System Sensor A310E, A320E Installation And Maintenance Instructions Manual

1
© System Sensor 2008 I56-2634-004ENPittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
DEUTSCH
ENGLISH
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A300 SERIES ASPIRATED SMOKE DETECTOR
should be monitored using a separate monitor module to return the fault.
A300E Series smoke detectors are powered by an external 24Vdc power supply .
With the use of an exhaust pipe, the system is IP65 rated, allowing its use in many harsh environments, and applications where regular hosing is performed.
CA UTION! The A300 Series has been independently tested and certified to CEA4022 and must be installed in strict compliance with these instructions if the certification is to be maintained.
SPECIFICATIONS
Number of Sensors: A310E:1 or 2 sensors. A320E: 2 sensors
(order separately, recommended: 7251 sensor). Internal Filtration: 2 stage dust particle filter Flow Monitoring: Thermal device, high and low thresholds.
10 element bar graph indication.
Relay fault reporting Supply Voltage: 24VDC (Nominal) 18-30VDC (12W min) Supply Current: 120 mA - 500 mA depending on fan speed
setting and supply voltage. Maximum
current 350mA @24VDC with no aspirating
pipe (See table 4 for typical currents/fan
speeds) Maximum Pipe Length: 1 Chan - 100 metres
2 Chan - 2 x 100 metres
Dependant on sensor type and application IP rating: IP53 / IP65 optional with exhaust fitted Operating Temperature: -10°C to 50°C
Operating Humidity: 10 to 95% RH (non-condensing) Fuse Type/Rating: ‘T’ European sub-miniature (TR5)
1.25 A Anti-surge
INTRODUCTION
There are many instances where aspirated smoke detectors are specified, but where the very high sensitivity that is normally inherent in these devices is an unnecessary expense. The A300E Series Aspirated Smoke Detector provides the perfect solution.
A300E Series aspirating smoke detectors are available in single or dual channel formats giving a large monitored area using sampling holes in the place of point detectors.
The A310E single channel unit has a single detection pipe, and may be used with one smoke sensor, or two sensors which can be configured for alarm coincidence at the panel to simulate a ‘Double Knock’ type operation. (Note: Not included in VdS appro val).
The A320E unit is equipped with two detection pipe channels and should be fitted with one sensor for each channel and can thus cover a greater area than the A310E.
A high performance aspirator and flow monitoring circuit ensure a constant, monitored flow level which can be displayed on a 10 element bar graph with adjustments for high and low flow thresholds.
The A300E Series units incorporate in-line air filters to remove dust particles from the air samples.
A300E Series Aspirating smoke detectors provide closed loop sampling whereby the exhausted air can be completely returned to the sampled area making them particularly suitable for prison cells.
A300E Series Aspirating smoke detectors use one or two standard intelligent or conventional smoke sensors which communicate their status directly with the control panel (Recommended: 7251 Laser Sensor). The A300E monitors its own systems and uses relay contacts to signal system faults. If using an intelligent fire system, these contacts
2D200-41-00
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
Pipe Specification For full details of pipe installation please see the appendix
at the back of this manual. Smoke tests should be performed before planning and
installing the pipe network. Material
For CEA4022 compliance, the pipe should be red ABS to EN 50086-1 (Crush 1, Impact 1, Temp 33).
Dimensions Metric: 25.0mmOD - 21mmID;
Imperial: 3/4"BSP (26.7mmOD - 20mmID) Note: Both metric and imperial sizes will fit into the unit.
Lengths may be cut as required, and joined by permanent sockets, removable socket unions or solvent welded.
The A300 inlet port is tapered to allow a push fit of the sampling pipe. The pipe should be cut squarely to ensure a good, airtight seal. Solvent adhesive should not be used for this joint.
Fixings The means of fixing the pipe to the structure will depend on
site conditions. The normal methods are pipe clips, saddle clamps or even tie wraps. Fixing centres are typically 1.5m apart.
Holes The sampling pipe is perforated with sampling holes at
design spacing. These are typically 3mm and can either be pre-drilled or drilled in situ. Care should be taken to avoid swarf entering the pipe. It is always good practice to blow compressed air through the pipe after drilling to clear any debris before final connection to the equipment. In standard configuration, with pipe hanging from ceiling, the holes will be placed underneath, so the smoke can easily rise up into
Figure 1: A300E Series Mounting Hole Centres
INSTALLATION A300E Series Installation
The front cover of the A300 will need to be removed to secure the unit permanently in place. This is done using the special key that is supplied, which fits into the screw hole in each corner of the unit. Please keep the key in a safe place.
The A300E should be secured to a suitable surface through the 4 corner fixing points as shown below using suitable fasteners, for example no.6 wood screws.
