Systemair V4.0-1-04, V4.0-1-05 User Manual

Communication manual
Access software from 4.0-1-04 to 4.3-1-00 EN
Document in original language | 153831 · A006
Table of contents
Chapter 1 About this document __________________________________________________________ 4
Introduction _______________________________________________________________________________ 4 Software version ___________________________________________________________________________ 4 Signal types _______________________________________________________________________________ 4
Chapter 2 System integration ___________________________________________________________ 6
Modbus __________________________________________________________________________________ 6 BACnet ___________________________________________________________________________________ 8 Watchdog_________________________________________________________________________________ 9 Ethernet setting ___________________________________________________________________________ 11 Type example addresses ____________________________________________________________________ 14
Chapter 3 Coil Status Register (0x) ______________________________________________________ 15 Chapter 4 Input Register (3x) ___________________________________________________________ 16 Chapter 5 Holding Register (4x) _________________________________________________________ 49 Chapter 6 Input Status Register (1x) ____________________________________________________ 102
Chapter 1 About this document 4

Chapter 1 About this document

Introduction

This document describes all Access signals that are accessible via EXOline, Modbus and BACnet.

Software version

Access version
Available
V4.0-1-04
Modbus are available
V4.0-1-05 later
EXOline, BACnet and Modbus are available
NaviPad 1.1.0.184 later
With Ethernet menu, static IP setting
Release column in register tables further down in this document tells from which software release variables was introduced or changed.

Signal types

All signals accessible from a SCADA system are described further in this document.

EXOL type

The EXOL type of the signals: R = Real (-3.3E38 - 3.3E38) I = Integer (-32768 - 32767) X = Index (0 - 255) L = Logic (0/1)

Modbus type

The Modbus type of the signals: 0x = Coil Status Register (1bit) 1x = Input Status Register (1bit) 4x = Holding Register (signed, 16bit or 32bit word) 3x = Input Register (signed, 16bit word or 32bit float)
Chapter 1 │About this document 5
Supported Modbus functions: 1 = Read Coils 2 = Read Discrete Input 3 = Read Holding Register 4 = Read Input Register 5 = Write Single Coil 6 = Write Single Register 15 = Write Multiple Coils 16 = Write Multiple Registers

BACnet type

The BACnet type of signals: 10XXX = Read and write binary 20XXX = Read binary 30XXX = Read and write analogue 40XXX = Read analogue 30XXX = Read and write multistate 40XXX = Read multistate
(Where XXX = Modbus address)
NOTE: In the variable lists contained in this manual, the following abbrevations are used: AV = Analogue Value BV = Binary Value MSV = Multistate Value
Chapter 2 System integration 6

Chapter 2 System integration

Modbus

Addresses

All addresses starts with 0, and due to that some Master devices starts address with 1 (equal to register) it’s in that case necessary to add all addresses in this document with +1.

Communication limitations

The Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two messages.

Baudrate

9600, 14 400, 19 200, 28 800, 38 400, 57 600, 76 800, 115 200 bps

Scale factor Modbus

Real signals could have scale factor according to Scale factor column in tables. In general 10 is used except for time setting signals which have scale factor 100, and air flow signals which have scale factor 1. Example, with a scale factor 10 of an temperature Integer value could then be interpreted as a value with one decimal. Integer, Index and Logic always have scale factor 1.

Unit

Real signal values could have an engineering unit according to Unit-column in tables, where T, Q and P represent temperature-, flow- and pressure unit according selected preference setting in the controller.

Modbus wiring, etc.

A protocol like Modbus consists of several layers (OSI-model). The bottom layer is always the physical layer; the number of wires and signal levels. The next layer describes the communication digits (number of data bits, stop-bits, parity etc). Next are the layers describing the Modbus-specific functions (number of digits per message, the meaning of different messages, etc.).
For Modbus, the bottom layer can be RS485, RS422, RS232 or Modbus TCP.

Max. 47 registers

A maximum of 47 registers can be read in one message.

Transmission mode

Access uses the RTU transmission mode for the communication ports. The transmission mode must be the same in the master unit and the slave units, since Modbus/RTU cannot understand Modbus/ASCII messages. The configuration parameter Word length is always 8 for Modbus/RTU.
Chapter 2 │System integration 7
When using Modbus TCP the controller Ethernet port in combination with TCP port setting 502 should be used.

Writing values

To override the output values, set the output to manual mode using a Modbus signal. Then set the corresponding ..._ManSet signal to the wanted level. These signals are listed in Chapter 5: Holding Registers. Remember that only values with a default value are adjustable, you will find these in the chapters Coil Status Register and Holding Register.

Configuration

Modbus TCP/IP enabled as default. Modbus RTU is enabled via configuration of the communication ports.
The communication parameters for the Modbus line is the most important thing to configure first. These parameters must be identical in both the master unit and slave units, since they define the structure of messages and the transmission speed.
The default configuration values of a Access controller are Slave address: 1 Word length: 8 bit Parity: none Stop bits: 2 bits Baud rate: 9600 bps

Slave address

A new Modbus slave address can be set for each air handling unit using the NaviPad. NOTE To change the Modbus slave address when using Modbus TCP/IP a communication port must
be temporarily configured as Modbus slave to access the slave address setting.
Chapter 2 │System integration 8

BACnet

Access from software version 4.0-1-05 is capable of communication via the BACnet-ASC (Application Specific Controller) protocol and from 4.3-1-00 with BACnet AAC (Advanced Application Controller).
In order to connect a Access application to a BMS (Building Management System) via BACnet/IP use the TCP/IP port.

BACnet/IP configuration (Activation status of BACnet/IP protocol)

Upon delivery, the BACnet/IP protocol is disabled as a default. To enable BACnet communication, simply change the setting “No” to “Yes”.

BACnet device name

This is the devices name that is shown on the BMS when a device is discovered.

BACnet device ID

The ID of a device, used to identify it on the BACnet network. This number cannot be duplicated anywhere on the BACnet network and must therefore be unique.

BBMD address and BACnet/IP port number

The BBMD address (BACnet/IP Broadcast Management Device) is used for discovering devices that are attached to different BACnet/IP subnets and separated by an IP router. The address is entered as
host:port, where “host” can be the host’s name if DNS is configured. If DNS is not configured, the
host address should be entered in the format “xxx.xxx.xxx.xxx”, followed by the port number (default setting 47808).
Example: mybbmd:47808 (with DNS configured) or 10.100.50.99:47808
Chapter 2 │System integration 9

DHCP

The Dynamic Host Configuration Protocol (DHCP) is a network protocol used on Internet Protocol (IP) networks for dynamic distribution of network configuration parameters, such as IP addresses, DNS servers and other services. The Access controller can be configured to either obtain an IP address from a DHCP server (dynamic) or the address can be set manually (static).
If static IP address needed for the Access cotroller, simply enter the IP address you wish to use along with the subnet mask, gateway address and DNS server address via the controller webinterface from
version 4.0-1-04 [Ethernet setting].

Watchdog

Access from software version 4.1-1-00 is capable of supervising communication recieved from a BMS master. One slave communication protocol can be monitored at a time. If no active communication from the BMS master is detected before the watchdog timeout elapses, an alarm message is generated.

BMS watchdog (Activation of protocol)

Upon delivery, the BMS watchdog is disabled as default. Activation and configuration of BMS watchdog is done via controller web menu Configuration / System settings / Communication / BMS watchdog

BMS protocol

To enable BMS watchdog, change the setting “None” to the protocol used for BMS communication.
Supported BMS slave protocols are EXOline, Modbus and BACnet.

Watchdog timeout

Configure the watchdog timeout setting between 10 to 3600 seconds (1 hour), default 60 seconds. A byte counter of received bytes is supposed to change since the last cycle. If counter has not been changed during the watchdog timeout setting the communication is considered faulty and an alarm message is generated.
Chapter 2 │System integration 10

Communication fault BMS master

When a communication fault with BMS is detected, values from BMS should be considered invalid. The alarm is configured default as Class C with no action.
Chapter 2 │System integration 11

Ethernet setting

When NaviPad and Control unit are connected directly to each other via switch module without any DHCP server they assign themselves with Auto-IP (Link-local) addresses and then randomly pick from address range 169.254.x.y (255.255.0.0).
The possibility of using a static IP address as alternative to a dynamic IP address (DHCP) is available from Access software version 4.0-1-04 and NaviPad software version 1.1.0.184. For manually setting a static IP address, please follow below steps.
1. From NaviPad log in to the AHU web page
2. Select Yes to enable settings AHU to static IP via AHU web interface
3. Edit AHU control unit IP address, subnet mask, gateway and DNS according your IP plan
4. Select Yes for Save IP settings
5. Press home button on NaviPad to log out from AHU web page
The NaviPad will then lose the connection to AHU since it’s probably is assigned to a not valid IP address anymore
6. In NaviPad system select Advanced HMI setting and select Ethernet (default login password
‘1111’)
7. Activate switch to enable Static IP setting
8. Edit NaviPad IP address, subnet mask and gateway according your IP plan
9. Use NaviPad to search for available devices and select AHU
NOTE The air handling unit and the NaviPad as well as any computer has to be connected on a local network within the same IP subnet.
NOTE If no gateway is available use either 0.0.0.0 or equal to the IP address set for the device.

Access controller

The below picture illustrates the appearance of Ethernet settings for controller in controller web menu from Access software version 4.0-1-04:
Chapter 2 │System integration 12

NaviPad

The below picture illustrates the appearance of Ethernet settings for the NaviPad from NaviPad software version 1.1.0.184:
Chapter 2 System integration 13
Chapter 2 System integration 14

Type example addresses

Example of useful register addresses in a flow chart for a AHU with rotary exchanger and a cooling unit.
Chapter 3 │Coil Status Register (0x) 15

Chapter 3 Coil Status Register (0x)

Signal name
EXOL type Modbus address RW
Bacnet
Function
Description
VentSettings.S_AlaAcknowAll
L
0000
RW
BV, 1000
Alarm setting
Command to acknowledge all alarms
VentSettings.S_FilterAlarmReset
L
0001
RW
BV, 1001
Alarm setting
Command to reset the alarm service interval counter
Chapter 4 Input Register (3x) 16

Chapter 4 Input Register (3x)

Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_MalfunctionSAF1_Status
X
0000
R 1 Alarm Status
Malfunction supply air fan 1
AlaData.Ala_MalfunctionSAF2_Status
X
0001
R 1 Alarm Status
Malfunction supply air fan 2
AlaData.Ala_MalfunctionSAF3_Status
X
0002
R 1 Alarm Status
Malfunction supply air fan 3
AlaData.Ala_MalfunctionSAF4_Status
X
0003
R 1 Alarm Status
Malfunction supply air fan 4
AlaData.Ala_MalfunctionSAF5_Status
X
0004
R 1 Alarm Status
Malfunction supply air fan 5
AlaData.Ala_MalfunctionEAF1_Status
X
0005
R 1 Alarm Status
Malfunction extract air fan 1
AlaData.Ala_MalfunctionEAF2_Status
X
0006
R 1 Alarm Status
Malfunction extract air fan 2
AlaData.Ala_MalfunctionEAF3_Status
X
0007
R 1 Alarm Status
Malfunction extract air fan 3
AlaData.Ala_MalfunctionEAF4_Status
X
0008
R 1 Alarm Status
Malfunction extract air fan 4
AlaData.Ala_MalfunctionEAF5_Status
X
0009
R 1 Alarm Status
Malfunction extract air fan 5
AlaData.Ala_AlarmSAF1_Status
X
0010
R 1 Alarm Status
Alarm supply air fan 1
AlaData.Ala_AlarmSAF2_Status
X
0011
R 1 Alarm Status
Alarm supply air fan 2
AlaData.Ala_AlarmSAF3_Status
X
0012
R 1 Alarm Status
Alarm supply air fan 3
AlaData.Ala_AlarmSAF4_Status
X
0013
R 1 Alarm Status
Alarm supply air fan 4
AlaData.Ala_AlarmSAF5_Status
X
0014
R 1 Alarm Status
Alarm supply air fan 5
AlaData.Ala_AlarmEAF1_Status
X
0015
R 1 Alarm Status
Alarm extract air fan 1
AlaData.Ala_AlarmEAF2_Status
X
0016
R 1 Alarm Status
Alarm extract air fan 2
Chapter 4 Input Register (3x) 17
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_AlarmEAF3_Status
X
0017
R 1 Alarm Status
Alarm extract air fan 3
AlaData.Ala_AlarmEAF4_Status
X
0018
R 1 Alarm Status
Alarm extract air fan 4
AlaData.Ala_AlarmEAF5_Status
X
0019
R 1 Alarm Status
Alarm extract air fan 5
AlaData.Ala_WarningSAF1_Status
X
0020
R 1 Alarm Status
Warning supply air fan 1
AlaData.Ala_WarningSAF2_Status
X
0021
R 1 Alarm Status
Warning supply air fan 2
AlaData.Ala_WarningSAF3_Status
X
0022
R 1 Alarm Status
Warning supply air fan 3
AlaData.Ala_WarningSAF4_Status
X
0023
R 1 Alarm Status
Warning supply air fan 4
AlaData.Ala_WarningSAF5_Status
X
0024
R 1 Alarm Status
Warning supply air fan 5
AlaData.Ala_WarningEAF1_Status
X
0025
R 1 Alarm Status
Warning extract air fan 1
AlaData.Ala_WarningEAF2_Status
X
0026
R 1 Alarm Status
Warning extract air fan 2
AlaData.Ala_WarningEAF3_Status
X
0027
R 1 Alarm Status
Warning extract air fan 3
AlaData.Ala_WarningEAF4_Status
X
0028
R 1 Alarm Status
Warning extract air fan 4
AlaData.Ala_WarningEAF5_Status
X
0029
R 1 Alarm Status
Warning extract air fan 5
AlaData.Ala_ExternalRunSAF_Status
X
0030
R 1 Alarm Status
External operation supply air fan
AlaData.Ala_ExternalRunEAF_Status
X
0031
R 1 Alarm Status
External operation extract air fan
AlaData.Ala_ExternalRunMotor1_Status
X
0032
R 1 Alarm Status
Extra fan motor 1 running
AlaData.Ala_ExternalRunMotor2_Status
X
0033
R 1 Alarm Status
Extra fan motor 2 running
AlaData.Ala_MalfunctionPumpHeater_Status
X
0034
R 1 Alarm Status
Malfunction pump heater
AlaData.Ala_MalfunctionPumpCooler_Status
X
0035
R 1 Alarm Status
Malfunction pump cooler
AlaData.Ala_MalfunctionPumpExchanger_Status
X
0036
R 1 Alarm Status
Malfunction pump exchanger
AlaData.Ala_MalfunctionFireDamper_Status
X
0037
R 1 Alarm Status
Malfunction fire damper
AlaData.Ala_MalfunctionDamper_Status
X
0038
R 1 Alarm Status
Malfunction damper
Chapter 4 Input Register (3x) 18
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_MalfunctionMotor1_Status
X
0039
R 1 Alarm Status
Malfunction extra fan motor 1
AlaData.Ala_MalfunctionMotor2_Status
X
0040
R 1 Alarm Status
Malfunction extra fan motor 2
AlaData.Ala_FireDamperExerciseStop_Status
X
0041
R 1 Alarm Status
Malfunction fire damper exercise
AlaData.Ala_MalfunctionPumpSequence1_Status
X
0042
R 1 Alarm Status
Malfunction pump sequence-A
AlaData.Ala_MalfunctionPumpSequence2_Status
X
0043
R 1 Alarm Status
Malfunction pump sequence-B
AlaData.Ala_MalfunctionPumpSequence3_Status
X
0044
R 1 Alarm Status
Malfunction pump sequence-C
AlaData.Ala_MalfunctionPumpSequence4_Status
X
0045
R 1 Alarm Status
Malfunction pump sequence-D
AlaData.Ala_MalfunctionPumpSequence5_Status
X
0046
R 1 Alarm Status
Malfunction pump sequence-E
AlaData.Ala_MalfunctionPumpSequence6_Status
X
0047
R 1 Alarm Status
Malfunction pump sequence-F
AlaData.Ala_MalfunctionPumpSequence7_Status
X
0048
R 1 Alarm Status
Malfunction pump sequence-G
AlaData.Ala_MalfunctionPumpSequence8_Status
X
0049
R 1 Alarm Status
Malfunction pump sequence-H
AlaData.Ala_MalfunctionPumpSequence9_Status
X
0050
R 1 Alarm Status
Malfunction pump sequence-I
AlaData.Ala_MalfunctionPumpSequence10_Status
X
0051
R 1 Alarm Status
Malfunction pump sequence-J
AlaData.Ala_FilterGuard1_Status
X
0052
R 1 Alarm Status
Filter alarm supply air
AlaData.Ala_FilterGuard2_Status
X
0053
R 1 Alarm Status
Filter alarm extract air
AlaData.Ala_FlowGuard_Status
X
0054
R 1 Alarm Status
Alarm low air flow
AlaData.Ala_ExternalFrostGuard_Status
X
0055
R 1 Alarm Status
Freeze protection guard
AlaData.Ala_DeicingGuard_Status
X
0056
R 1 Alarm Status
Defrosting guard exchanger
AlaData.Ala_FireAlarm_Status
X
0057
R 1 Alarm Status
Fire alarm
AlaData.Ala_SmokeAlarm_Status
X
0058
R 1 Alarm Status
Smoke alarm
AlaData.Ala_ExternalSwitch_Status
X
0059
R 1 Alarm Status
External stop
AlaData.Ala_ExternalAlarm_Status
X
0060
R 1 Alarm Status
External alarm
Chapter 4 Input Register (3x) 19
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ServiceStop_Status
X
0061
R 1 Alarm Status
Service stop
AlaData.Ala_ElectricOverheat_Status
X
0062
R 1 Alarm Status
Electric heater is overheated
AlaData.Ala_FrostRisk_Status
X
0063
R 1 Alarm Status
Warning freeze protection
AlaData.Ala_LowEfficiency_Status
X
0064
R 1 Alarm Status
Low efficiency exchanger
AlaData.Ala_AnalogueDeicing_Status
X
0065
R 1 Alarm Status
Defrosting alarm
AlaData.Ala_RotationguardExchanger_Status
X
0066
R 1 Alarm Status
Rotary exchanger alarm
AlaData.Ala_ExtraAlarm1_Status
X
0067
R 1 Alarm Status
Extra alarm 1
AlaData.Ala_ExtraAlarm2_Status
X
0068
R 1 Alarm Status
Extra alarm 2
AlaData.Ala_ExtraAlarm3_Status
X
0069
R 1 Alarm Status
Extra alarm 3
AlaData.Ala_ExtraAlarm4_Status
X
0070
R 1 Alarm Status
Extra alarm 4
AlaData.Ala_ExtraAlarm5_Status
X
0071
R 1 Alarm Status
Extra alarm 5
AlaData.Ala_ExtraAlarm6_Status
X
0072
R 1 Alarm Status
Extra alarm 6
AlaData.Ala_ExtraAlarm7_Status
X
0073
R 1 Alarm Status
Extra alarm 7
AlaData.Ala_ExtraAlarm8_Status
X
0074
R 1 Alarm Status
Extra alarm 8
AlaData.Ala_ExtraAlarm9_Status
X
0075
R 1 Alarm Status
Extra alarm 9
AlaData.Ala_ExtraAlarm10_Status
X
0076
R 1 Alarm Status
Extra alarm 10
AlaData.Ala_BatteryFail_Status
X
0077
R 1 Alarm Status
Internal battery error
AlaData.Ala_Service_Status
X
0078
R 1 Alarm Status
Alarm service interval
AlaData.Ala_RestartBlocked_Status
X
0079
R 1 Alarm Status
Restart blocked after power on
AlaData.Ala_ControlErrorSupplyTemp_Status
X
0080
R 1 Alarm Status
Deviation alarm supply air temperature
AlaData.Ala_ControlErrorSAF_Status
X
0081
R 1 Alarm Status
Deviation alarm supply air fan
AlaData.Ala_ControlErrorEAF_Status
X
0082
R 1 Alarm Status
Deviation alarm extract air fan
Chapter 4 Input Register (3x) 20
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ControlErrorHumidity_Status
X
0083
R 1 Alarm Status
Deviation alarm humidity control
AlaData.Ala_ControlErrorExtraController_Status
X
0084
R 1 Alarm Status
Deviation alarm extra controller
AlaData.Ala_HighTempSupply_Status
X
0085
R 1 Alarm Status
High supply air temperature
AlaData.Ala_LowTempSupply_Status
X
0086
R 1 Alarm Status
Low supply air temperature
AlaData.Ala_MaxLimitTempSupply_Status
X
0087
R 1 Alarm Status
Supply air temperature max limit
AlaData.Ala_MinLimitTempSupply_Status
X
0088
R 1 Alarm Status
Supply air temperature min limit
AlaData.Ala_HighTempRoom_Status
X
0089
R 1 Alarm Status
High room temperature
AlaData.Ala_LowTempRoom_Status
X
0090
R 1 Alarm Status
Low room temperature
AlaData.Ala_HighTempExtract_Status
X
0091
R 1 Alarm Status
High extract air temperature
AlaData.Ala_LowTempExtract_Status
X
0092
R 1 Alarm Status
Low extract air temperature
AlaData.Ala_HighTempOutdoor_Status
X
0093
R 1 Alarm Status
High outdoor air temperature
AlaData.Ala_LowTempOutdoor_Status
X
0094
R 1 Alarm Status
Low outdoor air temperature
AlaData.Ala_LowTempFrostGuard1_Status
X
0095
R 1 Alarm Status
Freeze protection alarm 1
AlaData.Ala_LowTempFrostGuard2_Status
X
0096
R 1 Alarm Status
Freeze protection alarm 2
AlaData.Ala_LowTempFrostGuard3_Status
X
0097
R 1 Alarm Status
Freeze protection alarm 3
AlaData.Ala_HighTempExtraSensor1_Status
X
0098
R 1 Alarm Status
High temperature extra sensor 1
AlaData.Ala_LowTempExtraSensor1_Status
X
0099
R 1 Alarm Status
Low temperature extra sensor 1
AlaData.Ala_HighTempExtraSensor2_Status
X
0100
R 1 Alarm Status
High temperature extra sensor 2
AlaData.Ala_LowTempExtraSensor2_Status
X
0101
R 1 Alarm Status
Low temperature extra sensor 2
AlaData.Ala_HighTempExtraSensor3_Status
X
0102
R 1 Alarm Status
High temperature extra sensor 3
AlaData.Ala_LowTempExtraSensor3_Status
X
0103
R 1 Alarm Status
Low temperature extra sensor 3
AlaData.Ala_HighTempExtraSensor4_Status
X
0104
R 1 Alarm Status
High temperature extra sensor 4
Chapter 4 Input Register (3x) 21
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_LowTempExtraSensor4_Status
X
0105
R 1 Alarm Status
Low temperature extra sensor 4
AlaData.Ala_HighTempExtraSensor5_Status
X
0106
R 1 Alarm Status
High temperature extra sensor 5
AlaData.Ala_LowTempExtraSensor5_Status
X
0107
R 1 Alarm Status
Low temperature extra sensor 5
AlaData.Ala_HighTempSelectedSensor1_Status
X
0108
R 1 Alarm Status
High temperature selected sensor 1
AlaData.Ala_LowTempSelectedSensor1_Status
X
0109
R 1 Alarm Status
Low temperature selected sensor 1
AlaData.Ala_HighTempSelectedSensor2_Status
X
0110
R 1 Alarm Status
High temperature selected sensor 2
AlaData.Ala_LowTempSelectedSensor2_Status
X
0111
R 1 Alarm Status
Low temperature selected sensor 2
AlaData.Ala_ManualControlUnit_Status
X
0112
R 1 Alarm Status
Manual operation air handling unit
AlaData.Ala_ManualControlSupply_Status
X
0113
R 1 Alarm Status
Manual operation supply air
AlaData.Ala_ManualControlSAF_Status
X
0114
R 1 Alarm Status
Manual operation supply air fan
AlaData.Ala_ManualControlEAF_Status
X
0115
R 1 Alarm Status
Manual operation extract air fan
AlaData.Ala_ManualControlHeater_Status
X
0116
R 1 Alarm Status
Manual operation heater
AlaData.Ala_ManualControlExchanger_Status
X
0117
R 1 Alarm Status
Manual operation exchanger
AlaData.Ala_ManualControlCooler_Status
X
0118
R 1 Alarm Status
Manual operation cooler
AlaData.Ala_ManualControlDamper_Status
X
0119
R 1 Alarm Status
Manual operation damper
AlaData.Ala_ManualControlPumpHeater_Status
X
0120
R 1 Alarm Status
Manual operation pump heater
AlaData.Ala_ManualControlPumpExchanger_Status
X
0121
R 1 Alarm Status
Manual operation pump exchanger
AlaData.Ala_ManualControlPumpCooler_Status
X
0122
R 1 Alarm Status
Manual operation pump cooler
AlaData.Ala_ManualControlDamperRecirculation_Status
X
0123
R 1 Alarm Status
Manual operation damper recirculation
AlaData.Ala_ManualControlDamperOutdoor_Status
X
0124
R 1 Alarm Status
Manual operation damper outdoor air
AlaData.Ala_ManualControlDamperExhaust_Status
X
0125
R 1 Alarm Status
Manual operation damper exhaust air
AlaData.Ala_ManualControlDamperFire_Status
X
0126
R 1 Alarm Status
Manual operation fire damper
Chapter 4 Input Register (3x) 22
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ManualControlSequence1_Status
X
0127
R 1 Alarm Status
Manual control sequence-A
AlaData.Ala_ManualControlSequence2_Status
X
0128
R 1 Alarm Status
Manual control sequence-B
AlaData.Ala_ManualControlSequence3_Status
X
0129
R 1 Alarm Status
Manual control sequence-C
AlaData.Ala_ManualControlSequence4_Status
X
0130
R 1 Alarm Status
Manual control sequence-D
AlaData.Ala_ManualControlSequence5_Status
X
0131
R 1 Alarm Status
Manual control sequence-E
AlaData.Ala_ManualControlSequence6_Status
X
0132
R 1 Alarm Status
Manual control sequence-F
AlaData.Ala_ManualControlSequence7_Status
X
0133
R 1 Alarm Status
Manual control sequence-G
AlaData.Ala_ManualControlSequence8_Status
X
0134
R 1 Alarm Status
Manual control sequence-H
AlaData.Ala_ManualControlSequence9_Status
X
0135
R 1 Alarm Status
Manual control sequence-I
AlaData.Ala_ManualControlSequence10_Status
X
0136
R 1 Alarm Status
Manual control sequence-J
AlaData.Ala_ManualControlOutput_Status
X
0137
R 1 Alarm Status
Output in manual operation
AlaData.Ala_ManualControlInput_Status
X
0138
R 1 Alarm Status
Input in manual operation
AlaData.Ala_ManualControlExtraController_Status
X
0139
R 1 Alarm Status
Manual operation extra controller
AlaData.Ala_ManualControlMotor1_Status
X
0140
R 1 Alarm Status
Manual operation external fan motor 1
AlaData.Ala_ManualControlMotor2_Status
X
0141
R 1 Alarm Status
Manual operation external fan motor 2
AlaData.Ala_ManualControlPretreatment_Status
X
0142
R 1 Alarm Status
Manual operation pretreatment
AlaData.Ala_SensorErrorTempOutdoor_Status
X
0143
R 1 Alarm Status
Sensor error outdoor air temperature
AlaData.Ala_SensorErrorTempIntake_Status
X
0144
R 1 Alarm Status
Sensor error intake air temperature
AlaData.Ala_SensorErrorTempSupply_Status
X
0145
R 1 Alarm Status
Sensor error supply air temperature
AlaData.Ala_SensorErrorTempExhaust_Status
X
0146
R 1 Alarm Status
Sensor error exhaust air temperature
AlaData.Ala_SensorErrorTempExtract_Status
X
0147
R 1 Alarm Status
Sensor error extract air temperature
AlaData.Ala_SensorErrorTempRoom1_Status
X
0148
R 1 Alarm Status
Sensor error room temperature 1
Chapter 4 Input Register (3x) 23
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_SensorErrorTempRoom2_Status
X
0149
R 1 Alarm Status
Sensor error room temperature 2
AlaData.Ala_SensorErrorTempRoom3_Status
X
0150
R 1 Alarm Status
Sensor error room temperature 3
AlaData.Ala_SensorErrorTempRoom4_Status
X
0151
R 1 Alarm Status
Sensor error room temperature 4
AlaData.Ala_SensorErrorPressureSAF_Status
X
0152
R 1 Alarm Status
Sensor error pressure supply air
AlaData.Ala_SensorErrorPressureEAF_Status
X
0153
R 1 Alarm Status
Sensor error pressure extract air
AlaData.Ala_SensorErrorFlowSAF_Status
X
0154
R 1 Alarm Status
Sensor error flow supply air
AlaData.Ala_SensorErrorFlowEAF_Status
X
0155
R 1 Alarm Status
Sensor error flow extract air
AlaData.Ala_SensorPressureExchangerSAF_Status
X
0156
R 1 Alarm Status
Sensor error flow exchanger supply air
AlaData.Ala_SensorPressureExchangerEAF_Status
X
0157
R 1 Alarm Status
Sensor error pressure exchanger extract air
AlaData.Ala_SensorErrorTempDeicing_Status
X
0158
R 1 Alarm Status
Sensor error defrosting temperature
AlaData.Ala_SensorErrorTempFrost1_Status
X
0159
R 1 Alarm Status
Sensor error freeze protection temperature 1
AlaData.Ala_SensorErrorTempFrost2_Status
X
0160
R 1 Alarm Status
Sensor error freeze protection temperature 2
AlaData.Ala_SensorErrorTempFrost3_Status
X
0161
R 1 Alarm Status
Sensor error freeze protection temperature 3
AlaData.Ala_SensorErrorCO2_Status
X
0162
R 1 Alarm Status
Sensor error CO2 room/extract air
AlaData.Ala_SensorErrorHumidityRoom_Status
X
0163
R 1 Alarm Status
Sensor error humidity room/extract air
AlaData.Ala_SensorErrorHumidityDuct_Status
X
0164
R 1 Alarm Status
Sensor error humidity supply air
AlaData.Ala_SensorErrorTempExtraController_Status
X
0165
R 1 Alarm Status
Sensor error extra controller
AlaData.Ala_SensorErrorExtCtrlSAF_Status
X
0166
R 1 Alarm Status
Signal error external control supply air fan
AlaData.Ala_SensorErrorExtCtrlEAF_Status
X
0167
R 1 Alarm Status
Signal error external control extract air fan
AlaData.Ala_SensorErrorHumidityOutdoor_Status
X
0168
R 1 Alarm Status
Sensor error humidity outdoor
AlaData.Ala_SensorErrorTempExtraSensor1_Status
X
0169
R 1 Alarm Status
Sensor error extra sensor 1
AlaData.Ala_SensorErrorTempExtraSensor2_Status
X
0170
R 1 Alarm Status
Sensor error extra sensor 2
Chapter 4 Input Register (3x) 24
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_SensorErrorTempExtraSensor3_Status
X
0171
R 1 Alarm Status
Sensor error extra sensor 3
AlaData.Ala_SensorErrorTempExtraSensor4_Status
X
0172
R 1 Alarm Status
Sensor error extra sensor 4
AlaData.Ala_SensorErrorTempExtraSensor5_Status
X
0173
R 1 Alarm Status
Sensor error extra sensor 5
AlaData.Ala_SensorErrorExtSupplySetp_Status
X
0174
R 1 Alarm Status
Sensor error external temperature setpoint
AlaData.Ala_SensorErrorExtFlowSetpoint_Status
X
0175
R 1 Alarm Status
Signal error external flow setpoint
AlaData.Ala_SensorErrorFilterGuard1_Status
X
0176
R 1 Alarm Status
Sensor error pressure filter supply air
AlaData.Ala_SensorErrorFilterGuard2_Status
X
0177
R 1 Alarm Status
Sensor error pressure filter extract air
AlaData.Ala_SensorErrorTempEfficiency_Status
X
0178
R 1 Alarm Status
Sensor error efficiency temp
AlaData.Ala_CommErrorDevice_Status
X
0179
R 1 Alarm Status
Fault communication device
AlaData.Ala_MalfunctionExtraController_Status
X
0180
R 1 Alarm Status
Malfunction Extra Controller
AlaData.Ala_InternalError_Status
X
0181
R 1 Alarm Status
Internal error
AlaData.Ala_SmokeDetectorService_Status
X
0182
R 1 Alarm Status
Smoke detector service
AlaData.Ala_SmokeDetectorError_Status
X
0183
R 1 Alarm Status
Smoke detector connection error
AlaData.Ala_MalfunctionPreheater_Status
X
0184
R 1 Alarm Status
Malfunction preheater
4.1-1-01
AlaData.Ala_CommunicationFaultBMS_Status
X
0185
R 1 Alarm Status
Communication fault BMS master
4.1-1-01
AlaData.Ala_LeakageHeaterValve_Status
X
0186
R 1 Alarm Status
Leakage heater valve
4.1-1-01
AlaData.Ala_SensorErrorTempPreheat_Status
X
0187
R 1 Alarm Status
Sensor error preheater temp
4.1-1-01
AlaData.Ala_MalfunctionSAF6_Status
X
0188
R 1 Alarm Status
Malfunction supply air fan 6
4.3-1-00
AlaData.Ala_MalfunctionSAF7_Status
X
0189
R 1 Alarm Status
Malfunction supply air fan 7
4.3-1-00
AlaData.Ala_MalfunctionSAF8_Status
X
0190
R 1 Alarm Status
Malfunction supply air fan 8
4.3-1-00
AlaData.Ala_MalfunctionEAF6_Status
X
0191
R 1 Alarm Status
Malfunction extract air fan 6
4.3-1-00
AlaData.Ala_MalfunctionEAF7_Status
X
0192
R 1 Alarm Status
Malfunction extract air fan 7
4.3-1-00
Chapter 4 Input Register (3x) 25
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_MalfunctionEAF8_Status
X
0193
R 1 Alarm Status
Malfunction extract air fan 8
4.3-1-00
AlaData.Ala_AlarmSAF6_Status
X
0194
R 1 Alarm Status
