Systemair WQL 20-190, WQH 20-190, WQRC 20-190 User Manual

Chiller
WQL/WQH/WQRC 20-190
Water Cooled Water Chillers Cooling Only, Heat Pump and Condenserless Versions Engineering Data Manual
21 to 193 kW
24 to 212 kW
Key point
14 sizes from 20 kW up to 190 kW
R410A refrigerant circuit with single or tandem Scroll compressors
2 different frames/configurations : 1 compressor/1 circuit up to 45 kW and
2 compressors/1 circuit from 50 kW to 190 kW
Reduced refrigerant charge (less than 10 kg per circuit for units up to size
90 kW)
New electronic controller with auto-adaptive function to reduce water
content in the piping system
WQL-WQH-WQRC 20-190
|
Condensing pressure control available as option for well application
Wide range of hydrokit for "Plug and Play" units
DHW (Domestic Hot Water) function available on the controller with 3-way
valve available as accessory
Victaulic joints for all internal water piping connections
Desuperheater heat exchanger available as option (50-190 sizes)
Sizes from 20 kW to 45 kW
with factory mounted hydrokit
Sizes from 50 kW to 190 kW
with factory mounted hydrokit
Sizes from 50 kW to 190 kW
without hydrokit
|
WQL-WQH-WQRC 20-190
Specifications
General
WQL/WQH/WQRC are new water to water units equipped with Scroll
compressors, optimized to work with R410A refrigerant.
3 different versions are available :
Cooling only units WQL
Heat pump units WQH
Remote condenser units WQRC
2 different acoustic options are available :
Standard (STD) : units are supplied with compressors box to reduce
noise emissions
Super Low Noise (S) : units are supplied with compressors box and
additional insulation panels on the cabinet in order to furtherly reduce noise impact
WQL/WQH/WQRC units are available in totally 14 sizes (20, 25, 30, 35, 40,
45, 50, 60, 75, 90, 120, 150, 170, 190), ranging from 20 to 190 kW in cooling operation and from 25 to 210 kW in heating operation.
WQL/WQH/WQRC units are available on two different structural frames
(F1 for 20-45 sizes, F2 for 50-190 sizes). Each unit is equipped with single refrigerant circuit, single hermetic scroll compressor for F1 sizes, and two hermetic scroll compressors (tandem) for F2 sizes.
Evaporators and condensers are brazed plate heat exchanger type.
Heat pump units (WQH) are equipped with reversible valve, thus allowing to reverse cycle on refrigerant side and not on water side.
Remote condenser units (WQRC) are not equipped with condenser heat exchangers, but equipped with stop valves on discharge and liquid lines in order to allow connection to remote condensers.
Cabinet and structure
Cabinet and structure are made of galvanized steel. All galvanized steel components are individually painted by a special painting process before assemblying of the unit. This painting system performs a homogeneous protection to the corrosion. The painting is a polyester powder based type, coloured in RAL 9001. The units are suitable for indoor installation.
Refrigerant circuit
Refrigerant circuit is equipped with one or two hermetic scroll compressors (depending on the frame), sight glass, filter-drier and mechanical expansion valve (electronic expansion valve is available as an option).
Heat pump units (WQH) refrigerant circuit is also provided with 4-way reversing valve and check valves system in order to always run liquid line in the same direction (both in cooling and in heating mode).
Remote condenser units (WQRC) refrigerant circuit is supplied without condenser and it is provided with liquid receiver, stop valves both on discharge and liquid lines, solenoid valve on liquid line.
The functional diagram of each circuit is shown in section "Refrigerant flow diagram".
Compressors
Compressors are hermetic scroll type fitted with an electronic control device ensuring protection of compressors against :
Overheating
Overloading
Reversal rotation
Phase loss
All compressors have direct-on-line starting and are mounted on rubber vibration isolators in order to minimize noise and vibration transmission.
Evaporators and condensers
Evaporator and condenser heat exchangers are brazed stainless steel plate type. They are insulated with a 10 mm thick closed cell polyethylene foam material and provide with Victaulic connections.
