System Sensor 2W-MOD2 User Manual

WARNING
Condition Maintenance relay (form C) Alarm relay (form A) Loop trouble relay (form A)
Normal OFF Open Close Loop trouble OFF Open Open Maintenance/Freeze trouble ON Open Close Loop trouble and ON Open Open
Maintenance/Freeze trouble Alarm OFF Close N/A Alarm and loop trouble OFF Close N/A Alarm and Maintenance/Freeze OFF Close N/A
trouble Terminal Location T e rminal 7 – N.O. Relay connected Relay connected between
Terminal 8 – Common between terminals terminals 10 and 12 Terminal 9 – N.C. 10 and 1 1
Green LED
Red LED
Y e llow LED
EZ Walk-Test Pushbutton
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Series
Loop Test/Maintenance Module
Model: 2W-MOD2
I56-2174-004
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing
This information is included as a quick reference installa­tion guide. Refer to the control panel installation manual for detailed system information. If the modules will be in­stalled in an existing operational system, inform the opera­tor and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual shall be left with the owner/user of this equipment.
General Description
The 2W-MOD2 allows a control panel to receive a “need for maintenance” signal from two–wire i3 series smoke detec­tors, model numbers 2W–B, 2WT–B, 2WTA–B, and 2WTR–B. The module uses a form C zone relay to initiate “out of sen­sitivity” and “freeze trouble”, a form A zone alarm relay and a second form A zone relay to indicate loop fault (see Figure
1). An EZ Walk Test puts all detectors on the loop into a Walk Test mode for easy verification of detector loop wiring.
Figure 1:
NOTE: If two–wire i3 detectors are used in conjunction with a style D initiating circuit, the 2W–MOD2 must be used to provide that capability. Ground fault on a mod-
ule’s two-wire loop can be indicated at a control panel if the control panel is capable of ground fault detection on the power supply to the module and meets NFPA 72 ground fault indication requirements for initiating device circuits. The installer must verify that capability.
Figure 3. Module LED modes:
Figure 2. Module front view:
Three LED’s on the module provide a local visual indica­tion of the module status(es).
The maintenance module allows two-wire smoke detectors to be used on any electrically compatible four-wire control panel.
D500-46-00 1 I56-2174-004
S0236-00
S0218-00
The module has loop trouble restoration detection. If the loop trouble (open loop) doesn’t exist any more, the mod­ule will restore to standby condition with a maximum delay of 1 minute. There is no delay in loop trouble detection.
If an alarm occurs while the module is indicating mainte­nance, the alarm will supercede maintenance.
If the green LED remains ON (no blinking) three minutes af­ter applying power, it means that the module has determined that no detector on its loop has communication capability. In this condition, the detectors are still capable of initiating alarm and loop trouble at the module. However, maintenance and freeze trouble, will not be indicated at the module, and EZ walk test will not be available. If i3 detectors are installed on the loop, verify wiring and system operation.
Control Panel
2W-MOD2
Aux. or Smoke Power
Fire Zone
Trouble Zone
Panel EOL
Panel EOL
12
11
10
9
8 7
1
2
3
4
5 6
Loop Style D wiring
3.9 K EOL (must not be used for Style D)
A2143-10
+
+
Two-wire listed smoke detectors. Do not mix models on the same loop.
Only one 2WTR–B per loop. Only one 2WTA–B per loop,
unless used with the RRS–MOD.
ALL CIRCUITS ARE SUPERVISED AND MUST BE POWER LIMITED.
Control Panel
2W-MOD2
Aux. or Smoke Power
Fire Zone
Panel EOL
12
11
10
9
8 7
1
2
3
4
5 6
+
Loop Style D wiring
ALL CIRCUITS ARE SUPERVISED AND MUST BE POWER LIMITED.
Two-wire listed smoke detectors. Do not mix models on the same loop.
Only one 2WTR–B per loop. Only one 2WTA–B per loop,
unless used with the RRS–MOD.
3.9 K EOL (must not be used for Style D)
A2143-10
+
Control Panel
2W-MOD2
Aux. or Smoke Power
Fire Zone
12
11
10
9
8 7
1
2
3
4
5 6
+
Panel EOL
Loop Style D wiring
3.9 K EOL (must not be used for Style D)
A2143-10
+
Two-wire listed smoke detectors. Do not mix models on the same loop.
Only one 2WTR–B per loop. Only one 2WTA–B per loop,
unless used with the RRS–MOD.
ALL CIRCUITS ARE SUPERVISED AND MUST BE POWER LIMITED.
For NFPA loop Style D wiring the EOL resistor is provided internal to the module. An external EOL resistor must not be connected at the last detector on the loop (see Fig­ures 5 – 7).
Compatibility Requirements
The 2W-MOD2 is marked with a compatibility/zone identi­fier as the last digit of a 5 digit code on the back of the unit. To ensure proper operation, this module shall be connected to compatible two-wire smoke detectors or the alarm con­tacts of four–wire i3 series detectors only. (Consult System Sensor’s 2-wire compatibility guide).
Figure 4. Mounting module
Wiring Diagram
Install module wiring in accordance with appropriate wir­ing diagrams (Figures 5 - 7). Reset is performed through power inputs 1 and 2.
Figure 5. The Module Wiring: maintenance signal is sent to a separate zone.
S0232-01
Figure 6. The Module Wiring: maintenance signal is indicated at the panel as a fire trouble.
S0235-00
S0233-01
Figure 7. The Module Wiring: two-wire detectors to four-wire panel conversion.
S0238-00
S0237-00
Mounting
Install in a dry indoor location. The 2W-MOD2 Mainte­nance Module mounts directly to 4 inch square electrical boxes (supplied by installer). The box must have a mini­mum depth of 2 1/8 inches. Secure module to box as shown in Figure 4.
D500-46-00 2 I56-2174-004
S0234-01
Loading...
+ 2 hidden pages