5600 Series
Mechanical Heat Detector
Single Circuit: 5601P, 5602, 5603, 5604
Dual Circuit: 5621, 5622, 5623, 5624
Specifications:
Operating Voltage/Contact Ratings (Resistive): 6 – 125 VAC / 3A
6 – 28 VDC / 1A
125 VDC / 0.3A
250 VDC / 0.1A
Maximum Installation Temperature: Models 5601P, 5603, 5621, and 5623: 100°F (38°C)
Models 5602, 5604, 5622, and 5624: 150°F (65.6°C)
Alarm Temperature: Models 5601P, 5603, 5621, and 5623: 135°F (57°C)
Models 5602, 5604, 5622, and 5624: 194°F (90°C)
Rate-of-Rise Threshold: 15°F (8.3°C) per minute
(models 5601P, 5602, 5621, and 5622 only)
Operating Humidity Range: 5 to 95% RH non-condensing
Input Terminals: 14 – 22 AWG
Back Box Mounting: 31⁄2˝ octagonal
4˝ octagonal
Single gang
4˝ square with a square to round plaster ring
Dimensions with mounting bracket: Diameter: 4.57 inches (11.6cm)
Height: 1.69 inches (4.3cm)
Weight: 6 oz. (170 grams)
CAUTION
To prevent the activation of the fixed temperature element, the shipping and storage temperature must not
exceed 122°F (50°C).
Before Installing
This detector must be installed in compliance with
the control panel installation manual and meet the
requirements of NFPA 72, and/or the local authority
having jurisdiction.
Read this manual carefully before using the detector. This manual should be left with the owner/user
of this equipment.
General Description
The 5600 series mechanical heat detector is intended for use in property protection applications,
or for non-life-safety installations where smoke detection is not practical or appropriate.
For life-safety installations, smoke detectors must
be used, in lieu of, or in addition to mechanical heat
detectors.
The 5600 series consists of both single- and dualcircuit heat detectors featuring fixed temperature
thermal sensors or combination fixed temperature/
rate-of-rise sensors, with temperature ratings of 135ºF
(57ºC) or 194ºF (90ºC).
Markings on the exterior of the detector indicate the
specific activation method and temperature rating. All
models are identified as either 135ºF/57ºC or 194ºF/
90ºC. Models equipped with combination fixed temperature/rate-of-rise sensors are marked FX/ROR.
Fixed temperature only models are marked FX.
Non-Resettable Fixed Temperature Sensor
The fixed temperature element reacts to heat by responding to a specific temperature setting (135ºF
or 194ºF). The detection method is based on the
spring action of a metal contact, held to the metal
chamber by a fusible alloy. When the temperature
reaches the alloy’s melting point, the metal contact
will depress the diaphragm, causing the electrical
contact to close the circuit. The circular external
heat collector is released from the detector to visually indicate that the detector has been activated.
NOTE: 5600 series Fixed Temperature models (5603,
5604, 5623, and 5624) are non-resettable, and cannot be tested.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
I56-2175-003R
D500-46-00 1 I56-2175-003R
Table 1. 5600 Series Mechanical Heat Detectors
Model
No.
Circuit
Temperature
Rating
Thermal Sensor
UL Maximum Spacing
(10-foot ceiling)
5601PSingle135ºF (57ºC)Fixed Temperature/Rate of Rise50-feet x 50-feet
5602Single194ºF (90ºC)Fixed Temperature/Rate of Rise50-feet x 50-feet
5603Single135ºF (57ºC)Fixed Temperature25-feet x 25-feet
5604Single194ºF (90ºC)Fixed Temperature25-feet x 25-feet
5621Dual135ºF (57ºC)Fixed Temperature/Rate of Rise50-feet x 50-feet
5622Dual194ºF (90ºC)Fixed Temperature/Rate of Rise50-feet x 50-feet
5623Dual135ºF (57ºC)Fixed Temperature25-feet x 25-feet
5624Dual194ºF (90ºC)Fixed Temperature25-feet x 25-feet
NOTE: Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.
FM Classification
RTI ratings are for installations which must comply with FM 3210.
Heat Detector TypeRTI Classification
Fixed 135°F RTI: SPECIAL
RoR and Fixed 135°F RTI: ULTRA FAST and SPECIAL (Respectively)
Fixed 194°F RTI: SPECIAL
RoR and Fixed 194°F RTI:ULTRA FAST and SPECIAL (Respectively)
Self-Restoring Rate-of-Rise (ROR) Sensor
The rate-of-rise element responds to a rapid rise of
temperature, approximately 15ºF (8.3ºC) per minute. As the temperature rises, the air within the
sealed chamber expands. Should the chamber air
expand faster than it can escape through the calibrated vent, the diaphragm is depressed, and the
electrical contact closes the circuit.
NOTE: Only the ROR element of 5600 series combination fixed temperature/ROR models (5601P,
5602, 5621, and 5622) are self-restoring, and may be
tested using a hair dryer or heat gun. When testing
the ROR element, to prevent the activation of the
fixed temperature element, the heat source must not
exceed the fixed temperature rating of the detector.
Figure 1. Bracket Mounting Locations:
A= 31⁄2˝ Octagonal box
B= 4˝ Octagonal box
C= Single gang box and 4˝
square with plaster ring
D= Directly to Wall/Ceiling
Mounting Bracket
All 5600 series detectors are equipped with a mounting bracket that includes mounting slots to accommodate single-gang, 3
1
⁄2˝ octagonal, and 4˝ octagonal
electrical boxes, as well as 4˝ square boxes equipped
with a plaster ring (Figure 1). The mounting bracket
is reversible to accommodate flush-mount and surface–mount installations (Figure 2).