Figure 2: Capillary Tube Sample Holes
End Cap The end of the pipe should be terminated with an end cap,
having a central hole typically 6mm in diameter. If the end cap is not used, then practically no air will be
drawn through the side holes. Without a hole in the end cap the contributions from the
side holes will tend to be very unbalanced. Bends Bends are either 45 or 90 degrees. For the 90-degree bends
it is very important that slow radii are used and not a sharp elbow , as this will introduce unacceptable pressure losses , and significantly increase the response times from holes beyond the bend.
T Pieces A T joint can be used on pipes to produce 2 branches. It is
recommended that the total number of holes in a resulting pipe system is no more than the number of holes estimated for a single pipe design. For example, if a single 100M pipe can have up to 18 holes, 2 branches can have up to 9 holes each. It is important that the branches have a balanced design - that is, they should be approximately equal in length and number/size of holes). For further information, please see the maximum pipe length/hole size data in Table 6 and the T Piece e xample shown later in the manual.
Exhaust
In most installations the exhaust should be left open, but there are some circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit; For example to reduce noise, reduce risk of interference/deliberate obstruction, improved environmental protection etc. Pipe of the same specification as the sample runs should be used and its length limited to a maximum of 10m to avoid significant reduction in the airflow. Care should be taken to position the new exhaust outlet where it cannot be accidentally or deliberately blocked.
A320E Installation
Where the two pipe A320E unit is used, it is important that the air flow through the two pipes is balanced otherwise the responses of the two sensors may be affected.
Figure 3: Pipe Accessories
45° AND 90° PIPE BENDS
END CAP
242 mm
1
6
7
m
m
1
8
4
m
m
259 mm
To A300 E
Ceiling
the hole. Capillary tubes can also be used with the holes as in figure 2.
3
© System Sensor 2008 I56-2634-004ENPittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
DEUTSCH
ENGLISH
A300E SERIES WIRING
Warning Before working on the system, notify the proper authorities that the system is undergoing maintenance and will be temporarily out of service. Ensure that all power is removed before opening the A300E unit.
Note: All wiring must be in accordance with local requirements The A300E connections are accessed by removing the unit
cover using the supplied key, and then carefully lifting the front display panel away from the A300E housing. The ribbon cable that connects the front display PCB to the main PCB may be unplugged if necessary .
The main PCB (See figure 4) includes wiring terminal blocks for connecting the 24V power supply to the A300E unit, accessing the fault relay contacts for each channel and the optional loop connections.
Power Connection
The A300E unit is designed to run from a nominal 24VDC supply. The supply should be connected to the 2 way connector on the main circuit board ensuring that the wires are correctly orientated. It is recommended that the wires should be a minimum size of 16 x 0.25mm (18AWG), or larger if the supply is further than 5m from the system.
A ferrite core is provided for EMC compliance. This should be fitted to the supply wiring as shown below.
The current drawn is dependent on the fan speed – see Table 4 for details.
LOOP OR ZONE CONNECTIONS FROM FIRE DETECTION CONTROL PANEL
Figure 4: A300E SERIES Terminal La yout
ASPIRATING SYSTEM CHANNEL 2 FAULT CONTACTS (A320E DUAL CHANNEL UNIT ONLY )
NO COM NC
NO COM NC
EXTERNAL POWER SUPPLY TO ASPIRATING SYSTEM
ASPIRATING SYSTEM CHANNEL 1 FAULT CONTACTS (BOTH A310E AND A320E)
+24VDC 0VDC
FUSE
LOOP IN (+) LOOP IN (-) LOOP OUT (+) LOOP OUT (-)
Sensor Connection
The loop terminals are linked via a ribbon cable to the +/­terminals mounted on the front display PCB, which facilitate connection to the sensor bases if required. The necessary bases (standard base B501 type for 7251 sensors) should be mounted on the front display panel using the M4 screws provided, with short wires connecting to the +/- terminals if used.
Loop wiring connections are made to either the pluggable terminal blocks or directly to sensor bases, both of which will accept wire sizes from 1mm² to 2.5mm². For best results, screened cable should be used. Refer to the control panel instructions for cable type limitations.
Once wiring has been completed, the A300E unit should be re-assembled in reverse order .
IMPORTANT
The glands on the top of the unit that provide entry for the cabling must to be sealed to ensure that the only air entering the unit is coming in through the sample pipes. all wiring must pass through the cable seals provided and no additional holes should be made. In order to pass a cable through a seal it is necessary to make a small hole in the centre of the seal with a pointed implement (e.g. small screwdriver) and then force the cable through the hole into the bo x. The small hole will expand to accommodate any cable diameter from 4 to 10mm and then provide an airtight seal.
