System Sensor 546-7000 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
Cover Tamper Switch
Specifications
Contact Ratings: 5.0A @ 125/250 VAC
2.5A @ 24 VDC
Overall Dimensions: 11/4˝H x 2˝W x 3/4˝D Operating Temperature Range: 32° to 120°F (0° to 49°C) Shipping Weight: 0.025 lb.
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTICE: This manual should be left with the owner/user of this equipment.
Do not leave unused wires exposed. Do not use in poten­tially explosive atmospheres.
General Information
This cover tamper switch mounts to all System Sensor WFD, WFDT, OSY2 and PIBV2 terminal block units. Cover removal produces a switch output. The unit will reset when the product cover is reinstalled.
Installation Guidelines
Before installing any cover tamper switch, be thoroughly familiar with:
Figure 1. Assembly Diagram:
NFPA 72: National Fire Alarm Code NFPA 13: Installation of Sprinkler Systems, specifically
section 3.17.
NFPA 25: Inspection, Testing and Maintenance of Sprin-
kler Systems, specifically chapters 4 and 5. Other applicable NFPA standards, local codes and the re­quirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the device to report an alarm or trouble condition. System Sen­sor is not responsible for devices that have been improperly installed, tested or maintained.
Mounting Instructions
1. Install switch mounting bracket onto terminal block us-
ing the 2 screws provided, shown in Figure 1.
2. Snap the switch onto the switch mounting bracket in po-
sition shown in Figure 1.
A78-1661-00
D770-05-00 1 I56-403-03
WARNING
High voltage. Electrocution hazard. Do not handle live AC wiring or work on a device to which AC power is applied. Doing so may result in severe injury of death.
Field Wiring
1) Wire as required per wiring diagram (Figure 2), placing the stripped wire lead under the correct terminal plate. Extra wire lead should be clipped and terminated with a wire nut to avoid shorting to housing.
Figure 2. Field Wiring:
Blue
Wire Nut
to nonsilenceable initiating zone of listed FACP
Red
COM COM
NC NO COM
BB
Typical Fire Alarm Control Panel Connection
Red
Wire Nut
BlackBlueBlack
COM COM
BB
AAAA
NC NO COM
NOTE: Where one wire already exists under the terminal
plate, connect the cover tamper wire under the op­posite side of the terminal plate.
2) When connected to a listed sprinkler/fire alarm control panel, the initiating circuit must be non-silenceable.
Wire Code:
Cover Tamper Switch:
(Non Alarm Condition)
(Cover Off)
end-of-line resistor
Waterflow or Supervisory Switch:
Com to B = Open Circuit Com to A = Closed Circuit
Black / Blue: Open Black / Red: Closed
Cover Tamper Switch
to power source compatible with bell
NC NO
COM
Red
B
Blue
Black
A
COM
Wire Nut
local
bell
Break wire as shown for supervision of connection. DO NOT allow stripped wire leads to extend beyond switch housing. DO NOT loop wires.
Typical Local Bell Connection
NOTE:
A78-1662-01
Local bell will activate when cover is removed.
Operational Testing
Always notify a central station monitoring waterflow or su­pervisory switch alarms before repairing, maintaining, or testing cover tamper switch devices.
Three-Year Limited Warranty
System Sensor warrants its enclosed cover tamper switch to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this cover tamper switch. No agent, representa­tive, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obli­gation of this Warranty shall be limited to the repair or replacement of any part of the cover tamper switch which is found to be defective in materials or workmanship under normal use and service during the three year pe­riod commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori­zation number, send defective units postage prepaid to: System Sensor,
D770-05-00 2 I56-403-03
1) Replace the cover and tighten the security screws with the security wrench. Store the wrench in a secure place.
2) Verify that circuit has reset by checking FACP.
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negli­gence or fault. Some states do not allow the exclusion or limitation of inci­dental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
© System Sensor 1996
Loading...