Alarm supply air fan 6
4.3-1-00
AlaData.Ala_AlarmSAF7_Status
X
0195
R 1 Alarm Status
Alarm supply air fan 7
4.3-1-00
AlaData.Ala_AlarmSAF8_Status
X
0196
R 1 Alarm Status
Alarm supply air fan 8
4.3-1-00
AlaData.Ala_AlarmEAF6_Status
X
0197
R 1 Alarm Status
Alarm extract air fan 6
4.3-1-00
AlaData.Ala_AlarmEAF7_Status
X
0198
R 1 Alarm Status
Alarm extract air fan 7
4.3-1-00
AlaData.Ala_AlarmEAF8_Status
X
0199
R 1 Alarm Status
Alarm extract air fan 8
4.3-1-00
AlaData.Ala_WarningSAF6_Status
X
0200
R 1 Alarm Status
Warning supply air fan 6
4.3-1-00
AlaData.Ala_WarningSAF7_Status
X
0201
R 1 Alarm Status
Warning supply air fan 7
4.3-1-00
AlaData.Ala_WarningSAF8_Status
X
0202
R 1 Alarm Status
Warning supply air fan 8
4.3-1-00
AlaData.Ala_WarningEAF6_Status
X
0203
R 1 Alarm Status
Warning extract air fan 6
4.3-1-00
AlaData.Ala_WarningEAF7_Status
X
0204
R 1 Alarm Status
Warning extract air fan 7
4.3-1-00
AlaData.Ala_WarningEAF8_Status
X
0205
R 1 Alarm Status
Warning extract air fan 8
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone1_Status
X
0206
R 1 Alarm Status
Malfunction heating zone 1
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone2_Status
X
0207
R 1 Alarm Status
Malfunction heating zone 2
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone3_Status
X
0208
R 1 Alarm Status
Malfunction heating zone 3
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone1_Status
X
0209
R 1 Alarm Status
Malfunction cooling zone 1
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone2_Status
X
0210
R 1 Alarm Status
Malfunction cooling zone 2
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone3_Status
X
0211
R 1 Alarm Status
Malfunction cooling zone 3
4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone1_Status
X
0212
R 1 Alarm Status
Deviation alarm supply air temperature zone 1
4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone2_Status
X
0213
R 1 Alarm Status
Deviation alarm supply air temperature zone 2
4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone3_Status
X
0214
R 1 Alarm Status
Deviation alarm supply air temperature zone 3
4.3-1-00
Chapter 4 Input Register (3x) 26
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_LowTempFrostGuardZone1_Status
X
0215
R 1 Alarm Status
Freeze protection alarm zone 1
4.3-1-00
AlaData.Ala_LowTempFrostGuardZone2_Status
X
0216
R 1 Alarm Status
Freeze protection alarm zone 2
4.3-1-00
AlaData.Ala_LowTempFrostGuardZone3_Status
X
0217
R 1 Alarm Status
Freeze protection alarm zone 3
4.3-1-00
AlaData.Ala_ElectricOverheatZone1_Status
X
0218
R 1 Alarm Status
Electric heater is overheated zone 1
4.3-1-00
AlaData.Ala_ElectricOverheatZone2_Status
X
0219
R 1 Alarm Status
Electric heater is overheated zone 2
4.3-1-00
AlaData.Ala_ElectricOverheatZone3_Status
X
0220
R 1 Alarm Status
Electric heater is overheated zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone1_Status
X
0221
R 1 Alarm Status
Sensor error supply air temperature zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone2_Status
X
0222
R 1 Alarm Status
Sensor error supply air temperature zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone3_Status
X
0223
R 1 Alarm Status
Sensor error supply air temperature zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone1_Status
X
0224
R 1 Alarm Status
Sensor error room temperature zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone2_Status
X
0225
R 1 Alarm Status
Sensor error room temperature zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone3_Status
X
0226
R 1 Alarm Status
Sensor error room temperature zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone1_Status
X
0227
R 1 Alarm Status
Sensor error extract temperature zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone2_Status
X
0228
R 1 Alarm Status
Sensor error extract temperature zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone3_Status
X
0229
R 1 Alarm Status
Sensor error extract temperature zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone1_Status
X
0230
R 1 Alarm Status
Sensor error freeze protection temperature zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone2_Status
X
0231
R 1 Alarm Status
Sensor error freeze protection temperature zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone3_Status
X
0232
R 1 Alarm Status
Sensor error freeze protection temperature zone 3
4.3-1-00
VentActual.A_AnalogInput(1)
R
0250
R
AV, 40250
10 Analogue input
Actual value AI1
VentActual.A_AnalogInput(2)
R
0251
R
AV, 40251
10 Analogue input
Actual value AI2
Chapter 4 Input Register (3x) 27
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AnalogInput(3)
R
0252
R
AV, 40252
10 Analogue input
Actual value AI3
VentActual.A_AnalogInput(4)
R
0253
R
AV, 40253
10 Analogue input
Actual value AI4
VentActual.A_AnalogInput(5)
R
0254
R
AV, 40254
10 Universal input
Actual value analog UI1
VentActual.A_AnalogInput(6)
R
0255
R
AV, 40255
10 Universal input
Actual value analog UI2
VentActual.A_AnalogInput(7)
R
0256
R
AV, 40256
10 Universal input
Actual value analog UI3
VentActual.A_AnalogInput(8)
R
0257
R
AV, 40257
10 Universal input
Actual value analog UI4
VentActual.A_AnalogInputExp1(1)
R
0258
R
AV, 40258
10 Analogue input
Actual value exp.unit 1 AI1
VentActual.A_AnalogInputExp1(2)
R
0259
R
AV, 40259
10 Analogue input
Actual value exp.unit 1 AI2
VentActual.A_AnalogInputExp1(3)
R
0260
R
AV, 40260
10 Analogue input
Actual value exp.unit 1 AI3
VentActual.A_AnalogInputExp1(4)
R
0261
R
AV, 40261
10 Analogue input
Actual value exp.unit 1 AI4
VentActual.A_AnalogInputExp1(5)
R
0262
R
AV, 40262
10 Universal input
Actual value exp.unit 1 analog UI1
VentActual.A_AnalogInputExp1(6)
R
0263
R
AV, 40263
10 Universal input
Actual value exp.unit 1 analog UI2
VentActual.A_AnalogInputExp1(7)
R
0264
R
AV, 40264
10 Universal input
Actual value exp.unit 1 analog UI3
VentActual.A_AnalogInputExp1(8)
R
0265
R
AV, 40265
10 Universal input
Actual value exp.unit 1 analog UI4
VentActual.A_AnalogInputExp2(1)
R
0266
R
AV, 40266
10 Analogue input
Actual value exp.unit 2 AI1
Chapter 4 Input Register (3x) 28
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AnalogInputExp2(2)
R
0267
R
AV, 40267
10 Analogue input
Actual value exp.unit 2 AI2
VentActual.A_AnalogInputExp2(3)
R
0268
R
AV, 40268
10 Analogue input
Actual value exp.unit 2 AI3
VentActual.A_AnalogInputExp2(4)
R
0269
R
AV, 40269
10 Analogue input
Actual value exp.unit 2 AI4
VentActual.A_AnalogInputExp2(5)
R
0270
R
AV, 40270
10 Universal input
Actual value exp.unit 2 analog UI1
VentActual.A_AnalogInputExp2(6)
R
0271
R
AV, 40271
10 Universal input
Actual value exp.unit 2 analog UI2
VentActual.A_AnalogInputExp2(7)
R
0272
R
AV, 40272
10 Universal input
Actual value exp.unit 2 analog UI3
VentActual.A_AnalogInputExp2(8)
R
0273
R
AV, 40273
10 Universal input
Actual value exp.unit 2 analog UI4
VentActual.A_AI_OutDoorTemp
R
0290
R
AV, 40290
10 T AI function
Actual value outdoor temperature
VentActual.A_AI_IntakeAirTemp
R
0291
R
AV, 40291
10 T AI function
Actual value intake air temperature
VentActual.A_AI_SupplyAirTemp
R
0292
R
AV, 40292
10 T AI function
Actual value supply air temperature
VentActual.A_AI_ExhaustAirTemp
R
0293
R
AV, 40293
10 T AI function
Actual value exhaust air temperature
VentActual.A_AI_ExtractAirTemp
R
0294
R
AV, 40294
10 T AI function
Actual value extract air temperature
VentActual.A_AI_RoomTemp1(0)
R
0295
R
AV, 40295
10 AI function
Actual value room temperature 1
VentActual.A_AI_RoomTemp2
R
0296
R
AV, 40296
10 AI function
Actual value room temperature 2
VentActual.A_AI_RoomTemp3
R
0297
R
AV, 40297
10 AI function
Actual value room temperature 3
Chapter 4 Input Register (3x) 29
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AI_RoomTemp4
R
0298
R
AV, 40298
10 AI function
Actual value room temperature 4
VentActual.A_AI_SAFPressure
R
0299
R
AV, 40299
10 P AI function
Actual value supply air pressure
VentActual.A_AI_EAFPressure
R
0300
R
AV, 40300
10 P AI function
Actual value extract air pressure
VentActual.A_AI_SAFFlow
R
0301
R
AV, 40301
1 Q AI function
Actual value supply air flow
4.3-1-00
VentActual.A_AI_EAFFlow
R
0302
R
AV, 40302
1 Q AI function
Actual value extract air flow
4.3-1-00
VentActual.A_ExchPressureSAF
R
0303
R
AV, 40303
10 AI function
Actual value exchanger supply flow
VentActual.A_AI_ExchPressureEAF
R
0304
R
AV, 40304
10 AI function
Actual value exchanger extract pressure
VentActual.A_AI_DeIcingTemp
R
0305
R
AV, 40305
10 AI function
Actual value defrosting temperature
VentActual.A_AI_FrostprotTemp1(0)
R
0306
R
AV, 40306
10 T AI function
Actual value freeze protection temperature 1
VentActual.A_AI_FrostprotTemp2
R
0307
R
AV, 40307
10 T AI function
Actual value freeze protection temperature 2
VentActual.A_AI_FrostprotTemp3
R
0308
R
AV, 40308
10 T AI function
Actual value freeze protection temperature 3
VentActual.A_AI_CO2
R
0309
R
AV, 40309
10
ppm
AI function
Actual value CO₂ room/extract air
VentActual.A_AI_HumidityRoom
R
0310
R
AV, 40310
10 % AI function
Actual value humidity room/extract air
VentActual.A_AI_HumidityDuct
R
0311
R
AV, 40311
10 % AI function
Actual value humidity duct
VentActual.A_AI_HumidityOutDoor
R
0312
R
AV, 40312
10 % AI function
Actual value humidity outdoor
Chapter 4 Input Register (3x) 30
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AI_ExtraControllerTemp
R
0313
R
AV, 40313
10 AI function
Actual value extra controller temperature
VentActual.A_AI_ExtSAFControl
R
0314
R
AV, 40314
10 AI function
Actual value external control supply air fan
VentActual.A_AI_ExtEAFControl
R
0315
R
AV, 40315
10 AI function
Actual value external control exract air fan
VentActual.A_AI_ExtraSensor1(0)
R
0316
R
AV, 40316
10 AI function
Actual value extra sensor 1
VentActual.A_AI_ExtraSensor2
R
0317
R
AV, 40317
10 AI function
Actual value extra sensor 2
VentActual.A_AI_ExtraSensor3
R
0318
R
AV, 40318
10 AI function
Actual value extra sensor 3
VentActual.A_AI_ExtraSensor4
R
0319
R
AV, 40319
10 AI function
Actual value extra sensor 4
VentActual.A_AI_ExtraSensor5
R
0320
R
AV, 40320
10 AI function
Actual value extra sensor 5
VentActual.A_AI_ExternalSupplySetP
R
0321
R
AV, 40321
10 AI function
Actual value external temperature setpoint
VentActual.A_AI_ExternalFlowSetP
R
0322
R
AV, 40322
1 AI function
Actual value external supply air flow setpoint
4.3-1-00
VentActual.A_AI_FilterGuard1(0)
R
0323
R
AV, 40323
10 AI function
Actual value supply air filter pressure
VentActual.A_AI_FilterGuard2
R
0324
R
AV, 40324
10 AI function
Actual value extract air filter pressure
VentActual.A_AI_EfficiencyTemp
R
0325
R
AV, 40325
10 AI function
Actual value efficiency temperature
VentActual.A_AI_PreHeatTemp
R
0326
R
AV, 40326
10 T AI function
Actual value preheater temperature
4.3-1-00
VentActual.A_AI_Zone1SupplyTemp(0)
R
0327
R
AV, 40327
10 T AI function
Actual value supply air temperature zone 1
4.3-1-00
Chapter 4 Input Register (3x) 31
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AI_Zone2SupplyTemp
R
0328
R
AV, 40328
10 T AI function
Actual value supply air temperature zone 2
4.3-1-00
VentActual.A_AI_Zone3SupplyTemp
R
0329
R
AV, 40329
10 T AI function
Actual value supply air temperature zone 3
4.3-1-00
VentActual.A_AI_Zone1ExtractTemp(0)
R
0330
R
AV, 40330
10 T AI function
Actual value extract air temperature zone 1
4.3-1-00
VentActual.A_AI_Zone2ExtractTemp
R
0331
R
AV, 40331
10 T AI function
Actual value extract air temperature zone 2
4.3-1-00
VentActual.A_AI_Zone3ExtractTemp
R
0332
R
AV, 40332
10 T AI function
Actual value extract air temperature zone 3
4.3-1-00
VentActual.A_AI_Zone1RoomTemp(0)
R
0333
R
AV, 40333
10 T AI function
Actual value room temperature zone 1
4.3-1-00
VentActual.A_AI_Zone2RoomTemp
R
0334
R
AV, 40334
10 T AI function
Actual value room temperature zone 2
4.3-1-00
VentActual.A_AI_Zone3RoomTemp
R
0335
R
AV, 40335
10 T AI function
Actual value room temperature zone 3
4.3-1-00
VentActual.A_RoomTemp
R
0336
R
AV, 40336
10 T AI function
Calculated average temperature of room sensor 1 to 4
VentActual.A_AI_ExchAirFlowSAF
R
0339
R
AV, 40339
1 Q AI function
Calculated flow exchanger supply air
4.3-1-00
VentActual.A_ExchAirFlowEAF
R
0340
R
AV, 40340
1 Q AI function
Calculated flow exchanger extract air
4.3-1-00
VentActual.A_AO_SequenceY1
R
0341
R
AV, 40341
10 % AO function
Actual value SEQ-A
VentActual.A_AO_SequenceY2
R
0342
R
AV, 40342
10 % AO function
Actual value SEQ-B
VentActual.A_AO_SequenceY3
R
0343
R
AV, 40343
10 % AO function
Actual value SEQ-C
VentActual.A_AO_SequenceY4
R
0344
R
AV, 40344
10 % AO function
Actual value SEQ-D
Chapter 4 Input Register (3x) 32
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AO_SequenceY5
R
0345
R
AV, 40345
10 % AO function
Actual value SEQ-E
VentActual.A_AO_SequenceY6
R
0346
R
AV, 40346
10 % AO function
Actual value SEQ-F
VentActual.A_AO_SequenceY7
R
0347
R
AV, 40347
10 % AO function
Actual value SEQ-G
VentActual.A_AO_SequenceY8
R
0348
R
AV, 40348
10 % AO function
Actual value SEG-H
VentActual.A_AO_SequenceY9
R
0349
R
AV, 40349
10 % AO function
Actual value SEQ-I
VentActual.A_AO_SequenceY10
R
0350
R
AV, 40350
10 % AO function
Actual value SEQ-J
VentActual.A_AO_ChangeOver1
R
0351
R
AV, 40351
10 % AO function
Actual value changeover 1
VentActual.A_AO_ChangeOver2
R
0352
R
AV, 40352
10 % AO function
Actual value changeover 2
VentActual.A_AO_SAF
R
0353
R
AV, 40353
10 % AO function
Actual value supply air fan
VentActual.A_AO_EAF
R
0354
R
AV, 40354
10 % AO function
Actual value extract air fan
VentActual.A_AO_Humidity
R
0355
R
AV, 40355
10 % AO function
Actual value humidity
VentActual.A_AO_StepController1
R
0356
R
AV, 40356
10 % AO function
Actual value step controller 1
VentActual.A_AO_StepController2
R
0357
R
AV, 40357
10 % AO function
Actual value step controller 2
VentActual.A_AO_ExtraController
R
0358
R
AV, 40358
10 % AO function
Actual value extra controller
VentActual.A_AO_AISignalOutput
R
0359
R
AV, 40359
10 % AO function
Actual value output from analog input signal
Chapter 4 Input Register (3x) 33
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AO_Auto_PreHeat
R
0360
R
AV, 40360
10 % AO function
Actual value preheater
4.3-1-00
VentActual.A_AO_Auto_Zone1Heat(0)
R
0361
R
AV, 40361
10 % AO function
Actual value heating zone 1
4.3-1-00
VentActual.A_AO_Auto_Zone2Heat
R
0362
R
AV, 40362
10 % AO function
Actual value heating zone 2
4.3-1-00
VentActual.A_AO_Auto_Zone3Heat
R
0363
R
AV, 40363
10 % AO function
Actual value heating zone 3
4.3-1-00
VentActual.A_AO_Auto_Zone1Cool(0)
R
0364
R
AV, 40364
10 % AO function
Actual value cooling zone 1
4.3-1-00
VentActual.A_AO_Auto_Zone2Cool
R
0365
R
AV, 40365
10 % AO function
Actual value cooling zone 2
4.3-1-00
VentActual.A_AO_Auto_Zone3Cool
R
0366
R
AV, 40366
10 % AO function
Actual value cooling zone 3
4.3-1-00
VentActual.A_AnalogOutput(1)
R
0370
R
AV, 40370
10 V Analogue output
Raw value AO1
VentActual.A_AnalogOutput(2)
R
0371
R
AV, 40371
10 V Analogue output
Raw value AO2
VentActual.A_AnalogOutput(3)
R
0372
R
AV, 40372
10 V Analogue output
Raw value AO3
VentActual.A_AnalogOutput(4)
R
0373
R
AV, 40373
10 V Analogue output
Raw value AO4
VentActual.A_AnalogOutput(5)
R
0374
R
AV, 40374
10 V Analogue output
Raw value AO5 VentActual.A_AnalogOutputExp1(1)
R
0375
R
AV, 40375
10 V Analogue output
Raw value exp.unit 1 AO1 VentActual.A_AnalogOutputExp1(2)
R
0376
R
AV, 40376
10 V Analogue output
Raw value exp.unit 1 AO2 VentActual.A_AnalogOutputExp1(3)
R
0377
R
AV, 40377
10 V Analogue output
Raw value exp.unit 1 AO3
Chapter 4 Input Register (3x) 34
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_AnalogOutputExp1(4)
R
0378
R
AV, 40378
10 V Analogue output
Raw value exp.unit 1 AO4 VentActual.A_AnalogOutputExp1(5)
R
0379
R
AV, 40379
10 V Analogue output
Raw value exp.unit 1 AO5 VentActual.A_AnalogOutputExp2(1)
R
0380
R
AV, 40380
10 V Analogue output
Raw value exp.unit 2 AO1 VentActual.A_AnalogOutputExp2(2)
R
0381
R
AV, 40381
10 V Analogue output
Raw value exp.unit 2 AO2 VentActual.A_AnalogOutputExp2(3)
R
0382
R
AV, 40382
10 V Analogue output
Raw value exp.unit 2 AO3 VentActual.A_AnalogOutputExp2(4)
R
0383
R
AV, 40383
10 V Analogue output
Raw value exp.unit 2 AO4 VentActual.A_AnalogOutputExp2(5)
R
0384
R
AV, 40384
10 V Analogue output
Raw value exp.unit 2 AO5
VentActual.A_Efficiency
R
0395
R
AV, 40395
10 % AI function
Calculated temperature efficiency exchanger
Chapter 4 Input Register (3x) 35
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_UnitMode
X
0396
R
MSV, 40396
1 - Unit information
Actual unit mode Modbus 0=Stop 1=Starting up 2=Low speed 3=Normal speed 4=High speed 5=Support heating 6=Support cooling 7=CO₂ 8=Free cooling 9=Cool down 10=Fire 11=Smoke 12=Recirculation 13=Defrosting Bacnet +1 offset for corresponding Modbus
VentActual.A_UnitModeControl
X
0397
R
MSV, 40397
1 Unit information
Indicates what is triggering the current run mode Modbus 1=Time schedule 2=Manual run 3=Digital Input 4=Alarm 5=External control 6=Service stop Bacnet +1 offset for corresponding Modbus
Chapter 4 Input Register (3x) 36
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_ActiveSeqType
X
0398
R
MSV, 40398
1 - Unit information
Active seq. type Modbus 0 =Heating 1 =Cooling Bacnet +1 offset for corresponding Modbus
VentActual.A_ActiveHeatSeqStep
X
0399
R
AV, 40399
1 - Unit information
Active heat sequence
VentActual.A_ActiveCoolSeqStep
X
0400
R
AV, 40400
1 - Unit information
Active cool sequence
VentActual.A_ActiveYSeq
X
0401
R
AV, 40401
1 - Unit information
Active sequence (SEQ-A to SEQ-J) 1=SEQ-A 10=SEQ-J
VentActual.A_SAFRunTime
R
0402
R
AV, 40402
10 - Unit information
Total run time supply air fan (hours)
VentActual.A_EAFRunTime
R
0403
R
AV, 40403
10 - Unit information
Total run time extract air fan (hours)
VentActual.A_DeIcingTime
X
0404
R
AV, 40404
1 Unit information
Run time in defrosting mode (minutes)
VentActual.A_NeedRunTime
I
0405
R
AV, 40405
1 Unit information
Run time in support control mode (minutes)
VentActual.A_CO2RunTime
I
0406
R
AV, 40406
1 Unit information
Run time in CO₂ mode (minutes)
VentActual.A_Y1Sequence
R
0408
R
AV, 40408
10 % PID output
Control signal sequence-A
VentActual.A_Y2Sequence
R
0409
R
AV, 40409
10 % PID output
Control signal sequence-B
VentActual.A_Y3Sequence
R
0410
R
AV, 40410
10 % PID output
Control signal sequence-C
Chapter 4 Input Register (3x) 37
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_Y4Sequence
R
0411
R
AV, 40411
10 % PID output
Control signal sequence-D
VentActual.A_Y5Sequence
R
0412
R
AV, 40412