Wiring Installation Guidelines
All wiring must be installed in compliance with the
National Electrical Code, applicable state and local
codes, and any special requirements of the local
Authority Having Jurisdiction. Proper wire gauges
should be used. The conductors used to connect
heat detectors to the alarm control panel and accessory devices should be color-coded to reduce the
Figure 2. Reversible Mounting Bracket:
Surface–mount
S0114-00
Flush–mount
S0113-00
S0115-00
D500-46-00 2 I56-2175-003R
likelihood of wiring errors. Improper connections
Control
Control
can prevent a system from responding properly in
the event of a fire.
The non-polarized screw terminals on the back of
the detector will accept 14–22 AWG wire. For best
system performance, all wiring should be installed
in separate grounded conduit; do not mix fire alarm
system wiring in the same conduit as any other
electrical wiring. Twisted pair may be used to provide additional protection against extraneous electrical interference.
Wire connections are made by stripping approximately 1⁄4˝ of the insulation from the end of the feed
wire, inserting it into the proper base terminal, and
tightening the screw to secure the wire in place.
Figure 3. Wiring Diagram – Single Circuit Models:
Panel
+
EOL
–
OR
Installation
Remove power from the alarm control unit or initiating device circuits before installing detectors.
1. Detach the detector from the mounting bracket by
rotating the detector 1⁄4 turn counter-clockwise.
2. Orient the mounting bracket properly for either a
flush- or surface-mount installation (Figure 2).
3. Select the pair of mounting holes suitable for the
junction box, (Figure 1) and secure the bracket
to the box.
4. Connect the wires to the detector per Figure 3 or
Figure 4, as applicable.
5. Place the detector onto the mounting bracket by
rotating clockwise. The detector will lock into
place with a “click”.
6. After all detectors have been installed, apply
power to the alarm control unit.
7. Test each detector as described in Testing.
8. Reset all the detectors at the alarm control unit.
9. Notify the proper authorities that the system is
in operation.
Auxiliary
Device
S0239-00
Figure 4. Wiring Diagram – Dual Circuit Models:
Panel
+
Auxiliary
Device
Auxiliary
Device
–
OR
Auxiliary
Device
D500-46-00 3 I56-2175-003R
Auxiliary
Device
EOL
S0240-00
Testing/Maintenance
WARNING
WARNING
The rate-of-rise mechanism may be subject to reduced sensitivity over time. Annual testing of the
rate-of-rise operation is therefore recommended.
Before testing, notify the proper authorities that
When testing the ROR element, to prevent the activation of the fixed temperature element, the heat
source must not exceed the fixed temperature rating
of the detector.
maintenance is being performed and the system will
be temporarily out of service. Disable the zone or
system undergoing maintenance to prevent any unwanted alarms.
Only the ROR element of 5600 series combination
fixed temperature/ROR models (5601P, 5602, 5621,
and 5622) are self-restoring, and may be tested using a hair dryer or heat gun.
5600 series fixed temperature models (5603, 5604,
5623, and 5624) are non-resettable, and cannot
be tested.
CAUTION
When using the RRS-MOD with model 2WTA-B, do
not mix the 2WTA-B with other model smoke detectors and dry contact closure devices, including
mechanical heat detectors, manual pull stations and
waterflow switches. Such mixing can cause a direct
short on the auxiliary power terminals, damaging
the control panel’s internal circuitry and/or damage
devices connected to the initiating device circuit.
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
Syst em S ensor wa rran ts i ts enclosed product to be
free from defec ts in mater ials and workma nship under
normal use and se rvice for a pe riod of three years from
date of manuf acture. System Sens or make s no other
express warranty for the encl osed prod uct. No ag ent,
representative, dealer, or emp loyee of th e Com pany
has the authority to increas e or alter the ob ligatio ns or
limitations of t his Warranty. The Compa ny’s obligati on
of this Warra nty shall b e limit ed to t he replacement of
any par t of th e product which is found to be defective in material s or work manship under normal use
and s ervice during t he three yea r period co mmencin g
with the date of manufa cture. After phoning System
Sensor’s t oll fre e n umber 800-SENS OR2 (736-7672)
for a Retu rn Authorizatio n number, se nd defective
uni ts pos tage prepai d to: System Sensor, Returns
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device
may not cause harmful interference, and (2) this device must accept any interference received, including interference that
may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Department, RA #______ ____, 3825 Ohio Avenue, St.
Charles, IL 60174. Pleas e include a note descri bing
the ma lfunction and sus pected cau se of failure. The
Company sha ll n ot b e ob ligated to replace units which
are found to be defe ctive because of dam age, unre asonable use, modifi cations, or alt erations occurring
after the date of manufacture. In no case shall the
Company be liable for any consequen tial or in cidental
damages for brea ch of this or any other Warranty, expressed or implie d whatsoever, even if the lo ss or damage is cau sed by the Comp any’s negligenc e or fa ult.
Some st ates do not allow the exclusion or limi tation
of incidenta l or conse quential damages, so the above
limitation or exclusi on may not appl y to you. This
Warran ty gives you sp ecific legal rights, and you may
also have o ther righ ts which vary fro m state to state.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.