INSTALLATION AND MAINTENANCE INSTRUCTIONS
4451HT and 4451HTA
I56-0690-005R
Plug-in Fixed Intermediate
Temperature Thermal Detectors
Specifications
Diameter: 4.1 inches (104 mm)
Height: 2.1 inches (53 mm)
Weight: 5 ounces (150 g)
Installation Temperatures: 32° to 150°F (0° to 66°C)
Operating Humidity Range: 10% to 93% Relative Humidity
Latching Alarm: Reset by momentary power interruption
Sensitivity: 190°F (88°C)
Operating Voltage: 15-35 VDC
Standby Current: 100 µA
Before Installing
This detector must be installed in compliance with the control panel installation manual and meet the requirements of
the authority having jurisdiction. In addition, the National
Fire Protection Association has published codes, standards,
and recommended practices for the installation and use of the
above appliances (NFPA 72). For installation in Canada, refer
to CAN/ULC-S524 and CEC Part 1, Sec. 32. Therefore, the installer must be familiar with these requirements, with local
codes, and any special requirements of the authority having
jurisdiction.
NOTICE: This manual should be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained
regularly following NFPA 72 requirements. The detector should
be cleaned at least once a year.
General Description
The 4451HT and 4451HTA detectors are fixed intermediate
temperature alarm thermal detectors utilizing a state-of-the-art
dual thermistor sensing circuit. These detectors are designed
to provide open area protection with 50-foot spacing capabil-
ity, and are to be used with compatible control panels only.
This listed spacing is based on a 10′ ceiling height and should
be reduced based on the table in Figure 1 for ceilings higher
than 10′.
Two LEDs on each detector light to provide 360° visibility of
the detector indication. Remote LED annunciator capability is
provided as standard, and the RA400Z remote LED annunciator is available as an optional accessory.
Base Selection And Wiring Guide
Refer to the installation instructions for the plug-in detector
bases for base selection and wiring instructions. System Sensor has available a variety of detector bases for these heat detectors, including 2-wire applications with and without relays
and/or current limiting resistors for use with control panels
that require one. These detectors are only to be used with 400
and 400B series bases.
Install the System Sensor plug-in base to be used with the
detector following the instructions in the base manual.
Installation
NOTE: All wiring must conform to applicable installation
codes and regulations.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Figure 1. Heat detector spacing reduction based on ceiling height:
Ceiling Height Above Up To And Including
(ft) (m) (ft) (m)
0 0 10 3.05 100
10 3.05 12 3.66 91
12 3.66 14 4.27 84
14 4.27 16 4.88 77
16 4.88 18 5.49 71
18 5.49 20 6.10 64
20 6.10 22 6.71 58
22 6.71 24 7.32 52
24 7.32 26 7.93 46
26 7.93 28 8.54 40
28 8.54 30 9.14 34
D400-54-00 1 I56-0690-005R
Percent Of Listed Spacing
NOTE: Verify that all detector bases are installed, that the ini-
TEST
MAGNET
LED
TEST MODULE
SOCKET
LED
tiating-device circuits have been tested, and that the wiring is
correct. (Refer to detector base manual for testing procedure.)
Disconnect the power from initiating-device circuits before installing detectors.
1. Install Detectors:
a. Insert the detector into the detector base.
b. Turn the detector clockwise until the detector drops
into place.
c. Continue turning detector clockwise to lock it in place.
Tamper-Resistance Feature
The detector bases include a feature that, when activated, prevents removal of the detector without the use of a tool. Refer
to the installation instruction manual of the detector base to
make use of this capability.
2. After all detectors have been installed, apply power to the
control unit.
3. Test the detector using the magnet as described under TESTING.
4. Reset the detector at the system control panel.
5. Notify the proper authorities the system is in operation.
Testing
Before testing, notify the proper authorities that the heat detector system is undergoing maintenance, and therefore the
system will temporarily be out of service. Disable the zone or
system undergoing maintenance to prevent unwanted alarms.
Detectors must be tested after installation and periodic maintenance. Test the detector as follows:
A. Test Magnet (System Sensor Model M02-04)
1. Position the magnet against the cover opposite the test
module socket. (See Figure 2.)
2. The LEDs on the detector should light within 10 sec-
onds. If the LEDs fail to light, check the power to the
detector and the wiring in the detector base.
3. Reset the detector at the system control panel.
B. Test Module (System Sensor Model MOD400R)
The MOD400R is used with a DMM or voltmeter to check the
detector sensitivity as described in the module’s manual.
C. Direct Heat Method (Heat Gun)
1. From the side of the detector, direct the heat toward
the sensor. Hold the heat source about 15 cm away to
prevent damage to the cover during testing.
Avoid exposing the detector cover to the heat source for more
than 15 seconds. Extended periods of extreme heat can melt
the plastic and damage the cover.
NOTE: If a detector goes into alarm, it will reset only if the detector has cooled and if its power is momentarily interrupted.
Check the control panel being used to determine whether the
RESET switch (or some other auxiliary device or control) momentarily cuts off power to the detector loop.
Detectors that fail these tests should be cleaned as described
under MAINTENANCE and retested. If the detectors still fail
these tests they should be returned for repair.
Maintenance
The 4451HT and 4451HTA detectors have been designed to be
as maintenance-free as possible. Normal air-borne dust, however, can accumulate on the detector’s sensing elements and
cause them to become less sensitive. All detectors should be
tested and cleaned at least once a year, and those in dustier
areas should be tested and cleaned more often. Detectors must
also be cleaned and tested immediately after a fire.
Before cleaning, notify the proper authorities that the system
is undergoing maintenance and therefore the system will temporarily be out of service. Disable the loop or system undergoing maintenance to prevent unwanted alarms.
1. Remove detector from mounting base.
2. Use a vacuum cleaner to remove dust from the
sensing chamber.
3. Reinstall the detector.
4. Test the detector as described under TESTING.
Figure 2. Test magnet position:
C0957-00
System Sensor warrants its enclosed heat detector to be free from defects in materials
and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this heat detec
tor. No agent, representative, dealer, or employee of the Company has the authority
to increase or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or replacement of any part
of the heat detector which is found to be defective in materials or workmanship
under normal use and service during the three year period commencing with the
date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2
(736-7672) for a Return Authorization number, send defective units postage prepaid
to: System Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St.
D400-54-00 2 I56-0690-005R
©2007 System Sensor
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
Charles, IL 60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace units which
-
are found to be defective because of damage, unreasonable use, modifications, or
alterations occurring after the date of manufacture. In no case shall the Company
be liable for any consequential or incidental damages for breach of this or any other
Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limita
tion of incidental or consequential damages, so the above limitation or exclusion
may not apply to you. This Warranty gives you specific legal rights, and you may
also have other rights which vary from state to state.
-