Electrical board
Electric equipment is built in compliance with CE standards. Easy accessible in front of the unit - through an access panel fixed with screws - the equipment is complete with :
Door lock main isolating switch
Compressor contactors and fuses
Compressor overload protection (optional only on F2 units)
Automatic circuit breaker switches (Standard on F1 units, optional on F2
units)
Phase sequence control
Clamps for remote start/stop switch
Clamps for remote summer/winter switch
Clamps for external flow switches (both exchangers)
Clamps for remote double set-point
Clamps for external interlock
Clamps for remote general alarm
Connection clamps to remote keyboard (optional)
Clamps for evaporator/condenser pump relay control (optional)
Clamps for boiler relay control (optional)
Clamps for dynamic set-point compensation (4-20 mA, 0-1 V, 0-5 V,
0-10 V)
Clamps for DHW 3-way valve (accessory)
Clamps for outdoor air temperature probe (accessory)
Electronic control SBW655
Soft-starter (optional)
Power factor correction capacitors (optional)
0-10 V clamps for condensing control (optional)
Control
A new optimized control is supplied on all the units with a simple user interface (possibility to customize keys functions and to set menus visibility).
In addition to standard features as water temperature control (with possibility to choose LWT/EWT probe), the control can also manage following functions :
DHW control with anti-legionella function daily and weekly activated
Dynamic set point (4-20 mA, 0-1V, 0-5V, 0-10V)
Double set point
OAT compensation
Boiler/Electrical heater integration
Condensing control
Auto adaptative function to reduce the water content of the plant
Managing of DHW 3-way valve (accessory)
Advanced pump management (both primary circuit and source side)
Remote keyboard (accessory) with possibility to connect (up to 100 m
distance) without any serial interface
WQL-WQH-WQRC 20-190
|
Safety
Each unit is equipped with following electrical / refrigerant / hydraulic safety devices :
Door lock main isolating switch
Phase monitor control
High pressure switch with manual reset
Discharge safety valve
Low pressure switch with automatic / manual reset
Anti-freeze probe (leaving water temperature)
Differential pressure switch (source / plant side)
Standards
WQL/WQH/WQRC are built in compliance with following standards :
Machinery Directive : 2006/42/EC
Low Voltage Directive : 2006/95/EC
Electromagnetic Compatibility Directive : 2014/30/EU
Pressure Equipment Directive : 2014/68/EU
And following harmonized European standards :
Safety of machinery - Basic concepts, general principles for design: UNI
EN ISO 12100-1 / 2
Safety of machinery - Safety Distances To Prevent Hazard Zones Being
Reached By Upper And Lower Limbs : EN ISO 13857
Safety of machinery - Electrical equipment of machines : EN 60204-1
Low-voltage switchgear and controlgear assemblies : EN 60439-1
Electromagnetic compatibility (EMC) - Immunity for industrial
environments : IEC EN 61000-6-2
Electromagnetic compatibility (EMC) - Emission standard for residential,
commercial and light-industrial environments : IEC EN 61000-6-3
Factory installed options
ModBus protocol kit for BMS
Compressor soft starter
Power factor correction capacitors
Electronic expansion valve
Compressor overload protection (only for F2 units)
Automatic circuit breaker (only for F2 units)
Condensing control kit
Electric heater wiring kit
Additional heating device wiring kit
Mechanical gauges kit
Compressor jacket
On board hydrokit (1P/both exchangers/SP for F1 units, 1P/2P/both
exchangers/SP-HP for F2 units)
Desuperheater (only for F2 units)
Field installed accessories
