System Sensor 885WP-B Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
Model 885WP-B Weatherproof Heat Detector with Fixed Temperature Alarm
Specifications
Before installing
General Description
Mounting
Tamper-resistant Feature
Figure2
Wiring Installation Guidelines
Figure 3
Figure 4.
Three-Y
ear Limited Warranty
Please refer to insert for the Limitations of Fire Alarm Systems (I56-1558-00)
System Sensor warrants its enclosed heat detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this HEAT detector. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period
  
ear Limited W
commencing with the date of manufacture. After phoning System Sensor for a Return Authorization Number, return defective units postage prepaid to the Company. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault.
4 I56-885-00CW
Rev.1
Diameter:
Height (including base):
Weight (including base): Operating Temperature Range: IP Rating: Sensitivity: Operating Voltage: Standby Current: Alarm Current:
Latching Alarm: Max .Air Velocity
10.2 cm (4")
4.8 cm (1.8") 170g (6.0 ounce)
-15qto 50qC (5qF to 122qF)
IP67 63qC (145.4qF) Fixed Temperature
8.5 to 30VDC İ50嘕$ Min. 2mA #3.1VDC Max. 80mA #6.5VDC Reset by momentary power interruption 20m/s
Please thoroughly read System Sensor manual which provides detailed information on detector spacing, place­ment, zoning, wiring, and special applications. Copies of this manual are available at no charge from System Sensor.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and main­tained regularly in accordance with the requirements of the local standards and regulations. The detector should be cleaned at least once a year.
Figure1.
Surface mounting of the 885WP-B
heat detector into a 50 /60 mm junction box.
weatherproof
Alignment when the detector is mounted into the base
Model 885WP-B is a 2-wire fixed temperature (63qC) heat detector. This detector is designed to provide open area protection in areas subject to moisture. This detector is sealed against the entry of moisture to a rating of IP67. The LED will latch on when the detector is in alarm.
Each 885WP-B detector is used with a mounting base that permits the detector to be mounted directly to a 50 mm or 60 mm junction box.
This detector includes a tamper-resistant feature that prevents its removal from the mounting base without the use of a key. To make the detector tamper-resistant, remove the tab from the tamper arm on the mounting base using a cutting tool. Remove the tamper key from the center of the mounting base by twisting it back and forth several times (see
). Once the detector is installed, it may be removed from the mounting base by inserting the T-shaped end of the key into the slot on the side of the unit and rotating the detector counter-clockwise.
This detector provides six wires which are divided into three groups, separately two red, two white and two black wires. Refer to
. .
Terminal Notes:
Red wire: Power / Detector Circuit +ve Black wire Power / Detector Circuit -ve (the power and
the LED uses the same cathode) White wire Remote LED +ve Wiring Diagram refers to
1 I56-885-00CW
Installation
Testing
Figure2.
Module 885WP-B weatherproof Heat
Detector
Mounting Bracket
Testing
Maintenance
Figure 3.
Maintenance
Figure 4. Detector Wiring Diagram
NOTE: All wiring must conform to applicable local
codes, ordinances and regulations.
NOTE: Verify that all detector bases are installed, that the
initiating-device circuits have been tested, and that the wiring is correct.
Remove power from initiating-device circuits before in-
WARNING
stalling detectors.
1. Place the detector on the mounting base and rotate clockwise until it drops into place.
2. Turn the detector clockwise in the mounting base until it clicks into place.
3. After all detectors have been installed, apply power to the control unit or initiating-device circuits.
4. Test the detector as described in
5. Reset the detector at the system control panel.
Te
.
6. Notify the proper authorities the system is in operation.
ALIGNMENT
Module 885WP-B weatherproof Heat
NOTCHES
TEMPER ARM
(CUT OFF SMALL TAB TO ACTUATE TAMPER-RESIST FEATURE-DEPRESS ARM WITH KEY TO
REMOVE DETECTOR)
TAMPER
KEY
NOTE: Before testing, notify the proper authorities that
the thermal detector system is undergoing mainte­nance and will temporarily be out of service. Disable the zone or system undergoing mainte-
nance to prevent unwanted alarms. Detectors must be tested after installation as well as after each time maintenance is performed. Test the 885WP-B as follows:
To test the 885WP-B you need a hair dryer. From the side of the detector, direct the heat toward the sensor. Hold the heat source about 15 cm away to prevent damage and apply heat to the cover during testing until it alarms.
A detector that fails these tests should first be cleaned as outlined in the the detector still fails , it should be returned for repair.
section which follows. If
Notify the proper authorities the system is back on line.
BLACK (-ve 2 wires)
WHITE (Remote LED +ve 2 wires)
Metal heat Collector
RED (+ve 2 wires)
1. Remove the detector from the mounting base by rotating it counter-clockwise.
NOTE: Before removing the detector, notify the proper
authorities that the fire detection system is undergoing maintenance and will temporarily be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
2. Vacuum the metal heat collector and surrounding area.
3. Clean the surface of the detector.
4. Reinstall the detector.
5. Test the detector as described in
Testing.
6. Notify the proper authorities the system is back in
operation.
RED wires
WHITE wire
BLACK wires
2 I56-885-00CW
3 I56-885-00CW
Loading...