extension
9. One filter adapter
10.One inlet tube end plug
11.Two #10 speed nuts
NOTE: The inlet sampling tube must be ordered sepa-
rately. It must be the correct length for the width of
the duct where it will be installed. See Table 1 on
page 4 to determine the inlet tube required for different duct widths.
[4] Limitations Of Duct Detectors
WARNING
The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION as a
means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.
DUCT DETECTOR
HOUSING
TERMINAL STRIP
PC BOARD
INSULATOR
DUCT DETECTOR
COVER
SAMPLING TUBE
MOUNTING
SCREWS
A78-1927-01
WARNING
This device will not operate without electrical power.
Frequently, fire situations may cause an interruption of
power. The system safeguards should be discussed with
your local fire protection specialist.
WARNING
This device does not sense smoke unless the ventilation
system is operating.
CAUTION
For this detector to function properly, it MUST be installed
according to the instructions in this manual. Furthermore,
the detector MUST be protected from the elements and operated within ALL electrical and environmental specifications listed in this manual. Failure to comply with these
requirements may prevent the detector from activating
when smoke is present in the air duct.
[5] Installation Sequence
StepPage
[5.1] Verify duct air flow direction and velocity2
[5.2] Drill the mounting holes3
[5.3] Secure the detector housing to the duct3
[5.4] Install the sampling tube3
[5.5] Complete the field wiring5
[5.6] Install the filters and check pressure differential8
[5.7] Perform detector check8
[5.8] Install the cover8
System Sensor supports this position and strongly recommends that the user read NFPA Standards 90A, 72, and 101.
The DH400ACDC Air Duct Smoke Detectors are listed per
[5.1] Verify Duct Air Flow Direction And Velocity
Model DH400ACDC detectors are designed to be used in air
handling systems having air velocities of 500 to 4000 feet
UL 268A.
D400-13-002I56-555-08
per minute. Be sure to check engineering specifications to
ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter to check the air
velocity in the duct.
[5.2] Drill The Mounting Holes
Remove the paper backing from the mounting template
supplied. Affix the template to the duct at the desired
mounting location. Make sure the template lies flat and
smooth on the duct. Center punch holes A and B. Drill the
holes as indicated on the template. Slide the two speed nuts
over the two small holes (hole A) next to the sampling tube
bushing holes (hole B) previously drilled in the duct. (See
Figure 3.)
[5.3] Secure The Detector Housing To The Duct
Remove the duct housing cover. Slide the foam gaskets over
the tube bushings as shown in Figure 2. Make sure the two
small holes in the gaskets line up with the two base mounting holes. Put one 5/16-inch O-ring over each of the two
#10 sheet metal screws. Use the two sheet metal screws to
screw the detector housing to the duct. CAUTION: Do not
overtighten the screws.
Figure 2. Installation of foam gaskets over sampling
tube bushings:
DUCT DETECTOR
HOUSING
EXHAUST TUBE
(EXTENSION BUSHING)
FOAM GASKETS
MOUNTING
SCREWS
O-RINGS
INLET SAMPLING
TUBE BUSHING
of air inlet holes on the tube. This tube must be purchased
separately. Order the correct length, as specified in Table 1,
for width of the duct where it will be installed. The exhaust
tube is molded into the base of the duct housing, and the
A2440-00 Exhaust Tube Extension is available as an accessory in those cases where the molded exhaust port does not
extend at least 2 inches into the duct.
The inlet tube is always installed in the centermost housing
bushing, with air inlet holes facing into the air flow. To assist proper installation, the tube’s mounting flange is
marked with arrows. Make sure the inlet tube is mounted
so that the arrows point into the air flow. Figure 5 shows
the various combinations of tube mounting configurations
with respect to air flow.
Mounting the detector housing in a vertical orientation is
acceptable, provided that the air flows directly into the
sampling tube holes as indicated in Figure 4.
Table 1. Inlet tubes required for different duct
widths:
Outside Duct WidthInlet Tube Required
1 to 2 ft.ST-1.5
2 to 4 ft.ST-3
4 to 8 ft.ST-5
8 to 12 ft.ST-10
SCREW HOLES FOR ATTACHING
DETECTOR HOUSING TO DUCT
A78-2045-00
Figure 3. Speed nut mounting location:
HOLE B
HOLE A
DUCT
WALL
SPEED
NUT
78-2046-00
[5.4] Install The Inlet
The inlet tube (shown in Figure 4) is identified by a series
D400-13-003I56-555-08
Figure 4. Air duct detector inlet sampling tube:
FLANGE
AIR HOLES
ARROWS
AIR FLOW DIRECTION
MUST FACE
INTO AIR FLOW
Figure 5. Tube mounting configurations with varying air flow direction:
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
AIR FLOW
DIRECTION
DUCT
DETECTOR
HOUSING
EXHAUST
TUBE
EXHAUST
TUBE
INLET
TUBE
INLET
TUBE
EXHAUST
TUBE
AIR FLOW
DIRECTION
INLET
TUBE
INLET
TUBE
END
PLUG
AIR FLOW
DIRECTION
DUCT
DETECTOR
HOUSING
A78-2047-00
DUCT
DETECTOR
HOUSING
AIR FLOW
DIRECTION
[5.4.1] Installation For Ducts Less Than 8 Feet Wide
1. If the tube is longer than the width of the air duct, drill a
3/4-inch hole in the duct directly opposite the hole already cut for the inlet tube. If the tube is shorter than thewidth of the air duct, install the end plug into the inlet
tube as shown in Figure 4. Sampling tubes over 3 ft. long
must be supported at the end opposite the duct detector.
