System Sensor A05-1003-002 User Manual

APPLICATIONS GUIDE
System
Smoke Detectors
1

Foreword

Studies have shown that in the United States the use of early warning fire and smoke detection systems has resulted in a significant reduction overall in fire deaths. The sooner a fire is detected, the better the chances are for survival.
A potential problem with smoke detectors is unwanted alarms that often result in people being desensitized to the alarm system or in severe cases dis­connecting the system. This is an industry-wide problem that in most cases is caused by improper application, installation and maintenance of smoke detectors. It is hoped that the information in this guide will be used by those involved with the application, installation and maintenance of fire alarm systems to minimize these problems.
APPLICATIONS GUIDE
System
Smoke Detectors

Contents

Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Section 1 – Standards that Apply . . . . . . . . . . . . . . . . . . . . . . . . . 2
NFPA Codes and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Building and Fire Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Testing Laboratories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Industry Publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Manufacturer’s Publications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Section 2 – How Smoke Detectors Work . . . . . . . . . . . . . . . . . . 3
Ionization Smoke Detector Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Photoelectric Smoke Detector Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Smoke Detector Design Consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Considerations in Selecting Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Smoke Detectors Have Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Section 3 – Typical System Layout . . . . . . . . . . . . . . . . . . . . . . . . 5
Electrical Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Class B Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Class A Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wireless Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
General Zoning Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fire Safety Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Smoke Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Wiring Techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wireless Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation Do’s and Don’ts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring and System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Section 4 – Proper Detector Applications,
Placement and Spacing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Where To Place Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Where Not To Place Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Special Application Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Standards for Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Detector Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Spacing Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Special Spacing Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Detectors in Air Handling and Air Conditioning Systems. . . . . . . . . . . . . . . . . 12
Detectors in Above-Ceiling Plenum Areas Including Plenums
Utilized as Part of the HVAC System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Section 5 – Testing, Maintenance and
Service of Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Typical Inspection, Test and Maintenance Practices . . . . . . . . . . . . . . . . . . . 13
Section 6 – Troubleshooting Techniques. . . . . . . . . . . . . . . . . . 14
What to Do About Unwanted Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Reasons for Unwanted Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintain an Alarm Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Effects of Location or Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Inspect Detector for Dirt and Review Maintenance. . . . . . . . . . . . . . . . . . . . . 14
Effects of other Systems on Alarm System Wiring. . . . . . . . . . . . . . . . . . . . . . 15
Miscellaneous Causes of Unwanted Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Responsibilities of Detector Owners and Installers . . . . . . . . . . . . . . . . . . . . 15
Where to Get Help if the Source of Unwanted Alarms Can’t be Found . . . . . 16
Appendix 1 – Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . . 17
Appendix 2 – Alarm Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

NFPA Codes and Standards

NFPA publishes standards for
the proper application, instal­lation, and maintenance of automatic smoke detectors. The principal codes and standards that should be reviewed before specifying or installing automatic smoke detectors are listed below:
National Fire Protection Association (NFPA) Batterymarch Park, Quincy, Massachusetts 02269-9101
NFPA publishes codes and standards concerning all phas­es of fire protection. Among those which directly concern automatic smoke detectors are:
NFPA 70: National Electrical Code NFPA 72: National Fire Alarm Code
NFPA 72 covers minimum performance, location, mount­ing, testing, and maintenance requirements of automatic fire detectors.
NFPA 90A: Standard for the Installation of Air Conditioning and Ventilating Systems NFPA 92A: Smoke Control Systems in Malls, Atria, and Large Areas
NFPA 90A and 92A provide information for the use of smoke detectors in ducts of HVAC systems and smoke con­trol systems.
NFPA 101: Life Safety Code
NFPA 101 specifies the requirements for smoke detection in both new and existing buildings depending on the type of occupancy.

Building and Fire Codes

There are three independent regional organizations which write model building and fire codes which become law when adopted by local and state governments. These codes specify smoke detector requirements based on building type and occupancy. The organizations are:
Building Officials and Code Administrators (BOCA) 4051 West Flossmoor Road, Country Club Hills, Illinois 60478-5795
BOCA’s National Building Code is generally used through­out the northeast and midwest regions of the United States.
International Conference of Building Officials (ICBO) 5360 Workman Mill Road, Whittier, California 90601­2298
ICBO’s Uniform Building Code is generally used through­out the West and Southwest regions of the United States.
Southern Building Code Congress International (SBCCI) 900 Montclair Road, Birmingham, Alabama 35213-1206
SBCCI’s Standard Building Code is generally used in the South and Southeast regions of the United States.
International Code Council, Inc. (International Building Code/International Fire Code) 5360 Workman Mill Road, Whittier, California 90601­2298
The organizations listed above have formed an umbrella organization known as the International Code Council (ICC), for the purpose of combining the codes produced by the above three organizations into a single set of model building and fire codes. ICC’s International Building Code and International Fire Code were first published in 2000 and have been adopted by some states.

