System Sensor AFD User Manual

Important
Please Read Carefully And Save
This instruction manual contains important information about the instal­lation and operation of waterflow detectors. Purchasers who install water­flow detectors for use by others must leave this manual or a copy of it with the user. Read all instructions carefully before beginning. Follow only those instruc­tions that apply to the model you are installing.
Use vane-type waterflow detectors in wet-pipe systems only. Do NOT use them in dry pipe, deluge, or preaction systems. The sudden inrush of water in such systems may break the vane or damage the mechanism. Do not use in potentially explosive atmospheres. Do not allow unused wires to remain exposed.
Principles Of Operation
Vane-type waterflow detectors mount to water-filled pipes in sprinkler sys­tems. Waterflow in the pipe deflects a vane, which produces a switched output–usually after a specified delay. All waterflow detectors have a con­trolled delay mechanism. Delays do NOT accumulate; they reset if the flow of water stops before the entire delay has elapsed. All switches actu­ate when the water flow rate is 10 gallons per minute or greater, but will not actuate if the flow rate is less than 4 gallons per minute. This System Sensor installation manual covers the following waterflow detectors for sprinkler/fire alarm applications.
Accuflow Models Pipe Diameter Pipe Schedules
AFD20 2" 5 through 40 AFD25 2-1/2" 7 through 40 AFD30-2 3" 7 through 40 AFD35 3-1/2" 7 through 40 AFD40 4" 7 through 40 AFD50 5" 7 through 40 AFD60 6" 7 through 40 AFD80 8" 10 through 40
Do NOT use any of the AFD models on copper pipe. The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from functioning properly. Do NOT install steel or iron pipe sections in copper piping for mounting a waterflow detector. Incompatibility between the dissimilar metals causes bimetallic corrosion.
CAUTION
CAUTION
AFD Accuflow
Vane-type Waterflow Detector with Solid State Time Retard
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Installation Guidelines
Before installing any waterflow alarm device, be thoroughly familiar with:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems NFPA 25: Inspection, Testing and Maintenance of Sprinkler Systems
Other applicable NFPA standards, local codes, and the requirements of the authority having jurisdiction NOTE: Installation methods other than those listed in this installation
manual may prevent the device from reporting the flow of water in the event the associated sprinkler system is activated by a fire. System Sensor is not responsible for devices that have been improperly installed, tested, or maintained.
2.
Locate detector 6 to 7 ft. above the floor to protect from potential damage
.
3. On horizontal runs, position the detector on the top or side of the pipe. Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector. For vertical flow applications, mount the detector on pipe through which water flows upward. Otherwise, the unit may not operate properly.
4. Mount the detector at least 6 inches from a fitting that changes the direction of water flow and no less than 24 inches from a valve or drain.
Mounting Instructions
1. Drain the pipe.
2. Cut a hole at the desired location. Center the hole in the pipe, as shown in Figure 2, and be sure the hole is perpendicular to the center of the pipe. Before drilling, use a punch or scribe to mark the drill site to prevent the bit from slipping. If the hole is off center, the vane will bind against the inside wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See Table 1 for hole size.
When drilling the hole with a hole saw, make certain that the center of the cut does not remain in the pipe.
3. Remove burrs and sharp edges from the hole. Clean and remove all scale and foreign matter from the inside of the pipe for one diameter on each side of the hole to ensure free movement of the vane. Clean the outside of the pipe to remove dirt, metal chips, and cutting lubri­cant.
CAUTION
Specifications
Contact Ratings: 0.6 A @ 125 VAC; 2 A @ 30VDC Triggering Threshold Bandwidth
(Flow Rate): 4 to 10 gpm Static Pressure Rating: 450 PSI (Max) 2” – 8” Dimensions, Installed: 3.5"H x 3.0"W x 6.7"D Operating Temperature Range: 32°F to 120°F (0°C to 49°C) Compatible Pipe: See Accuflow models listed below Shipping Weight: 4 to 7 lb., according to size. Enclosure Rating: NEMA Type 4 Voltage Range: 8.4–35 V (DC–FWR); 108–132 VAC Power Requirements: 300µA at 12 and 24 V (DC–FWR) or
400µA at 120 VAC
U.S. Patent Number: 6,084,521; 3,845,259
Panel Compatibility:
The AFD waterflow indicators may receive power and operate on a two­wire initiating zone of a fire alarm control panel. When determining com­patibility of these devices, the standby operating voltage of the control panel must be between 8.5 and 35 volts. In the standby mode, the AFD draws a maximum current of 0.3 mA. In alarm, the AFD acts as a short across the initiating zone (similar to a manual fire box). For two wire
conventional fire alarm control panels, not more than 5 waterflow indicators may be connected to a single initiating zone. The maximum
retard/reset time of the waterflow indicator plus the initiating zone shall not exceed 90 seconds.
For two wire addressable control panels, the number of waterflow indicators connected to the panel’s signaling line circuit shall be lim­ited only by the circuit’s current capacity.