Figure WF: Ho w to Fit the Ferrite
NO COM NC
NO COM NC
4D200-41-00
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
T1 (-)
T1 (-)
T2 (+)
T2 (+)
B501
B501
T1 (-)
T1 (-)
T2 (+)
T2 (+)
B501
B501
(Wiring when base #2 not fitted)
WIRING CONFIGURA TION
The A310E and A320E may be wired in several different configurations, dependant on the application and information required. Typical configurations are shown below .
For the single channel A310E, either one or two sensors can be used (to simulate “double knock” type applications). For the A320E dual channel system, sensor 1 monitors channel 1, and sensor 2 monitors channel 2. See relevant sensor and module manuals for correct wiring to the device or base.
LOOP (+) IN LOOP (-) IN LOOP (+) OUT LOOP (-) OUT
Sensor Arrangement 1.
See figure 5. Two analogue addressable sensors are wired through the aspirating unit. Loop connections are made to the terminal block on the A300E main PCB.
Note: This configuration can increase the loop impedance by up to one Ohm. If this is lik ely to cause a problem, use Sensor Arrangement 2 below .
MAIN PCB
DISPLAY PCB
Sensor Arrangement 2.
See Figure 6. The analogue sensors are connected directly to the fire control panel on the loop. The loop wiring is made directly to the sensor bases.
SENSOR #2
SENSOR #1
A300E ASPIRATING SYSTEM ENCLOSURE
A300E ASPIRATING SYSTEM ENCLOSURE
MAIN PCB
DISPLAY PCB
LOOP (+) LOOP (-)
LOOP (+) LOOP (-)
SENSOR#2
SENSOR#1
Figure 5: Wiring Configuration 1
Figure 6: Wiring Configuration 2
5
© System Sensor 2008 I56-2634-004ENPittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
DEUTSCH
ENGLISH
T1 (-)
T1 (-)
T5 (+)
T5 (+)
B524IEFT-1
(Wiring when base #2 not fitted)
T6 (+)
T6 (+)
T1 (-)
T1 (-)
T6 (+)
T5 (+)
T5 (+)
B524IEFT-1
T6 (+)
Using Isolator Bases
The A310E and A320E may be fitted with isolator bases (B524IEFT-1) if required. The basic configurations used on the previous page are amended below .
Sensor Arrangement 1 with Isolator Bases
See figure 30. Analogue addressable sensors are wired through the aspirating unit. Loop connections are made to the terminal block on the A300E main PCB.
Figure 30: Wiring Configuration 1 with Isolator Bases
A300E ASPIRATING SYSTEM ENCLOSURE
DISPLAY PCB MAIN PCB
SENSOR#2
SENSOR#1
LOOP (+) IN LOOP (-) IN LOOP (+) OUT
LOOP (-) OUT
Sensor Arrangement 2 with Isolator Bases
See Figure 40. The analogue sensors are connected directly to the fire control panel on the loop. The loop wiring is made directly to the sensor bases.
Figure 40: Wiring Configuration 2 with Isolator Bases
A300E ASPIRATING SYSTEM ENCLOSURE
DISPLAY PCB
MAIN PCB
SENSOR#2
SENSOR#1
LOOP (+) LOOP (-)
LOOP (+) LOOP (-)
6D200-41-00
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
Fault Reporting
Fault monitoring of the A300E unit should be reported back to the panel using one of the suggested input module arrangements:
For the A310E, a single input M210E module can be used (see Figure 50). For the A320E, a dual input M220E can be used if separate fault reporting for each channel is required (see Figure 50).
Alternatively, an M210E module can be used if common fault reporting from both channels of the A320E is sufficient within the system (see Figure 60).
If the wiring and module must remain within the aspirating unit, an M503ME micro module can be used in place of the M210E.
47K R
47K R
4
7
K
R
Figure 50: Suggested Wiring for A310E / A320E Using M210E / M220E Module
A300E ASPIRATING SYSTEM ENCLOSURE
DISPLAY PCB
MAIN PCB
SENSOR #2
SENSOR #1
EXTERNAL PSU +24V EXTERNAL PSU 0V
M210E OR M220E INPUT MODULE
(A320E AND M220E ONLY )
LOOP (+) LOOP (-)
LOOP (+) LOOP (-)
Figure 60: Suggested Wiring f or A320E Using M210E Module (Common F ault Reporting)
A300E ASPIRATING SYSTEM ENCLOSURE
MAIN PCB
DISPLAY PCB
EXTERNAL PSU +24V EXTERNAL PSU 0V
SENSOR #2
SENSOR #1
LOOP (+) LOOP (-)
M210E INPUT MODULE
LOOP (+) LOOP (-)
Loading...
+ 11 hidden pages