System Sensor 2W-MOD2 User Manual

WARNING
Condition Maintenance relay (form C) Alarm relay (form A) Loop trouble relay (form A)
Normal OFF Open Close Loop trouble OFF Open Open Maintenance/Freeze trouble ON Open Close Loop trouble and ON Open Open
Maintenance/Freeze trouble Alarm OFF Close N/A Alarm and loop trouble OFF Close N/A Alarm and Maintenance/Freeze OFF Close N/A
trouble Terminal Location T e rminal 7 – N.O. Relay connected Relay connected between
Terminal 8 – Common between terminals terminals 10 and 12 Terminal 9 – N.C. 10 and 1 1
Green LED
Red LED
Y e llow LED
EZ Walk-Test Pushbutton
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Series
Loop Test/Maintenance Module
Model: 2W-MOD2
I56-2174-004
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Before Installing
This information is included as a quick reference installa­tion guide. Refer to the control panel installation manual for detailed system information. If the modules will be in­stalled in an existing operational system, inform the opera­tor and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual shall be left with the owner/user of this equipment.
General Description
The 2W-MOD2 allows a control panel to receive a “need for maintenance” signal from two–wire i3 series smoke detec­tors, model numbers 2W–B, 2WT–B, 2WTA–B, and 2WTR–B. The module uses a form C zone relay to initiate “out of sen­sitivity” and “freeze trouble”, a form A zone alarm relay and a second form A zone relay to indicate loop fault (see Figure
1). An EZ Walk Test puts all detectors on the loop into a Walk Test mode for easy verification of detector loop wiring.
Figure 1:
NOTE: If two–wire i3 detectors are used in conjunction with a style D initiating circuit, the 2W–MOD2 must be used to provide that capability. Ground fault on a mod-
ule’s two-wire loop can be indicated at a control panel if the control panel is capable of ground fault detection on the power supply to the module and meets NFPA 72 ground fault indication requirements for initiating device circuits. The installer must verify that capability.
Figure 3. Module LED modes:
Figure 2. Module front view:
Three LED’s on the module provide a local visual indica­tion of the module status(es).
The maintenance module allows two-wire smoke detectors to be used on any electrically compatible four-wire control panel.
D500-46-00 1 I56-2174-004
S0236-00
S0218-00
The module has loop trouble restoration detection. If the loop trouble (open loop) doesn’t exist any more, the mod­ule will restore to standby condition with a maximum delay of 1 minute. There is no delay in loop trouble detection.
If an alarm occurs while the module is indicating mainte­nance, the alarm will supercede maintenance.
If the green LED remains ON (no blinking) three minutes af­ter applying power, it means that the module has determined that no detector on its loop has communication capability. In this condition, the detectors are still capable of initiating alarm and loop trouble at the module. However, maintenance and freeze trouble, will not be indicated at the module, and EZ walk test will not be available. If i3 detectors are installed on the loop, verify wiring and system operation.
Control Panel
2W-MOD2
Aux. or Smoke Power
Fire Zone
Trouble Zone
Panel EOL
Panel EOL
12
11
10
9
8 7
1
2
3
4
5 6
Loop Style D wiring
3.9 K EOL (must not be used for Style D)
A2143-10
+
+
Two-wire listed smoke detectors. Do not mix models on the same loop.
Only one 2WTR–B per loop. Only one 2WTA–B per loop,
unless used with the RRS–MOD.
ALL CIRCUITS ARE SUPERVISED AND MUST BE POWER LIMITED.
Control Panel
2W-MOD2
Aux. or Smoke Power
Fire Zone
Panel EOL
12
11
10
9
8 7
1
2
3
4
5 6
+
Loop Style D wiring
ALL CIRCUITS ARE SUPERVISED AND MUST BE POWER LIMITED.
Two-wire listed smoke detectors. Do not mix models on the same loop.
Only one 2WTR–B per loop. Only one 2WTA–B per loop,
unless used with the RRS–MOD.
