System Sensor 4WT-B, 2WT-B, 4W-B User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
Photoelectric Smoke Detector
Models: 2W-B, 2WT-B
4W-B, 4WT-B
Before Installing
Please read thoroughly System Sensor manual A05-1003, Applications Guide for System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wir ing, and special applications. Copies of this manual are available from System Sensor at no charge.
NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regu­larly following NFPA 72 requirements. At a minimum, cleaning should be performed annually.
General Description
Models 2W-B and 2WT-B are 2-wire photoelectric smoke detec tors; models 4W-B and 4WT-B are 4-wire photoelectric smoke detectors. All models incorporate a state-of-the-art optical sensing chamber and an advanced microprocessor. The microprocessor allows the detector to automatically adjust its sensitivity back to the factory setting when it becomes more sensitive due to contaminants settling in its chamber. In order for this feature to work properly, the chamber must never be opened while power is applied to the smoke detector. This includes cleaning, maintenance or screen replacement. Should it become necessary, the screen/sensing chamber is field replaceable. Models 2WT-B and 4WT-B also feature a restorable, built-in, fixed temperature (135°F) thermal detector and are also capable of sensing a freeze condition if the temperature is below 41°F.
3
All i
Series detectors are designed to provide open area protec­tion. Two-wire models must be used with compatible UL Listed panels only.
When used with an i Series 2W-MOD module (refer to installation manual D500-46-00), the 2W-B and 2WT-B are capable of generating a “maintenance needed” signal. The 2W-MOD can indicate a need for cleaning, replacement, or a freeze condition (2WT-B only) at the control panel or module.
Installation of the 2W-B, 2WT-B, 4W-B, and 4WT-B detectors is simplified by the use of a mounting base that may be pre-wired to the system, allowing the detector to be easily installed or removed. The mounting base installation is further simplified by the incorporation of features compatible with drywall fasteners.
3
Series compatible control panel or the i
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Two LEDs on the detector provide a local visual indication of the detector’s status:
-
Table 1: Detector LED Modes
Green LED Red LED Power-up Blink 10 sec Blink 10 sec Normal (standby) Blink 5 sec Out of sensitivity Freeze Trouble
Blink 5 sec
Blink 10 sec
Alarm Solid
After an initial power-up delay, the red and green LEDs will blink synchronously once every ten seconds. It will take approximately 80 seconds for the detector to finish the power-up cycle (see Table 2).
-
Table 2: Power-up Sequence for LED Status Indication*
Condition Duration Initial LED Status Indication 80 seconds Initial LED Status Indication
4 minutes
(if excessive electrical noise is present)
*Refer to Electrical Specifications for start-up time in conjunction with panel alarm verification.
NOTE: If, during power-up, the detector determines there is excessive electrical noise in the system such as those caused by improper grounding of the system or the conduit, both LEDs will blink for up to 4 minutes before displaying detector status (see Table 2).
After power-up has completed and the detector is functioning normally within its listed sensitivity range, the green LED blinks once every five seconds. If the detector is in need of maintenance because its sensitivity has shifted outside the listed limits, the red
3
LED blinks once every five seconds. When the detector is in the alarm mode, the red LED latches on. The LED indication must not be used in lieu of the tests specified under
Testing. In a freeze
trouble condition, the red LED will blink once every 10 seconds (refer to Table 1).
To measure the detector’s sensitivity, the i
3
Series Model SENS­RDR Infrared Sensitivity Reader tool (see Figure 4) should be used.
Models 2W-B and 2WT-B also include an output that allows an optional Model RA400Z Remote Annunciator to be connected.
Mounting
3
Each i
Series detector is supplied with a mounting base that can
be mounted:
1. To a single gang box, or
2. To a 3
1
2-inch or 4-inch octagonal box, or
3. To a 4-inch square box with a plaster ring, or
4. Direct mount or to ceiling using drywall fasteners (Figure 2).
D100-96-00 1 I56-1800-08R
Figure 1: Mounting of Detector
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code, applicable state and local codes, and any special requirements of the local Authority Having Jurisdiction.
S0121-00
The i3Series heads and bases are keyed so that a 2-wire head will only mount to a 2-wire base, and a 4-wire head will only mount to a 4-wire base. The heads and bases are clearly identified as either 2-wire or 4-wire. When mounting the i
3
Series, ensure that
the head is mounted to the correct base.
Tamper-Resistant Feature
3
The i
Series detectors include a tamper-resistant feature that prevents removal from the mounting base without the use of a tool. To engage the tamper-resistant feature, cut the small plastic tab located on the mounting base (Figure 2), and then install the detector. To remove the detector from the base once it has been made tamper resistant, use a small screwdriver to depress the square tamper release tab, located on the skirt of the mounting base, and turn the detector counterclockwise.
Figure 2: Tamper-Resistant Feature
DIRECT MOUNT HOLES
Proper wire gauges should be used. The conductors used to con nect smoke detectors to the alarm control panel and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from respond ing properly in the event of a fire.
The screw terminals in the mounting base will accept 14–22 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit; do not mix fire alarm system wiring in the same conduit as any other electrical wiring. Twisted pair may be used to provide additional protection against extraneous electrical interference.
Wire connections are made by stripping approximately
1
4-inch of insulation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire in place.
Two-Wire Compatibility
System Sensor two-wire smoke detectors are marked with a compatibility identifier located on the label on the back of the product. For two-wire models 2W-B and 2WT-B, connect detectors only to compatible alarm control panels as identified by System Sensor’s compatibility chart. This chart contains the current list of detectors and UL Listed compatible control units. A copy of this list is available from System Sensor upon request.
-
-
SNAP OFF TAB FOR TAMPER LOCK
TAMPER RELEASE TAB
S0226-00
Do NOT Install Detectors in the Following Areas:
• In or near areas where particles of combustion are normally present such as kitchens; in garages (vehicle exhaust); near furnaces, hot water heaters, or gas space heaters.
• In very cold or very hot areas.
• In wet or excessively humid areas, or next to bathrooms with showers.
• In dusty, dirty, or insect-infested areas.
• Near fresh air inlets or returns or excessively drafty areas. Air conditioners, heaters, fans, and fresh air intakes and returns can drive smoke away from the detector.
Consult NFPA 72, the local Authority Having Jurisdiction (AHJ), and/or applicable codes for specific information regarding the spacing and placement of smoke detectors.
CAUTION
Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose.
Wiring Diagrams Figure 3a: Wiring Diagram, 2W-B and 2WT-B
+
2-WIRE ZONE
RA400Z
(
(
(
(
2-WIRE CONTROL PANEL
( 1 ) + IN
3
2
)
)
– IN/OUT
+ OUT
2W-B or 2WT-B
5
4
)
)
RA –
RA +
( 1 ) + IN
( 2 ) + OUT
2W-B or 2WT-B
Figure 3b: Wiring Diagram, 4W-B and 4WT-B
AUX OR
+
SMOKE
POWER
IDC
+
(
(
(
4-WIRE CONTROL PANEL
( 1 ) + IN
(
3
2
)
)
– IN/OUT
+ OUT
4W-B or 4WT-B
5
4
)
)
COM
NO
( 1 ) + IN
( 2 ) + OUT
4W-B or 4WT-B
(
(
4
3
)
)
RA +
– IN/OUT
(
(
4
3
)
)
NO
– IN/OUT
RA400Z
( 5 ) RA –
( 5 ) COM
EOL RESISTOR
EOL RELAY (
A77-716B
EOL RESISTOR
S0133-00
)
S0134-00
D100-96-00 2 I56-1800-08R
Loading...
+ 2 hidden pages