System Sensor 5600 User Manual

WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS
5600 Series Mechanical Heat Detector Single Circuit: 5601P, 5602, 5603, 5604 Dual Circuit: 5621, 5622, 5623, 5624
Specifications:
Operating Voltage/Contact Ratings (Resistive): 6 – 125 VAC / 3A 6 – 28 VDC / 1A 125 VDC / 0.3A 250 VDC / 0.1A Maximum Installation Temperature: Models 5601P, 5603, 5621, and 5623: 100°F (38°C) Models 5602, 5604, 5622, and 5624: 150°F (65.6°C) Alarm Temperature: Models 5601P, 5603, 5621, and 5623: 135°F (57°C) Models 5602, 5604, 5622, and 5624: 194°F (90°C) Rate-of-Rise Threshold: 15°F (8.3°C) per minute (models 5601P, 5602, 5621, and 5622 only) Operating Humidity Range: 5 to 95% RH non-condensing Input Terminals: 14 – 22 AWG Back Box Mounting: 31⁄2˝ octagonal 4˝ octagonal Single gang 4˝ square with a square to round plaster ring Dimensions with mounting bracket: Diameter: 4.57 inches (11.6cm) Height: 1.69 inches (4.3cm) Weight: 6 oz. (170 grams)
CAUTION
To prevent the activation of the fixed temperature element, the shipping and storage temperature must not exceed 122°F (50°C).
Before Installing
This detector must be installed in compliance with the control panel installation manual and meet the requirements of NFPA 72, and/or the local authority having jurisdiction.
Read this manual carefully before using the detec­tor. This manual should be left with the owner/user of this equipment.
The 5600 series mechanical heat detector is in­tended for use in property protection applications, or for non-life-safety installations where smoke de­tection is not practical or appropriate.
For life-safety installations, smoke detectors must be used, in lieu of, or in addition to mechanical heat detectors.
The 5600 series consists of both single- and dual­circuit heat detectors featuring fixed temperature thermal sensors or combination fixed temperature/ rate-of-rise sensors, with temperature ratings of 135ºF (57ºC) or 194ºF (90ºC).
Markings on the exterior of the detector indicate the specific activation method and temperature rating. All models are identified as either 135ºF/57ºC or 194ºF/ 90ºC. Models equipped with combination fixed tem­perature/rate-of-rise sensors are marked FX/ROR. Fixed temperature only models are marked FX.
Non-Resettable Fixed Temperature Sensor
The fixed temperature element reacts to heat by re­sponding to a specific temperature setting (135ºF or 194ºF). The detection method is based on the spring action of a metal contact, held to the metal chamber by a fusible alloy. When the temperature reaches the alloy’s melting point, the metal contact will depress the diaphragm, causing the electrical contact to close the circuit. The circular external heat collector is released from the detector to visu­ally indicate that the detector has been activated.
NOTE: 5600 series Fixed Temperature models (5603, 5604, 5623, and 5624) are non-resettable, and can­not be tested.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
I56-2175-003R
D500-46-00 1 I56-2175-003R
Table 1. 5600 Series Mechanical Heat Detectors
Model
No.
Circuit
Temperature
Rating
Thermal Sensor
UL Maximum Spacing
(10-foot ceiling)
5601P Single 135ºF (57ºC) Fixed Temperature/Rate of Rise 50-feet x 50-feet
5602 Single 194ºF (90ºC) Fixed Temperature/Rate of Rise 50-feet x 50-feet 5603 Single 135ºF (57ºC) Fixed Temperature 25-feet x 25-feet 5604 Single 194ºF (90ºC) Fixed Temperature 25-feet x 25-feet 5621 Dual 135ºF (57ºC) Fixed Temperature/Rate of Rise 50-feet x 50-feet 5622 Dual 194ºF (90ºC) Fixed Temperature/Rate of Rise 50-feet x 50-feet 5623 Dual 135ºF (57ºC) Fixed Temperature 25-feet x 25-feet 5624 Dual 194ºF (90ºC) Fixed Temperature 25-feet x 25-feet
NOTE: Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.
FM Classification
RTI ratings are for installations which must comply with FM 3210.
Heat Detector Type RTI Classification
Fixed 135°F RTI: SPECIAL
RoR and Fixed 135°F RTI: ULTRA FAST and SPECIAL (Respectively)
Fixed 194°F RTI: SPECIAL
RoR and Fixed 194°F RTI: ULTRA FAST and SPECIAL (Respectively)
Self-Restoring Rate-of-Rise (ROR) Sensor
The rate-of-rise element responds to a rapid rise of temperature, approximately 15ºF (8.3ºC) per min­ute. As the temperature rises, the air within the sealed chamber expands. Should the chamber air expand faster than it can escape through the cali­brated vent, the diaphragm is depressed, and the electrical contact closes the circuit.
NOTE: Only the ROR element of 5600 series com­bination fixed temperature/ROR models (5601P, 5602, 5621, and 5622) are self-restoring, and may be tested using a hair dryer or heat gun. When testing the ROR element, to prevent the activation of the fixed temperature element, the heat source must not exceed the fixed temperature rating of the detector.
