System Sensor 6500R, 6500RS Installation And Maintenance Instructions Manual

I56-2081-013 © System Sensor 2009DB200-01-01
1
DEUTSCH
ESPAÑOL
ENGLISH ITALIANO
FRANÇAIS
GENERAL
The model 6500RS includes an integral servo controlled calibrated test filter, which allows automatic remote alarm testing.
SPECIFICATIONS: General
Range: 5 to 70m
70m to 100m using optional 6500-LRK/BEAMLRK
Sensitivity: Level 1: 25% Obscuration
Level 2: 30% Obscuration Level 3: 40% Obscuration Level 4: 50% Obscuration Level 5: 30% to 50% Adjusting (Acclimate) Level 6: 40% to 50% Adjusting (Acclimate)
Maximum angular misalignment: Detector: ± 0.5°
Reflector: ± 10°
Environmental
Temperature Range: -30°C to 55°C Humidity: 10% to 93% Relative Humidity
(Non-condensing)
Mechanical
Dimensions (Without Faceplate): 230mm x 178mm x 84mm Dimensions (With Faceplate): 253mm x 193mm x 84mm Wiring: 1mm² to 2.5mm² Adjustment Angle: ±10° Horizontal and Ver tical
Electrical
Voltage Range: 6500R: 10.2 to 32 VDC
6500RS: 15 to 32VDC Avg. Standby Current: 17mA at 24 VDC Max. Alarm Current: 38.5mA at 24VDC Max. Fault Current: 8.5mA at 24 VDC 6500RS Test Mode: 500mA peak Relay Contact Ratings: 0.5A at 30 VDC Remote Output (Alarm): Voltage: 15 to 32VDC
dependant on supply
Current: 6mA to 15mA,
Limited by 2.2KΩ Resistor
PARTS LIST Description Quantity
Transmitter/Receiver Unit 1 Paintable Trim Ring 1 Reflector (6500REFL) 1 Plug in terminal blocks 5 Instruction Manual 1 Orange Alignment Assistance Label 1 Alarm 0 ohm Shunt 1 Alarm Limiting Resistor 470 ohm 1 Alarm Limiting Resistor 680 ohm 1 Alarm Limiting Resistor 1000 ohm 1 Schottky Diode 1
APPROVED ACCESSORIES 6500-LRK/BEAMLRK
Long Range Kit comprising three additional 20cm x 20cm reflectors, which may be mounted in a square with the supplied reflector, permitting the detector to be used for ranges from 70m to 100m.
6500-MMK/BEAMMMK
Multi-Mounting Kit allowing the 6500 to be mounted to ceilings, or to walls where the detector and reflector cannot be mounted within 10° of one another. One kit mounts either the transmitter/receiver unit or reflector. If the transmitter/receiver is mounted on the 6500-MMK/ BEAMMMK, then the 6500-SMK/BEAMSMK must be used. Note that only a single 20cm x 20cm reflector can be mounted using the MMKs: The 6500-LRK/BEAMLRK is not compatible with the MMKs.
6500-SMK/BEAMSMK
Surface Mounting Kit for the transmitter receiver (also used in combination with the MMK) to give an additional 43mm depth to assist surface mounting and to permit side entry cabling.
6500RTS-KEY
Remote test and annunciator accessory that enables the detector to be tested remotely, providing test and reset functions, a Red LED to indicate alarm conditions and a Yellow LED to indicate fault conditions.
DETECTOR MOUNTING Location
The 6500 must be located in accordance with local standards and guidelines, for example BS5839 part 1. For general information, refer to the application guide for projected beam smoke detectors available on request from your supplier.
Mounting Position
Beam detectors require a very stable mounting surface for proper operation. A surface that moves, shifts, vibrates, or warps over time may cause false alarm or fault conditions. Initial selection of a proper mounting surface will eliminate nuisance alarms and fault signals. Mount the detector on a stable mounting surface such as brick, concrete, a sturdy load-bearing wall, support column, structural beam, or other surface that is not expected to experience vibration or movement over time. DO NOT MOUNT the beam detector on corrugated metal walls, sheet metal walls, external building sheathing, external siding, suspended ceilings, steel web trusses, rafters, non­structural beam, joists, or other such surfaces. The reflector has a much greater tolerance to movement than the transmitter/receiver, hence in cases where only one stable mounting surface as defined above can be used, the transmitter/receiver unit should be mounted to the stable surface. See specifications for maximum permissible angular misalignment; movement outside these limits may cause nuisance alarms and faults.