Testing Laboratories

Testing laboratories test smoke detectors, control panels and other components of fire alarm systems to verify con­formance with NFPA requirements and their own stan­dards. Equipment that passes their tests are identified by a label and/or listing.
Underwriters Laboratories, Inc. (UL) 333 Pfingsten Road, Northbrook, Illinois 60062 1655 Scott Boulevard, Santa Clara, California 95050 1285 Walt Whitman Road, Melville, New York 11747 12 Laboratory Drive, P.O. Box 13995, Research Triangle Park, North Carolina
UL publishes an annual directory listing fire protection equipment which bear the UL label. Its standards which apply to smoke detectors are:
UL 217: Single and Multiple Station Smoke Detectors UL 268: Smoke Detectors for Fire Protection Signaling Systems UL 268A: Smoke Detectors for Duct Applications UL 864: Standard for Control Units for Fire Protective Signaling Systems
Factory Mutual Research (FM) 11 51 Boston-Providence Turnpike, P.O. Box 9102, Norwood, Massachusetts 02062
FM publishes an annual report listing fire protection equip­ment which bears its label.
APPLICATIONS GUIDE: SYSTEM SMOKE DETECTORS
2
The purpose of this guide is
to provide information con­cerning the proper application of smoke detectors used in conjunction with fire alarm systems. It outlines basic prin­ciples that should be considered in the application of early warning fire and smoke detection devices. Operating char­acteristics of detectors and environmental factors, which may aid, delay or prevent their operation, are presented.
Fire protection engineers, mechanical and electrical engi­neers, fire service personnel, fire alarm designers and
Section 1
Standards That Apply

Introduction

installers should find the contents both educational and informative.
Though this information is based upon industry expertise and many years of experience, it is intended to be used only as a technical guide. The requirements of applicable codes and standards, as well as directives of the Authorities Having Jurisdiction (AHJ’s) should be followed. In partic­ular, the most current version of NFPA 72 for installation and testing of systems is a key element in the effectiveness of smoke detection systems.
Manufacturer’s Publications
The manufacturer of the smoke detectors being used should be contacted for any published information on their products.
SYSTEM SENSOR
3

Industry Publications

NEMA Guide for Proper Use of Smoke Detectors in Duct Applications NEMA Training Manual on Fire Alarm Systems NEMA Guide to Code Requirements for Fire Protective Signaling and Detection Systems NEMA Guide for proper Use of System Smoke Detectors
There are two basic types of smoke detectors in use today; ionization and photoelectric.
The sensing chambers of these detectors use different principles of operation to sense the visible or invisible particles of combustion given off in developing fires.