10 % PID output
Control signal sequence-E
VentActual.A_Y6Sequence
R
0413
R
AV, 40413
10 % PID output
Control signal sequence-F
VentActual.A_Y7Sequence
R
0414
R
AV, 40414
10 % PID output
Control signal sequence-G
VentActual.A_Y8Sequence
R
0415
R
AV, 40415
10 % PID output
Control signal sequence-H
VentActual.A_Y9Sequence
R
0416
R
AV, 40416
10 % PID output
Control signal sequence-I
VentActual.A_Y10Sequence
R
0417
R
AV, 40417
10 % PID output
Control signal sequence-J
VentActual.A_SAF
R
0418
R
AV, 40418
10 % PID output
Control signal supply air fan
VentActual.A_EAF
R
0419
R
AV, 40419
10 % PID output
Control signal extract air fan
VentActual.A_SAFSpeed
X
0420
R
MSV, 40420
1 - Unit information
Actual level supply air fan Modbus 0=Off 1=Low speed 2=Normal speed 3=High speed 4=Manual setpoint 5=Manual output Bacnet +1 offset for corresponding Modbus
VentActual.A_EAFSpeed
X
0421
R
MSV, 40421
1 - Unit information
Actual level extract air fan (See signal list for A_SAFSpeed)
Chapter 4 Input Register (3x) 38
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_CompLowSpeedSAF(0)
R
0422
R
AV, 40422
10 P Unit information
Pressure/flow compensation low speed supply air fan
VentActual.A_CompNormalSpeedSAF
R
0423
R
AV, 40423
10 P Unit information
Pressure/flow compensation normal speed supply air fan
VentActual.A_CompHighSpeedSAF
R
0424
R
AV, 40424
10 P Unit information
Pressure/flow compensation high speed supply air fan
VentActual.A_CompLowSpeedEAF(0)
R
0425
R
AV, 40425
10 P Unit information
Pressure/flow compensation low speed extract air fan
VentActual.A_CompNormalSpeedEAF
R
0426
R
AV, 40426
10 P Unit information
Pressure/flow compensation normal speed extract air fan
VentActual.A_CompHighSpeedEAF
R
0427
R
AV, 40427
10 P Unit information
Pressure/flow compensation high speed extract air fan
VentActual.A_AlarmACount(0)
X
0428
R
AV, 40428
1 - Unit information
Number of unacknowledged A-alarms
VentActual.A_AlarmBCount
X
0429
R
AV, 40429
1 - Unit information
Number of unacknowledged B-alarms
VentActual.A_AlarmCCount
X
0430
R
AV, 40430
1 - Unit information
Number of unacknowledged C-alarms
VentActual.A_SumAlarm1Count(0)
X
0431
R
AV, 40431
1 Unit information
Number of SumAlarm1 alarms
VentActual.A_SumAlarm2Count
X
0432
R
AV, 40432
1 Unit information
Number of SumAlarm2 alarms
VentActual.A_SupplyPID_SetP
R
0433
R
AV, 40433
10 T PID Setpoint
Actual setpoint supply air temperature
VentActual.A_SAFPID_SetP
R
0434
R
AV, 40434
10
P/Q
PID Setpoint
Actual setpoint supply air fan
VentActual.A_EAFPID_SetP
R
0435
R
AV, 40435
10
P/Q
PID Setpoint
Actual setpoint extract air fan
VentActual.A_FrostPID1_Output(0)
R
0436
R
AV, 40436
10 % PID output
Control signal frost protection 1
Chapter 4 Input Register (3x) 39
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_FrostPID2_Output
R
0437
R
AV, 40437
10 % PID output
Control signal frost protection 2
VentActual.A_FrostPID3_Output
R
0438
R
AV, 40438
10 % PID output
Control signal frost protection 3
VentActual.A_CO2PID_Output
R
0439
R
AV, 40439
10 % PID output
Control signal CO₂
VentActual.A_DeIcePID_Output
R
0440
R
AV, 40440
10 % PID output
Control signal defrosting
VentActual.A_HumidityPID_Output
R
0441
R
AV, 40441
10 % PID output
Control signal humidity
VentActual.A_SFP
R
0443
R
AV, 40443
10 - Unit information
Actual SFP
VentActual.A_SFPDay
R
0444
R
AV, 40444
10 - Unit information
Average SFP (day)
VentActual.A_SFPMonth
R
0445
R
AV, 40445
10 - Unit information
Average SFP (30 days)
VentComActual.CA_MotorSpeedHzSAF(1)
R
0446
R
AV, 40446
10
Hz
Fan data
Motor speed frequency supply air fan 1
VentComActual.CA_MotorSpeedHzSAF(2)
R
0447
R
AV, 40447
10
Hz
Fan data
Motor speed frequency supply air fan 2
VentComActual.CA_MotorSpeedHzSAF(3)
R
0448
R
AV, 40448
10
Hz
Fan data
Motor speed frequency supply air fan 3
VentComActual.CA_MotorSpeedHzSAF(4)
R
0449
R
AV, 40449
10
Hz
Fan data
Motor speed frequency supply air fan 4
VentComActual.CA_MotorSpeedHzSAF(5)
R
0450
R
AV, 40450
10
Hz
Fan data
Motor speed frequency supply air fan 5
VentComActual.CA_MotorSpeedHzEAF(1)
R
0451
R
AV, 40451
10
Hz
Fan data
Motor speed frequency extract air fan 1
VentComActual.CA_MotorSpeedHzEAF(2)
R
0452
R
AV, 40452
10
Hz
Fan data
Motor speed frequency extract air fan 2
Chapter 4 Input Register (3x) 40
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_MotorSpeedHzEAF(3)
R
0453
R
AV, 40453
10
Hz
Fan data
Motor speed frequency extract air fan 3
VentComActual.CA_MotorSpeedHzEAF(4)
R
0454
R
AV, 40454
10
Hz
Fan data
Motor speed frequency extract air fan 4
VentComActual.CA_MotorSpeedHzEAF(5)
R
0455
R
AV, 40455
10
Hz
Fan data
Motor speed frequency extract air fan 5
VentComActual.CA_MotorSpeedRpmSAF(1)
R
0456
R
AV, 40456
10
rpm
Fan data
Motor speed rpm supply air fan 1
VentComActual.CA_MotorSpeedRpmSAF(2)
R
0457
R
AV, 40457
10
rpm
Fan data
Motor speed rpm supply air fan 2
VentComActual.CA_MotorSpeedRpmSAF(3)
R
0458
R
AV, 40458
10
rpm
Fan data
Motor speed rpm supply air fan 3
VentComActual.CA_MotorSpeedRpmSAF(4)
R
0459
R
AV, 40459
10
rpm
Fan data
Motor speed rpm supply air fan 4
VentComActual.CA_MotorSpeedRpmSAF(5)
R
0460
R
AV, 40460
10
rpm
Fan data
Motor speed rpm supply air fan 5
VentComActual.CA_MotorSpeedRpmEAF(1)
R
0461
R
AV, 40461
10
rpm
Fan data
Motor speed rpm extract air fan 1
VentComActual.CA_MotorSpeedRpmEAF(2)
R
0462
R
AV, 40462
10
rpm
Fan data
Motor speed rpm extract air fan 2
VentComActual.CA_MotorSpeedRpmEAF(3)
R
0463
R
AV, 40463
10
rpm
Fan data
Motor speed rpm extract air fan 3
VentComActual.CA_MotorSpeedRpmEAF(4)
R
0464
R
AV, 40464
10
rpm
Fan data
Motor speed rpm extract air fan 4
VentComActual.CA_MotorSpeedRpmEAF(5)
R
0465
R
AV, 40465
10
rpm
Fan data
Motor speed rpm extract air fan 5
VentComActual.CA_MotorCurrentSAF(1)
R
0466
R
AV, 40466
10 A Fan data
Motor current supply air fan 1
VentComActual.CA_MotorCurrentSAF(2)
R
0467
R
AV, 40467
10 A Fan data
Motor current supply air fan 2
Chapter 4 Input Register (3x) 41
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_MotorCurrentSAF(3)
R
0468
R
AV, 40468
10 A Fan data
Motor current supply air fan 3
VentComActual.CA_MotorCurrentSAF(4)
R
0469
R
AV, 40469
10 A Fan data
Motor current supply air fan 4
VentComActual.CA_MotorCurrentSAF(5)
R
0470
R
AV, 40470
10 A Fan data
Motor current supply air fan 5
VentComActual.CA_MotorCurrentEAF(1)
R
0471
R
AV, 40471
10 A Fan data
Motor current extract air fan 1
VentComActual.CA_MotorCurrentEAF(2)
R
0472
R
AV, 40472
10 A Fan data
Motor current extract air fan 2
VentComActual.CA_MotorCurrentEAF(3)
R
0473
R
AV, 40473
10 A Fan data
Motor current extract air fan 3
VentComActual.CA_MotorCurrentEAF(4)
R
0474
R
AV, 40474
10 A Fan data
Motor current extract air fan 4
VentComActual.CA_MotorCurrentEAF(5)
R
0475
R
AV, 40475
10 A Fan data
Motor current extract air fan 5
VentComActual.CA_MotorPowerSAF(1)
R
0476
R
AV, 40476
10 Fan data
Motor power supply air fan 1
VentComActual.CA_MotorPowerSAF(2)
R
0477
R
AV, 40477
10 Fan data
Motor power supply air fan 2
VentComActual.CA_MotorPowerSAF(3)
R
0478
R
AV, 40478
10 Fan data
Motor power supply air fan 3
VentComActual.CA_MotorPowerSAF(4)
R
0479
R
AV, 40479
10 Fan data
Motor power supply air fan 4
VentComActual.CA_MotorPowerSAF(5)
R
0480
R
AV, 40480
10 Fan data
Motor power supply air fan 5
VentComActual.CA_MotorPowerEAF(1)
R
0481
R
AV, 40481
10 Fan data
Motor power extract air fan 1
VentComActual.CA_MotorPowerEAF(2)
R
0482
R
AV, 40482
10 Fan data
Motor power extract air fan 2
Chapter 4 Input Register (3x) 42
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_MotorPowerEAF(3)
R
0483
R
AV, 40483
10 Fan data
Motor power extract air fan 3
VentComActual.CA_MotorPowerEAF(4)
R
0484
R
AV, 40484
10 Fan data
Motor power extract air fan 4
VentComActual.CA_MotorPowerEAF(5)
R
0485
R
AV, 40485
10 Fan data
Motor power extract air fan 5
VentComActual.CA_ActiveFaultSAF(1)
I
0486
R
AV, 40486
1 Fan data
Error code supply air fan 1
VentComActual.CA_ActiveFaultSAF(2)
I
0487
R
AV, 40487
1 Fan data
Error code supply air fan 2
VentComActual.CA_ActiveFaultSAF(3)
I
0488
R
AV, 40488
1 Fan data
Error code supply air fan 3
VentComActual.CA_ActiveFaultSAF(4)
I
0489
R
AV, 40489
1 Fan data
Error code supply air fan 4
VentComActual.CA_ActiveFaultSAF(5)
I
0490
R
AV, 40490
1 Fan data
Error code supply air fan 5
VentComActual.CA_ActiveFaultEAF(1)
I
0491
R
AV, 40491
1 Fan data
Error code extract air fan 1
VentComActual.CA_ActiveFaultEAF(2)
I
0492
R
AV, 40492
1 Fan data
Error code extract air fan 2
VentComActual.CA_ActiveFaultEAF(3)
I
0493
R
AV, 40493
1 Fan data
Error code extract air fan 3
VentComActual.CA_ActiveFaultEAF(4)
I
0494
R
AV, 40494
1 Fan data
Error code extract air fan 4
VentComActual.CA_ActiveFaultEAF(5)
I
0495
R
AV, 40495
1 Fan data
Error code extract air fan 5
VentComActual.CA_ActualSpeedSAF(1)
R
0496
R
AV, 40496
10 Fan data
Actual speed supply air fan 1
VentComActual.CA_ActualSpeedSAF(2)
R
0497
R
AV, 40497
10 Fan data
Actual speed supply air fan 2
Chapter 4 Input Register (3x) 43
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_ActualSpeedSAF(3)
R
0498
R
AV, 40498
10 Fan data
Actual speed supply air fan 3
VentComActual.CA_ActualSpeedSAF(4)
R
0499
R
AV, 40499
10 Fan data
Actual speed supply air fan 4
VentComActual.CA_ActualSpeedSAF(5)
R
0500
R
AV, 40500
10 Fan data
Actual speed supply air fan 5
VentComActual.CA_ActualSpeedEAF(1)
R
0501
R
AV, 40501
10 Fan data
Actual speed extract air fan 1
VentComActual.CA_ActualSpeedEAF(2)
R
0502
R
AV, 40502
10 Fan data
Actual speed extract air fan 2
VentComActual.CA_ActualSpeedEAF(3)
R
0503
R
AV, 40503
10 Fan data
Actual speed extract air fan 3
VentComActual.CA_ActualSpeedEAF(4)
R
0504
R
AV, 40504
10 Fan data
Actual speed extract air fan 4
VentComActual.CA_ActualSpeedEAF(5)
R
0505
R
AV, 40505
10 Fan data
Actual speed extract air fan 5
VentComActual.CA_AccumPowerSAF(1)
R
0506
R
AV, 40506
10 Fan data
Accumulated power supply air fan 1
VentComActual.CA_AccumPowerSAF(2)
R
0507
R
AV, 40507
10 Fan data
Accumulated power supply air fan 2
VentComActual.CA_AccumPowerSAF(3)
R
0508
R
AV, 40508
10 Fan data
Accumulated power supply air fan 3
VentComActual.CA_AccumPowerSAF(4)
R
0509
R
AV, 40509
10 Fan data
Accumulated power supply air fan 4
VentComActual.CA_AccumPowerSAF(5)
R
0510
R
AV, 40510
10 Fan data
Accumulated power supply air fan 5
VentComActual.CA_AccumPowerEAF(1)
R
0511
R
AV, 40511
10 Fan data
Accumulated power extract air fan 1
VentComActual.CA_AccumPowerEAF(2)
R
0512
R
AV, 40512
10 Fan data
Accumulated power extract air fan 2
Chapter 4 Input Register (3x) 44
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_AccumPowerEAF(3)
R
0513
R
AV, 40513
10 Fan data
Accumulated power extract air fan 3
VentComActual.CA_AccumPowerEAF(4)
R
0514
R
AV, 40514
10 Fan data
Accumulated power extract air fan 4
VentComActual.CA_AccumPowerEAF(5)
R
0515
R
AV, 40515
10 Fan data
Accumulated power extract air fan 5
VentComActual.CA_VVXFault
I
0516
R
AV, 40516
1 Exchanger data
Error code exchanger
VentComActual.CA_DamperActPos(1)
R
0517
R
AV, 40517
10 % Damper data
Actual position damper 1
VentComActual.CA_DamperActPos(2)
R
0518
R
AV, 40518
10 % Damper data
Actual position damper 2
VentComActual.CA_DamperActPos(3)
R
0519
R
AV, 40519
10 % Damper data
Actual position damper 3
VentComActual.CA_DamperActPos(4)
R
0520
R
AV, 40520
10 % Damper data
Actual position damper 4
VentComActual.CA_DamperActPos(5)
R
0521
R
AV, 40521
10 % Damper data
Actual position damper 5
VentComActual.CA_DamperFault(1)
I
0522
R
AV, 40522
1 Damper data
Error code damper 1
VentComActual.CA_DamperFault(2)
I
0523
R
AV, 40523
1 Damper data
Error code damper 2
VentComActual.CA_DamperFault(3)
I
0524
R
AV, 40524
1 Damper data
Error code damper 3
VentComActual.CA_DamperFault(4)
I
0525
R
AV, 40525
1 Damper data
Error code damper 4
VentComActual.CA_DamperFault(5)
I
0526
R
AV, 40526
1 Damper data
Error code damper 5
VentActual.A_EnergyFanPwr
R
0527
R
AV, 40527
10 Energy insight
Actual power usage for all fans
4.1-1-01
Chapter 4 Input Register (3x) 45
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_EnergyHeaterPwr
R
0528
R
AV, 40528
10 Energy insight
Actual power usage for water heater
4.1-1-01
VentActual.A_EnergyExchangerPwr
R
0529
R
AV, 40529
10 Energy insight
Actual power recovery for exchanger
4.1-1-01
VentActual.A_AI_Zone1FrostprotTemp(0)
R
0530
R
AV, 40530
10 T AI function
Actual value freeze protection temperature zone 1
4.3-1-00
VentActual.A_AI_Zone2FrostprotTemp
R
0531
R
AV, 40531
10 T AI function
Actual value freeze protection temperature zone 2
4.3-1-00
VentActual.A_AI_Zone3FrostprotTemp
R
0532
R
AV, 40532
10 T AI function
Actual value freeze protection temperature zone 3
4.3-1-00 VentActual.A_AI_SAFFlow
R
0533
R 1 Q AI function
Actual value supply air flow (32-bit float)
4.3-1-00
VentActual.A_AI_EAFFlow
R
0535
R 1 Q AI function
Actual value extract air flow (32-bit float)
4.3-1-00
VentActual.A_AI_ExchAirFlowSAF
R
0537
R 1 Q AI function
Calculated flow exchanger supply air (32-bit float)
4.3-1-00
VentComActual.CA_MotorSpeedHzSAF(6)
R
0539
R
AV, 40539
10 Fan data
Motor speed frequency supply air fan 6
4.3-1-00
VentComActual.CA_MotorSpeedHzSAF(7)
R
0540
R
AV, 40540
10 Fan data
Motor speed frequency supply air fan 7
4.3-1-00
VentComActual.CA_MotorSpeedHzSAF(8)
R
0541
R
AV, 40541
10 Fan data
Motor speed frequency supply air fan 8
4.3-1-00
VentComActual.CA_MotorSpeedHzEAF(6)
R
0542
R
AV, 40542
10 Fan data
Motor speed frequency extract air fan 6
4.3-1-00
VentComActual.CA_MotorSpeedHzEAF(7)
R
0543
R
AV, 40543
10 Fan data
Motor speed frequency extract air fan 7
4.3-1-00
VentComActual.CA_MotorSpeedHzEAF(8)
R
0544
R
AV, 40544
10 Fan data
Motor speed frequency extract air fan 8
4.3-1-00
VentComActual.CA_MotorSpeedRpmSAF(6)
R
0545
R
AV, 40545
10 Fan data
Motor speed rpm supply air fan 6
4.3-1-00
VentComActual.CA_MotorSpeedRpmSAF(7)
R
0546
R
AV, 40546
10 Fan data
Motor speed rpm supply air fan 7
4.3-1-00
Chapter 4 Input Register (3x) 46
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_MotorSpeedRpmSAF(8)
R
0547
R
AV, 40547
10 Fan data
Motor speed rpm supply air fan 8
4.3-1-00
VentComActual.CA_MotorSpeedRpmEAF(6)
R
0548
R
AV, 40548
10 Fan data
Motor speed rpm extract air fan 6
4.3-1-00
VentComActual.CA_MotorSpeedRpmEAF(7)
R
0549
R
AV, 40549
10 Fan data
Motor speed rpm extract air fan 7
4.3-1-00
VentComActual.CA_MotorSpeedRpmEAF(8)
R
0550
R
AV, 40550
10 Fan data
Motor speed rpm extract air fan 8
4.3-1-00
VentComActual.CA_MotorCurrentSAF(6)
R
0551
R
AV, 40551
10 Fan data
Motor current supply air fan 6
4.3-1-00
VentComActual.CA_MotorCurrentSAF(7)
R
0552
R
AV, 40552
10 Fan data
Motor current supply air fan 7
4.3-1-00
VentComActual.CA_MotorCurrentSAF(8)
R
0553
R
AV, 40553
10 Fan data
Motor current supply air fan 8
4.3-1-00
VentComActual.CA_MotorCurrentEAF(6)
R
0554
R
AV, 40554
10 Fan data
Motor current extract air fan 6
4.3-1-00
VentComActual.CA_MotorCurrentEAF(7)
R
0555
R
AV, 40555
10 Fan data
Motor current extract air fan 7
4.3-1-00
VentComActual.CA_MotorCurrentEAF(8)
R
0556
R
AV, 40556
10 Fan data
Motor current extract air fan 8
4.3-1-00
VentComActual.CA_MotorPowerSAF(6)
R
0557
R
AV, 40557
10 Fan data
Motor power supply air fan 6
4.3-1-00
VentComActual.CA_MotorPowerSAF(7)
R
0558
R
AV, 40558
10 Fan data
Motor power supply air fan 7
4.3-1-00
VentComActual.CA_MotorPowerSAF(8)
R
0559
R
AV, 40559
10 Fan data
Motor power supply air fan 8
4.3-1-00
VentComActual.CA_MotorPowerEAF(6)
R
0560
R
AV, 40560
10 Fan data
Motor power extract air fan 6
4.3-1-00
VentComActual.CA_MotorPowerEAF(7)
R
0561
R
AV, 40561
10 Fan data
Motor power extract air fan 7
4.3-1-00
Chapter 4 Input Register (3x) 47
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_MotorPowerEAF(8)
R
0562
R
AV, 40562
10 Fan data
Motor power extract air fan 8
4.3-1-00
VentComActual.CA_ActiveFaultSAF(6)
I
0563
R
AV, 40563
1 Fan data
Error code supply air fan 6
4.3-1-00
VentComActual.CA_ActiveFaultSAF(7)
I
0564
R
AV, 40564
1 Fan data
Error code supply air fan 7
4.3-1-00
VentComActual.CA_ActiveFaultSAF(8)
I
0565
R
AV, 40565
1 Fan data
Error code supply air fan 8
4.3-1-00
VentComActual.CA_ActiveFaultEAF(6)
I
0566
R
AV, 40566
1 Fan data
Error code extract air fan 6
4.3-1-00
VentComActual.CA_ActiveFaultEAF(7)
I
0567
R
AV, 40567
1 Fan data
Error code extract air fan 7
4.3-1-00
VentComActual.CA_ActiveFaultEAF(8)
I
0568
R
AV, 40568
1 Fan data
Error code extract air fan 8
4.3-1-00
VentComActual.CA_ActualSpeedSAF(6)
R
0569
R
AV, 40569
10 Fan data
Actual speed supply air fan 6
4.3-1-00
VentComActual.CA_ActualSpeedSAF(7)
R
0570
R
AV, 40570
10 Fan data
Actual speed supply air fan 7
4.3-1-00
VentComActual.CA_ActualSpeedSAF(8)
R
0571
R
AV, 40571
10 Fan data
Actual speed supply air fan 8
4.3-1-00
VentComActual.CA_ActualSpeedEAF(6)
R
0572
R
AV, 40572
10 Fan data
Actual speed extract air fan 6
4.3-1-00
VentComActual.CA_ActualSpeedEAF(7)
R
0573
R
AV, 40573
10 Fan data
Actual speed extract air fan 7
4.3-1-00
VentComActual.CA_ActualSpeedEAF(8)
R
0574
R
AV, 40574
10 Fan data
Actual speed extract air fan 8
4.3-1-00
VentComActual.CA_AccumPowerSAF(6)
R
0575
R
AV, 40575
10 Fan data
Accumulated power supply air fan 6
4.3-1-00
VentComActual.CA_AccumPowerSAF(7)
R
0576
R
AV, 40576
10 Fan data
Accumulated power supply air fan 7
4.3-1-00
Chapter 4 Input Register (3x) 48
Signal name
EXOL type Modbus address RW Bacnet
Scale factor Unit
Function
Description
Release
VentComActual.CA_AccumPowerSAF(8)
R
0577
R
AV, 40577
10 Fan data
Accumulated power supply air fan 8
4.3-1-00
VentComActual.CA_AccumPowerEAF(6)
R
0578
R
AV, 40578
10 Fan data
Accumulated power extract air fan 6
4.3-1-00
VentComActual.CA_AccumPowerEAF(7)
R
0579
R
AV, 40579
10 Fan data
Accumulated power extract air fan 7
4.3-1-00
VentComActual.CA_AccumPowerEAF(8)
R
0580
R
AV, 40580
10 Fan data
Accumulated power extract air fan 8
4.3-1-00
VentActual.A_SupplyPID_SetP_Cool
R
0581
AV, 40581
10 T Unit information
Cooling setpoint supply air temperature
4.3-1-00
VentActual.A_SupplyPID_SetP_Heat
R
0582
AV, 40582
10 T Unit information
Heating setpoint supply air temperature
4.3-1-00
VentActual.A_DeHumidity_SetP
R
0583
AV, 40583
10
%RH
Unit information
Dehumidification setpoint
4.3-1-00
VentActual.A_Humidity_SetP
R
0584
AV, 40584
10
%RH
Unit information
Humidification setpoint
4.3-1-00
VentActual.A_HumidityMode
X
0585
MSV, 40585
1 Unit information
Humidity control mode Modbus 0=Not active 1=Humidification 2=Dehumidification Bacnet +1 offset for corresponding Modbus
4.3-1-00
Chapter 5 Holding Register (4x) 49