Remote ON-OFF
Remote keyboard panel
Sequencer up to 4 units
Condensing control kit
Water temperature sensor for DHW tank
Outdoor air sensor for weather compensation
Electric heater wiring kit
Additional heating device wiring kit
Pressostatic water valve for well application (only for F1 units)
Compressor jacket
Refrigerating systems and heat pumps. Safety and environmental
requirements : EN 378-1 / 2
Metallic products - Types of inspection documents : EN 10204
Copper and copper alloys. Seamless, round copper tubes for air
conditioning and refrigeration : BS EN 12735-1 / 2
Pressure equipment for refrigerating systems and heat pumps. General
requirements : BS EN 14276-1 / 2
Refrigerating systems and heat pumps - Pressure relief devices and their
associated piping - Methods for calculation : BS EN 13136
Metallic industrial piping : BS EN 13480-3
Flow switch
Pressure switch
Victaulic to threaded pipe connection
3-way valve for DHW production
Spring type anti-vibration mounts (only for F2 units)
Water filter
Valves IN/OUT (only for F1 units)
|
1
VALVE (OPTIONAL)
WQL-WQH-WQRC 20-190
Refrigerant Flow Diagram - WQL 20 to 45
AT
A
2 6
C
F
E
S
S
43
SM
MECHANICAL EXPANSION
VALVE (STANDARD)
B
5
D
G
H
S
UNIT
CONTROL
SUCTION LINE
ST BT
EXV
CONTROL
COMPONENTS
1 Compressor
2 Condenser
3 Drier filter
4 Sight glass
5 Mechanical expansion valve
6 Evaporator
7 Electronic expansion valve
3 4 7
ELECTRONIC EXPANSION
SAFETY / CONTROL DEVICES
A High pressure switch (42 bar)
B Low pressure switch (2 bar)
AT High pressure transducer (optional)
BT Low pressure transducer
C Water differential pressure switch
D Water differential pressure switch
E Outlet water temperature sensor
F Inlet water temperature sensor
G Inlet water temperature sensor
H Outlet water temperature sensor
S 5/16" Shrader connection (service only)
ST Suction temperature probe
Pipe connection with Shrader valve
Refrigerant Flow Diagram - WQL 50 to 190
VALVE (OPTIONAL)
WQL-WQH-WQRC 20-190
|
8
I
AT
2 6
C
F
E
S
1
S S
A
OIL EQUAL.
43
MECHANICAL EXPANSION
VALVE (STANDARD)
B
D
G
H
5
S
UNIT
CONTROL
SUCTION LINE
ST BT
EXV
CONTROL
COMPONENTS
1 Compressors
2 Condenser
3 Drier filter
4 Sight glass
5 Mechanical expansion valve
6 Evaporator
7 Electronic expansion valve
8 Desuperheater
3 4 7
ELECTRONIC EXPANSION
SAFETY / CONTROL DEVICES
A High pressure switch (40.5 bar)
B Low pressure switch (2 bar)
AT High pressure transducer (optional)
BT Low pressure transducer
C Water differential pressure switch
D Water differential pressure switch
E Outlet water temperature sensor
F Inlet water temperature sensor
G Inlet water temperature sensor
H Outlet water temperature sensor
I PED pressure valve (45 bar)
S 5/16" Shrader connection (service only)
Pipe connection with Shrader valve
|
2
VALVE (OPTIONAL)
WQL-WQH-WQRC 20-190
Refrigerant Flow Diagram - WQH 20 to 45
AT
3
C
F
E
S
ON
4
S
A
5
MECHANICAL EXPANSION
1
6
VALVE (STANDARD)
S
B
7
D
G
H
88
8
S
8
ST
BT
EEV
CONTROL
UNIT
CONTROL
COMPONENTS
1 Compressor
2 4-way valve
3 Condenser
4 Drier filter
5 Sight glass
6 Mechanical expansion valve
7 Evaporator
8 Check valve
9 Electronic expansion valve
4
ELECTRONICAL EXPANSION
SAFETY / CONTROL DEVICES
A High pressure switch (42 bar)
B Low pressure switch (2 bar)
AT High pressure transducer (optional)
BT Low pressure transducer
C Water differential pressure switch
D Water differential pressure switch
E Outlet water temperature sensor
F Inlet water temperature sensor
G Inlet water temperature sensor
H Outlet water temperature sensor
S 5/16" Shrader connection (service only)
Pipe connection with Shrader valve
5
9
Refrigerant Flow Diagram - WQH 50 to 190
VALVE (OPTIONAL)
2
10
I
AT
1
S
A
OIL EQUAL.