3.9 K EOL (must not be used for Style D)
A2143-10
+
Control Panel
2W-MOD2
Aux. or Smoke Power
Fire Zone
12
11
10
9
8 7
1
2
3
4
5 6
+
Panel EOL
Loop Style D wiring
3.9 K EOL (must not be used for Style D)
A2143-10
+
Two-wire listed smoke detectors. Do not mix models on the same loop.
Only one 2WTR–B per loop. Only one 2WTA–B per loop,
unless used with the RRS–MOD.
ALL CIRCUITS ARE SUPERVISED AND MUST BE POWER LIMITED.
For NFPA loop Style D wiring the EOL resistor is provided internal to the module. An external EOL resistor must not be connected at the last detector on the loop (see Fig­ures 5 – 7).
Compatibility Requirements
The 2W-MOD2 is marked with a compatibility/zone identi­fier as the last digit of a 5 digit code on the back of the unit. To ensure proper operation, this module shall be connected to compatible two-wire smoke detectors or the alarm con­tacts of four–wire i3 series detectors only. (Consult System Sensor’s 2-wire compatibility guide).
Figure 4. Mounting module
Wiring Diagram
Install module wiring in accordance with appropriate wir­ing diagrams (Figures 5 - 7). Reset is performed through power inputs 1 and 2.
Figure 5. The Module Wiring: maintenance signal is sent to a separate zone.
S0232-01
Figure 6. The Module Wiring: maintenance signal is indicated at the panel as a fire trouble.
S0235-00
S0233-01
Figure 7. The Module Wiring: two-wire detectors to four-wire panel conversion.
S0238-00
S0237-00
Mounting
Install in a dry indoor location. The 2W-MOD2 Mainte­nance Module mounts directly to 4 inch square electrical boxes (supplied by installer). The box must have a mini­mum depth of 2 1/8 inches. Secure module to box as shown in Figure 4.
D500-46-00 2 I56-2174-004
S0234-01
CAUTION
WARNING
Wiring Installation Guidelines
WARNING
All wiring must be installed in compliance with the Na­tional Electrical Code, applicable state and local codes, and any special requirements of the local authority having ju­risdiction (AHJ).
Proper wire gauges should be used. The conductors used to connect the module to the alarm control panel, smoke detectors and accessory devices should be color-coded to reduce the likelihood of wiring errors. Improper connec­tions can prevent a system from responding properly in the event of a fire.
The screw terminals in the mounting base will accept 14-24 gauge wire. For best system performance, all wiring should be installed in separate grounded conduit; do not mix fire alarm system wiring in the same conduit as any other elec­trical wiring. Twisted pair may be used to provide addi­tional protection against extraneous electrical interference.
Wire connections are made by stripping about 1/4 inch of insulation from the end of the feed wire, inserting it into the proper terminal, and tightening the screw to secure the wire in place.
Installation
Remove power from alarm control unit or initiating device circuits before installing modules.
After all modules have been installed, notify the proper au­thorities that the system is in operation.
Testing
NOTE: Before testing, notify the proper authorities that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system un­dergoing maintenance to prevent any unwanted alarms.
Modules must be tested after installation and following pe­riodic maintenance. Testing should be performed at least once a year.
Timing at Power-Up or Reset
Two minutes after power-up, the module will check for communication, high maintenance, low maintenance, and freeze trouble with each communication spaced 1 minute apart. If a valid response to the communication check is received, the module will check for freeze trouble every 4 hours, low and high maintenance every 24 hours, and will recheck communication every 24 hours. Whenever the module fails to receive a valid response to the communica­tion checks, it will verify the result with another commu­nication check one minute later. If it still fails to receive a valid response, the module will cease to communicate until a valid reset from the panel. In this mode, the module is still
able to detect alarm and wiring fault from the 2-wire loop. NOTE: If an alarm occurs on the 2W-MOD2 zone before
the 2W–MOD2 has completed its power–up sequence, the module’s green LED will remain on. To reset this condition, the system must be reset and the module must be allowed to complete its power–up sequence.
