14D200-41-00
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
As seen in the previous section on response times, shorter pipe runs
minimise dilution. In Table 1.3.1 there is a rough guide to varying dilution
rates for wide-bore systems - IMPORTANT: The different
characteristics of each installation must also be taken into account
when assessing the dilution rate. many factors can affect this, as
previously discussed.
Table 1.3.1 General Dilution Rates for Wide-Bore Systems
1.4 Pipe Construction and Sampling Holes
Single channel System Sensor aspirating detectors have a maximum
pipe length of 100 metres.
Dual channel aspirating detectors have a maximum pipe length of 100
metres for each channel. Wherever possible, the pipe lengths for each
channel need to be kept to broadly similar lengths (for example, if
channel 1 has a pipe length of 30 m, channel 2 should be approximately
the same length). Failure to do this can result in slow response times,
thereby negating some of the early warning ability of the system.
System Sensor recommends that ABS piping be used due to its
strength and heat resistant properties. The pipe sections should be
glued together using a suitable ABS glue to avoid separation or leaks.
If a section of pipe is likely to need to be disconnected for some reason
in the future, removable unions should be used instead.
Important: Never glue pipes into the aspirating detector unit itself.
Sampling holes should be 3mm in diameter. The end of the pipe should
be capped and have a hole of 6mm in diameter.
Important: Elbows and bends in the pipe system can affect the
flow of air/smoke through the pipes and should only be used
when necessary.
Capillary Sampling
Short lengths of small diameter flexible pipe may be spurred off from
the main wide-bore pipe. This pipe should have an internal diameter of
no less than 7mm and can be of lengths up to 2 metres. For this a
sampling point assembly should be used (an example is shown below).
Capillary tubes can be used to provide concealed sampling points. If
the sampling points need to be as unobtrusive as possible, the
capillary allows the point to be placed flush to the surface. These are
most commonly used when the main wide-bore pipe runs through a
ceiling void, with capillary sample pipes placed through the false
ceiling.
Note 1: It is recommended to avoid running lengths of pipe with
both standard sampling holes and capillary sampling points on
them as this can unbalance the airflow and slow the response
time from the capillary points.
Note 2: Though British Standard BS 5839-1 states that there
must be a minimum of 25mm between the ceiling and the
sampling point of a detector, because the aspirating system
actually draws air through the sampling points (holes in the
pipework in this case), it can be possible to mount the sampling
points flush with the ceiling providing this will not be
detrimental to the effectiveness of the system to detect fire (see
1.1 Smoke Tests).
1.5 The Design Process
When designing the actual sampling pipe network there are many
factors that need to be considered. The site must be carefully
surveyed and as much information as possible should be gathered.
1.5.1 Requirements
The first consideration is to precisely ascertain the requirements of the
installation. Once these have been decided, the type of situation can be
looked at.
1.5.2 Activities
The types of activities that take place within the space are very
important. A public area of a particular shape could well have different
system requirements to a warehouse of a similar shape.
Other information such as the expected hours of operation, whether
the area is manned or unmanned and whether any pollution or dirty air
is present should also be taken into account.
1.5.3 Physical Characteristics
Once the general installation type has been considered, the physical
characteristics of the space should be looked at.
· Is it a room, void, cabinet or enclosure?
· Are there any floor or ceiling voids and, if so, how are they
divided, are there any ducts, what are these used for and are
there any services already present?
· What are the exact measurements of the space?
· What materials have been used and are there any areas where
the network has to avoid?
· Are there any existing fire protection systems and where are
they situated?
1.5.4 Environmental Conditions
The environment within the space can have a very significant bearing
on which sampling method should be used to protect it. As already
mentioned, the smoke tests are vital in gathering this information. This
can tell you the patterns of air movement, the rate of circulation and
whether the airflow is static at any point. Other considerations include:
· If fresh air is introduced, at what rate and in what quantity?
· Is a reference detector necessary due to pollution?
· What is the temperature and relative humidity and are these
constant or variable?
· Are there any activities that may produce smoke, dust, steam
or flames and how often does this occur?
1.5.5 Risk Assessment
With any installation it is likely that some areas require more protection
than others. This could be because of expensive equipment or a
particularly vulnerable area such as a store for flammable materials.
These more susceptible areas must be considered along with any
structural hazards such as synthetic materials and foams or soft wood
partitioning.
1.5.6 Potential Sites
There are also factors to consider when deciding where to position the
detector unit itself. The main aim when positioning the unit is to tr y to
ensure a balanced system. This means that the pipes should be kept at
similar lengths. It is also important to try and keep response times and
dilution to a minimum.
The unit requires a power supply and access will be required for
maintenance. There may also be aesthetic reasons why a particular
position is not suitable.
1.5.7 Exhaust Pipe
The exhaust pipe on the bottom of the aspirating detector unit can have
piping added should it be required, for example if the air passing
through the detector needs to be returned to its source. Extra piping
can also be used to reduce the noise of the fan if needed.