Mounting Considerations
There must be a permanent clear line of vision between the detector and the reflector.
Reflective objects should be a minimum of 380mm from the line of sight between the detector and reflector to avoid compromise of the protected area by reflected light.
Direct sunlight or strong lights into the transmitter/receiver unit should be avoided. There should be a minimum of 10° between the paths of the light source and the detector beam.
Operation of the detector through panes of glass should be avoided if possible. If it is necessary to pass though glass, the angle between the beam and glass should be set a minimum of 10° off perpendicular, and operation through multiple panes should be avoided.
Mounting
The transmitter/receiver unit may be mounted directly to the wall, with rear cable entry. The detector base has four primary mounting holes, one in each corner of the base. All four holes must be used to provide secure mounting. In order to mount the detector to the wall, the outer cover must be removed after unscrewing its four retaining screws.
INSTALLATION AND MAINTENANCE INSTRUCTIONS
6500R AND 6500RS REFLECTIVE TYPE PROJECTED BEAM
SMOKE DETECTOR
I56-2081-013 © System Sensor 2009DB200-01-01
2
OPTICAL LINE OF SIGHT
WALL MOUNTING SCREW X 4
COVER SCREW X 4
W
ALL
ACCEPTABLE MOUNTING LOCATIONS FOR REFLECTOR
REFLECTOR
REFLECTOR
Figure 2a: Reflector Mounting Guidelines
Figure 2b: Reflector Mounting Guidelines
Please refer to the relevant kit instructions if the transmitter/receiver is to be mounted onto the 6500-SMK/BEAMSMK or 6500-MMK/ BEAMMMK allowing more flexibility for cable entry.
Figure 1: Transmitter/Receiver Wall Mounting
The reflector is mounted directly to the wall using all four of its mounting holes, one in each corner. The reflector must be mounted such that the plane of the reflector is perpendicular to the optical line of sight to the transmitter/receiver unit. The maximum tolerance for non­perpendicular mounting locations is 10°. If this tolerance is not possible, then the MMK should be used, see MMK instructions for mounting details.
10° MAXIMUM
Figure 3: Detector Terminal Connections
FAULT N.C.
FAULT COM
REMOTE TROUBLE OUT
NOT USED
REMOTE ALARM OUT
AUX (-)
TEST INPUT
RESET INPUT
POWER IN (+)
POWER IN (-)
POWER OUT (+)
POWER OUT (-)
ALARM N.O.
ALARM COM
ALARM N.O.
ALARM COM
ALARM LIMITING RESISTOR
ALARM LIMITING RESISTOR
SCHOTTKY DIODE (A)
SCHOTTKY DIODE (K)
Figure 4: 6500RTS-KEY Wiring
SEE 6500RTS-KEY INSTALLATION INSTRUCTIONS FOR 6500RTS-KEY ELECTRICAL RATINGS
T2-1: REMOTE ALARM OUTPUT
T3-3: REMOTE TROUBLE OUTPUT
T2-2: AUX (-)
T2-4: RESET INPUT
T2-2: AUX (-)
T2-3: TEST INPUT
GREEN
ORANGE
BLACK
RED
YELLOW
YELLOW
WIRING
Note: All wiring must be installed in accordance with local requirements.
Warning: Before working on the system, notify the proper authorities that the system is undergoing maintenance and will be temporarily out of service.
Wiring connections are made to pluggable terminal blocks, which can accept wire sizes from 1mm² to 2.5mm². For best results screened cable should be used. Refer to the control panel instructions for cable type limitations
6500R / 6500RS
1 2 3 4 1 2 3 4
1 2 3 4 1 2 3 4 1 2 3 4
T3 T2 T1 T4 T5
Signal Name Terminal Normal State Active Comment
State
Reset Input T2-4 High impedance 0V Momentarily connect to
Aux- to operate
Test Input T2-3 High impedance 0V Momentarily connect to
Aux- to operate
Aux- T2-2 0V - Internally connected to
Power -ve
Remote Alarm Out T2-1 High impedance +24V Via 2.2k ohms current
limit resistor
Remote Fault Out T3-3 High impedance +24V Via 2.2k ohms current
limit resistor
Table 0: Use of Input – Output Signals
.
Loading...
+ 4 hidden pages