When using the RRS-MOD with model 2WTA-B, do not mix the 2WTA-B with other model smoke detectors and dry con­tact closure devices, including mechanical heat detectors, manual pull stations and waterflow switches. Such mixing can cause a direct short on the auxiliary power terminals, damaging the control panel’s internal circuitry and/or dam­age devices connected to the initiating device circuit.
EZ Walk Test
The 2W-MOD2 has a push button for EZ Walk Test mode (see Figure 2.). The EZ Walk Test feature is available 6 min­utes after power-up or panel reset. If the push button is pressed momentarily the module will activate EZ Walk Test for five minutes. All detectors on the loop should enter EZ Walk Test mode. See i3 detector manual for detector re­sponse in EZ Walk Test mode.
NOTE: EZ Walk Test cannot be initiated if the Green LED is not blinking.
If the 2W-MOD2 is in normal condition (Green LED blink­ing) and pressing the push button does not initiate EZ Walk Test, wait one minute and try again.
At the end of the five minute period, the module will ter­minate EZ Walk Test and the yellow LED will stop blink­ing. The EZ Walk Test period can be extended by pressing the push button a multiple number of times. For example, pressing the push button N times will result in a Walk Test duration of 5*N minutes.
If an alarm occurs during EZ Walk Test, the alarm condition will supercede EZ Walk Test (alarm is the highest priority).
The EZ Walk Test shall not be used in lieu of functional test­ing (alarm, trouble and other functional tests) of the system.
If a module or detector fails the test, its wiring should be checked. If the module still fails, it should be replaced.
Notify the proper authorities when the system is back in service.
D500-46-00 3 I56-2174-004
Specifications:
Electrical Mechanical
Supply Voltage - Min. 8.5 Volts (Power limited) Height: 4.5 inches Max. 30 Volts (Power limited) Width: 4.0 inches Max.Ripple Voltage: 30% of applied voltage Depth: 1.25 inches Max. Standby Current: 30mA (12 detectors on loop) Weight: 0.5 pound Max. Alarm Current: 90mA (Includes packaging Alarm Contact Ratings: 0.5 Amp @ 36 V DC, Resistive materials)
Maintenance Contact Ratings: 2 Amp @ 30 V DC, Resistive Min. Reset Voltage: 6 Volts Min. Reset Time: 0.3 sec. Operating Temperature Range: 14°F to 122°F (-10°C to 50 °C) Operating Humidity Range: 0 to 95% RH non-condensing Storage Temperature Range: –4°F to 158°F (–20°C to 70 °C) Initial Communication Cycle: 2-6 minutes after power-up or panel reset EZ Walk Test Available: 6 minutes after power-up or panel reset
2-wire compatibility
Min. loop voltage: 10 Volts Max. loop voltage: 11.5 Volts Max. loop resistance: 50 ohm Max. loop ripple: 1 Vpp Max. Loading Capacitance: 0.01 mF Max. Alarm current: 40 mA Max. Reset Voltage: 0.3 V Alarm Delay: No Min. Alarm reset time: 0.3 sec. Max. normal load current: 1.25 mA Zone Type: Standard EOL Device: 3.9 KΩ (0.25W, 5%) Loop style: B, D Compatibility/Zone identifier: A Max. detectors per zone: Models 2W–B and 2WT–B: 12 Model 2WTR–B: 1 Model 2WTA–B: 1 NOTE: When used with the RRS–MOD reversal relay/synchroniza-
tion module and the 2W–MOD2, a maximum of 12 2WTA–B detec­tors are allowed per zone.
Three-Year Limited Warranty
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obliga­tion of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workman­ship under normal use and service during the three year period com­mencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to pro­vide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
D500-46-00 4 I56-2174-004 ©2006 System Sensor
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modi­fications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limita­tion of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Loading...