|
WQL-WQH-WQRC 20-190
S
B
3
C
F
E
S
ON
7
D
G
H
88
8
4
5
MECHANICAL EXPANSION
6
VALVE (STANDARD)
S
8
ST
BT
EEV
CONTROL
4
5
ELECTRONICAL EXPANSION
9
UNIT
CONTROL
COMPONENTS
1 Compressors
2 4-way valve
3 Condenser
4 Drier filter
5 Sight glass
6 Mechanical expansion valve
7 Evaporator
8 Check valve
9 Electronic expansion valve
10 Desuperheater
SAFETY / CONTROL DEVICES
A High pressure switch (40.5 bar)
B Low pressure switch (2 bar)
AT High pressure transducer (optional)
BT Low pressure transducer
C Water differential pressure switch
D Water differential pressure switch
E Outlet water temperature sensor
F Inlet water temperature sensor
G Inlet water temperature sensor
H Outlet water temperature sensor
I PED pressure relief valve (45 bar)
S 5/16" Shrader connection (service only)
Pipe connection with Shrader valve
|
ELECTRONIC EXPANSION
VALVE (OPTIONAL)
10
WQL-WQH-WQRC 20-190
Refrigerant Flow Diagram - WQRC 20 to 45
2
3
AT
4
5
S
A
6
1
7
MECHANICAL EXPANSION
VALVE (STANDARD)
BS
9
8
S
D
UNIT
CONTROL
G
H
SUCTION LINE
ST
BT
EXV
CONTROL
COMPONENTS
1 Compressor
2 Globe valve
3 Globe valve
4 Liquid receiver
5 Solenoid valve
6 Drier filter
7 Sight glass
8 Mechanical expansion valve
9 Evaporator
10 Electronic expansion valve
SAFETY / CONTROL DEVICES
A High pressure switch (42 bar)
B Low pressure switch (2 bar)
AT High pressure transducer (optional)
BT Low pressure transducer
D Water differential pressure switch
G Inlet water temperature sensor
H Outlet water temperature sensor
S 5/16" Shrader connection (service only)
ST Suction temperature probe
Pipe connection with Shrader valve
6
7
10
Refrigerant Flow Diagram - WQRC 50 to 190
VALVE (OPTIONAL)
WQL-WQH-WQRC 20-190
|
11
S
1
OIL EQUAL.
6
B
7
MECHANICAL EXPANSION
8
VALVE (STANDARD)
S
9
S
D
UNIT
CONTROL
G
H
SUCTION LINE
ST
BT
EXV
CONTROL
I
2
3
AT
4
A
5
COMPONENTS
1 Compressors
2 Globe valve
3 Globe valve
4 Liquid receiver
5 Solenoid valve
6 Drier filter
7 Sight glass
8 Mechanical expansion valve
9 Evaporator
10 Electronic expansion valve
SAFETY / CONTROL DEVICES
A High pressure switch (40.5 bar)
B Low pressure switch (2 bar)
AT High pressure transducer (optional)
BT Low pressure transducer
D Water differential pressure switch
G Inlet water temperature sensor
H Outlet water temperature sensor
I PED pressure valve (45 bar)
S 5/16" Shrader connection (service only)
ST Suction temperature probe
Pipe connection with Shrader valve
6
7
ELECTRONIC EXPANSION
10
|
OUTLET
OUTLET
12
WQL-WQH-WQRC 20-190
Hydraulic Circuit Diagram - WQL/WQH 20 to 45
Hydraulic system basic
D
A
B
C
1
2
8
8
6
7
6
5
E
4
INLET
5
E
3
COMPONENTS
1 Plate heat exchanger 2 Water filter 3 Water outlet 4 Water inlet 5 Globe valve 6 Flexible pipes 7 By-pass valve 8 Pressure point/drainage
SAFETY / CONTROL DEVICES
A Water differential pressure switch B Inlet water temperature sensor C Outlet water temperature sensor D Vent valve E Thermometer
Hydraulic system 1P condenser
A
B
C
1
Unit side Probes
D
2
3
9
9
7
8
7
6
E
5
INLET
6
E
4
COMPONENTS