Figure 1. Bracket Mounting Locations:
A= 31⁄2˝ Octagonal box B= 4˝ Octagonal box C= Single gang box and 4˝ square with plaster ring D= Directly to Wall/Ceiling
Mounting Bracket
All 5600 series detectors are equipped with a mount­ing bracket that includes mounting slots to accom­modate single-gang, 3
1
2˝ octagonal, and 4˝ octagonal electrical boxes, as well as 4˝ square boxes equipped with a plaster ring (Figure 1). The mounting bracket is reversible to accommodate flush-mount and sur­face–mount installations (Figure 2).
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable state and local codes, and any special requirements of the local Authority Having Jurisdiction. Proper wire gauges should be used. The conductors used to connect heat detectors to the alarm control panel and ac­cessory devices should be color-coded to reduce the
Figure 2. Reversible Mounting Bracket:
Surface–mount
S0114-00
Flush–mount
S0113-00
S0115-00
D500-46-00 2 I56-2175-003R
likelihood of wiring errors. Improper connections
Control
Control
can prevent a system from responding properly in the event of a fire.
The non-polarized screw terminals on the back of the detector will accept 14–22 AWG wire. For best system performance, all wiring should be installed in separate grounded conduit; do not mix fire alarm system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to pro­vide additional protection against extraneous elec­trical interference.
Wire connections are made by stripping approxi­mately 1⁄4˝ of the insulation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire in place.
Figure 3. Wiring Diagram – Single Circuit Models:
Panel
+
EOL
OR
Installation
Remove power from the alarm control unit or initi­ating device circuits before installing detectors.
1. Detach the detector from the mounting bracket by
rotating the detector 1⁄4 turn counter-clockwise.
2. Orient the mounting bracket properly for either a
flush- or surface-mount installation (Figure 2).
3. Select the pair of mounting holes suitable for the
junction box, (Figure 1) and secure the bracket to the box.
4. Connect the wires to the detector per Figure 3 or
Figure 4, as applicable.
5. Place the detector onto the mounting bracket by
rotating clockwise. The detector will lock into place with a “click”.
6. After all detectors have been installed, apply
power to the alarm control unit.
7. Test each detector as described in Testing.
8. Reset all the detectors at the alarm control unit.
9. Notify the proper authorities that the system is
in operation.
Auxiliary
Device
S0239-00
Figure 4. Wiring Diagram – Dual Circuit Models:
Panel
+
Auxiliary
Device
Auxiliary
Device
OR
Auxiliary
Device
D500-46-00 3 I56-2175-003R
Auxiliary
Device
EOL
S0240-00
Testing/Maintenance
WARNING
WARNING
The rate-of-rise mechanism may be subject to re­duced sensitivity over time. Annual testing of the rate-of-rise operation is therefore recommended.
Before testing, notify the proper authorities that
When testing the ROR element, to prevent the ac­tivation of the fixed temperature element, the heat source must not exceed the fixed temperature rating of the detector.
maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any un­wanted alarms.
Only the ROR element of 5600 series combination fixed temperature/ROR models (5601P, 5602, 5621, and 5622) are self-restoring, and may be tested us­ing a hair dryer or heat gun.
5600 series fixed temperature models (5603, 5604, 5623, and 5624) are non-resettable, and cannot be tested.
CAUTION
When using the RRS-MOD with model 2WTA-B, do not mix the 2WTA-B with other model smoke de­tectors and dry contact closure devices, including mechanical heat detectors, manual pull stations and waterflow switches. Such mixing can cause a direct short on the auxiliary power terminals, damaging the control panel’s internal circuitry and/or damage devices connected to the initiating device circuit.
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
Syst em S ensor wa rran ts i ts enclosed product to be free from defec ts in mater ials and workma nship under normal use and se rvice for a pe riod of three years from date of manuf acture. System Sens or make s no other express warranty for the encl osed prod uct. No ag ent, representative, dealer, or emp loyee of th e Com pany has the authority to increas e or alter the ob ligatio ns or limitations of t his Warranty. The Compa ny’s obligati on of this Warra nty shall b e limit ed to t he replacement of any par t of th e product which is found to be defec­tive in material s or work manship under normal use and s ervice during t he three yea r period co mmencin g with the date of manufa cture. After phoning System Sensor’s t oll fre e n umber 800-SENS OR2 (736-7672) for a Retu rn Authorizatio n number, se nd defective uni ts pos tage prepai d to: System Sensor, Returns
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in ac­cordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
D500-46-00 4 I56-2175-003R ©2009 System Sensor
Department, RA #______ ____, 3825 Ohio Avenue, St. Charles, IL 60174. Pleas e include a note descri bing the ma lfunction and sus pected cau se of failure. The Company sha ll n ot b e ob ligated to replace units which are found to be defe ctive because of dam age, unre a­sonable use, modifi cations, or alt erations occurring after the date of manufacture. In no case shall the Company be liable for any consequen tial or in cidental damages for brea ch of this or any other Warranty, ex­pressed or implie d whatsoever, even if the lo ss or dam­age is cau sed by the Comp any’s negligenc e or fa ult. Some st ates do not allow the exclusion or limi tation of incidenta l or conse quential damages, so the above limitation or exclusi on may not appl y to you. This Warran ty gives you sp ecific legal rights, and you may also have o ther righ ts which vary fro m state to state.
Loading...