Chapter 5 Holding Register (4x)

Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(0).T1
R
0000
RW 100 Time channel
Low speed Monday start time 1 (HH.MM)
TimeDp.Posts(0).T2
R
0001
RW 100 Time channel
Low speed Monday stop time 1
TimeDp.Posts(0).T3
R
0002
RW 100 Time channel
Low speed Monday start time 2
TimeDp.Posts(0).T4
R
0003
RW 100 Time channel
Low speed Monday stop time 2
TimeDp.Posts(1).T1
R
0004
RW 100 Time channel
Low speed Tuesday start time 1
TimeDp.Posts(1).T2
R
0005
RW 100 Time channel
Low speed Tuesday stop time 1
TimeDp.Posts(1).T3
R
0006
RW 100 Time channel
Low speed Tuesday start time 2
TimeDp.Posts(1).T4
R
0007
RW 100 Time channel
Low speed Tuesday stop time 2
TimeDp.Posts(2).T1
R
0008
RW 100 Time channel
Low speed Wednesday start time 1
TimeDp.Posts(2).T2
R
0009
RW 100 Time channel
Low speed Wednesday stop time 1
TimeDp.Posts(2).T3
R
0010
RW 100 Time channel
Low speed Wednesday start time 2
TimeDp.Posts(2).T4
R
0011
RW 100 Time channel
Low speed Wednesday stop time 2
TimeDp.Posts(3).T1
R
0012
RW 100 Time channel
Low speed Thursday start time 1
TimeDp.Posts(3).T2
R
0013
RW 100 Time channel
Low speed Thursday stop time 1
TimeDp.Posts(3).T3
R
0014
RW 100 Time channel
Low speed Thursday start time 2
TimeDp.Posts(3).T4
R
0015
RW 100 Time channel
Low speed Thursday stop time 2
TimeDp.Posts(4).T1
R
0016
RW 100 Time channel
Low speed Friday start time 1
Chapter 5 Holding Register (4x) 50
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(4).T2
R
0017
RW 100 Time channel
Low speed Friday stop time 1
TimeDp.Posts(4).T3
R
0018
RW 100 Time channel
Low speed Friday start time 2
TimeDp.Posts(4).T4
R
0019
RW 100 Time channel
Low speed Friday stop time 2
TimeDp.Posts(5).T1
R
0020
RW 100 Time channel
Low speed Saturday start time 1
TimeDp.Posts(5).T2
R
0021
RW 100 Time channel
Low speed Saturday stop time 1
TimeDp.Posts(5).T3
R
0022
RW 100 Time channel
Low speed Saturday start time 2
TimeDp.Posts(5).T4
R
0023
RW 100 Time channel
Low speed Saturday stop time 2
TimeDp.Posts(6).T1
R
0024
RW 100 Time channel
Low speed Sunday start time 1
TimeDp.Posts(6).T2
R
0025
RW 100 Time channel
Low speed Sunday stop time 1
TimeDp.Posts(6).T3
R
0026
RW 100 Time channel
Low speed Sunday start time 2
TimeDp.Posts(6).T4
R
0027
RW 100 Time channel
Low speed Sunday stop time 2
TimeDp.Posts(7).T1
R
0028
RW 100 Time channel
Low speed holiday start time 1
TimeDp.Posts(7).T2
R
0029
RW 100 Time channel
Low speed holiday stop time 1
TimeDp.Posts(7).T3
R
0030
RW 100 Time channel
Low speed holiday start time 2
TimeDp.Posts(7).T4
R
0031
RW 100 Time channel
Low speed holiday stop time 2
TimeDp.Posts(8).T1
R
0032
RW 100 Time channel
Normal speed Monday start time 1
TimeDp.Posts(8).T2
R
0033
RW 100 Time channel
Normal speed Monday stop time 1
TimeDp.Posts(8).T3
R
0034
RW 100 Time channel
Normal speed Monday start time 2
TimeDp.Posts(8).T4
R
0035
RW 100 Time channel
Normal speed Monday stop time 2
TimeDp.Posts(9).T1
R
0036
RW 100 Time channel
Normal speed Tuesday start time 1
TimeDp.Posts(9).T2
R
0037
RW 100 Time channel
Normal speed Tuesday stop time 1
TimeDp.Posts(9).T3
R
0038
RW 100 Time channel
Normal speed Tuesday start time 2
Chapter 5 Holding Register (4x) 51
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(9).T4
R
0039
RW 100 Time channel
Normal speed Tuesday stop time 2
TimeDp.Posts(10).T1
R
0040
RW 100 Time channel
Normal speed Wednesday start time 1
TimeDp.Posts(10).T2
R
0041
RW 100 Time channel
Normal speed Wednesday stop time 1
TimeDp.Posts(10).T3
R
0042
RW 100 Time channel
Normal speed Wednesday start time 2
TimeDp.Posts(10).T4
R
0043
RW 100 Time channel
Normal speed Wednesday stop time 2
TimeDp.Posts(11).T1
R
0044
RW 100 Time channel
Normal speed Thursday start time 1
TimeDp.Posts(11).T2
R
0045
RW 100 Time channel
Normal speed Thursday stop time 1
TimeDp.Posts(11).T3
R
0046
RW 100 Time channel
Normal speed Thursday start time 2
TimeDp.Posts(11).T4
R
0047
RW 100 Time channel
Normal speed Thursday stop time 2
TimeDp.Posts(12).T1
R
0048
RW 100 Time channel
Normal speed Friday start time 1
TimeDp.Posts(12).T2
R
0049
RW 100 Time channel
Normal speed Friday stop time 1
TimeDp.Posts(12).T3
R
0050
RW 100 Time channel
Normal speed Friday start time 2
TimeDp.Posts(12).T4
R
0051
RW 100 Time channel
Normal speed Friday stop time 2
TimeDp.Posts(13).T1
R
0052
RW 100 Time channel
Normal speed Saturday start time 1
TimeDp.Posts(13).T2
R
0053
RW 100 Time channel
Normal speed Saturday stop time 1
TimeDp.Posts(13).T3
R
0054
RW 100 Time channel
Normal speed Saturday start time 2
TimeDp.Posts(13).T4
R
0055
RW 100 Time channel
Normal speed Saturday stop time 2
TimeDp.Posts(14).T1
R
0056
RW 100 Time channel
Normal speed Sunday start time 1
TimeDp.Posts(14).T2
R
0057
RW 100 Time channel
Normal speed Sunday stop time 1
TimeDp.Posts(14).T3
R
0058
RW 100 Time channel
Normal speed Sunday start time 2
TimeDp.Posts(14).T4
R
0059
RW 100 Time channel
Normal speed Sunday stop time 2
TimeDp.Posts(15).T1
R
0060
RW 100 Time channel
Normal speed holiday start time 1
Chapter 5 Holding Register (4x) 52
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(15).T2
R
0061
RW 100 Time channel
Normal speed holiday stop time 1
TimeDp.Posts(15).T3
R
0062
RW 100 Time channel
Normal speed holiday start time 2
TimeDp.Posts(15).T4
R
0063
RW 100 Time channel
Normal speed holiday stop time 2
TimeDp.Posts(16).T1
R
0064
RW 100 Time channel
High speed Monday start time 1
TimeDp.Posts(16).T2
R
0065
RW 100 Time channel
High speed Monday stop time 1
TimeDp.Posts(16).T3
R
0066
RW 100 Time channel
High speed Monday start time 2
TimeDp.Posts(16).T4
R
0067
RW 100 Time channel
High speed Monday stop time 2
TimeDp.Posts(17).T1
R
0068
RW 100 Time channel
High speed Tuesday start time 1
TimeDp.Posts(17).T2
R
0069
RW 100 Time channel
High speed Tuesday stop time 1
TimeDp.Posts(17).T3
R
0070
RW 100 Time channel
High speed Tuesday start time 2
TimeDp.Posts(17).T4
R
0071
RW 100 Time channel
High speed Tuesday stop time 2
TimeDp.Posts(18).T1
R
0072
RW 100 Time channel
High speed Wednesday start time 1
TimeDp.Posts(18).T2
R
0073
RW 100 Time channel
High speed Wednesday stop time 1
TimeDp.Posts(18).T3
R
0074
RW 100 Time channel
High speed Wednesday start time 2
TimeDp.Posts(18).T4
R
0075
RW 100 Time channel
High speed Wednesday stop time 2
TimeDp.Posts(19).T1
R
0076
RW 100 Time channel
High speed Thursday start time 1
TimeDp.Posts(19).T2
R
0077
RW 100 Time channel
High speed Thursday stop time 1
TimeDp.Posts(19).T3
R
0078
RW 100 Time channel
High speed Thursday start time 2
TimeDp.Posts(19).T4
R
0079
RW 100 Time channel
High speed Thursday stop time 2
TimeDp.Posts(20).T1
R
0080
RW 100 Time channel
High speed Friday start time 1
TimeDp.Posts(20).T2
R
0081
RW 100 Time channel
High speed Friday stop time 1
TimeDp.Posts(20).T3
R
0082
RW 100 Time channel
High speed Friday start time 2
Chapter 5 Holding Register (4x) 53
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(20).T4
R
0083
RW 100 Time channel
High speed Friday stop time 2
TimeDp.Posts(21).T1
R
0084
RW 100 Time channel
High speed Saturday start time 1
TimeDp.Posts(21).T2
R
0085
RW 100 Time channel
High speed Saturday stop time 1
TimeDp.Posts(21).T3
R
0086
RW 100 Time channel
High speed Saturday start time 2
TimeDp.Posts(21).T4
R
0087
RW 100 Time channel
High speed Saturday stop time 2
TimeDp.Posts(22).T1
R
0088
RW 100 Time channel
High speed Sunday start time 1
TimeDp.Posts(22).T2
R
0089
RW 100 Time channel
High speed Sunday stop time 1
TimeDp.Posts(22).T3
R
0090
RW 100 Time channel
High speed Sunday start time 2
TimeDp.Posts(22).T4
R
0091
RW 100 Time channel
High speed Sunday stop time 2
TimeDp.Posts(23).T1
R
0092
RW 100 Time channel
High speed holiday start time 1
TimeDp.Posts(23).T2
R
0093
RW 100 Time channel
High speed holiday stop time 1
TimeDp.Posts(23).T3
R
0094
RW 100 Time channel
High speed holiday start time 2
TimeDp.Posts(23).T4
R
0095
RW 100 Time channel
High speed holiday stop time 2
TimeDp.Posts(24).T1
R
0096
RW 100 Time channel
Extra time channel 1 Monday start time 1
TimeDp.Posts(24).T2
R
0097
RW 100 Time channel
Extra time channel 1 Monday stop time 1
TimeDp.Posts(24).T3
R
0098
RW 100 Time channel
Extra time channel 1 Monday start time 2
TimeDp.Posts(24).T4
R
0099
RW 100 Time channel
Extra time channel 1 Monday stop time 2
TimeDp.Posts(25).T1
R
0100
RW 100 Time channel
Extra time channel 1 Tuesday start time 1
TimeDp.Posts(25).T2
R
0101
RW 100 Time channel
Extra time channel 1 Tuesday stop time 1
TimeDp.Posts(25).T3
R
0102
RW 100 Time channel
Extra time channel 1 Tuesday start time 2
TimeDp.Posts(25).T4
R
0103
RW 100 Time channel
Extra time channel 1 Tuesday stop time 2
TimeDp.Posts(26).T1
R
0104
RW 100 Time channel
Extra time channel 1 Wednesday start time 1
Chapter 5 Holding Register (4x) 54
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(26).T2
R
0105
RW 100 Time channel
Extra time channel 1 Wednesday stop time 1
TimeDp.Posts(26).T3
R
0106
RW 100 Time channel
Extra time channel 1 Wednesday start time 2
TimeDp.Posts(26).T4
R
0107
RW 100 Time channel
Extra time channel 1 Wednesday stop time 2
TimeDp.Posts(27).T1
R
0108
RW 100 Time channel
Extra time channel 1 Thursday start time 1
TimeDp.Posts(27).T2
R
0109
RW 100 Time channel
Extra time channel 1 Thursday stop time 1
TimeDp.Posts(27).T3
R
0110
RW 100 Time channel
Extra time channel 1 Thursday start time 2
TimeDp.Posts(27).T4
R
0111
RW 100 Time channel
Extra time channel 1 Thursday stop time 2
TimeDp.Posts(28).T1
R
0112
RW 100 Time channel
Extra time channel 1 Friday start time 1
TimeDp.Posts(28).T2
R
0113
RW 100 Time channel
Extra time channel 1 Friday stop time 1
TimeDp.Posts(28).T3
R
0114
RW 100 Time channel
Extra time channel 1 Friday start time 2
TimeDp.Posts(28).T4
R
0115
RW 100 Time channel
Extra time channel 1 Friday stop time 2
TimeDp.Posts(29).T1
R
0116
RW 100 Time channel
Extra time channel 1 Saturday start time 1
TimeDp.Posts(29).T2
R
0117
RW 100 Time channel
Extra time channel 1 Saturday stop time 1
TimeDp.Posts(29).T3
R
0118
RW 100 Time channel
Extra time channel 1 Saturday start time 2
TimeDp.Posts(29).T4
R
0119
RW 100 Time channel
Extra time channel 1 Saturday stop time 2
TimeDp.Posts(30).T1
R
0120
RW 100 Time channel
Extra time channel 1 Sunday start time 1
TimeDp.Posts(30).T2
R
0121
RW 100 Time channel
Extra time channel 1 Sunday stop time 1
TimeDp.Posts(30).T3
R
0122
RW 100 Time channel
Extra time channel 1 Sunday start time 2
TimeDp.Posts(30).T4
R
0123
RW 100 Time channel
Extra time channel 1 Sunday stop time 2
TimeDp.Posts(31).T1
R
0124
RW 100 Time channel
Extra time channel 1 holiday start time 1
TimeDp.Posts(31).T2
R
0125
RW 100 Time channel
Extra time channel 1 holiday stop time 1
TimeDp.Posts(31).T3
R
0126
RW 100 Time channel
Extra time channel 1 holiday start time 2
Chapter 5 Holding Register (4x) 55
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(31).T4
R
0127
RW 100 Time channel
Extra time channel 1 holiday stop time 2
TimeDp.Posts(32).T1
R
0128
RW 100 Time channel
Extra time channel 2 Monday start time 1
TimeDp.Posts(32).T2
R
0129
RW 100 Time channel
Extra time channel 2 Monday stop time 1
TimeDp.Posts(32).T3
R
0130
RW 100 Time channel
Extra time channel 2 Monday start time 2
TimeDp.Posts(32).T4
R
0131
RW 100 Time channel
Extra time channel 2 Monday stop time 2
TimeDp.Posts(33).T1
R
0132
RW 100 Time channel
Extra time channel 2 Tuesday start time 1
TimeDp.Posts(33).T2
R
0133
RW 100 Time channel
Extra time channel 2 Tuesday stop time 1
TimeDp.Posts(33).T3
R
0134
RW 100 Time channel
Extra time channel 2 Tuesday start time 2
TimeDp.Posts(33).T4
R
0135
RW 100 Time channel
Extra time channel 2 Tuesday stop time 2
TimeDp.Posts(34).T1
R
0136
RW 100 Time channel
Extra time channel 2 Wednesday start time 1
TimeDp.Posts(34).T2
R
0137
RW 100 Time channel
Extra time channel 2 Wednesday stop time 1
TimeDp.Posts(34).T3
R
0138
RW 100 Time channel
Extra time channel 2 Wednesday start time 2
TimeDp.Posts(34).T4
R
0139
RW 100 Time channel
Extra time channel 2 Wednesday stop time 2
TimeDp.Posts(35).T1
R
0140
RW 100 Time channel
Extra time channel 2 Thursday start time 1
TimeDp.Posts(35).T2
R
0141
RW 100 Time channel
Extra time channel 2 Thursday stop time 1
TimeDp.Posts(35).T3
R
0142
RW 100 Time channel
Extra time channel 2 Thursday start time 2
TimeDp.Posts(35).T4
R
0143
RW 100 Time channel
Extra time channel 2 Thursday stop time 2
TimeDp.Posts(36).T1
R
0144
RW 100 Time channel
Extra time channel 2 Friday start time 1
TimeDp.Posts(36).T2
R
0145
RW 100 Time channel
Extra time channel 2 Friday stop time 1
TimeDp.Posts(36).T3
R
0146
RW 100 Time channel
Extra time channel 2 Friday start time 2
TimeDp.Posts(36).T4
R
0147
RW 100 Time channel
Extra time channel 2 Friday stop time 2
TimeDp.Posts(37).T1
R
0148
RW 100 Time channel
Extra time channel 2 Saturday start time 1
Chapter 5 Holding Register (4x) 56
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(37).T2
R
0149
RW 100 Time channel
Extra time channel 2 Saturday stop time 1
TimeDp.Posts(37).T3
R
0150
RW 100 Time channel
Extra time channel 2 Saturday start time 2
TimeDp.Posts(37).T4
R
0151
RW 100 Time channel
Extra time channel 2 Saturday stop time 2
TimeDp.Posts(38).T1
R
0152
RW 100 Time channel
Extra time channel 2 Sunday start time 1
TimeDp.Posts(38).T2
R
0153
RW 100 Time channel
Extra time channel 2 Sunday stop time 1
TimeDp.Posts(38).T3
R
0154
RW 100 Time channel
Extra time channel 2 Sunday start time 2
TimeDp.Posts(38).T4
R
0155
RW 100 Time channel
Extra time channel 2 Sunday stop time 2
TimeDp.Posts(39).T1
R
0156
RW 100 Time channel
Extra time channel 2 holiday start time 1
TimeDp.Posts(39).T2
R
0157
RW 100 Time channel
Extra time channel 2 holiday stop time 1
TimeDp.Posts(39).T3
R
0158
RW 100 Time channel
Extra time channel 2 holiday start time 2
TimeDp.Posts(39).T4
R
0159
RW 100 Time channel
Extra time channel 2 holiday stop time 2
TimeDp.Posts(40).T1
R
0160
RW 100 Time channel
Extra time channel 3 Monday start time 1
TimeDp.Posts(40).T2
R
0161
RW 100 Time channel
Extra time channel 3 Monday stop time 1
TimeDp.Posts(40).T3
R
0162
RW 100 Time channel
Extra time channel 3 Monday start time 2
TimeDp.Posts(40).T4
R
0163
RW 100 Time channel
Extra time channel 3 Monday stop time 2
TimeDp.Posts(41).T1
R
0164
RW 100 Time channel
Extra time channel 3 Tuesday start time 1
TimeDp.Posts(41).T2
R
0165
RW 100 Time channel
Extra time channel 3 Tuesday stop time 1
TimeDp.Posts(41).T3
R
0166
RW 100 Time channel
Extra time channel 3 Tuesday start time 2
TimeDp.Posts(41).T4
R
0167
RW 100 Time channel
Extra time channel 3 Tuesday stop time 2
TimeDp.Posts(42).T1
R
0168
RW 100 Time channel
Extra time channel 3 Wednesday start time 1
TimeDp.Posts(42).T2
R
0169
RW 100 Time channel
Extra time channel 3 Wednesday stop time 1
TimeDp.Posts(42).T3
R
0170
RW 100 Time channel
Extra time channel 3 Wednesday start time 2
Chapter 5 Holding Register (4x) 57
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(42).T4
R
0171
RW 100 Time channel
Extra time channel 3 Wednesday stop time 2
TimeDp.Posts(43).T1
R
0172
RW 100 Time channel
Extra time channel 3 Thursday start time 1
TimeDp.Posts(43).T2
R
0173
RW 100 Time channel
Extra time channel 3 Thursday stop time 1
TimeDp.Posts(43).T3
R
0174
RW 100 Time channel
Extra time channel 3 Thursday start time 2
TimeDp.Posts(43).T4
R
0175
RW 100 Time channel
Extra time channel 3 Thursday stop time 2
TimeDp.Posts(44).T1
R
0176
RW 100 Time channel
Extra time channel 3 Friday start time 1
TimeDp.Posts(44).T2
R
0177
RW 100 Time channel
Extra time channel 3 Friday stop time 1
TimeDp.Posts(44).T3
R
0178
RW 100 Time channel
Extra time channel 3 Friday start time 2
TimeDp.Posts(44).T4
R
0179
RW 100 Time channel
Extra time channel 3 Friday stop time 2
TimeDp.Posts(45).T1
R
0180
RW 100 Time channel
Extra time channel 3 Saturday start time 1
TimeDp.Posts(45).T2
R
0181
RW 100 Time channel
Extra time channel 3 Saturday stop time 1
TimeDp.Posts(45).T3
R
0182
RW 100 Time channel
Extra time channel 3 Saturday start time 2
TimeDp.Posts(45).T4
R
0183
RW 100 Time channel
Extra time channel 3 Saturday stop time 2
TimeDp.Posts(46).T1
R
0184
RW 100 Time channel
Extra time channel 3 Sunday start time 1
TimeDp.Posts(46).T2
R
0185
RW 100 Time channel
Extra time channel 3 Sunday stop time 1
TimeDp.Posts(46).T3
R
0186
RW 100 Time channel
Extra time channel 3 Sunday start time 2
TimeDp.Posts(46).T4
R
0187
RW 100 Time channel
Extra time channel 3 Sunday stop time 2
TimeDp.Posts(47).T1
R
0188
RW 100 Time channel
Extra time channel 3 holiday start time 1
TimeDp.Posts(47).T2
R
0189
RW 100 Time channel
Extra time channel 3 holiday stop time 1
TimeDp.Posts(47).T3
R
0190
RW 100 Time channel
Extra time channel 3 holiday start time 2
TimeDp.Posts(47).T4
R
0191
RW 100 Time channel
Extra time channel 3 holiday stop time 2
TimeDp.Posts(48).T1
R
0192
RW 100 Time channel
Extra time channel 4 Monday start time 1
Chapter 5 Holding Register (4x) 58
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(48).T2
R
0193
RW 100 Time channel
Extra time channel 4 Monday stop time 1
TimeDp.Posts(48).T3
R
0194
RW 100 Time channel
Extra time channel 4 Monday start time 2
TimeDp.Posts(48).T4
R
0195
RW 100 Time channel
Extra time channel 4 Monday stop time 2
TimeDp.Posts(49).T1
R
0196
RW 100 Time channel
Extra time channel 4 Tuesday start time 1
TimeDp.Posts(49).T2
R
0197
RW 100 Time channel
Extra time channel 4 Tuesday stop time 1
TimeDp.Posts(49).T3
R
0198
RW 100 Time channel
Extra time channel 4 Tuesday start time 2
TimeDp.Posts(49).T4
R
0199
RW 100 Time channel
Extra time channel 4 Tuesday stop time 2
TimeDp.Posts(50).T1
R
0200
RW 100 Time channel
Extra time channel 4 Wednesday start time 1
TimeDp.Posts(50).T2
R
0201
RW 100 Time channel
Extra time channel 4 Wednesday stop time 1
TimeDp.Posts(50).T3
R
0202
RW 100 Time channel
Extra time channel 4 Wednesday start time 2
TimeDp.Posts(50).T4
R
0203
RW 100 Time channel
Extra time channel 4 Wednesday stop time 2
TimeDp.Posts(51).T1
R
0204
RW 100 Time channel
Extra time channel 4 Thursday start time 1
TimeDp.Posts(51).T2
R
0205
RW 100 Time channel
Extra time channel 4 Thursday stop time 1
TimeDp.Posts(51).T3
R
0206
RW 100 Time channel
Extra time channel 4 Thursday start time 2
TimeDp.Posts(51).T4
R
0207
RW 100 Time channel
Extra time channel 4 Thursday stop time 2
TimeDp.Posts(52).T1
R
0208
RW 100 Time channel
Extra time channel 4 Friday start time 1
TimeDp.Posts(52).T2
R
0209
RW 100 Time channel
Extra time channel 4 Friday stop time 1
TimeDp.Posts(52).T3
R
0210
RW 100 Time channel
Extra time channel 4 Friday start time 2
TimeDp.Posts(52).T4
R
0211
RW 100 Time channel
Extra time channel 4 Friday stop time 2
TimeDp.Posts(53).T1
R
0212
RW 100 Time channel
Extra time channel 4 Saturday start time 1
TimeDp.Posts(53).T2
R
0213
RW 100 Time channel
Extra time channel 4 Saturday stop time 1
TimeDp.Posts(53).T3
R
0214
RW 100 Time channel
Extra time channel 4 Saturday start time 2
Chapter 5 Holding Register (4x) 59
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeDp.Posts(53).T4
R
0215
RW 100 Time channel
Extra time channel 4 Saturday stop time 2
TimeDp.Posts(54).T1
R
0216
RW 100 Time channel
Extra time channel 4 Sunday start time 1
TimeDp.Posts(54).T2
R
0217
RW 100 Time channel
Extra time channel 4 Sunday stop time 1
TimeDp.Posts(54).T3
R
0218
RW 100 Time channel
Extra time channel 4 Sunday start time 2
TimeDp.Posts(54).T4
R
0219
RW 100 Time channel
Extra time channel 4 Sunday stop time 2
TimeDp.Posts(55).T1
R
0220
RW 100 Time channel
Extra time channel 4 holiday start time 1
TimeDp.Posts(55).T2
R
0221
RW 100 Time channel
Extra time channel 4 holiday stop time 1
TimeDp.Posts(55).T3
R
0222
RW 100 Time channel
Extra time channel 4 holiday start time 2
TimeDp.Posts(55).T4
R
0223
RW 100 Time channel
Extra time channel 4 holiday stop time 2
TimeHp.Posts(0).FromDate
R
0224
RW 100 Time channel
Holiday period 1 start date (MM.DD)
TimeHp.Posts(0).ToDate
R
0225
RW 100 Time channel
Holiday period 1 end date (MM.DD)
TimeHp.Posts(1).FromDate
R
0226
RW 100 Time channel
Holiday period 2 start date (MM.DD)
TimeHp.Posts(1).ToDate
R
0227
RW 100 Time channel
Holiday period 2 end date (MM.DD)
TimeHp.Posts(2).FromDate
R
0228
RW 100 Time channel
Holiday period 3 start date (MM.DD)
TimeHp.Posts(2).ToDate
R
0229
RW 100 Time channel
Holiday period 3 end date (MM.DD)
TimeHp.Posts(3).FromDate
R
0230
RW 100 Time channel
Holiday period 4 start date (MM.DD)
TimeHp.Posts(3).ToDate
R
0231
RW 100 Time channel
Holiday period 4 end date (MM.DD)
TimeHp.Posts(4).FromDate
R
0232
RW 100 Time channel
Holiday period 5 start date (MM.DD)
TimeHp.Posts(4).ToDate
R
0233
RW 100 Time channel
Holiday period 5 end date (MM.DD)
TimeHp.Posts(5).FromDate
R
0234
RW 100 Time channel
Holiday period 6 start date (MM.DD)
TimeHp.Posts(5).ToDate
R
0235
RW 100 Time channel
Holiday period 6 end date (MM.DD)
TimeHp.Posts(6).FromDate
R
0236
RW 100 Time channel
Holiday period 7 start date (MM.DD)
Chapter 5 Holding Register (4x) 60
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeHp.Posts(6).ToDate
R
0237
RW 100 Time channel
Holiday period 7 end date (MM.DD)
TimeHp.Posts(7).FromDate
R
0238
RW 100 Time channel
Holiday period 8 start date (MM.DD)
TimeHp.Posts(7).ToDate
R
0239
RW 100 Time channel
Holiday period 8 end date (MM.DD)
TimeHp.Posts(8).FromDate
R
0240
RW 100 Time channel
Holiday period 9 start date (MM.DD)
TimeHp.Posts(8).ToDate
R
0241
RW 100 Time channel
Holiday period 9 end date (MM.DD)
TimeHp.Posts(9).FromDate
R
0242
RW 100 Time channel
Holiday period 10 start date (MM.DD)
TimeHp.Posts(9).ToDate
R
0243
RW 100 Time channel
Holiday period 10 end date (MM.DD)
TimeHp.Posts(10).FromDate
R
0244
RW 100 Time channel
Holiday period 11 start date (MM.DD)
TimeHp.Posts(10).ToDate
R
0245
RW 100 Time channel
Holiday period 11 end date (MM.DD)
TimeHp.Posts(11).FromDate
R
0246
RW 100 Time channel
Holiday period 12 start date (MM.DD)
TimeHp.Posts(11).ToDate
R
0247
RW 100 Time channel
Holiday period 12 end date (MM.DD)
TimeHp.Posts(12).FromDate
R
0248
RW 100 Time channel
Holiday period 13 start date (MM.DD)
TimeHp.Posts(12).ToDate
R
0249
RW 100 Time channel
Holiday period 13 end date (MM.DD)
TimeHp.Posts(13).FromDate
R
0250
RW 100 Time channel
Holiday period 14 start date (MM.DD)
TimeHp.Posts(13).ToDate
R
0251
RW 100 Time channel
Holiday period 14 end date (MM.DD)
TimeHp.Posts(14).FromDate
R
0252
RW 100 Time channel
Holiday period 15 start date (MM.DD)
TimeHp.Posts(14).ToDate
R
0253
RW 100 Time channel
Holiday period 15 end date (MM.DD)
TimeHp.Posts(15).FromDate
R
0254
RW 100 Time channel
Holiday period 16 start date (MM.DD)
TimeHp.Posts(15).ToDate
R
0255
RW 100 Time channel
Holiday period 16 end date (MM.DD)
TimeHp.Posts(16).FromDate
R
0256
RW 100 Time channel
Holiday period 17 start date (MM.DD)
TimeHp.Posts(16).ToDate
R
0257
RW 100 Time channel
Holiday period 17 end date (MM.DD)
TimeHp.Posts(17).FromDate
R
0258
RW 100 Time channel
Holiday period 18 start date (MM.DD)
Chapter 5 Holding Register (4x) 61
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimeHp.Posts(17).ToDate
R
0259
RW 100 Time channel
Holiday period 18 end date (MM.DD)
TimeHp.Posts(18).FromDate
R
0260
RW 100 Time channel
Holiday period 19 start date (MM.DD)
TimeHp.Posts(18).ToDate
R
0261
RW 100 Time channel
Holiday period 19 end date (MM.DD)
TimeHp.Posts(19).FromDate
R
0262
RW 100 Time channel
Holiday period 20 start date (MM.DD)
TimeHp.Posts(19).ToDate
R
0263
RW 100 Time channel
Holiday period 20 end date (MM.DD)
TimeHp.Posts(20).FromDate
R
0264
RW 100 Time channel
Holiday period 21 start date (MM.DD)
TimeHp.Posts(20).ToDate
R
0265
RW 100 Time channel
Holiday period 21 end date (MM.DD)
TimeHp.Posts(21).FromDate
R
0266
RW 100 Time channel
Holiday period 22 start date (MM.DD)
TimeHp.Posts(21).ToDate
R
0267
RW 100 Time channel
Holiday period 22 end date (MM.DD)
TimeHp.Posts(22).FromDate
R
0268
RW 100 Time channel
Holiday period 23 start date (MM.DD)
TimeHp.Posts(22).ToDate
R
0269
RW 100 Time channel
Holiday period 23 end date (MM.DD)
TimeHp.Posts(23).FromDate
R
0270
RW 100 Time channel
Holiday period 24 start date (MM.DD)
TimeHp.Posts(23).ToDate
R
0271
RW 100 Time channel
Holiday period 24 end date (MM.DD)
TimePro.TC_FanLowSpeed_Status
X
0272
RW
MSV, 30272
1 Operation
override
Manual/Auto Low Speed time channel Modbus 0=Manual off 1=Manual on 2=Forced off 3=Forced on 4=Auto Bacnet +1 offset for corresponding Modbus
TimePro.TC_FanNormalSpeed_Status
X
0273
RW
MSV, 30273
1 Operation
override
Manual/Auto Normal Speed time channel (See signal list for FanLowSpeed_Status)
TimePro.TC_FanHighSpeed_Status