2. Slide the tube into the centermost housing bushing. Position the tube so that the arrows point into the air flow.
3. Secure the tube flange to the housing bushing with two
#6 self-tapping screws.
4. For tubes longer than the width of the air duct, the tube
should extend out of the opposite side of the duct. If
there are more than 2 holes in the section of the tube extending out of the duct, select a different length using
Table 1. Otherwise, trim the end of the tube protruding
through the duct so that 1 to 2 inches of the tube extend
outside the duct. Plug this end with the end plug and
DUCT
DETECTOR
HOUSING
EXHAUST
TUBE
INLET
TUBE
A78-1812-01
tape closed any holes in the protruding section of the
tube. Be sure to seal the duct when the tube protrudes.
WARNING
In no case should more than 2 air inlet holes be cut off the
tube. There must be a minimum of 10 holes in the tube exposed to the air stream.
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install inlet tubes in ducts more than 8 feet
wide, work must be performed inside the air duct.
Sampling of air in ducts wider than 8 feet is
accomplished by using the ST-10 inlet sampling
tube. If the tube is shorter than the width of the air
duct, install the end plug into the inlet tube as
shown in Figure 4 and support the end opposite
the duct detector.
D400-13-004I56-555-08
Install the inlet tube as follows:
1. Drill a 3/4-inch hole in the duct directly opposite the
hole already drilled for the inlet tube.
2. Slide the inlet tube with the flange into the centermost
housing bushing. Position the tube so that the arrows
point into the air flow. Secure the tube flange to the
housing bushing with two #6 self-tapping screws.
3. From inside the duct, couple the other section of the in-
let tube to the section already installed using the 1/2inch conduit fitting supplied. Make sure that the holes
on both of the air inlet tubes are lined up and facing into
the air flow.
4. Trim the end of the tube protruding through the duct so
that 1 to 2 inches of the tube extend outside the duct.
Plug this end with the end plug and tape closed any
holes in the protruding section of the tube. Be sure to
seal the duct when the tube protrudes.
NOTE: An alternate method to using the ST-10 is to use
two ST-5 inlet tubes. Remove the flange from one
of the tubes and install as described above. After
the installation, use electrical tape to close off
some of the sampling holes so that there is a total
of 10 to 12 holes spaced as evenly as possible
across the width of the duct.
[5.5] Field Wiring
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction. Proper wire gauges should be used. The conductors
used to connect smoke detectors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a
system from responding properly in the event of a fire.
For signal wiring, (the wiring between interconnected detectors or from detectors to auxiliary devices), it is usually
recommended that single-conductor wire be no smaller
than 18 gauge. The duct detector terminals accommodate
wire sizes up to 14 gauge. The last foot of conduit should
be flexible steel conduit (available in electrical supply
houses), which facilitates installation and puts less strain
on the conduit holes in the housing. Solid conduit connections may be used, if desired.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loop.
Air currents inside the duct may cause excessive vibration,
especially when the longer sampling tubes are used. In
these cases a 3 inch floor flange (available at most plumbing supply stores) may be used to fasten the sampling tube
to the other side of the duct. When using the flange/connector mounting technique, drill a 1 inch to 1-1/4-inch hole
where the flange will be used.
[5.4.3] Modifications Of Inlet Sampling Tubes
There may be applications where duct widths are not what
is specified for the installation. In such cases, it is permissible to modify an inlet sampling tube that is longer than
necessary to span the duct width.
Use a 0.193-inch diameter (#11) drill and add the appropriate number of holes so that the total number of holes exposed to the air flow in the duct is 10 to 12. Space the
additional holes as evenly as possible over the length of the
tube.
Wiring Instructions
The DH400ACDC detectors are designed for easy wiring.
The housing provides a terminal strip with clamping plates.
Wiring connections are made by stripping about 3/8-inch
of insulation from the end of the wire, sliding the bare end
under the plate, and tightening the clamping plate screw.
The DH400ACDC duct detector is designed to operate from
24 VDC, 24 VAC, 120 VAC, or 240 VAC.
The detector may be wired for interconnection to UL listed
control panels, or for stand alone service per NFPA 90A.
Refer to the wiring diagrams of Figures 6, 7, and 8 to select
the appropriate circuit for your application.
D400-13-005I56-555-08
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.