Ionization Smoke Detector Operation

A typical ionization chamber consists of two electrically charged plates and a radioactive source (typically Americium 241) for ionizing the air between the plates. (See Figure 1.) The radioactive source emits particles that collide with the air molecules and dislodge their electrons. As molecules lose electrons, they become positively charged ions. As other molecules gain electrons, they become negatively charged ions. Equal numbers of positive and negative ions are created. The positively charged ions are attracted to the negatively charged electrical plate, while the negatively charged ions are attracted to the pos­itively charged plate. (See Figure 2.) This creates a small ionization current that can be measured by electronic cir­cuitry connected to the plates (“normal” condition in the detector).
Particles of combustion are much larger than the ionized air molecules. As particles of combustion enter an ioniza­tion chamber, ionized air molecules collide and combine with them. (See Figure 3.) Some particles become posi­tively charged and some become negatively charged. As these relatively large particles continue to combine with many other ions, they become recombination centers, and the total number of ionized particles in the chamber is reduced. This reduction in the ionized particles results in a decrease in the chamber current that is sensed by elec­tronic circuitry monitoring the chamber. When the current is reduced by a predetermined amount, a threshold is crossed and “alarm” condition is established.
Changes in humidity and atmospheric pressure affect the chamber current and create an effect similar to the effect of particles of combustion entering the sensing chamber. To compensate for the possible effects of humidity and pressure changes, the dual ionization chamber was developed and has become commonplace in the smoke detector market.
A dual-chamber detector utilizes two ionization chambers; one is a sensing chamber that is open to the outside air. (See Figure 4). The sensing chamber is affected by partic­ulate matter, humidity, and atmospheric pressure. The other is a reference chamber that is partially closed to out­side air and affected only by humidity and atmospheric pressure, because its tiny openings block the entry of larg­er particulate matter including particles of combustion.
Electronic circuitry monitors both chambers and compares their outputs. If the humidity or the atmospheric pressure changes, both chambers’ outputs are affected equally and cancel each other. When combustion particles enter the sensing chamber, its current decreases while the current of the reference chamber remains unchanged. The resulting current imbalance is detected by the electronic circuitry. (See Figure 5.) There are a number of conditions that can affect dual-chamber ionization sensors; dust, excessive humidity (condensation), significant air currents, and tiny insects can be misread as particles of combustion by the electronic circuitry monitoring the sensors.
Section 2
How Smoke Detectors Work
Figure 1: Particle Radiation Pattern
Figure 2: Ion Distribution
Figure 3: Ion and Particles of Combustion Distribution
Figure 5: Dual Chamber with
Particles of Combustion
Figure 4: Dual Chamber
Sensing Chamber Source
Reference Chamber (Current Stable)
Sensing Chamber (Current Decreasing)
Reference Chamber (Current Stable)
APPLICATIONS GUIDE: SYSTEM SMOKE DETECTORS
4

Photoelectric Smoke Detector Operation

Smoke produced by a fire affects the intensity of a light beam passing through air. The smoke can block or obscure the beam. It can also cause the light to scatter due to reflec­tion off the smoke particles. Photoelectric smoke detectors are designed to sense smoke by utilizing these effects of smoke on light.
Photoelectric Light Scattering Smoke Detector
Most photoelectric smoke detectors are of the spot type and operate on the light scattering principle. A light-emitting diode (LED) is beamed into an area not normally “seen” by a photosensitive element, generally a photodiode. (See Figure 6.) When smoke particles enter the light path, light strikes the particles (Figure 7) and is reflected onto the pho­tosensitive device causing the detector to respond.
Photoelectric Light Obscuration Smoke Detector
Another type of photoelectric detector, the light obscura­tion detector, employs a light source and a photosensitive receiving device, such as a photodiode (see Figure 8). When smoke particles partially block the light beam (Figure 9), the reduction in light reaching the photosensi­tive device alters its output. The change in output is sensed by the detector’s circuitry, and when the threshold is crossed, an alarm is initiated. Obscuration type detectors are usually of the projected beam type where the light source spans the area to be protected.

Smoke Detector Design Considerations

Smoke detectors are based on simple concepts, but certain design considerations need to be observed. They should produce an alarm signal when smoke is detected, but should minimize the impact of an unwanted signal which can arise from a variety of causes. In an ionization detec­tor, dust and dirt can accumulate on the radioactive source and cause it to become more sensitive. In a photoelectric detector, light from the light source may be reflected off the walls of the sensing chamber and be seen by the photo­sensitive device when no smoke is present. The entrance of insects, dirt, drywall dust, and other forms of contamina­tion into the sensing chamber can also reflect light from the light source onto the photosensitive device.
Electrical transients and some kinds of radiated energy can affect the circuitry of both ionization and photoelectric smoke detectors and be interpreted by the electronic cir­cuitry to be smoke, resulting in nuisance alarms.
The allowable sensitivity ranges for both types of detectors are established by Underwriters Laboratories, Inc. and all are verified by their performance in fire tests. Regardless of their principle of operation all smoke detectors are required to respond to the same test fires.