X
0274
RW
MSV, 30274
1 Operation
override
Manual/Auto High Speed time channel (See signal list for FanLowSpeed_Status)
Chapter 5 Holding Register (4x) 62
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
TimePro.TC_Extra1_Status
X
0275
RW
MSV, 30275
1 Operation
override
Manual/Auto Timer output 1 (See signal list for FanLowSpeed_Status)
TimePro.TC_Extra2_Status
X
0276
RW
MSV, 30276
1 Operation
override
Manual/Auto Timer output 2 (See signal list for FanLowSpeed_Status)
TimePro.TC_Extra3_Status
X
0277
RW
MSV, 30277
1 Operation
override
Manual/Auto Timer output 3 (See signal list for FanLowSpeed_Status)
TimePro.TC_Extra4_Status
X
0278
RW
MSV, 30278
1 Operation
override
Manual/Auto Timer output 4 (See signal list for FanLowSpeed_Status)
QSystem.Minute
X
0280
RW
AV, 30280
1 Real Time Clock
Real time clock: Minute 0-59
QSystem.Hour
X
0281
RW
AV, 30281
1 Real Time Clock
Real time clock: Hour 0-23
QSystem.WDay
X
0282
RW
AV, 30282
1 Real Time Clock
Real time clock: Day of Week 1-7, 1=Monday
QSystem.Week
X
0283
RW
AV, 30283
1 Real Time Clock
Real time clock: Week number 1-53
QSystem.Date
X
0284
RW
AV, 30284
1 Real Time Clock
Real time clock: Day of month 1-31
QSystem.Month
X
0285
RW
AV, 30285
1 Real Time Clock
Real time clock: Month 1-12
QSystem.Year
X
0286
RW
AV, 30286
1 Real Time Clock
Real time clock: Year 0-99
AlaData.Ala_MalfunctionSAF1_DelayValue
I
0287
RW 1 Alarm setting
Alarm delay malfunction supply air fan 1
AlaData.Ala_MalfunctionSAF2_DelayValue
I
0288
RW 1 Alarm setting
Alarm delay malfunction supply air fan 2
AlaData.Ala_MalfunctionSAF3_DelayValue
I
0289
RW 1 Alarm setting
Alarm delay malfunction supply air fan 3
AlaData.Ala_MalfunctionSAF4_DelayValue
I
0290
RW 1 Alarm setting
Alarm delay malfunction supply air fan 4
AlaData.Ala_MalfunctionSAF5_DelayValue
I
0291
RW 1 Alarm setting
Alarm delay malfunction supply air fan 5
AlaData.Ala_MalfunctionEAF1_DelayValue
I
0292
RW 1 Alarm setting
Alarm delay malfunction extract air fan 1
AlaData.Ala_MalfunctionEAF2_DelayValue
I
0293
RW 1 Alarm setting
Alarm delay malfunction extract air fan 2
AlaData.Ala_MalfunctionEAF3_DelayValue
I
0294
RW 1 Alarm setting
Alarm delay malfunction extract air fan 3
AlaData.Ala_MalfunctionEAF4_DelayValue
I
0295
RW 1 Alarm setting
Alarm delay malfunction extract air fan 4
Chapter 5 Holding Register (4x) 63
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_MalfunctionEAF5_DelayValue
I
0296
RW 1 Alarm setting
Alarm delay malfunction extract air fan 5
AlaData.Ala_AlarmSAF1_DelayValue
I
0297
RW 1 Alarm setting
Alarm delay alarm supply air fan 1
AlaData.Ala_AlarmSAF2_DelayValue
I
0298
RW 1 Alarm setting
Alarm delay alarm supply air fan 2
AlaData.Ala_AlarmSAF3_DelayValue
I
0299
RW 1 Alarm setting
Alarm delay alarm supply air fan 3
AlaData.Ala_AlarmSAF4_DelayValue
I
0300
RW 1 Alarm setting
Alarm delay alarm supply air fan 4
AlaData.Ala_AlarmSAF5_DelayValue
I
0301
RW 1 Alarm setting
Alarm delay alarm supply air fan 5
AlaData.Ala_AlarmEAF1_DelayValue
I
0302
RW 1 Alarm setting
Alarm delay alarm extract air fan 1
AlaData.Ala_AlarmEAF2_DelayValue
I
0303
RW 1 Alarm setting
Alarm delay alarm extract air fan 2
AlaData.Ala_AlarmEAF3_DelayValue
I
0304
RW 1 Alarm setting
Alarm delay alarm extract air fan 3
AlaData.Ala_AlarmEAF4_DelayValue
I
0305
RW 1 Alarm setting
Alarm delay alarm extract air fan 4
AlaData.Ala_AlarmEAF5_DelayValue
I
0306
RW 1 Alarm setting
Alarm delay alarm extract air fan 5
AlaData.Ala_WarningSAF1_DelayValue
I
0307
RW 1 Alarm setting
Alarm delay warning supply air fan 1
AlaData.Ala_WarningSAF2_DelayValue
I
0308
RW 1 Alarm setting
Alarm delay warning supply air fan 2
AlaData.Ala_WarningSAF3_DelayValue
I
0309
RW 1 Alarm setting
Alarm delay warning supply air fan 3
AlaData.Ala_WarningSAF4_DelayValue
I
0310
RW 1 Alarm setting
Alarm delay warning supply air fan 4
AlaData.Ala_WarningSAF5_DelayValue
I
0311
RW 1 Alarm setting
Alarm delay warning supply air fan 5
AlaData.Ala_WarningEAF1_DelayValue
I
0312
RW 1 Alarm setting
Alarm delay warning extract air fan 1
AlaData.Ala_WarningEAF2_DelayValue
I
0313
RW 1 Alarm setting
Alarm delay warning extract air fan 2
AlaData.Ala_WarningEAF3_DelayValue
I
0314
RW 1 Alarm setting
Alarm delay warning extract air fan 3
AlaData.Ala_WarningEAF4_DelayValue
I
0315
RW 1 Alarm setting
Alarm delay warning extract air fan 4
AlaData.Ala_WarningEAF5_DelayValue
I
0316
RW 1 Alarm setting
Alarm delay warning extract air fan 5
AlaData.Ala_ExternalRunSAF_DelayValue
I
0317
RW 1 Alarm setting
Alarm delay external operation supply air fan
Chapter 5 Holding Register (4x) 64
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ExternalRunEAF_DelayValue
I
0318
RW 1 Alarm setting
Alarm delay external operation extract air fan
AlaData.Ala_ExternalRunMotor1_DelayValue
I
0319
RW 1 Alarm setting
Alarm delay extra fan motor 1 running
AlaData.Ala_ExternalRunMotor2_DelayValue
I
0320
RW 1 Alarm setting
Alarm delay extra fan motor 2 running
AlaData.Ala_MalfunctionPumpHeater_DelayValue
I
0321
RW 1 Alarm setting
Alarm delay malfunction pump heater
AlaData.Ala_MalfunctionPumpCooler_DelayValue
I
0322
RW 1 Alarm setting
Alarm delay malfunction pump cooler
AlaData.Ala_MalfunctionPumpExchanger_DelayValue
I
0323
RW 1 Alarm setting
Alarm delay malfunction pump exchanger
AlaData.Ala_MalfunctionFireDamper_DelayValue
I
0324
RW 1 Alarm setting
Alarm delay malfunction fire damper
AlaData.Ala_MalfunctionDamper_DelayValue
I
0325
RW 1 Alarm setting
Alarm delay malfunction damper
AlaData.Ala_MalfunctionMotor1_DelayValue
I
0326
RW 1 Alarm setting
Alarm delay malfunction extra fan motor 1
AlaData.Ala_MalfunctionMotor2_DelayValue
I
0327
RW 1 Alarm setting
Alarm delay malfunction extra fan motor 2
AlaData.Ala_FireDamperExerciseStop_DelayValue
I
0328
RW 1 Alarm setting
Alarm delay fire damper exercise stop
AlaData.Ala_MalfunctionPumpSequence1_DelayValue
I
0329
RW 1 Alarm setting
Alarm delay malfunction pump sequence-A
AlaData.Ala_MalfunctionPumpSequence2_DelayValue
I
0330
RW 1 Alarm setting
Alarm delay malfunction pump sequence-B
AlaData.Ala_MalfunctionPumpSequence3_DelayValue
I
0331
RW 1 Alarm setting
Alarm delay malfunction pump sequence-C
AlaData.Ala_MalfunctionPumpSequence4_DelayValue
I
0332
RW 1 Alarm setting
Alarm delay malfunction pump sequence-D
AlaData.Ala_MalfunctionPumpSequence5_DelayValue
I
0333
RW 1 Alarm setting
Alarm delay malfunction pump sequence-E
AlaData.Ala_MalfunctionPumpSequence6_DelayValue
I
0334
RW 1 Alarm setting
Alarm delay malfunction pump sequence-F
AlaData.Ala_MalfunctionPumpSequence7_DelayValue
I
0335
RW 1 Alarm setting
Alarm delay malfunction pump sequence-G
AlaData.Ala_MalfunctionPumpSequence8_DelayValue
I
0336
RW 1 Alarm setting
Alarm delay malfunction pump sequence-H
AlaData.Ala_MalfunctionPumpSequence9_DelayValue
I
0337
RW 1 Alarm setting
Alarm delay malfunction pump sequence-I
AlaData.Ala_MalfunctionPumpSequence10_DelayValue
I
0338
RW 1 Alarm setting
Alarm delay malfunction pump sequence-J
AlaData.Ala_FilterGuard1_DelayValue
I
0339
RW 1 Alarm setting
Alarm delay filter alarm supply air
Chapter 5 Holding Register (4x) 65
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_FilterGuard2_DelayValue
I
0340
RW 1 Alarm setting
Alarm delay filter alarm extract air
AlaData.Ala_FlowGuard_DelayValue
I
0341
RW 1 Alarm setting
Alarm delay alarm low air flow
AlaData.Ala_ExternalFrostGuard_DelayValue
I
0342
RW 1 Alarm setting
Alarm delay freeze protection guard
AlaData.Ala_DeicingGuard_DelayValue
I
0343
RW 1 Alarm setting
Alarm delay defrosting guard exchanger
AlaData.Ala_FireAlarm_DelayValue
I
0344
RW 1 Alarm setting
Alarm delay fire alarm
AlaData.Ala_SmokeAlarm_DelayValue
I
0345
RW 1 Alarm setting
Alarm delay smoke alarm
AlaData.Ala_ExternalSwitch_DelayValue
I
0346
RW 1 Alarm setting
Alarm delay external stop
AlaData.Ala_ExternalAlarm_DelayValue
I
0347
RW 1 Alarm setting
Alarm delay external alarm
AlaData.Ala_ServiceStop_DelayValue
I
0348
RW 1 Alarm setting
Alarm delay service stop
AlaData.Ala_ElectricOverheat_DelayValue
I
0349
RW 1 Alarm setting
Alarm delay electric heater is overheated
AlaData.Ala_FrostRisk_DelayValue
I
0350
RW 1 Alarm setting
Alarm delay warning freeze protection
AlaData.Ala_LowEfficiency_DelayValue
I
0351
RW 1 Alarm setting
Alarm delay low efficiency exchanger
AlaData.Ala_AnalogueDeicing_DelayValue
I
0352
RW 1 Alarm setting
Alarm delay defrosting alarm
AlaData.Ala_RotationguardExchanger_DelayValue
I
0353
RW 1 Alarm setting
Alarm delay rotary exchanger alarm
AlaData.Ala_ExtraAlarm1_DelayValue
I
0354
RW 1 Alarm setting
Alarm delay extra alarm 1
AlaData.Ala_ExtraAlarm2_DelayValue
I
0355
RW 1 Alarm setting
Alarm delay extra alarm 2
AlaData.Ala_ExtraAlarm3_DelayValue
I
0356
RW 1 Alarm setting
Alarm delay extra alarm 3
AlaData.Ala_ExtraAlarm4_DelayValue
I
0357
RW 1 Alarm setting
Alarm delay extra alarm 4
AlaData.Ala_ExtraAlarm5_DelayValue
I
0358
RW 1 Alarm setting
Alarm delay extra alarm 5
AlaData.Ala_ExtraAlarm6_DelayValue
I
0359
RW 1 Alarm setting
Alarm delay extra alarm 6
AlaData.Ala_ExtraAlarm7_DelayValue
I
0360
RW 1 Alarm setting
Alarm delay extra alarm 7
AlaData.Ala_ExtraAlarm8_DelayValue
I
0361
RW 1 Alarm setting
Alarm delay extra alarm 8
Chapter 5 Holding Register (4x) 66
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ExtraAlarm9_DelayValue
I
0362
RW 1 Alarm setting
Alarm delay extra alarm 9
AlaData.Ala_ExtraAlarm10_DelayValue
I
0363
RW 1 Alarm setting
Alarm delay extra alarm 10
AlaData.Ala_BatteryFail_DelayValue
I
0364
RW 1 Alarm setting
Alarm delay internal battery error
AlaData.Ala_Service_DelayValue
I
0365
RW 1 Alarm setting
Alarm delay alarm service interval
AlaData.Ala_RestartBlocked_DelayValue
I
0366
RW 1 Alarm setting
Alarm delay restart blocked after power on
AlaData.Ala_ControlErrorSupplyTemp_DelayValue
I
0367
RW 1 Alarm setting
Alarm delay deviation alarm supply air temperature
AlaData.Ala_ControlErrorSAF_DelayValue
I
0368
RW 1 Alarm setting
Alarm delay deviation alarm supply air fan
AlaData.Ala_ControlErrorEAF_DelayValue
I
0369
RW 1 Alarm setting
Alarm delay deviation alarm extract air fan
AlaData.Ala_ControlErrorHumidity_DelayValue
I
0370
RW 1 Alarm setting
Alarm delay deviation alarm humidity control
AlaData.Ala_ControlErrorExtraController_DelayValue
I
0371
RW 1 Alarm setting
Alarm delay deviation alarm extra controller
AlaData.Ala_HighTempSupply_DelayValue
I
0372
RW 1 Alarm setting
Alarm delay high supply air temperature
AlaData.Ala_LowTempSupply_DelayValue
I
0373
RW 1 Alarm setting
Alarm delay low supply air temperature
AlaData.Ala_MaxLimitTempSupply_DelayValue
I
0374
RW 1 Alarm setting
Alarm delay supply air temperature max limit
AlaData.Ala_MinLimitTempSupply_DelayValue
I
0375
RW 1 Alarm setting
Alarm delay supply air temperature min limit
AlaData.Ala_HighTempRoom_DelayValue
I
0376
RW 1 Alarm setting
Alarm delay high room temperature
AlaData.Ala_LowTempRoom_DelayValue
I
0377
RW 1 Alarm setting
Alarm delay low room temperature
AlaData.Ala_HighTempExtract_DelayValue
I
0378
RW 1 Alarm setting
Alarm delay high extract air temperature
AlaData.Ala_LowTempExtract_DelayValue
I
0379
RW 1 Alarm setting
Alarm delay low extract air temperature
AlaData.Ala_HighTempOutdoor_DelayValue
I
0380
RW 1 Alarm setting
Alarm delay high outdoor air temperature
AlaData.Ala_LowTempOutdoor_DelayValue
I
0381
RW 1 Alarm setting
Alarm delay low outdoor air temperature
AlaData.Ala_LowTempFrostGuard1_DelayValue
I
0382
RW 1 Alarm setting
Alarm delay freeze protection alarm 1
Chapter 5 Holding Register (4x) 67
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_LowTempFrostGuard2_DelayValue
I
0383
RW 1 Alarm setting
Alarm delay freeze protection alarm 2
AlaData.Ala_LowTempFrostGuard3_DelayValue
I
0384
RW 1 Alarm setting
Alarm delay freeze protection alarm 3
AlaData.Ala_HighTempExtraSensor1_DelayValue
I
0385
RW 1 Alarm setting
Alarm delay high temperature extra sensor 1
AlaData.Ala_LowTempExtraSensor1_DelayValue
I
0386
RW 1 Alarm setting
Alarm delay low temperature extra sensor 1
AlaData.Ala_HighTempExtraSensor2_DelayValue
I
0387
RW 1 Alarm setting
Alarm delay high temperature extra sensor 2
AlaData.Ala_LowTempExtraSensor2_DelayValue
I
0388
RW 1 Alarm setting
Alarm delay low temperature extra sensor 2
AlaData.Ala_HighTempExtraSensor3_DelayValue
I
0389
RW 1 Alarm setting
Alarm delay high temperature extra sensor 3
AlaData.Ala_LowTempExtraSensor3_DelayValue
I
0390
RW 1 Alarm setting
Alarm delay low temperature extra sensor 3
AlaData.Ala_HighTempExtraSensor4_DelayValue
I
0391
RW 1 Alarm setting
Alarm delay high temperature extra sensor 4
AlaData.Ala_LowTempExtraSensor4_DelayValue
I
0392
RW 1 Alarm setting
Alarm delay low temperature extra sensor 4
AlaData.Ala_HighTempExtraSensor5_DelayValue
I
0393
RW 1 Alarm setting
Alarm delay high temperature extra sensor 5
AlaData.Ala_LowTempExtraSensor5_DelayValue
I
0394
RW 1 Alarm setting
Alarm delay low temperature extra sensor 5
AlaData.Ala_HighTempSelectedSensor1_DelayValue
I
0395
RW 1 Alarm setting
Alarm delay high temperature selected sensor 1
AlaData.Ala_LowTempSelectedSensor1_DelayValue
I
0396
RW 1 Alarm setting
Alarm delay low temperature selected sensor 1
AlaData.Ala_HighTempSelectedSensor2_DelayValue
I
0397
RW 1 Alarm setting
Alarm delay high temperature selected sensor 2
AlaData.Ala_LowTempSelectedSensor2_DelayValue
I
0398
RW 1 Alarm setting
Alarm delay low temperature selected sensor 2
AlaData.Ala_ManualControlUnit_DelayValue
I
0399
RW 1 Alarm setting
Alarm delay manual operation air handling unit
AlaData.Ala_ManualControlSupply_DelayValue
I
0400
RW 1 Alarm setting
Alarm delay manual operation supply air
AlaData.Ala_ManualControlSAF_DelayValue
I
0401
RW 1 Alarm setting
Alarm delay manual operation supply air fan
AlaData.Ala_ManualControlEAF_DelayValue
I
0402
RW 1 Alarm setting
Alarm delay manual operation extract air fan
AlaData.Ala_ManualControlHeater_DelayValue
I
0403
RW 1 Alarm setting
Alarm delay manual operation heater
AlaData.Ala_ManualControlExchanger_DelayValue
I
0404
RW 1 Alarm setting
Alarm delay manual operation exchanger
Chapter 5 Holding Register (4x) 68
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ManualControlCooler_DelayValue
I
0405
RW 1 Alarm setting
Alarm delay manual operation cooler
AlaData.Ala_ManualControlDamper_DelayValue
I
0406
RW 1 Alarm setting
Alarm delay manual operation damper
AlaData.Ala_ManualControlPumpHeater_DelayValue
I
0407
RW 1 Alarm setting
Alarm delay manual operation pump heater
AlaData.Ala_ManualControlPumpExchanger_DelayValu e
I
0408
RW 1 Alarm setting
Alarm delay manual operation pump exchanger AlaData.Ala_ManualControlPumpCooler_DelayValue
I
0409
RW 1 Alarm setting
Alarm delay manual operation pump cooler
AlaData.Ala_ManualControlDamperRecirculation_Dela yValue
I
0410
RW 1 Alarm setting
Alarm delay manual operation damper recirculation
AlaData.Ala_ManualControlDamperOutdoor_DelayValu e
I
0411
RW 1 Alarm setting
Alarm delay manual operation damper outdoor air
AlaData.Ala_ManualControlDamperExhaust_DelayValu e
I
0412
RW 1 Alarm setting
Alarm delay manual operation damper exhaust air
AlaData.Ala_ManualControlDamperFire_DelayValue
I
0413
RW 1 Alarm setting
Alarm delay manual operation fire damper
AlaData.Ala_ManualControlSequence1_DelayValue
I
0414
RW 1 Alarm setting
Alarm delay manual control sequence-A
AlaData.Ala_ManualControlSequence2_DelayValue
I
0415
RW 1 Alarm setting
Alarm delay manual control sequence-B
AlaData.Ala_ManualControlSequence3_DelayValue
I
0416
RW 1 Alarm setting
Alarm delay manual control sequence-C
AlaData.Ala_ManualControlSequence4_DelayValue
I
0417
RW 1 Alarm setting
Alarm delay manual control sequence-D
AlaData.Ala_ManualControlSequence5_DelayValue
I
0418
RW 1 Alarm setting
Alarm delay manual control sequence-E
AlaData.Ala_ManualControlSequence6_DelayValue
I
0419
RW 1 Alarm setting
Alarm delay manual control sequence-F
AlaData.Ala_ManualControlSequence7_DelayValue
I
0420
RW 1 Alarm setting
Alarm delay manual control sequence-G
AlaData.Ala_ManualControlSequence8_DelayValue
I
0421
RW 1 Alarm setting
Alarm delay manual control sequence-H
AlaData.Ala_ManualControlSequence9_DelayValue
I
0422
RW 1 Alarm setting
Alarm delay manual control sequence-I
AlaData.Ala_ManualControlSequence10_DelayValue
I
0423
RW 1 Alarm setting
Alarm delay manual control sequence-J
AlaData.Ala_ManualControlOutput_DelayValue
I
0424
RW 1 Alarm setting
Alarm delay output in manual operation
Chapter 5 Holding Register (4x) 69
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ManualControlInput_DelayValue
I
0425
RW 1 Alarm setting
Alarm delay input in manual operation
AlaData.Ala_ManualControlExtraController_DelayValu e
I
0426
RW 1 Alarm setting
Alarm delay manual operation extra controller
AlaData.Ala_ManualControlMotor1_DelayValue
I
0427
RW 1 Alarm setting
Alarm delay manual operation external fan motor 1
AlaData.Ala_ManualControlMotor2_DelayValue
I
0428
RW 1 Alarm setting
Alarm delay manual operation external fan motor 2
AlaData.Ala_ManualControlPretreatment_DelayValue
I
0429
RW 1 Alarm setting
Alarm delay manual operation pretreatment
AlaData.Ala_SensorErrorTempOutdoor_DelayValue
I
0430
RW 1 Alarm setting
Alarm delay sensor error outdoor air temperature
AlaData.Ala_SensorErrorTempIntake_DelayValue
I
0431
RW 1 Alarm setting
Alarm delay sensor error intake air temperature
AlaData.Ala_SensorErrorTempSupply_DelayValue
I
0432
RW 1 Alarm setting
Alarm delay sensor error supply air temperature
AlaData.Ala_SensorErrorTempExhaust_DelayValue
I
0433
RW 1 Alarm setting
Alarm delay sensor error exhaust air temperature
AlaData.Ala_SensorErrorTempExtract_DelayValue
I
0434
RW 1 Alarm setting
Alarm delay sensor error extract air temperature
AlaData.Ala_SensorErrorTempRoom1_DelayValue
I
0435
RW 1 Alarm setting
Alarm delay sensor error room temperature 1
AlaData.Ala_SensorErrorTempRoom2_DelayValue
I
0436
RW 1 Alarm setting
Alarm delay sensor error room temperature 2
AlaData.Ala_SensorErrorTempRoom3_DelayValue
I
0437
RW 1 Alarm setting
Alarm delay sensor error room temperature 3
AlaData.Ala_SensorErrorTempRoom4_DelayValue
I
0438
RW 1 Alarm setting
Alarm delay sensor error room temperature 4
AlaData.Ala_SensorErrorPressureSAF_DelayValue
I
0439
RW 1 Alarm setting
Alarm delay sensor error pressure supply air
AlaData.Ala_SensorErrorPressureEAF_DelayValue
I
0440
RW 1 Alarm setting
Alarm delay sensor error pressure extract air
AlaData.Ala_SensorErrorFlowSAF_DelayValue
I
0441
RW 1 Alarm setting
Alarm delay sensor error flow supply air
AlaData.Ala_SensorErrorFlowEAF_DelayValue
I
0442
RW 1 Alarm setting
Alarm delay sensor error flow extract air
Chapter 5 Holding Register (4x) 70
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_SensorPressureExchangerSAF_DelayValue
I
0443
RW 1 Alarm setting
Alarm delay sensor error flow exchanger supply air
AlaData.Ala_SensorPressureExchangerEAF_DelayValue
I
0444
RW 1 Alarm setting
Alarm delay sensor error pressure exchanger extract air
AlaData.Ala_SensorErrorTempDeicing_DelayValue
I
0445
RW 1 Alarm setting
Alarm delay sensor error defrosting temperature
AlaData.Ala_SensorErrorTempFrost1_DelayValue
I
0446
RW 1 Alarm setting
Alarm delay sensor error freeze protection temperature 1
AlaData.Ala_SensorErrorTempFrost2_DelayValue
I
0447
RW 1 Alarm setting
Alarm delay sensor error freeze protection temperature 2
AlaData.Ala_SensorErrorTempFrost3_DelayValue
I
0448
RW 1 Alarm setting
Alarm delay sensor error freeze protection temperature 3
AlaData.Ala_SensorErrorCO2_DelayValue
I
0449
RW 1 Alarm setting
Alarm delay sensor error CO2 room/extract air
AlaData.Ala_SensorErrorHumidityRoom_DelayValue
I
0450
RW 1 Alarm setting
Alarm delay sensor error humidity room/extract air
AlaData.Ala_SensorErrorHumidityDuct_DelayValue
I
0451
RW 1 Alarm setting
Alarm delay sensor error humidity supply air
AlaData.Ala_SensorErrorTempExtraController_DelayVa lue
I
0452
RW 1 Alarm setting
Alarm delay sensor error extra controller
AlaData.Ala_SensorErrorExtCtrlSAF_DelayValue
I
0453
RW 1 Alarm setting
Alarm delay signal error external control supply air fan
AlaData.Ala_SensorErrorExtCtrlEAF_DelayValue
I
0454
RW 1 Alarm setting
Alarm delay signal error external control extract air fan
AlaData.Ala_SensorErrorHumidityOutdoor_DelayValue
I
0455
RW 1 Alarm setting
Alarm delay sensor error humidity outdoor
AlaData.Ala_SensorErrorTempExtraSensor1_DelayValu e
I
0456
RW 1 Alarm setting
Alarm delay sensor error extra sensor 1
AlaData.Ala_SensorErrorTempExtraSensor2_DelayValu e
I
0457
RW 1 Alarm setting
Alarm delay sensor error extra sensor 2
AlaData.Ala_SensorErrorTempExtraSensor3_DelayValu e
I
0458
RW 1 Alarm setting
Alarm delay sensor error extra sensor 3
Chapter 5 Holding Register (4x) 71
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_SensorErrorTempExtraSensor4_DelayValu e
I
0459
RW 1 Alarm setting
Alarm delay sensor error extra sensor 4
AlaData.Ala_SensorErrorTempExtraSensor5_DelayValu e
I
0460
RW 1 Alarm setting
Alarm delay sensor error extra sensor 5
AlaData.Ala_SensorErrorExtSupplySetp_DelayValue
I
0461
RW 1 Alarm setting
Alarm delay sensor error external temperature setpoint
AlaData.Ala_SensorErrorExtFlowSetpoint_DelayValue
I
0462
RW 1 Alarm setting
Alarm delay signal error external flow setpoint
AlaData.Ala_SensorErrorFilterGuard1_DelayValue
I
0463
RW 1 Alarm setting
Alarm delay sensor error pressure filter supply air
AlaData.Ala_SensorErrorFilterGuard2_DelayValue
I
0464
RW 1 Alarm setting
Alarm delay sensor error pressure filter extract air
AlaData.Ala_SensorErrorTempEfficiency_DelayValue
I
0465
RW 1 Alarm setting
Alarm delay sensor error efficiency temperature exchanger
AlaData.Ala_CommErrorDevice_DelayValue
I
0466
RW 1 Alarm setting
Alarm delay communication fault device
AlaData.Ala_MalfunctionExtraController_DelayValue
I
0467
RW 1 Alarm setting
Alarm delay malfunction extra controller
AlaData.Ala_InternalError_DelayValue
I
0468
RW 1 Alarm setting
Alarm delay internal error
AlaData.Ala_SmokeDetectorService_DelayValue
I
0469
RW 1 Alarm setting
Alarm delay service smoke detector
AlaData.Ala_SmokeDetectorError_DelayValue
I
0470
RW 1 Alarm setting
Alarm delay connection error smoke detector
AlaData.Ala_MalfunctionPreheater_DelayValue
I
0471
RW 1 Alarm setting
Alarm delay malfunction preheater
4.1-1-01
AlaData.Ala_CommunicationFaultBMS_DelayValue
I
0472
RW 1 Alarm setting
Alarm delay communication fault BMS master
4.1-1-01
AlaData.Ala_LeakageHeaterValve_DelayValue
I
0473
RW 1 Alarm setting
Alarm delay leakage heater valve
4.1-1-01
AlaData.Ala_SensorErrorTempPreheat_DelayValue
I
0474
RW 1
sec
Alarm setting
Alarm delay sensor error preheater temperature
4.1-1-00
AlaData.Ala_MalfunctionSAF6_DelayValue
I
0475
RW 1
sec
Alarm setting
Alarm delay malfunction supply air fan 6
4.3-1-00
AlaData.Ala_MalfunctionSAF7_DelayValue
I
0476
RW 1
sec
Alarm setting
Alarm delay malfunction supply air fan 7
4.3-1-00
AlaData.Ala_MalfunctionSAF8_DelayValue
I
0477
RW 1
sec
Alarm setting
Alarm delay Malfunction supply air fan 8
4.3-1-00
Chapter 5 Holding Register (4x) 72
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_MalfunctionEAF6_DelayValue
I
0478
RW 1
sec
Alarm setting
Alarm delay malfunction extract air fan 6
4.3-1-00
AlaData.Ala_MalfunctionEAF7_DelayValue
I
0479
RW 1
sec
Alarm setting
Alarm delay malfunction extract air fan 7
4.3-1-00
AlaData.Ala_MalfunctionEAF8_DelayValue
I
0480
RW 1
sec
Alarm setting
Alarm delay malfunction extract air fan 8
4.3-1-00
AlaData.Ala_AlarmSAF6_DelayValue
I
0481
RW 1
sec
Alarm setting
Alarm delay alarm supply air fan 6
4.3-1-00
AlaData.Ala_AlarmSAF7_DelayValue
I
0482
RW 1
sec
Alarm setting
Alarm delay alarm supply air fan 7
4.3-1-00
AlaData.Ala_AlarmSAF8_DelayValue
I
0483
RW 1
sec
Alarm setting
Alarm delay alarm supply air fan 8
4.3-1-00
AlaData.Ala_AlarmEAF6_DelayValue
I
0484
RW 1
sec
Alarm setting
Alarm delay alarm extract air fan 6
4.3-1-00
AlaData.Ala_AlarmEAF7_DelayValue
I
0485
RW 1
sec
Alarm setting
Alarm delay alarm extract air fan 7
4.3-1-00
AlaData.Ala_AlarmEAF8_DelayValue
I
0486
RW 1
sec
Alarm setting
Alarm delay alarm extract air fan 8
4.3-1-00
AlaData.Ala_WarningSAF6_DelayValue
I
0487
RW 1
sec
Alarm setting
Alarm delay warning supply air fan 6
4.3-1-00
AlaData.Ala_WarningSAF7_DelayValue
I
0488
RW 1
sec
Alarm setting
Alarm delay warning supply air fan 7
4.3-1-00
AlaData.Ala_WarningSAF8_DelayValue
I
0489
RW 1
sec
Alarm setting
Alarm delay warning supply air fan 8
4.3-1-00
AlaData.Ala_WarningEAF6_DelayValue
I
0490
RW 1
sec
Alarm setting
Alarm delay warning extract air fan 6
4.3-1-00
AlaData.Ala_WarningEAF7_DelayValue
I
0491
RW 1
sec
Alarm setting
Alarm delay warning extract air fan 7
4.3-1-00