1 Plate heat exchanger 2 Pump 3 Water filter 4 Water outlet 5 Water inlet 6 Globe valve 7 Flexible pipes 8 By-pass valve 9 Pressure point/drainage
SAFETY / CONTROL DEVICES
A Water differential pressure switch B Inlet water temperature sensor C Outlet water temperature sensor D Vent valve E Thermometer
Unit side Probes
Hydraulic Circuit Diagram - WQL/WQH 20 to 45 (continued)
OUTLET
Hydraulic system 1P evaporator
D
WQL-WQH-WQRC 20-190
|
13
A
B
C
COMPONENTS
1 Plate heat exchanger 2 Pump 3 Water filter 4 Pressure expansion tank 5 Water outlet 6 Water inlet 7 Globe valve 8 Flexible pipes 9 By-pass valve
10 Pressure point/drainage
1
2
4
SAFETY / CONTROL DEVICES
A Water differential pressure switch B Inlet water temperature sensor C Outlet water temperature sensor D Vent valve E Thermometer
Unit side Probes
3
10
10
8
9
8
7
E
6
INLET
7
E
5
|
OUTLET
OUTLET
14
WQL-WQH-WQRC 20-190
Hydraulic Circuit Diagram - WQL/WQH 50 to 190
Hydraulic system basic
A
B
C
1- C
2
8
8
6
7
6
5
E
4
INLET
5
3
E
OUTLET
A
B
C
COMPONENTS
1C Condenser 1E Evaporator
2 Water filter 3 Water outlet 4 Water inlet 5 Globe valve 6 Flexible pipes
1- E
SAFETY / CONTROL DEVICES
A Water differential pressure switch B Inlet water temperature sensor C Outlet water temperature sensor D Vent valve E Thermometer
Unit side
Probes 7 By-pass valve 8 Pressure point/drainage
Hydraulic system 1P condenser and 1P evaporator
D
1- C
D
1- E
COMPONENTS
1C Condenser 1E Evaporator
2 Pump 3 Water filter 4 Pressure expansion tank 5 Water outlet 6 Water inlet 7 Globe valve 8 Flexible pipes 9 By-pass valve
10 Pressure point/drainage
SAFETY / CONTROL DEVICES
A Water differential pressure switch B Inlet water temperature sensor C Outlet water temperature sensor D Vent valve E Thermometer
Unit side Probes
A
B
C
A
B
C
2
8
8
2
4
2
3
10
10
3
10
10
6
7
6
8
9
8
8
9
8
5
E
4
INLET
5
E
E
E
E
E
3
7
6
INLET
7
5
7
6
INLET
7
5
OUTLET
Hydraulic Circuit Diagram - WQL/WQH 50 to 190 (continued)
OUTLET
OUTLET
Hydraulic system 2P condenser and 2P evaporator
WQL-WQH-WQRC 20-190
|
15
2
D
A
B
C
A
B
C
1- C
D
1- E
10
2
10
2
10
2
10
F
3
11
11
F
4
3
11
11
8
9
8
8
9
8
7
E
6
INLET
7
E
E
E
5
7
6
INLET
7
5
COMPONENTS
1C Condenser 1E Evaporator
2 Pump 3 Water filter 4 Pressure expansion tank 5 Water outlet 6 Water inlet 7 Globe valve 8 Flexible pipes 9 By-pass valve
10 Non-return valve 11 Pressure point/drainage
SAFETY / CONTROL DEVICES
A Water differential pressure switch B Inlet water temperature sensor C Outlet water temperature sensor D Vent valve E Thermometer F Water safety valve (6 bar)
Unit side
Probes
|
20
25
30
35
40
45
50
55
60
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20
25
30
35
40
45
50
55
60
16
WQL-WQH-WQRC 20-190
Operating Limits
WQL/WQH 20 - 190
Chilled liquid
Leaving water temperature
Maximum operating pressure bar 6
Heated liquid
Leaving water temperature
Maximum operating pressure bar 6
Power supply voltage 400 V, 3 ph, 50 Hz (+/- 10%)
Note : Maximum % glycol (ethylenic or propilenic) : 40%.