Considerations in Selecting Detectors

The characteristics of an ionization detector make it more suitable for detection of fast flaming fires that are charac­terized by combustion particles in the 0.01 to 0.4 micron size range. Photoelectric smoke detectors are better suited to detect slow smoldering fires that are characterized by particulates in the 0.4 to 10.0 micron size range. Each type of detector can detect both types of fires, but their respec­tive response times will vary, depending on the type of fire.
Because the protected buildings normally contain a variety of combustibles, it is often very difficult to predict what size particulate matter will be produced by a developing fire. The fact that different ignition sources can have dif­ferent effects on a given combustible further complicates the selection. A lighted cigarette, for example, will usually produce a slow smoldering fire if it is dropped on a sofa or bed. However, if the cigarette happens to fall upon a news­paper on top of a sofa or bed, the resulting fire may be characterized more by flames than by smoldering smoke.
The innumerable combustion profiles possible with vari­ous fire loads and possible ignition sources make it difficult to select the type of detector best suited for a particular application.
Figure 6: Light Scattering Detector
Figure 7: Light Scattering Detector with Smoke
Figure 8: Light Obscuration Detector
Figure 9: Light Obscuration Detector with Smoke
Light Source Light Sensitive Device
Light Source Light Sensitive Device
Light Source Light Sensitive Device
Light Source Light Sensitive Device

Wiring Supervision

The initiating circuits that con-
nect smoke detectors to a con-
trol panel should be super­vised so that a fault (trouble) condition that could interfere with the proper operation of the circuit will be detected and annunciated.
Smoke detectors are generally categorized as either 2-wire or 4-wire detectors. Two-wire detectors derive their power directly from the same fire alarm control panel alarm initi­ating device circuit over which they report an alarm. Because of their dependency on the initiating circuit, 2-wire detectors must be tested and listed for compatibility with the control panel to be used, to ensure proper operation.
Four-wire detectors are powered from a separate pair of wires, and, like the 2-wire detector, apply an electrical short across the associated alarm initiating device circuit to transmit an alarm (Figure 10). Because they do not derive power from the alarm initiating device circuit, electrical compatibility is predicated upon the operating parameters of the power supply to which the detectors are connected and not the initiating circuit. Supervision of the power to 4-wire detectors is mandated through the use of an end-of­line power supervision relay. When power is on, the relay contacts of the end-of-line relay are closed and connected in series with the end-of-line resistor beyond the last initi­ating device. Loss of power at any point in the power sup­ply circuit will cause the relay to de-energize and a trouble condition to occur on the initiating circuit.
NOTE*: Refer to the fire alarm control panel manufacturer’s operating manual to determine the ability of a specific initi­ating circuit to react in a “Class B” or “Class A” fashion.
For more information, see NFPA 72-1999, paragraphs A-2-
3.6.1.2, A-2-3.6.1.1, A-2-3.6.1.2(a), and A-2-3.6.1.2(b).
NFPA 72 requirements also dictate that alarm notification appliances (including smoke detectors with built-in sounders) produce the 3-pulse temporal pattern fire alarm evacuation signal described in ANSI S3.41. (Audible Emergency Evacuation Signals)
Situations Where Other Types of Detectors May Be Used
In certain circumstances where standard smoke detectors are unsuitable, special-purpose detectors, such as flame detectors, heat detectors, and other detection devices may be used.
The application of these special types of detectors should be based on an engineering survey and used in accordance with the manufacturer’s installation instructions provided.

Smoke Detectors Have Limitations

Smoke detectors offer the earliest possible warning of fire. They have saved thousands of lives in the past and will
SYSTEM SENSOR
5
save more in the future. Nevertheless, smoke detectors do have limitations. They may not provide early warning of a fire developing on another level of a building. A first floor detector, for example, may not detect a second floor fire. For this reason, detectors should be located on every level of a building. In addition, detectors may not sense a fire developing on the other side of a closed door. In areas where doors are usually closed, detectors should be locat­ed on both sides of the door.
As already indicated, detectors have sensing limitations. Ionization detectors are better at detecting fast, flaming fires than slow, smoldering fires. Photoelectric smoke detectors sense smoldering fires better than flaming fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is always best. A given detector may not always provide sig­nificant advance warning of fires when fire protection prac­tices are inadequate, nor when caused by violent explo­sions, escaping gas, improper storage of flammable liquids such as cleaning solvents, etc.
Section 3
Ty pical System Layout

Class B Circuits

Class B circuits differentiate between short circuits across the loop (alarm) and opens on the loop (trouble). Supervision of this circuit is accomplished by passing a low current through the installation wiring and an end-of-line resistor. Increases or decreases in this supervisory current are monitored by the fire alarm control panel and will cause alarm or trouble conditions, respectively, to be indi­cated. A single open in a Class B circuit disables all devices electrically beyond the open.
*NFPA 72 now classifies initiating device circuits by “Style” and “Class”. Style B is an example of a Class B circuit; Style D is an example of a Class A circuit.
Figure 10: Two-Wire Detector Circuit
END OF LINE
RESISTOR
TYPICAL
INITIATING
DEVICES
INITIATING DEVICE
CIRCUIT
ZONE 1
TROUBLE ALARM
FIRE ALARM CONTROL UNIT
PRIMARY
POWER
SUPPLY
APPLICATIONS GUIDE: SYSTEM SMOKE DETECTORS
6