AlaData.Ala_WarningEAF8_DelayValue
I
0492
RW 1
sec
Alarm setting
Alarm delay warning extract air fan 8
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone1_DelayValue
I
0493
RW 1
sec
Alarm setting
Alarm delay malfunction heating zone 1
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone2_DelayValue
I
0494
RW 1
sec
Alarm setting
Alarm delay malfunction heating zone 2
4.3-1-00
AlaData.Ala_MalfunctionHeatingZone3_DelayValue
I
0495
RW 1
sec
Alarm setting
Alarm delay malfunction heating zone 3
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone1_DelayValue
I
0496
RW 1
sec
Alarm setting
Alarm delay malfunction cooling zone 1
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone2_DelayValue
I
0497
RW 1
sec
Alarm setting
Alarm delay malfunction cooling zone 2
4.3-1-00
AlaData.Ala_MalfunctionCoolingZone3_DelayValue
I
0498
RW 1
sec
Alarm setting
Alarm delay malfunction cooling zone 3
4.3-1-00
Chapter 5 Holding Register (4x) 73
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_ControlErrorSupplyTempZone1_DelayVal ue
I
0499
RW 1
min
Alarm setting
Alarm delay deviation alarm supply temperature zone 1
4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone2_DelayVal ue
I
0500
RW 1
min
Alarm setting
Alarm delay deviation alarm supply temperature zone 2
4.3-1-00
AlaData.Ala_ControlErrorSupplyTempZone3_DelayVal ue
I
0501
RW 1
min
Alarm setting
Alarm delay deviation alarm supply temperature zone 3
4.3-1-00 AlaData.Ala_LowTempFrostGuardZone1_DelayValue
I
0502
RW 1
sec
Alarm setting
Alarm delay freeze protection alarm zone 1
4.3-1-00
AlaData.Ala_LowTempFrostGuardZone2_DelayValue
I
0503
RW 1
sec
Alarm setting
Alarm delay freeze protection alarm zone 2
4.3-1-00
AlaData.Ala_LowTempFrostGuardZone3_DelayValue
I
0504
RW 1
sec
Alarm setting
Alarm delay freeze protection alarm zone 3
4.3-1-00
AlaData.Ala_ElectricOverheatZone1_DelayValue
I
0505
RW 1
sec
Alarm setting
Alarm delay electric heater is overheated zone 1
4.3-1-00
AlaData.Ala_ElectricOverheatZone2_DelayValue
I
0506
RW 1
sec
Alarm setting
Alarm delay electric heater is overheated zone 2
4.3-1-00
AlaData.Ala_ElectricOverheatZone3_DelayValue
I
0507
RW 1
sec
Alarm setting
Alarm delay electric heater is overheated zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone1_DelayValu e
I
0508
RW 1
sec
Alarm setting
Alarm delay sensor error supply air temp zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone2_DelayValu e
I
0509
RW 1
sec
Alarm setting
Alarm delay sensor error supply air temp zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempSupplyZone3_DelayValu e
I
0510
RW 1
sec
Alarm setting
Alarm delay sensor error supply air temp zone 3
4.3-1-00 AlaData.Ala_SensorErrorTempRoomZone1_DelayValue
I
0511
RW 1
sec
Alarm setting
Alarm delay sensor error room temp zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone2_DelayValue
I
0512
RW 1
sec
Alarm setting
Alarm delay sensor error room temp zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempRoomZone3_DelayValue
I
0513
RW 1
sec
Alarm setting
Alarm delay sensor error room temp zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone1_DelayValu e
I
0514
RW 1
sec
Alarm setting
Alarm delay sensor error extract temp zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempExtractZone2_DelayValu e
I
0515
RW 1
sec
Alarm setting
Alarm delay sensor error extract temp zone 2
4.3-1-00
Chapter 5 Holding Register (4x) 74
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
AlaData.Ala_SensorErrorTempExtractZone3_DelayValu e
I
0516
RW 1
sec
Alarm setting
Alarm delay sensor error extract temp zone 3
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone1_DelayValue
I
0517
RW 1
sec
Alarm setting
Alarm delay sensor error freeze protection zone 1
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone2_DelayValue
I
0518
RW 1
sec
Alarm setting
Alarm delay sensor error freeze protection zone 2
4.3-1-00
AlaData.Ala_SensorErrorTempFrostZone3_DelayValue
I
0519
RW 1
sec
Alarm setting
Alarm delay sensor error freeze protection zone 3
4.3-1-00
VentSettings.S_AirFlowK(10)
R
0537
RW
AV, 30537
10 Flow calculation
K-constant for calculating air flow: SAF pressure airflow = S_AirFlowK * A_AI_SAFPressure^S_AirFlowx
VentSettings.S_AirFlowX(10)
R
0538
RW
AV, 30538
100 Flow calculation
X-constant for calculating air flow: SAF pressure
VentSettings.S_AirFlowK(11)
R
0539
RW
AV, 30539
10 Flow calculation
K-constant for calculating air flow: EAF pressure
VentSettings.S_AirFlowX(11)
R
0540
RW
AV, 30540
100 Flow calculation
X-constant for calculating air flow: EAF pressure
VentSettings.S_AirFlowK(12)
R
0541
RW
AV, 30541
10 Flow calculation
K-constant for calculating air flow: Supply air flow
VentSettings.S_AirFlowX(12)
R
0542
RW
AV, 30542
100 Flow calculation
X-constant for calculating air flow: Supply air flow
VentSettings.S_AirFlowK(13)
R
0543
RW
AV, 30543
10 Flow calculation
K-constant for calculating air flow: Extract air flow
VentSettings.S_AirFlowX(13)
R
0544
RW
AV, 30544
100 Flow calculation
X-constant for calculating air flow: Extract air flow
VentSettings.S_AirFlowK(14)
R
0545
RW
AV, 30545
10 Flow calculation
K-constant for calculating air flow: Exchanger supply flow
VentSettings.S_AirFlowX(14)
R
0546
RW
AV, 30546
100 Flow calculation
X-constant for calculating air flow: Exchanger supply flow
Chapter 5 Holding Register (4x) 75
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_AirFlowK(15)
R
0547
RW
AV, 30547
10 Flow calculation
K-constant for calculating air flow: Exchanger extract pressure
VentSettings.S_AirFlowX(15)
R
0548
RW
AV, 30548
0 Flow calculation
X-constant for calculating air flow: Exchanger extract pressure
VentSettings.S_DOSelect_SeqPumpY1(0)
X
0549
RW
MSV, 30549
1 Operation
override
Running mode pump sequence-A Modbus 0=Manual off 1=Manual on 2=Auto Bacnet +1 offset for corresponding Modbus
VentSettings.S_DOSelect_SeqPumpY2
X
0550
RW
MSV, 30550
1 Operation
override
Running mode pump sequence-B (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY3
X
0551
RW
MSV, 30551
1 Operation
override
Running mode pump sequence-C (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY4
X
0552
RW
MSV, 30552
1 Operation
override
Running mode pump sequence-D (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY5
X
0553
RW
MSV, 30553
1 Operation
override
Running mode pump sequence-E (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY6
X
0554
RW
MSV, 30554
1 Operation
override
Running mode pump sequence-F (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY7
X
0555
RW
MSV, 30555
1 Operation
override
Running mode pump sequence-G (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY8
X
0556
RW
MSV, 30556
1 Operation
override
Running mode pump sequence-H (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY9
X
0557
RW
MSV, 30557
1 Operation
override
Running mode pump sequence-I (See signal list for DOSelect_SeqPumpY1(0))
VentSettings.S_DOSelect_SeqPumpY10
X
0558
RW
MSV, 30558
1 Operation
override
Running mode pump sequence-J (See signal list for DOSelect_SeqPumpY1(0))
Chapter 5 Holding Register (4x) 76
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_DOSelect_RecirculationAirDamper
X
0559
RW
MSV, 30559
1 Operation
override
Running mode recirculation damper: Modbus 0=Close 1=Open 2=Auto Bacnet +1 offset for corresponding Modbus
VentSettings.S_DOSelect_OutdoorAirDamper
X
0560
RW
MSV, 30560
1 Operation
override
Running mode outdoor air damper: (See signal list for DOSelect_RecirculationAirDamper)
VentSettings.S_DOSelect_ExhaustAirDamper
X
0561
RW
MSV, 30561
1 Operation
override
Running mode exhaust air damper: (See signal list for DOSelect_RecirculationAirDamper)
VentSettings.S_DOSelect_HumidityStart
X
0562
RW
MSV, 30562
1 Operation
override
Running mode humidity start signal (See signal list for DOSelect_RecirculationAirDamper)
VentSettings.S_DOSelect_ChangeOver1
X
0563
RW
MSV, 30563
1 Operation
override
Select changeOver 1 External Modbus 0=Heating 1=Cooling 2=Auto Bacnet +1 offset for corresponding Modbus
VentSettings.S_DOSelect_ChangeOver2
X
0564
RW
MSV, 30564
1 Operation
override
Select changeOver 2 External (See signal list for DOSelect_ChangeOver1)
Chapter 5 Holding Register (4x) 77
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_AirUnitAutoMode
X
0565
RW
MSV, 30565
1 Operation
override
Running mode air handling unit: Modbus 0=Off 1=Manual mode 2=Auto 3=Low speed 4=Normal speed 5=High speed Bacnet +1 offset for corresponding Modbus
VentSettings.S_AirUnitManual
X
0566
RW
MSV, 30566
1 Operation
override
Mode selection for air handling unit in running mode: manual mode Modbus 0=Stop 1=Starting up 2=Low speed run 3=Normal speed run 4=High speed run 5=Heating support run 6=Cooling support run 7=CO₂ Run 8=Free cool run 9=Fan stop run 10=Fire run 11=Smoke run 12=Recirculation run 13=DeIcing run Bacnet +1 offset for corresponding Modbus
Chapter 5 Holding Register (4x) 78
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_SAFAutoMode
X
0567
RW
MSV, 30567
1 Operation
override
Running mode supply air fan: 0=Off, 1=Manual output, 2=Auto, 3=Manual setpoint, 4=Low speed, 5=Normal speed, 6=High speed Bacnet +1 offset for corresponding Modbus
VentSettings.S_SAFManualSetpoint
R
0568
RW
AV, 30568
10
P/Q
Operation override
Manual setpoint supply air fan if running mode: Manual setpoint
VentSettings.S_SAFManualOutput
R
0569
RW
AV, 30569
10 % Operation
override
Manual output supply air fan if running mode: Manual output
VentSettings.S_EAFAutoMode
X
0570
RW
MSV, 30570
1 Operation
override
Running mode extract air fan: (See signal list for SAFAutoMode)
VentSettings.S_EAFManualSetpoint
R
0571
RW
AV, 30571
10
P/Q
Operation override
Manual setpoint extract air fan if running mode: Manual setpoint
VentSettings.S_EAFManualOutput
R
0572
RW
AV, 30572
10 % Operation
override
Manual output extract air fan if running mode: Manual output
Chapter 5 Holding Register (4x) 79
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_ExternalControl
X
0573
RW
MSV, 30573
1 Operation
override
External control: Modbus 0=No External control, 1=Extended run speed 1, 2=Extended run speed 2, 3=Extended run speed 3, 4=External stop, 5=External stop with support control, 6=Start Free cooling, 7 = Recirculation Bacnet +1 offset for corresponding Modbus
VentSettings.S_AirUnitServiceStop
X
0574
RW
MSV, 30574
1 Operation
override
Stop the air handling unit with No 1 prio. Modbus 0 = No 1 = Yes Bacnet +1 offset for corresponding Modbus
VentSettings.S_SeqPumpOutdLimitYx(1)
R
0575
RW
AV, 30575
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-A
VentSettings.S_SeqPumpOutdLimitYx(2)
R
0576
RW
AV, 30576
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-B
VentSettings.S_SeqPumpOutdLimitYx(3)
R
0577
RW
AV, 30577
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-C
VentSettings.S_SeqPumpOutdLimitYx(4)
R
0578
RW
AV, 30578
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-D
VentSettings.S_SeqPumpOutdLimitYx(5)
R
0579
RW
AV, 30579
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-E
VentSettings.S_SeqPumpOutdLimitYx(6)
R
0580
RW
AV, 30580
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-F
Chapter 5 Holding Register (4x) 80
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_SeqPumpOutdLimitYx(7)
R
0581
RW
AV, 30581
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-G
VentSettings.S_SeqPumpOutdLimitYx(8)
R
0582
RW
AV, 30582
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-H
VentSettings.S_SeqPumpOutdLimitYx(9)
R
0583
RW
AV, 30583
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-I
VentSettings.S_SeqPumpOutdLimitYx(10)
R
0584
RW
AV, 30584
10 Unit setting
Outdoor temperature limit to allow pump stop sequence-J
VentSettings.S_VentControl
X
0585
RW
MSV, 30585
1 Temperature
setting
Select temperature control type: Modbus 0=Supply air 1=Supply air outdoor compensated 2=Room cascade 3=Extract air cascade 4=Room (summer) else supply air 5=Extract air (summer) else supply air 6=Room cascade outdoor compensated 7=Extract air cascade outdoor compensated 8=Extract air dependent supply air temperature Bacnet +1 offset for corresponding Modbus
Chapter 5 Holding Register (4x) 81
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_FanType
X
0586
RW
MSV, 30586
1 Fan setting
Select fan control type: Modbus 0=Pressure 1=Flow 2=Manual 3=External 4=Supply air pressure with extract air fan slave 5=Supply air pressure with extract air flow slave 6=Extract air pressure with supply air fan slave 7=Extract air pressure with supply air flow slave Bacnet +1 offset for corresponding Modbus
VentSettings.S_SupplySetpoint
R
0588
RW
AV, 30588
10 Temperature
setting
Setpoint supply air temperature when constant supply air temperature function
VentSettings.S_ExtractSetpoint
R
0589
RW
AV, 30589
10 Temperature
setting
Setpoint extract air temperature if extract control
VentSettings.S_SupplySetpointMax
R
0590
RW
AV, 30590
10 Temperature
setting
Max limit supply temperature setpoint if cascade control
VentSettings.S_SupplySetpointMin
R
0591
RW
AV, 30591
10 Temperature
setting
Min limit supply temperature setpoint if cascade control
VentSettings.S_SupplySetpOffsetLow
R
0592
RW
AV, 30592
10 Temperature
setting
Offset temperature setpoint if low speed
VentSettings.S_SupplySetpOffsetHigh
R
0593
RW
AV, 30593
10 Temperature
setting
Offset temperature setpoint if high speed
VentSettings.S_Curve1_X1
R
0594
RW
AV, 30594
10 T Temperature
setting
Outdoor compensation curve point 1 sensor value
VentSettings.S_Curve1_X2
R
0595
RW
AV, 30595
10 T Temperature
setting
Outdoor compensation curve point 2 sensor value
Chapter 5 Holding Register (4x) 82
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_Curve1_X3
R
0596
RW
AV, 30596
10 T Temperature
setting
Outdoor compensation curve point 3 sensor value
VentSettings.S_Curve1_X4
R
0597
RW
AV, 30597
10 T Temperature
setting
Outdoor compensation curve point 4 sensor value
VentSettings.S_Curve1_X5
R
0598
RW
AV, 30598
10 T Temperature
setting
Outdoor compensation curve point 5 sensor value
VentSettings.S_Curve1_X6
R
0599
RW
AV, 30599
10 T Temperature
setting
Outdoor compensation curve point 6 sensor value
VentSettings.S_Curve1_X7
R
0600
RW
AV, 30600
10 T Temperature
setting
Outdoor compensation curve point 7 sensor value
VentSettings.S_Curve1_X8
R
0601
RW
AV, 30601
10 T Temperature
setting
Outdoor compensation curve point 8 sensor value
VentSettings.S_Curve1_Y1
R
0602
RW
AV, 30602
10 T Temperature
setting
Outdoor compensation curve point 1 setpoint
VentSettings.S_Curve1_Y2
R
0603
RW
AV, 30603
10 T Temperature
setting
Outdoor compensation curve point 2 setpoint
VentSettings.S_Curve1_Y3
R
0604
RW
AV, 30604
10 T Temperature
setting
Outdoor compensation curve point 3 setpoint
VentSettings.S_Curve1_Y4
R
0605
RW
AV, 30605
10 T Temperature
setting
Outdoor compensation curve point 4 setpoint
VentSettings.S_Curve1_Y5
R
0606
RW
AV, 30606
10 T Temperature
setting
Outdoor compensation curve point 5 setpoint
VentSettings.S_Curve1_Y6
R
0607
RW
AV, 30607
10 T Temperature
setting
Outdoor compensation curve point 6 setpoint
VentSettings.S_Curve1_Y7
R
0608
RW
AV, 30608
10 T Temperature
setting
Outdoor compensation curve point 7 setpoint
VentSettings.S_Curve1_Y8
R
0609
RW
AV, 30609
10 T Temperature
setting
Outdoor compensation curve point 8 setpoint
Chapter 5 Holding Register (4x) 83
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_SAFSetpointSelect
X
0610
RW
MSV, 30610
1 Fan setting
Setpoint selection supply air fan: Modbus 0=Constant setpoints 1=Offset of normal speed setpoint Bacnet +1 offset for corresponding Modbus
VentSettings.S_EAFSetpointSelect
X
0611
RW
MSV, 30611
1 Fan setting
Setpoint selection extract air fan: (See signal list for SAFSetpointSelect)
VentSettings.S_SAFLowSpeedPressure(0)
R
0612
RW
AV, 30612
10 P Fan setting
Pressure setpoint supply air fan low speed
VentSettings.S_SAFNormalSpeedPressure
R
0613
RW
AV, 30613
10 P Fan setting
Pressure setpoint supply air fan normal speed
VentSettings.S_SAFHighSpeedPressure
R
0614
RW
AV, 30614
10 P Fan setting
Pressure setpoint supply air fan high speed
VentSettings.S_EAFLowSpeedPressure(0)
R
0615
RW
AV, 30615
10 P Fan setting
Pressure setpoint extract air fan low speed
VentSettings.S_EAFNormalSpeedPressure
R
0616
RW
AV, 30616
10 P Fan setting
Pressure setpoint extract air fan normal speed
VentSettings.S_EAFHighSpeedPressure
R
0617
RW
AV, 30617
10 P Fan setting
Pressure setpoint extract air fan high speed
VentSettings.S_SAFLowspeedAirFlow(0)
R
0618
RW
AV, 30618
1 Q Fan setting
Flow setpoint supply air fan low speed
4.3-1-00
VentSettings.S_SAFNormalspeedAirFlow
R
0619
RW
AV, 30619
1 Q Fan setting
Flow setpoint supply air fan normal speed
4.3-1-00
VentSettings.S_SAFHighspeedAirFlow
R
0620
RW
AV, 30620
1 Q Fan setting
Flow setpoint supply air fan high speed
4.3-1-00
VentSettings.S_EAFLowspeedAirFlow(0)
R
0621
RW
AV, 30621
1 Q Fan setting
Flow setpoint extract air fan low speed
4.3-1-00
VentSettings.S_EAFNormalspeedAirFlow
R
0622
RW
AV, 30622
1 Q Fan setting
Flow setpoint extract air fan normal speed
4.3-1-00
VentSettings.S_EAFHighspeedAirFlow
R
0623
RW
AV, 30623
1 Q Fan setting
Flow setpoint extract air fan high speed
4.3-1-00
VentSettings.S_SAFLowSpeedOutput(0)
R
0624
RW
AV, 30624
10 % Fan setting
Output signal supply air fan low speed if manual control
VentSettings.S_SAFNormalSpeedOutput
R
0625
RW
AV, 30625
10 % Fan setting
Output signal supply air fan normal speed if manual control
VentSettings.S_SAFHighspeedOutput
R
0626
RW
AV, 30626
10 % Fan setting
Output signal supply air fan high speed if manual control
Chapter 5 Holding Register (4x) 84
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_EAFLowSpeedOutput(0)
R
0627
RW
AV, 30627
10 % Fan setting
Output signal extract air fan low speed if manual control
VentSettings.S_EAFNormalSpeedOutput
R
0628
RW
AV, 30628
10 % Fan setting
Output signal extract air fan normal speed if manual control
VentSettings.S_EAFHighspeedOutput
R
0629
RW
AV, 30629
10 % Fan setting
Output signal extract air fan high speed if manual control
VentSettings.S_SAFLowSpeedPressureOffset
R
0630
RW
AV, 30630
10 P Fan setting
Offset supply air fan low speed if pressure control
VentSettings.S_SAFHighSpeedPressureOffset
R
0631
RW
AV, 30631
10 P Fan setting
Offset supply air fan high speed if pressure control
VentSettings.S_SAFLowSpeedAirFlowOffset
R
0632
RW
AV, 30632
1 Q Fan setting
Offset supply air fan low speed if flow control
4.3-1-00
VentSettings.S_SAFHighSpeedAirFlowOffset
R
0633
RW
AV, 30633
1 Q Fan setting
Offset supply air fan high speed if flow control
4.3-1-00
VentSettings.S_SAFLowSpeedOutputOffset
R
0634
RW
AV, 30634
10 % Fan setting
Offset supply air fan low speed if manual control
VentSettings.S_SAFHighSpeedOutputOffset
R
0635
RW
AV, 30635
10 % Fan setting
Offset supply air fan high speed if manual control
VentSettings.S_EAFLowSpeedPressureOffset
R
0636
RW
AV, 30636
10 P Fan setting
Offset extract air fan low speed if pressure control
VentSettings.S_EAFHighSpeedPressureOffset
R
0637
RW
AV, 30637
10 P Fan setting
Offset extract air fan high speed if pressure control
VentSettings.S_EAFLowSpeedAirFlowOffset
R
0638
RW
AV, 30638
1 Q Fan setting
Offset extract air fan low speed if flow control
4.3-1-00
VentSettings.S_EAFHighSpeedAirFlowOffset
R
0639
RW
AV, 30639
1 Q Fan setting
Offset extract air fan high speed if flow control
4.3-1-00
VentSettings.S_EAFLowSpeedOutputOffset
R
0640
RW
AV, 30640
10 % Fan setting
Offset extract air fan low speed if manual control
VentSettings.S_EAFHighSpeedOutputOffset
R
0641
RW
AV, 30641
10 % Fan setting
Offset extract air fan high speed if manual control
Chapter 5 Holding Register (4x) 85
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_SAFModeFreeCool
X
0642
RW
MSV, 30642
1 Operation
override
Selected speed in free cooling mode supply air fan: Modbus 0=Off/Auto, normal setpoint 1=Manual setpoint 2=Manual output 3=Low speed setpoint 4=Normal speed setpoint 5=High speed setpoint Bacnet +1 offset for corresponding Modbus
VentSettings.S_SAFManSetpFreeCool
R
0643
RW
AV, 30643
10
P/Q
Operation override
Manual setpoint in free cooling mode supply air fan
VentSettings.S_SAFManOutFreeCool
R
0644
RW
AV, 30644
10 % Operation
override
Manual output in free cooling mode supply air fan
VentSettings.S_SAFModeFire
X
0645
RW
MSV, 30645
1 Operation
override
Selected speed in fire mode supply air fan: (See signal list for SAFModeFreeCool)
VentSettings.S_SAFManSetpFire
R
0646
RW
AV, 30646
10
P/Q
Operation override
Manual setpoint in fire mode supply air fan
VentSettings.S_SAFManOutFire
R
0647
RW
AV, 30647
10 % Operation
override
Manual output in fire mode supply air fan
VentSettings.S_SAFModeSmoke
X
0648
RW
MSV, 30648
1 Operation
override
Selected speed in smoke mode supply air fan: (See signal list for SAFModeFreeCool)
VentSettings.S_SAFManSetpSmoke
R
0649
RW
AV, 30649
10
P/Q
Operation override
Manual setpoint in smoke mode supply air fan
VentSettings.S_SAFManOutSmoke
R
0650
RW
AV, 30650
10 % Operation
override
Manual output in smoke mode supply air fan
VentSettings.S_SAFModeRecirculation
X
0651
RW
MSV, 30651
1 Operation
override
Selected speed in recirculation mode supply air fan: (See signal list for SAFModeFreeCool)
Chapter 5 Holding Register (4x) 86
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_SAFManSetpRecirculation
R
0652
RW
AV, 30652
10
P/Q
Operation override
Manual setpoint in recirculation mode supply air fan
VentSettings.S_SAFManOutRecirculation
R
0653
RW
AV, 30653
10 % Operation
override
Manual output in recirculation mode supply air fan
VentSettings.S_EAFModeFreeCool
X
0654
RW
MSV, 30654
1 Operation
override
Selected speed in freecool mode extract air fan: (See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpFreeCool
R
0655
RW
AV, 30655
10
P/Q
Operation override
Manual setpoint in freecool mode extract air fan
VentSettings.S_EAFManOutFreeCool
R
0656
RW
AV, 30656
10 % Operation
override
Manual output in freecool mode extract air fan
VentSettings.S_EAFModeFire
X
0657
RW
MSV, 30657
1 Operation
override
Selected speed in fire mode extract air fan: (See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpFire
R
0658
RW
AV, 30658
10
P/Q
Operation override
Manual setpoint in fire mode extract air fan
VentSettings.S_EAFManOutFire
R
0659
RW
AV, 30659
10 % Operation
override
Manual output in fire mode extract air fan
VentSettings.S_EAFModeSmoke
X
0660
RW
MSV, 30660
1 Operation
override
Selected speed in smoke mode extract air fan: (See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpSmoke
R
0661
RW
AV, 30661
10
P/Q
Operation override
Manual setpoint in smoke mode extract air fan
VentSettings.S_EAFManOutSmoke
R
0662
RW
AV, 30662
10 % Operation
override
Manual output in smoke mode extract air fan
VentSettings.S_EAFModeRecirculation
X
0663
RW
MSV, 30663
1 Operation
override
Selected speed in recirculation mode extract air fan: (See signal list for SAFModeFreeCool)
VentSettings.S_EAFManSetpRecirculation
R
0664
RW
AV, 30664
10
P/Q
Operation override
Manual setpoint in recirculation mode extract air fan
VentSettings.S_EAFManOutRecirculation
R
0665
RW
AV, 30665
10 % Operation
override
Manual output in recirculation mode extract air fan
Chapter 5 Holding Register (4x) 87
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_EAFFrequencyFact
R
0666
RW
AV, 30666
10 Fan setting
Flow slave factor extract air fan if fan control type: Supply air pressure with extract air flow slave
VentSettings.S_ExtractPID_Pband
R
0667
RW
AV, 30667
10 PID setting
P-band extract air temperature
VentSettings.S_ExtractPID_Itime
R
0668
RW
AV, 30668
1 PID setting
I-time extract air temperature
VentSettings.S_SAFPID_Pband
R
0669
RW
AV, 30669
10 PID setting
P-band pressure supply air fan
VentSettings.S_SAFPID_Itime
R
0670
RW
AV, 30670
1 PID setting
I-time pressure supply air fan
VentSettings.S_EAFPID_Pband
R
0671
RW
AV, 30671
10 PID setting
P-band pressure extract air fan
VentSettings.S_EAFPID_Itime
R
0672
RW
AV, 30672
1 PID setting
I-time pressure extract air fan
VentSettings.S_FrostPID1_PBand(0)
R
0673
RW
AV, 30673
10 PID setting
P-band freeze protection 1
VentSettings.S_FrostPID1_ITime(0)
R
0674
RW
AV, 30674
1 PID setting
I-time freeze protection 1
VentSettings.S_FrostPID2_Pband
R
0675
RW
AV, 30675
10 PID setting
P-band freeze protection 2
VentSettings.S_FrostPID2_ITime
R
0676
RW
AV, 30676
1 PID setting
I-time freeze protection 2
VentSettings.S_FrostPID3_Pband
R
0677
RW
AV, 30677
10 PID setting
P-band freeze protection 3
VentSettings.S_FrostPID3_ITime
R
0678
RW
AV, 30678
1 PID setting
I-time freeze protection 3
VentSettings.S_CO2PID_Pband
R
0679
RW
AV, 30679
