INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-2964-002
APA151 Annunciator
3825 Ohio Avenue, St. Charles, Illinois 60174
with Piezo Alert
Specifications
Dimensions: 4.6˝ L × 2.9˝ W × .45˝ D
Weight: .17 lbs.
Electrical Requirements:
Voltage: Regulated 24VDC
Operational Voltage: 16–33 VDC
Maximum Operating Current: 30mA
Connections: #6 binding head screws, 12 AWG to 18 AWG wire
UL Reverberant Room: 81 dBA min. @ 10 ft.
Standard Operating Temperature: 0°C to 49°C (32°F to 120°F)
Humidity Range: 10% to 93% non-condensing
NOTICE: These models were only tested at the 16-33 Volt
DC limits. This does not include the 80% low-end or 110%
high-end voltage limits. This manual shall be left with the
owner/user of this equipment.
General Information
The National Fire Protection Association (NFPA) has published codes, standards, and recommended practices for the
installation and use of this product. It is recommended that
the installer be familiar with these requirements, with local
codes, and any special requirements of the local authority
having jurisdiction. For further information, consult NFPA
72 and 90A requirements.
The System Sensor APA151 annunciator with piezo alert
is an audible signal appliance for fire alarm service. It is
intended for use in System Sensor 4-wire conventional duct
smoke detector applications without a system control panel
to comply with NFPA 90A.
The APA151 provides a red alarm LED, with an audible annunciation of an alarm signal, and a green power LED.
Figure 1:
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
A0360-01
D640-02-00 1 I56-2964-002
APA151 Contents
15
19
14
3
20
Alarm Signal
Aux. Power +
Sup. N. O.
Sup. COM
Aux. Power –
NOTE: Wiring diagram shown is for DH100ACDC 4-wire duct
smoke detector system equipped without a control panel.
Alarm
(Red LED)
Power
(Green LED)
Common
4-Wire Wiring to APA151
APA151DH100ACDC
5
6
7
10
(+)Alarm Signal
(-)Aux. Power
Audible Piezo Alert with alarm and power (trouble) leds. For stand alone
applications only. APA151 recommended for complance to NFPA 90A.
Locate in normally occupied area of premises.
Alarm
(Red LED)
Power
(Green LED)
Common
APA151DH400ACDC
Trouble
Contacts
11
Field
Installed
Jumper
(+)Aux. Power
1 APA151 annunciator with piezo alert
1 screw pack (containing two mounting screws)
Installation
Wire the APA151 as shown in Figure 2. Limit wire runs to
25 ohms or less per interconnecting wire.
Secure the APA151 to the single gang box using the two
screws provided, or directly to the wall or ceiling.
Operational Test
Consult the wiring diagrams below to insure proper wiring
to the APA151.
Supply power to the duct smoke detector. Visually check
the supervisory LED (green) to make sure it is operational.
Put the detector into alarm state. The alarm LED (red) will
light, and the piezo horn will sound. Reset the detector.
Figure 2: Wiring diagram for DH400ACDC to APA151:
H0534-01
Figure 3: Wiring diagram for DH100ACDC to APA151:
H0581-01
The sounder will not operate if the power is cut off for any reason.
The sounder may not be heard. The loudness of the sounder meets or exceeds the cur-
rent standards. However, the sounder may not alert a sound sleeper or one who has
recently used drugs or has been drinking alcoholic beverages. This sounder may not
be heard if it is placed in an area that is separated by a closed door, or if it is located
on a different floor from the person in a hazardous situation, or if it is placed too far
System Sensor warrants its enclosed product to be free from defects in
materials and workmanship under normal use and service for a period
of three years from date of manufacture. System Sensor makes no other
express warranty for the enclosed product. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of
the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns
D640-02-00 2 I56-2964-002
©2007 System Sensor
The Limitations of Sounders
away to be heard over ambient noise, such as, traffic, air conditioners, machinery or
musical appliances that may prevent alert persons from hearing the alarm.
The sounder may not be heard by persons who are hearing-impaired. In this case, a
visual indicator shall also be used.
For these reasons, Pittway recommends that sounders (85dBA minimum at 10 feet)
used in a residence shall be placed on every level and in every bedroom that does not
have a smoke detector with a built-in sounder.
Three-Year Limited Warranty
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
Please include a note describing the malfunction and suspected cause
of failure. The Company shall not be obligated to replace units which
are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no
case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s
negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you. This Warranty gives you specific legal
rights, and you may also have other rights which vary from state to state.