Class A Circuits

Class A circuits also differentiate between short circuits across the loop and opens on the loop. Supervision is accomplished by monitoring the level of current passing through the installation wiring and the end-of-line resistor, which in a Class A circuit is an integral part of the fire alarm control panel. Class A wiring must return to and be terminated in the control panel. This technique requires a minimum of four conductors to be terminated at the panel, and further requires that the fire alarm control panel is designed to monitor Class A circuits. The additional cir­cuitry necessary for Class A supervision enables the con­trol panel to “condition” the initiating circuit to monitor the initiating circuit from both ends when in a trouble mode due to an open fault on the loop. This “conditioning” ensures that all devices are capable of responding and reporting an alarm despite a single open or non-simultane­ous single ground fault on a circuit conductor.
The compatibility considerations of smoke detectors that were detailed in Class B circuits apply with Class A as well (Figure 11).
Figure 11: 2-Wire Detectors – Style D (Class A) Circuit

Wireless Circuits

Wireless detectors and their internal transmitters derive their operating power from their internal battery or batter­ies and are listed by Underwriters Laboratories, Inc. in accordance with requirements of NFPA 72. Supervision of the internal battery power source is incorporated within the smoke detector circuitry. If the battery power source depletes to the threshold specified by Underwriters Laboratories, the smoke detector will sound a local alert and initiate a trouble signal once each hour for a minimum of seven days or until the battery or batteries are replaced.
The wireless initiating devices are supervised for tamper and/or removal by initiating a distinct trouble signal. Each wireless device also initiates a test transmission every hour to verify the reliability of the communication circuit. Any device failing to communicate is identified on the control panel no less than every four hours.

General Zoning Guidelines

The faster the source of an alarm can be pinpointed, the faster action can be taken. Although formal rules for zon­ing are not given in fire protection codes, except for wire­less devices where each smoke detector must be individu­ally identified, it is always sensible to zone any system that contains more than a small number of detectors. Experienced detector installers and system designers rec­ommend the following:
• Establish at least one zone on every protected floor.
• Zone natural subdivisions of a large building, such as separate wings on a single floor.
• Minimize the number of detectors in each zone. Fewer detectors on a zone will speed up locating the fire and simplify troubleshooting.
• Install duct detectors in different zones than open-area detectors for troubleshooting and locating purposes.

Fire Safety Functions

Often smoke detectors are utilized to control ancillary equipment. Most detectors used in releasing service have auxiliary relay contacts which are directly connected to the system or device to be controlled. Care should be taken to ensure that detectors utilized in such a manner are approved for releasing service. A few of the typical appli­cations are as follows:
•To control the flow of smoke in air handling and air conditioning systems.
•To release doors to contain smoke in a fire situation.
•To release locks to allow exit in a fire situation.
•To capture and recall elevators in a fire situation.
•To activate a suppression system.
Spacing and placement requirements for detectors used in releasing service may be different from detectors used in conventional open area applications. It is recommended that 4-wire detectors be used in these situations because depending on the control panel and detectors used, more than one detector relay on a circuit may not receive enough power from the 2-wire circuit to operate during alarm.

Smoke Detector Installation

Wiring Installation Guidelines
All fire alarm system installation wiring should be installed in compliance with Article 760 of NFPA 70, the National Electrical Code (NEC), the manufacturer’s instructions and the requirements of the authority having jurisdiction.
Typical Wiring Techniques
The primary rule of installation wiring is:
“Follow the Manufacturer’s Instructions”
This rule cannot be overemphasized. The requirement for electrical supervision of the installation wires and their connections to initiating devices makes fire alarm system installation wiring very different than general wiring.
TYPICAL
INITIATING
DEVICES
INITIATING DEVICE
CIRCUIT
ZONE 1
TROUBLE ALARM
FIRE ALARM CONTROL UNIT
PRIMARY
POWER SUPPLY
INITIATING DEVICE
CIRCUIT RETURN
Loading...
+ 14 hidden pages