10 PID setting
P-band CO₂
VentSettings.S_CO2PID_Itime
R
0680
RW
AV, 30680
1 PID setting
I-time CO₂
VentSettings.S_RoomPID_Pband
R
0681
RW
AV, 30681
10 PID setting
P-band room temperature
VentSettings.S_RoomPID_Itime
R
0682
RW
AV, 30682
1 PID setting
I-time room temperature
VentSettings.S_DeIcePID_Pband
R
0683
RW
AV, 30683
10 PID setting
P-band defrosting
VentSettings.S_DeIcePID_Itime
R
0684
RW
AV, 30684
1 PID setting
I-time defrosting
VentSettings.S_HumidityPID_Pband
R
0685
RW
AV, 30685
10 PID setting
P-band humidity control
VentSettings.S_HumidityPID_Itime
R
0686
RW
AV, 30686
1 PID setting
I-time humidity control
Chapter 5 Holding Register (4x) 88
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_ExtraPID_Pband
R
0687
RW
AV, 30687
10 PID setting
P-band extra controller
VentSettings.S_ExtraPID_Itime
R
0688
RW
AV, 30688
1 PID setting
I-time extra controller
VentSettings.S_SAFAirFlowPID_Pband
R
0689
RW
AV, 30689
1 PID setting
P-band flow supply air fan
4.3-1-00
VentSettings.S_SAFPID_Itime
R
0690
RW
AV, 30690
1 PID setting
I-time flow supply air fan
VentSettings.S_EAFAirFlowPID_Pband
R
0691
RW
AV, 30691
1 PID setting
P-band flow extract air fan
4.3-1-00
VentSettings.S_EAFPID_Itime
R
0692
RW
AV, 30692
1 PID setting
I-time flow extract air fan
VentSettings.S_SeqY1PID_Pband
R
0693
RW
AV, 30693
10 PID setting
P-band sequence-A
VentSettings.S_SeqY1PID_ITime
R
0694
RW
AV, 30694
1 PID setting
I-time sequence-A
VentSettings.S_SeqY2PID_Pband
R
0695
RW
AV, 30695
10 PID setting
P-band sequence-B
VentSettings.S_SeqY2PID_ITime
R
0696
RW
AV, 30696
1 PID setting
I-time sequence-B
VentSettings.S_SeqY3PID_Pband
R
0697
RW
AV, 30697
10 PID setting
P-band sequence-C
VentSettings.S_SeqY3PID_ITime
R
0698
RW
AV, 30698
1 PID setting
I-time sequence-C
VentSettings.S_SeqY4PID_Pband
R
0699
RW
AV, 30699
10 PID setting
P-band sequence-D
VentSettings.S_SeqY4PID_ITime
R
0700
RW
AV, 30700
1 PID setting
I-time sequence-D
VentSettings.S_SeqY5PID_Pband
R
0701
RW
AV, 30701
10 PID setting
P-band sequence-E
VentSettings.S_SeqY5PID_ITime
R
0702
RW
AV, 30702
1 PID setting
I-time sequence-E
VentSettings.S_SeqY6PID_Pband
R
0703
RW
AV, 30703
10 PID setting
P-band sequence-F
VentSettings.S_SeqY6PID_ITime
R
0704
RW
AV, 30704
1 PID setting
I-time sequence-F
VentSettings.S_SeqY7PID_Pband
R
0705
RW
AV, 30705
10 PID setting
P-band sequence-G
VentSettings.S_SeqY7PID_ITime
R
0706
RW
AV, 30706
1 PID setting
I-time sequence-G
VentSettings.S_SeqY8PID_Pband
R
0707
RW
AV, 30707
10 PID setting
P-band sequence-H
VentSettings.S_SeqY8PID_ITime
R
0708
RW
AV, 30708
1 PID setting
I-time sequence-H
Chapter 5 Holding Register (4x) 89
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_SeqY9PID_Pband
R
0709
RW
AV, 30709
10 PID setting
P-band sequence-I
VentSettings.S_SeqY9PID_ITime
R
0710
RW
AV, 30710
1 PID setting
I-time sequence-I
VentSettings.S_SeqY10PID_Pband
R
0711
RW
AV, 30711
10 PID setting
P-band sequence-J
VentSettings.S_SeqY10PID_ITime
R
0712
RW
AV, 30712
1 PID setting
I-time sequence-J
VentSettings.S_AOSelect_Humidity
X
0713
RW
MSV, 30713
1 Operation
override
Control mode humidity control: Modbus 0=Off 1=Manual 2=Auto Bacnet +1 offset for corresponding Modbus
VentSettings.S_AOManual_Humidity
R
0714
RW
AV, 30714
10 Operation
override
Control signal humidity control if manual mode
VentSettings.S_AOSelect_ExtraController
X
0715
RW
MSV, 30715
1 Operation
override
Control mode extra controller: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_ExtraController
R
0716
RW
AV, 30716
10 Operation
override
Control signal extra controller if manual mode
VentSettings.S_AOSelect_SequenceY1
X
0717
RW
MSV, 30717
1 Operation
override
Control mode SEQ-A: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY1
R
0718
RW
AV, 30718
10 Operation
override
Control signal SEQ-A if manual mode
VentSettings.S_AOSelect_SequenceY2
X
0719
RW
MSV, 30719
1 Operation
override
Control mode SEQ-B: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY2
R
0720
RW
AV, 30720
10 Operation
override
Control signal SEQ-B if manual mode
VentSettings.S_AOSelect_SequenceY3
X
0721
RW
MSV, 30721
1 Operation
override
Control mode SEQ-C: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY3
R
0722
RW
AV, 30722
10 Operation
override
Control signal SEQ-C if manual mode
Chapter 5 Holding Register (4x) 90
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_AOSelect_SequenceY4
X
0723
RW
MSV, 30723
1 Operation
override
Control mode SEQ-D: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY4
R
0724
RW
AV, 30724
10 Operation
override
Control signal SEQ-D if manual mode
VentSettings.S_AOSelect_SequenceY5
X
0725
RW
MSV, 30725
1 Operation
override
Control mode SEQ-E: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY5
R
0726
RW
AV, 30726
10 Operation
override
Control signal SEQ-E if manual mode
VentSettings.S_AOSelect_SequenceY6
X
0727
RW
MSV, 30727
1 Operation
override
Control mode SEQ-F: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY6
R
0728
RW
AV, 30728
10 Operation
override
Control signal SEQ-F if manual mode
VentSettings.S_AOSelect_SequenceY7
X
0729
RW
MSV, 30729
1 Operation
override
Control mode SEQ-G: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY7
R
0730
RW
AV, 30730
10 Operation
override
Control signal SEQ-G if manual mode
VentSettings.S_AOSelect_SequenceY8
X
0731
RW
MSV, 30731
1 Operation
override
Control mode SEQ-H: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY8
R
0732
RW
AV, 30732
10 Operation
override
Control signal SEQ-H if manual mode
VentSettings.S_AOSelect_SequenceY9
X
0733
RW
MSV, 30733
1 Operation
override
Control mode SEQ-I: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY9
R
0734
RW
AV, 30734
10 Operation
override
Control signal SEQ-I if manual mode
VentSettings.S_AOSelect_SequenceY10
X
0735
RW
MSV, 30735
1 Operation
override
Control mode SEQ-J: (See signal list for AOSelect_Humidity)
VentSettings.S_AOManual_SequenceY10
R
0736
RW
AV, 30736
10 Operation
override
Control signal SEQ-J if manual mode
VentSettings.S_FreeCoolDayLimit
R
0737
RW
AV, 30737
10 T Free cooling
Outdoor temperature min limit during day to allow start of free cooling
Chapter 5 Holding Register (4x) 91
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_FreeCoolHighLimit
R
0738
RW
AV, 30738
10 T Free cooling
Outdoor temperature max limit during night to stop free cooling
VentSettings.S_FreeCoolLowLimit
R
0739
RW
AV, 30739
10 T Free cooling
Outdoor temperature min limit during night to stop free cooling
VentSettings.S_FreeCoolRoomLimit
R
0740
RW
AV, 30740
10 T Free cooling
Room temperature min limit during night to stop free cooling
VentSettings.S_FreeCoolStartTime
X
0741
RW
AV, 30741
1 Free cooling
Start hour free cooling (00-24)
VentSettings.S_FreeCoolStopTime
X
0742
RW
AV, 30742
1 Free cooling
Stop hour free cooling (00-24)
VentSettings.S_FreeCoolHeatBlockTime
I
0743
RW
AV, 30743
1
min
Free cooling
Time to block heat output after free cooling
VentSettings.S_CO2StartLimit
R
0744
RW
AV, 30744
10
ppm
CO₂
Start limit CO₂ fan start/stop function
VentSettings.S_CO2DemandDiff
R
0745
RW
AV, 30745
10
ppm
CO₂
Hysteresis to stop CO₂ fan start/stop function
VentSettings.S_CO2Setpoint
R
0746
RW
AV, 30746
10
ppm
CO₂
Setpoint CO₂ mixing damper function
VentSettings.S_CO2MinTime
I
0747
RW
AV, 30747
1
min
CO₂
Min run time CO₂ fan start/stop function
VentSettings.S_NeedControl
X
0748
RW
AV, 30748
1 Support control
Enable support control if the unit is stopped
VentSettings.S_NeedHeatStart
R
0749
RW
AV, 30749
10 T Support control
Room temperature to start the unit if support heating is active
VentSettings.S_NeedHeatStop
R
0750
RW
AV, 30750
10 T Support control
Room temperature to stop the unit if support heating is active
VentSettings.S_NeedCoolStart
R
0751
RW
AV, 30751
10 T Support control
Room temperature to start the unit if support cooling is active
VentSettings.S_NeedCoolStop
R
0752
RW
AV, 30752
10 T Support control
Room temperature for stop the unit if support cooling is active
VentSettings.S_NeedMinTime
I
0753
RW
AV, 30753
1
min
Support control
Min run time support control
Chapter 5 Holding Register (4x) 92
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_FireDampersAutoMode
X
0754
RW
MSV, 30754
1 - Operation
override
Running mode fire damper: Modbus 0=Close 1=Open 2=Auto Bacnet +1 offset for corresponding Modbus
VentSettings.S_DeIcingSetpoint
R
0755
RW
AV, 30756
10 T Unit setting
Setpoint temperature defrosting
VentSettings.S_DeIcingHyst
R
0756
RW
AV, 30757
10 T Unit setting
Hysteresis to stop defrosting
VentSettings.S_DeIcingMinTime
X
0757
RW
AV, 30758
1 Unit setting
Min run time defrosting
VentSettings.S_DeIcingSAFTempStop
R
0758
RW
AV, 30758
10 T Unit setting
Outdoor temperature min limit to stop supply air fan when defrosting
VentSettings.S_HumiditySetpoint
R
0759
RW
AV, 30759
10
%RH Humidity control
Setpoint humidity room/extract air
VentSettings.S_HumidityMaxDuct
R
0760
RW
AV, 30760
10
%RH Humidity control
Max limit humidity supply air
VentSettings.S_HumidityHyst
R
0761
RW
AV, 30761
10
%RH Humidity control
Hysteresis to start humidity control after stop max limitation
VentSettings.S_HumidityMaxDiff
R
0762
RW
AV, 30762
10
%RH Alarm setting
Alarm limit deviation alarm humidity control VentSettings.S_HumidityStartLimit
R
0763
RW
AV, 30763
10 % Humidity control
Step start point humidity control
VentSettings.S_HumidityStopLimit
R
0764
RW
AV, 30764
10 % Humidity control
Step stop point humidity control
VentSettings.S_RoomSetP
R
0765
RW
AV, 30765
10 T Temperature
setting
Setpoint room temperature if room temperature control
VentSettings.S_FrostProtSPRun(0)
R
0766
RW
AV, 30766
10 T Alarm setting
Alarm limit freeze protection alarm 1
VentSettings.S_FrostProtSPStop(0)
R
0767
RW
AV, 30767
10 T Unit setting
Setpoint freeze protection 1 if standby mode
VentSettings.S_FrostProtPGain(0)
R
0768
RW
AV, 30768
10 T Unit setting
P-band freeze protection 1 if running mode (setpoint=alarm limit+P-band)
Chapter 5 Holding Register (4x) 93
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_FrostProtSPRun(1)
R
0769
RW
AV, 30769
10 Alarm setting
Alarm limit freeze protection alarm 2
VentSettings.S_FrostProtSPStop(1)
R
0770
RW
AV, 30770
10 Unit setting
Setpoint freeze protection 2 if standby mode
VentSettings.S_FrostProtPGain(1)
R
0771
RW
AV, 30771
10 Unit setting
P-band freeze protection 2 if running mode (setpoint=alarm limit+P-band)
VentSettings.S_FrostProtSPRun(2)
R
0772
RW
AV, 30772
10 Alarm setting
Alarm limit freeze protection alarm 3
VentSettings.S_FrostProtSPStop(2)
R
0773
RW
AV, 30773
10 Unit setting
Setpoint freeze protection 3 if standby mode
VentSettings.S_FrostProtPGain(2)
R
0774
RW
AV, 30774
10 Unit setting
P-band freeze protection 3 if running mode (setpoint=alarm limit+P-band)
VentSettings.S_ExtraControllerSetP
R
0775
RW
AV, 30775
10 T Extra controller
Setpoint extra controller
VentSettings.S_ExtraControllerMode
X
0776
RW
MSV, 30776
1 Extra controller
Control mode extra controller Modbus 0=Heating Controller 1=Cooling Controller Bacnet +1 offset for corresponding Modbus
VentSettings.S_SumAlarm1(0)
X
0777
RW
MSV, 30777
1 Unit setting
Setting for sum alarm 1 (alarm levels) Modbus 0=Off 1=A+B+C 2=A+B 3=B+C 4=A+C 5=A 6=B 7=C Bacnet +1 offset for corresponding Modbus
VentSettings.S_SumAlarm2
X
0778
RW
MSV, 30778
1 Unit setting
Setting for sum alarm 2 (alarm levels) (See signal list for SumAlarm1(0))
Chapter 5 Holding Register (4x) 94
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_AlarmOutput
X
0779
RW
AV, 30779
1 Unit setting
Setting of alarm number used for universal alarm output Status: 0=Off 1=AlaPt(1)=Ala_MalfunctionSAF1 2=AlaPt(2)=Ala_MalfunctionSAF2 etc.
VentSettings.S_SupplyMaxDiff
R
0780
RW
AV, 30780
10 T Alarm setting
Alarm limit deviation alarm supply air temperature
VentSettings.S_SupplyHighAlarmLimit
R
0781
RW
AV, 30781
10 T Alarm setting
Alarm limit high supply air temperature
VentSettings.S_SupplyLowAlarmLimit
R
0782
RW
AV, 30782
10 T Alarm setting
Alarm limit low supply air temperature
VentSettings.S_EfficiencyLowLimit
R
0783
RW
AV, 30783
10 % Alarm setting
Alarm limit low efficiency exchanger
VentSettings.S_RoomHighLimit
R
0784
RW
AV, 30784
10 T Alarm setting
Alarm limit high room temperature
VentSettings.S_RoomLowLimit
R
0785
RW
AV, 30785
10 T Alarm setting
Alarm limit low room temperature
VentSettings.S_ExtractAirTempHigh
R
0786
RW
AV, 30786
10 T Alarm setting
Alarm limit high extract air temperature
VentSettings.S_ExtractAirTempLow
R
0787
RW
AV, 30787
10 T Alarm setting
Alarm limit low extract air temperature
VentSettings.S_SAFMaxDiffPressure
R
0788
RW
AV, 30788
10 P Alarm setting
Alarm limit deviation alarm supply air fan
VentSettings.S_EAFMaxDiffPressure
R
0789
RW
AV, 30789
10 P Alarm setting
Alarm limit deviation alarm extract air fan
VentSettings.S_RecircSetP
R
0790
RW
AV, 30790
10 Recirculation
Setpoint recirculation if temperature control
VentSettings.S_RecircTempControl
X
0791
RW
MSV, 30791
1 Recirculation
Supply air temperature control if recirculation: Modbus 0=No temperature control 1=Heating/cooling 2=Only heating 3=Only cooling Bacnet +1 offset for corresponding Modbus
Chapter 5 Holding Register (4x) 95
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_RecircMaxRoomTemp
R
0792
RW
AV, 30792
10 Recirculation
If higher room temp when Recirculation run recirculation damper is closed and fresh air damper is opend
VentSettings.S_RecircFreeCool
X
0793
RW
AV, 30793
1 Recirculation
Allow free cooling if recirculation
VentSettings.S_RecircSAFOffset
R
0794
RW
AV, 30794
1 Recirculation
Offset pressure/flow supply air fan if recirculation
4.3-1-00
VentSettings.S_RecircEAFOffset
R
0795
RW
AV, 30795
1 Recirculation
Offset pressure/flow extract air fan if recirculation (this is not used)
4.3-1-00 VentSettings.S_RecircSetPOffset
R
0796
RW
AV, 30796
10 Recirculation
Offset for recirculation setpoint
VentSettings.S_FilterAlarmTime
I
0797
RW
AV, 30797
1 Alarm setting
Time (in months) for alarm service interval counter
VentSettings.S_ExtraSensor1HighLimit(0)
R
0798
RW
AV, 30798
10 T Alarm setting
Alarm limit high temperature extra sensor 1
VentSettings.S_ExtraSensor2HighLimit
R
0799
RW
AV, 30799
10 T Alarm setting
Alarm limit high temperature extra sensor 2
VentSettings.S_ExtraSensor3HighLimit
R
0800
RW
AV, 30800
10 T Alarm setting
Alarm limit high temperature extra sensor 3
VentSettings.S_ExtraSensor4HighLimit
R
0801
RW
AV, 30801
10 T Alarm setting
Alarm limit high temperature extra sensor 4
VentSettings.S_ExtraSensor5HighLimit
R
0802
RW
AV, 30802
10 T Alarm setting
Alarm limit high temperature extra sensor 5
VentSettings.S_ExtraSensor1LowLimit(0)
R
0803
RW
AV, 30803
10 T Alarm setting
Alarm limit low temperature extra sensor 1
VentSettings.S_ExtraSensor2LowLimit
R
0804
RW
AV, 30804
10 T Alarm setting
Alarm limit low temperature extra sensor 2
VentSettings.S_ExtraSensor3LowLimit
R
0805
RW
AV, 30805
10 T Alarm setting
Alarm limit low temperature extra sensor 3
VentSettings.S_ExtraSensor4LowLimit
R
0806
RW
AV, 30806
10 T Alarm setting
Alarm limit low temperature extra sensor 4
VentSettings.S_ExtraSensor5LowLimit
R
0807
RW
AV, 30807
10 T Alarm setting
Alarm limit low temperature extra sensor 5
VentSettings.S_SelectedSensor1(0)
X
0808
RW
AV, 30808
1 Alarm setting
Select sensor 1 for high & low temperature selected sensor alarm 0 = Not active 1 = A_AI_OutDoorTemp
....
Chapter 5 Holding Register (4x) 96
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_SelectedSensor1HighLimit(0)
R
0809
RW
AV, 30809
10 Alarm setting
Alarm limit high temperature selected sensor 1
VentSettings.S_SelectedSensor1LowLimit(0)
R
0810
RW
AV, 30810
10 Alarm setting
Alarm limit low temperature selected sensor 1
VentSettings.S_SelectedSensor2
X
0811
RW
AV, 30811
1 Alarm setting
Select sensor 2 for high & low temperature selected sensor alarm 0 = Not active 1 = A_AI_OutDoorTemp
....
VentSettings.S_SelectedSensor2HighLimit
R
0812
RW
AV, 30812
10 Alarm setting
Alarm limit high temperature selected sensor 2
VentSettings.S_SelectedSensor2LowLimit
R
0813
RW
AV, 30813
10 Alarm setting
Alarm limit low temperature selected sensor 2
VentSettings.S_SupplyPIDFreeze
X
0814
RW
MSV, 30814
1 Unit setting
Freeze supply temperature PID control
VentSettings.S_FanComp1X1(0)
R
0815
RW
AV, 30815
10 Fan compensation curve
Curve 1 point 1 sensor value
VentSettings.S_FanComp1Y1(0)
R
0816
RW
AV, 30816
10 Fan compensation curve
Curve 1 point 1 setpoint compensation
VentSettings.S_FanComp1X2(0)
R
0817
RW
AV, 30817
10 Fan compensation curve
Curve 1 point 2 sensor value
VentSettings.S_FanComp1Y2(0)
R
0818
RW
AV, 30818
10 Fan compensation curve
Curve 1 point 2 setpoint compensation
VentSettings.S_FanComp1X3(0)
R
0819
RW
AV, 30819
10 Fan compensation curve
Curve 1 point 3 sensor value
VentSettings.S_FanComp1Y3(0)
R
0820
RW
AV, 30820
10 Fan compensation curve
Curve 1 point 3 setpoint compensation
Chapter 5 Holding Register (4x) 97
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_FanComp2X1
R
0821
RW
AV, 30821
10 Fan compensation curve
Curve 2 point 1 sensor value
VentSettings.S_FanComp2Y1
R
0822
RW
AV, 30822
10 Fan compensation curve
Curve 2 point 1 setpoint compensation
VentSettings.S_FanComp2X2
R
0823
RW
AV, 30823
10 Fan compensation curve
Curve 2 point 2 sensor value
VentSettings.S_FanComp2Y2
R
0824
RW
AV, 30824
10 Fan compensation curve
Curve 2 point 2 setpoint compensation
VentSettings.S_FanComp2X3
R
0825
RW
AV, 30825
10 Fan compensation curve
Curve 2 point 3 sensor value
VentSettings.S_FanComp2Y3
R
0826
RW
AV, 30826
10 Fan compensation curve
Curve 2 point 3 setpoint compensation
VentSettings.S_FanComp3X1
R
0827
RW
AV, 30827
10 Fan compensation curve
Curve 3 point 1 sensor value
VentSettings.S_FanComp3Y1
R
0828
RW
AV, 30828
10 Fan compensation curve
Curve 3 point 1 setpoint compensation
VentSettings.S_FanComp3X2
R
0829
RW
AV, 30829
10 Fan compensation curve
Curve 3 point 2 sensor value
VentSettings.S_FanComp3Y2
R
0830
RW
AV, 30830
10 Fan compensation curve
Curve 3 point 2 setpoint compensation
Chapter 5 Holding Register (4x) 98
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_FanComp3X3
R
0831
RW
AV, 30831
10 Fan compensation curve
Curve 3 point 3 sensor value
VentSettings.S_FanComp3Y3
R
0832
RW
AV, 30832
10 Fan compensation curve
Curve 3 point 3 setpoint compensation VentSettings.S_NeutralZone
R
0833
RW
AV, 30833
10 T Unit setting
Neutral zone around supply setpoint before heating and cooling.
VentSettings.S_FreeCoolSAFOffset
R
0834
RW
AV, 30834
1
P/Q
Free cooling
Setpoint offset supply air fan if free cooling
4.3-1-00
VentSettings.S_FreeCoolEAFOffset
R
0835
RW
AV, 30835
1
P/Q
Free cooling
Setpoint offset extract air fan if free cooling
4.3-1-00
VentSettings.S_FilterGuard1Limit_X1(0)
R
0836
RW
AV, 30836
1 Q Alarm setting
Limit X1 filter guard supply
4.3-1-00
VentSettings.S_FilterGuard1Limit_Y1
R
0837
RW
AV, 30837
10 P Alarm setting
Limit Y1 filter guard supply
VentSettings.S_FilterGuard1Limit_X2
R
0838
RW
AV, 30838
1 Q Alarm setting
Limit X2 filter guard supply
4.3-1-00
VentSettings.S_FilterGuard1Limit_Y2
R
0839
RW
AV, 30839
10 P Alarm setting
Limit Y2 filter guard supply
VentSettings.S_FilterGuard2Limit_X1(0)
R
0840
RW
AV, 30840
1 Q Alarm setting
Limit X1 filter guard extract
4.3-1-00
VentSettings.S_FilterGuard2Limit_Y1
R
0841
RW
AV, 30841
10 P Alarm setting
Limit Y1 filter guard extract
VentSettings.S_FilterGuard2Limit_X2
R
0842
RW
AV, 30842
1 Q Alarm setting
Limit X2 filter guard extract
4.3-1-00
VentSettings.S_FilterGuard2Limit_Y2
R
0843
RW
AV, 30843
10 P Alarm setting
Limit Y2 filter guard extract
VentSettings.S_SummerModeSupplySetpoint
R
0844
RW
AV, 30844
10 T Summer setting
Supply air temp setpoint at summer time
VentSettings.S_SummerModeOutdoortemp
R
0845
RW
AV, 30845
10 T Summer setting
Outdoor temp for switching between summer and winter mode
VentSettings.S_SummerModeStartDate
X
0846
RW 1 Summer setting
Date for start of summer period
VentSettings.S_SummerModeStartMonth
X
0847
RW 1 Summer setting
Month for start of summer period
VentSettings.S_SummerModeStopDate
X
0848
RW 1 Summer setting
Date for stop of summer period
VentSettings.S_SummerModeStopMonth
X
0849
RW 1 Summer setting
Month for stop of summer period
Chapter 5 Holding Register (4x) 99
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentActual.A_BMS_OutDoorTemp
R
0850
RW
AV, 30850
10 T AI function
Outdoor temperature sent from BMS system
4.1-1-01
VentSettings.S_EnergyHeaterLeakagedT
R
0851
RW
AV, 30851
10 T Energy insight
Alarm limit in delta T, for leakage heater valve
4.1-1-01
VentSettings.S_Zone1SetP(0)
R
0852
RW
AV, 30852
10 T Temperature setting
Setpoint zone 1 air temperature
4.3-1-00
VentSettings.S_Zone2SetP
R
0853
RW
AV, 30853
10 T Temperature setting
Setpoint zone 2 air temperature
4.3-1-00
VentSettings.S_Zone3SetP
R
0854
RW
AV, 30854
10 T Temperature setting
Setpoint zone 3 air temperature
4.3-1-00
VentSettings.S_Zone1SetpointMax(0)
R
0855
RW
AV, 30855
10 T Temperature setting
Max limit of zone 1 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone1SetpointMin(0)
R
0856
RW
AV, 30856
10 T Temperature setting
Min limit of zone 1 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone2SetpointMax
R
0857
RW
AV, 30857
10 T Temperature setting
Max limit of zone 2 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone2SetpointMin
R
0858
RW
AV, 30858
10 T Temperature setting
Min limit of zone 2 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone3SetpointMax
R
0859
RW
AV, 30859
10 T Temperature setting
Max limit of zone 3 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone3SetpointMin
R
0860
RW
AV, 30860
10 T Temperature setting
Min limit of zone 3 supply setpoint if cascade control
4.3-1-00
VentSettings.S_Zone1NeutralZone(0)
R
0861
RW
AV, 30861
10 T Temperature setting
Neutral zone around supply setpoint before heating and cooling zone 1.
4.3-1-00
VentSettings.S_Zone2NeutralZone
R
0862
RW
AV, 30862
10 T Temperature setting
Neutral zone around supply setpoint before heating and cooling zone 2.
4.3-1-00
VentSettings.S_Zone3NeutralZone
R
0863
RW
AV, 30863
10 T Temperature setting
Neutral zone around supply setpoint before heating and cooling zone 3.
4.3-1-00 VentSettings.S_FrostProtSPRunZone1
R
0864
RW
AV, 30864
10 T Alarm setting
Alarm limit freeze protection alarm zone 1
4.3-1-00
VentSettings.S_FrostProtSPStopZone1
R
0865
RW
AV, 30865
10 T Unit setting
Setpoint freeze protection zone 1 if standby mode
4.3-1-00
Chapter 5 Holding Register (4x) 100
Signal name
EXOL type Modbus address RW
Bacnet
Scale factor Unit
Function
Description
Release
VentSettings.S_FrostProtPGainZone1
R
0866
RW
AV, 30866
10 T Unit setting
P-band freeze protection zone 1 if running mode (setpoint=alarm limit+P-band)
4.3-1-00 VentSettings.S_FrostProtSPRunZone2
R
0867
RW
AV, 30867
10 T Alarm setting
Alarm limit freeze protection alarm zone 2
4.3-1-00
VentSettings.S_FrostProtSPStopZone2
R
0868
RW
AV, 30868
10 T Unit setting
Setpoint freeze protection zone 2 if standby mode
4.3-1-00
VentSettings.S_FrostProtPGainZone2
R
0869
RW
AV, 30869
10 T Unit setting
P-band freeze protection zone 2 if running mode (setpoint=alarm limit+P-band)
4.3-1-00 VentSettings.S_FrostProtSPRunZone3
R
0870
RW
AV, 30870
10 T Alarm setting
Alarm limit freeze protection alarm zone 3
4.3-1-00
VentSettings.S_FrostProtSPStopZone3
R
0871
RW
AV, 30871
10 T Unit setting
Setpoint freeze protection zone 3 if standby mode
4.3-1-00
VentSettings.S_FrostProtPGainZone3
R
0872
RW
AV, 30872
10 T Unit setting
P-band freeze protection zone 3 if running mode (setpoint=alarm limit+P-band)
4.3-1-00 VentSettings.S_SAFLowspeedAirFlow(0)
R
0873
RW 1 Q Fan setting
Flow setpoint supply air fan low speed (32-bit float)
4.3-1-00
VentSettings.S_SAFNormalspeedAirFlow
R
0875
RW 1 Q Fan setting
Flow setpoint supply air fan normal speed (32­bit float)
4.3-1-00
VentSettings.S_SAFHighspeedAirFlow
R
0877
RW 1 Q Fan setting
Flow setpoint supply air fan high speed (32-bit float)
4.3-1-00
VentSettings.S_EAFLowspeedAirFlow(0)
R
0879
RW 1 Q Fan setting
Flow setpoint extract air fan low speed (32-bit float)
4.3-1-00
VentSettings.S_EAFNormalspeedAirFlow
R
0881
RW 1 Q Fan setting
Flow setpoint extract air fan normal speed (32­bit float)
4.3-1-00
VentSettings.S_EAFHighspeedAirFlow
R
0883
RW 1 Q Fan setting
Flow setpoint extract air fan high speed (32-bit float)
4.3-1-00
VentSettings.S_DelayedStartDXCool
R
0885
RW
AV, 30885
10 T Temperature setting
Min setpoint deviation to allow start of DX­cooling
4.3-1-00
VentSettings.S_DelayedStartDXHeat
R
0886
RW
AV, 30886
10 T Temperature setting
Min setpoint deviation to allow start of DX­heating
4.3-1-00