Systemair VAV duct pressure control kit Topvex SC/TC Installation instructions

VAV duct pressure control kit Topvex SC/TC
Installation instructions
Document in original language | 247018 · A001
GB
© Copyright Systemair AB All rights reserved E&OE
Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
247018 | A001
1 General VAV-kit .... .... .... . ... . .... .... .... .... .... .... .... .1
2 Warnings. .... . .... .... .... .... .... .... .... .... . ... . .... .... .... 1
3 Mount pressure transmitters.. .... .... .... .... .... .... . ...1
4 Wiring.... .... . ... . .... .... .... .... .... .... .... .... . .... ... . .... .2
5 Configuration guide Topvex (Access) ... .... .... .... .... 3
5.1 Log in ... .... .... ..... ... . .... .... .... .... .... .... .... . .3
5.2 Configuration wizard . . ... . .... .... .... .... .... .... .3
5.3 Activation.. .... .... .... .... . ... . .... .... .... .... .... ..3
5.4 Allocation . .... .... .... .... ..... ... . .... .... .... .... ...4
5.5 Operation settings ... . ... . ... . .... .... .... .... .... ..5
5.6 Save local settings... .... .... . ... . ... . .... .... .... ..5
Contents
247018 | A001
General VAV-kit |

1 General VAV-kit

The VAV duct pressure control kit is used for VAV control of air handling units. Included in the kit are: 2 pcs of pressure transmitters PTE (Pressure Transmitter Extract), PTS (Pressure Transmitter Supply), pressure outlet, tubes, electrical ca­bles (4 m) and installation instruction.
The pressure transmitters max working range is 0...1250 Pa.

2 Warnings

Danger
• Disconnect the mains power supply to the unit before performing any maintenance or electrical work.
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
• Beware of sharp edges during mounting.

3 Mount pressure transmitters

Mount the pressure transmitters in the supply and extract air ducts (figure 1) and connect according to the wiring dia­gram, figure 2.
Supply duct, connect the tube from the supply duct to +. Extract duct, connect the tube from the extract duct to -.
1
Connect the electrical cables to the electrical connection box.
Fig. 1
Supply air
247018 | A001
Exhaust air Outdoor air
Extract air
Wiring
White
Yellow
Brown
White
Yellow
Brown
White
Yellow
Brown
1 2 3 4
1 2 3 4
1
6
1 2 3 4 5 6
1
6
24V
0V
AI5
T15
24V
0V
AI4
T16
PTE
PTS
White
Yellow
Brown
PTE
PTS
|
2

4 Wiring

Change the settings of the dip-switches according to table 1.
Fig. 2
Table 1 Dip-switch 2, 3 and 4
Dip-switch setting
Pressure range (Pa)
2 = OFF, 3 = OFF, 4 = OFF 0...50
2 = ON, 3 = OFF, 4 = OFF 0...100
2 = OFF, 3 = ON, 4 = OFF 0...300
2 = ON, 3 = ON, 4 = OFF 0...500
2 = OFF, 3 = OFF, 4 = ON 0...700
2 = ON, 3 = OFF, 4 = ON 0...1000
2 = OFF, 3 = ON, 4 = ON 0...1250
247018 | A001

5 Configuration guide Topvex (Access)

5.1 Log in

Log in with service mode using password 0612.
Overview:
Service
0612
Login
Step by step:
Configuration guide Topvex (Access)
|
3
1.
2.
3.
4.
Open the log in window
Select service from drop down list
Type in password 0612
Press Login.

5.2 Configuration wizard

A configuration wizard is available from software version 4.1. By using the wizard, the following steps in chapter 5.3 and chapter 5.4 can be omitted.
Configuration > Configuration wizard
Set up Pressure control
20 Oct 12:45

5.3 Activation

Activate pressure control.
>
Select Pressure as Fan control type in the Configuration > Function configuration > Function acti­vation menu.
Overview:
Configuration > Function Configuration > Function activation
Fan control type
Step by step:
1.
2. Select Function configuration
3. Select Function activation
4. Select Pressure as Fan control type.
Select Configuration from the navigation icons
247018 | A001
20 Oct 12:45
Pressure
|
4
Configuration guide Topvex (Access)

5.4 Allocation

Setup differential pressure sensors.
Select I/O placement for the differential pressure sensors and set the sensors’ measuring range in the Configura- tion > I/O allocation settings > Analog inputsmenu.
Overview:
Configuration > I/O allocation settings > Analog inputs
Analogue inputs
Pressure supply air Controller
Pressure extract air
Configuration > ... > Analog inputs > Pressure supply air
Sensor value at V
Sensor value at V
min
max
20 Oct 12:45
Device Position
AI4
Controller
AI5
20 Oct 12:45
0.0
500.0
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select AI4 as signal for Pressure supply air
5. Select AI5 as signal for Pressure extract air
6. Select Pressure supply air
7. Set Sensor value at V
8. Set Sensor value at V
the same as the start point of the sensor’s selected measuring range
min
the same as the end point of the sensor’s selected measuring range
max
9. Go back to Analog inputs (use the navigation path Configuration > I/O allocation settings > Analog inputs)
10.Select Pressure extract air and repeat steps 7 and 8.
247018 | A001
Configuration guide Topvex (Access)

5.5 Operation settings

Adjust the fan pressure set points in the Data & Settings > Fan Control > Fan setpoints.
Overview:
|
5
Data settings > Fan control > Fan setpoints
Setpoint low speed supply air fan
Setpoint low speed extract air fan
Setpoint normal speed supply air fan
Setpoint normal speed extract air fan
Setpoint high speed supply air fan
Setpoint high speed extract air fan
Step by step:
1.
2. Select Fan control
3. Select Fan setpoints
4. Select and adjust set points for the available fan speed levels.
Select Data & settings from the navigation icons
20 Oct 12:45
100 Pa
100 Pa
200 Pa
200 Pa
200 Pa
200 Pa

5.6 Save local settings

When the installation is complete and all functions are tested it is recommended to save a local backup of the current configuration in the controller.
Select Yes on Commissioning settings in the Configuration > System settings > Save and restore set- tings menu.
Overview:
Configuration > System settings > Save and restore settings
Save commissioning settings
Step by step:
1.
2. Select System settings
3. Select Save and restore
4. Select Yes on Save commissioning settings.
Select Configuration from the navigation icons
20 Oct 12:45
Yes
247018 | A001