Water °C +5 to +18 Brine °C -8 / +5 (with glycol and electronic expansion valve); +5/+18 (standard application) ΔT water °K 3 to 8
Water °C +25 to +55 ΔT water °K 3 to 15
Water
+
Water
Glycol
Condenser leaving water temperature (°C)Condensing temperature (°C)
Evaporator leaving water temperature (°C)
WQRC 20 - 190
Chilled liquid
Leaving water temperature
Maximum operating pressure bar 6 Condensing temperature °C +30 to +58 Power supply voltage 400 V, 3 ph, 50 Hz (+/- 10%)
Note : Maximum % glycol (ethylenic or propilenic) : 40%.
Water °C +5 to +18 Brine °C -8 / +5 (with glycol and electronic expansion valve); +5/+18 (standard application) Temperature spread °K 3 to 8
Water
+
Glycol
Evaporator leaving water temperature (°C)
Water
Correction Factors
Unit capacity, absorbed power, brine flow rate, brine pressure drop, have to be corrected according to following formula :
Corrected unit capacity
x K
i
E,P
c
E,P
i
Q
CORRECTED/GLYCOL
= Q
NOMINAL
x Kc x K
where :
= capacity corrective factor according to LWT (ΔT = 5 [K]) refer to Table 1
K
c
E
= capacity corrective factor according to glycol percentage (ETHYLENE GLYCOL) refer to Table 2
K
c
P
= capacity corrective factor according to glycol percentage (PROPYLENE GLYCOL) refer to Table 4
K
c
Corrected unit absorbed power
P
CORRECTED/GLYCOL
where :
= absorbed power corrective factor according to LWT (ΔT = 5 [K]) refer to Table 1
K
i
E
= absorbed power corrective factor according to glycol percentage (ETHYLENE GLYCOL) refer to Table 2
K
i
P
= absorbed power corrective factor according to glycol percentage (PROPYLENE GLYCOL) refer to Table 4
K
i
= P
NOMINAL
x K
WQL-WQH-WQRC 20-190
|
17
Corrected brine flow rate
G
CORRECTED/GLYCOL
where :
G
RE-CALCULATED
E
= flow rate corrective factor according to glycol percentage (ETHYLENE GLYCOL) refer to Table 2
K
f
K
f
= flow rate according to P
P
= flow rate corrective factor according to glycol percentage (PROPYLENE GLYCOL) refer to Table 4
CORRECTED/GLYCOL
(P
CORRECTED/GLYCOL
= G
RE-CALCULATED
x 860 / ΔT / 3600)
x K
Corrected brine pressure drop
P
CORRECTED/GLYCOL
where :
P
RE-CALCULATED
E
= pressure drop corrective factor according to glycol percentage (ETHYLENE GLYCOL) refer to Table 2
K
p
P
K
p
Table 1
Leaving water
temperature
[LWT] (°C)
(ΔT=5 [K])
= pressure drop according to G
CORRECTED/GLYCOL
= pressure drop corrective factor according to glycol percentage (PROPYLENE GLYCOL) refer to Table 5
K
c
7 1.000 1.000 4 0.887 0.940 2 0.816 0.900 0 0.748 0.865
-2 0.685 0.826
-4 0.624 0.788
-6 0.568 0.753
-8 0.513 0.718
-10 0.461 0.683
K
i
Table 2
Ethylene Glycol Percentage % 0 10 20 30 35 40
Freezing point (1) °C 0 -4 -10 -17 -21 -25
Minimum leaving water temperature allowed °C 6 2 -2 -6 -8 -8
Capacity corrective factor (2)
Absorbed power corrective factor (2)
Flow rate corrective factor
Pressure drop corrective factor (3)
(1) ASHRAE Handbook Fundamentals. (2) Valid for LWT=7 °C. If LWT < 7°C consider K (3) Valid for LWT > 5 °C. If LWT < 5 °C then refer to Table 3.
(K
BPHE
x (G
= P
RE-CALCULATED
CORRECTED/GLYCOL
)2)
x K
E,P
f
E,P
p
E
K
1 0.995 0.985 0.970 0.963 0.955
c
E
K
1 0.998 0.995 0.985 0.983 0.980
i
E
K
1 1.015 1.050 1.085 1.123 1.160
f
E
K
1 1.070 1.160 1.235 1.283 1.330
p
c
x K
E
and Ki x K
c
E
.
i
Loading...
+ 37 hidden pages