D770-29-00 1 I56-1570-003R
4. Seat the gasket against the saddle and mount the detector directly to the pipe. Carefully roll the vane opposite the direction of flow and insert it through the hole. Seat the saddle firmly against the pipe so that the locating boss goes into the hole.
5. Install the U-bolt, tightening the nuts alternately to ensure a uniform seal. See Table 2 for torque values.
6. Remove the metal cover with the tamper-proof wrench provided. Move the actuator lever back and forth to check for binding. If the vane binds, remove the detector and correct the cause before pro­ceeding.
Pre-operation
Fill the sprinkler system and check for leaks around the waterflow detec­tor. If it leaks, first check for the proper torque on the U-bolt nuts. If the leak persists, drain the system and remove the detector (refer to Maintenance). Check for dirt or foreign objects under the gasket, and make sure that the pipe surface is not dented. Reinstall the detector and check again for leaks. Do not proceed until all leaks have been stopped.
Be sure the direction-of-flow arrow points in the right direction or else water flow will go unreported. See Figure 9.
Wiring
High Voltage. Electrocution Hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in injury or death.
1. All models have two wires and two sets of terminals. Relay Wires (W1 & W2 designated on PCB): These wires are con­nected to a latching normally open (as in No Flow) relay contact. They are isolated from all electronics. They will close and cause a short when water flows and the retard time elapses. They will remain short­ed until waterflow stops. Once waterflow stops, these contacts will re­open. Power Terminals (T2 designated on PCB): This is a two screw terminal block. The Accuflow gets its power from these terminals. These terminals must have voltage present from the FACP or other suit­able source of power before anything will work. If no power is present, the Accuflow will not provide proper alarm signals. These terminals will accept power in any polarity as well as AC-line power. Aux Relay Terminals (T1 designated on PCB): This is a THREE screw terminal block. These terminals are connected to a latching Form C relay. In no flow conditions, COM is connected to A. When flow is detected COM will disconnect from A and connect to B. This relay will latch in that state and reset after water stops flowing.
2. Adjust Dip Switch to desired time delay. See Figure 11. For Dip Switch location, see Figure 9.
3. When connected to a listed sprinkler/fire alarm control panel, the ini­tiating circuit must be nonsilenceable.
4. A ground screw is provided with all waterflow detectors. When grounding is required, clamp wire with screw in hole located between conduit entrance holes. See Figure 10A, page 4.
5. If a second conduit entry is required, remove the knockout plug using a flat blade screwdriver as shown on Figure 10B, page 4. Strike sharply with a hammer to pierce the wall of the knockout plug. Move to an adjacent wall section and repeat until the plug falls out. Make sure that the waterflow detector is supported adequately during this oper­ation to avoid injury.
NOTE: Power terminals must be connected to FACP or other non-
silenceable initiating circuit.
Operation Testing
Always notify a central station monitoring waterflow alarms before repairing, maintaining, or testing waterflow alarm devices.
1. Replace the cover and tighten the tamper proof screws with the tamp­er proof wrench. Store the wrench in a secure place.
2. Open the inspector’s test valve and time how long it takes for the detec­tor to indicate a flow condition. The detector should remain activated until the inspector’s test valve is closed. Air pockets in the sprinkler system may increase the apparent delay.
WARNING
CAUTION
A78-1609-00
Figure 1. Mounting dimensions:
3
3-3/4
Pipe saddle
U-bolt nut
Plastic vane
Pipe
U-bolt
Overall width = pipe diameter + 3
Pipe diameter
plus 5-1/4
Maintenance
To prevent accidental water damage, control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced.
Inspect detectors monthly for leaks and replace if a leak occurs. Test detec­tors at least monthly, as described under Operational Testing, to ensure proper operation. Test more often if required by the authority having juris­diction.
Under normal conditions, System Sensor waterflow detectors should pro­vide years of trouble-free service.
Do not repair or replace any other waterflow detector components. If any other part of the detector does not perform properly, replace the entire detector. Failure to follow this instruction may result in failure of the detector to report the flow of water.
To remove a detector:
1. Drain the pipe.
2. Turn off electrical power to the detector and disconnect the wiring.
3. Loosen the nuts and remove the U-bolts.
4. Gently lift the saddle far enough to get your fingers under it. Then, roll the vane so it will fit through the hole while continuing to lift the waterflow detector saddle.
5. Lift the detector clear of the pipe.
If a vane breaks in a pipe, find and remove it. If it is not removed, the vane may restrict the flow of water to all or part of the sprinkler system.
CAUTION
Table 1:
AFD MODEL Hole Size
20, 25, 35 1-1/4
"
30-2, 40, 50, 60,80 2
"
Table 2:
AFD MODEL Torque
20, 25, 35 30 - 35 ft-lb
30-2, 40, 50, 60, 80 55 - 60 ft-lb
Figure 2. Mounting hole location:
A78-1496-07
Wrong
Right
Remove burrs from edge of hole. Clean out scale and foreign matter for one pipe diameter on each side of hole.
D770-29-00 2 I56-1570-003R
Loading...
+ 2 hidden pages