System Sensor 7251A Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
7251A Intelligent Laser Smoke Sensor
Specifications
Operating Voltage Range: 15 to 32 VDC Standby Current: 330 Max. Alarm Current (LED on:) 6.5 mA @ 24 VDC Operating Humidity Range: 10% to 93% Relative Humidity, noncondensing Operating Temperature Range: 0°C to 38°C (32°F to 100°F) Height: 1.7 inches (43 mm) installed in B210LPA Base Diameter: 6.1 inches (155 mm) installed in B210LPA Base
4.1 inches (104 mm) installed in B501A Base Weight: 5.0 oz. (142 g) Additional Bases Available: All 200/500 Series bases are compatible.
µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
Before Installing
This sensor must be installed in compliance with the con­trol panel system installation manual. The installation must meet the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with CAN/ULC S524.
Model 7251A is a plug-in type smoke sensor that uses a laser based sensing chamber. The sensor uses analog­addressable communications to transmit smoke density and other information to the control panel. Rotary-decade switches are provided for setting the sensor’s address. Two LEDs on the sensor are controlled by the panel to indicate sensor status. An output is provided for connection to an optional remote LED annunciator (P/N RA400Z).
This detector requires compatible addressable com­munications to function properly. Connect this sensor to listed-compatible control panels only.
Spacing
System Sensor recommends spacing sensors in compli­ance with CAN/ULC S524. In low air flow applications with smooth ceilings, space sensors 30 feet apart. For spe­cific information regarding sensor spacing, placement, and special applications, refer to CAN/ULC S524 or the System Sensor Guide For Proper Use of System Smoke Detectors, available from System Sensor (P/N I56-407-XX).
All wiring must be installed in compliance with the Canadian Electrical Code, applicable local codes, and any special requirements of the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper connections will prevent a sys tem from responding properly in the event of a fire.
Remove power from the communication line before installing sensors.
All wiring must conform to applicable local codes, ordi­nances, and regulations.
1. Wire the sensor base (supplied separately) per the wir­ing diagram, see Figure 1.
2. Set the desired address on the sensor address switch­es, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control unit and activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
-
Wiring Instructions
D200-09-00 1 I56-1986-000
CAUTION
3
2
1
3
2
1
+
+
OPTIONAL RETURN LOOP
RE M OTE ANNUN C IATOR
+
Figure 1. Wiring diagram:
CAUTION
ULC Listed Compatible
Control Panel
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling or construction.
Testing
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodi­cally thereafter. Testing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer maximum per­formance when tested and maintained in compliance with CAN/ULC S536.
The sensor can be tested in the following ways: A. Functional: Magnet Test (P/N M02-04-01 or M02-09-
00)
This sensor can be functionally tested with a test mag-
net. The test magnet electronically simulates smoke in the sensing chamber, testing the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as
Do not loop wire under terminal 1 or 2. Break wire run to provide supervision of connection.
C0100-00
shown in Figure 3.
2. The sensor should alarm the panel. Two LEDs on the sensor are controlled by the panel
to indicate sensor status. Coded signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical documentation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry: Aerosol Generator (Gemini 501)
The GEMINI model 501 aerosol generator can be used for smoke entry testing. Set the generator to represent 4%/ft. to 5%/ft. obstruction as described in the GEMINI 501 manual. Using the bowl shaped applicator, apply aerosol until the panel alarms.
A sensor that fails any of these tests should be cleaned as described under CLEANING, and retested. If the sensor fails after cleaning, it must be replaced and returned for repair.
When testing is complete, restore the system to nor­mal operation and notify the proper authorities that the system is back in operation.
D200-09-00 2 I56-1986-000
Loading...
+ 2 hidden pages