Communication manual
Access software from 4.0-1-04 to 4.3-1-00
EN
Document in original language | 153831 · A006
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg3.png)
Table of contents
Chapter 1 About this document __________________________________________________________ 4
Introduction _______________________________________________________________________________ 4
Software version ___________________________________________________________________________ 4
Signal types _______________________________________________________________________________ 4
Chapter 2 System integration ___________________________________________________________ 6
Modbus __________________________________________________________________________________ 6
BACnet ___________________________________________________________________________________ 8
Watchdog_________________________________________________________________________________ 9
Ethernet setting ___________________________________________________________________________ 11
Type example addresses ____________________________________________________________________ 14
Chapter 3 Coil Status Register (0x) ______________________________________________________ 15
Chapter 4 Input Register (3x) ___________________________________________________________ 16
Chapter 5 Holding Register (4x) _________________________________________________________ 49
Chapter 6 Input Status Register (1x) ____________________________________________________ 102
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg4.png)
Chapter 1 │About this document 4
Chapter 1 About this document
Introduction
This document describes all Access signals that are accessible via EXOline, Modbus and BACnet.
Software version
EXOline, BACnet and Modbus are available
With Ethernet menu, static IP setting
Release column in register tables further down in this document tells from which software release
variables was introduced or changed.
Signal types
All signals accessible from a SCADA system are described further in this document.
EXOL type
The EXOL type of the signals:
R = Real (-3.3E38 - 3.3E38)
I = Integer (-32768 - 32767)
X = Index (0 - 255)
L = Logic (0/1)
Modbus type
The Modbus type of the signals:
0x = Coil Status Register (1bit)
1x = Input Status Register (1bit)
4x = Holding Register (signed, 16bit or 32bit word)
3x = Input Register (signed, 16bit word or 32bit float)
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg5.png)
Chapter 1 │About this document 5
Supported Modbus functions:
1 = Read Coils
2 = Read Discrete Input
3 = Read Holding Register
4 = Read Input Register
5 = Write Single Coil
6 = Write Single Register
15 = Write Multiple Coils
16 = Write Multiple Registers
BACnet type
The BACnet type of signals:
10XXX = Read and write binary
20XXX = Read binary
30XXX = Read and write analogue
40XXX = Read analogue
30XXX = Read and write multistate
40XXX = Read multistate
(Where XXX = Modbus address)
NOTE: In the variable lists contained in this manual, the following abbrevations are used:
AV = Analogue Value
BV = Binary Value
MSV = Multistate Value
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg6.png)
Chapter 2 │System integration 6
Chapter 2 System integration
Modbus
Addresses
All addresses starts with 0, and due to that some Master devices starts address with 1 (equal to register)
it’s in that case necessary to add all addresses in this document with +1.
Communication limitations
The Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two
messages.
Baudrate
9600, 14 400, 19 200, 28 800, 38 400, 57 600, 76 800, 115 200 bps
Scale factor Modbus
Real signals could have scale factor according to Scale factor column in tables. In general 10 is used
except for time setting signals which have scale factor 100, and air flow signals which have scale
factor 1. Example, with a scale factor 10 of an temperature Integer value could then be interpreted as
a value with one decimal. Integer, Index and Logic always have scale factor 1.
Unit
Real signal values could have an engineering unit according to Unit-column in tables, where T, Q and
P represent temperature-, flow- and pressure unit according selected preference setting in the
controller.
Modbus wiring, etc.
A protocol like Modbus consists of several layers (OSI-model). The bottom layer is always the
physical layer; the number of wires and signal levels. The next layer describes the communication
digits (number of data bits, stop-bits, parity etc). Next are the layers describing the Modbus-specific
functions (number of digits per message, the meaning of different messages, etc.).
For Modbus, the bottom layer can be RS485, RS422, RS232 or Modbus TCP.
Max. 47 registers
A maximum of 47 registers can be read in one message.
Transmission mode
Access uses the RTU transmission mode for the communication ports. The transmission mode must
be the same in the master unit and the slave units, since Modbus/RTU cannot understand
Modbus/ASCII messages. The configuration parameter Word length is always 8 for Modbus/RTU.
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg7.png)
Chapter 2 │System integration 7
When using Modbus TCP the controller Ethernet port in combination with TCP port setting 502
should be used.
Writing values
To override the output values, set the output to manual mode using a Modbus signal. Then set the
corresponding ..._ManSet signal to the wanted level. These signals are listed in Chapter 5: Holding
Registers. Remember that only values with a default value are adjustable, you will find these in the
chapters Coil Status Register and Holding Register.
Configuration
Modbus TCP/IP enabled as default. Modbus RTU is enabled via configuration of the communication
ports.
The communication parameters for the Modbus line is the most important thing to configure first.
These parameters must be identical in both the master unit and slave units, since they define the
structure of messages and the transmission speed.
The default configuration values of a Access controller are
Slave address: 1
Word length: 8 bit
Parity: none
Stop bits: 2 bits
Baud rate: 9600 bps
Slave address
A new Modbus slave address can be set for each air handling unit using the NaviPad.
NOTE To change the Modbus slave address when using Modbus TCP/IP a communication port must
be temporarily configured as Modbus slave to access the slave address setting.
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg8.png)
Chapter 2 │System integration 8
BACnet
Access from software version 4.0-1-05 is capable of communication via the BACnet-ASC
(Application Specific Controller) protocol and from 4.3-1-00 with BACnet AAC (Advanced
Application Controller).
In order to connect a Access application to a BMS (Building Management System) via BACnet/IP
use the TCP/IP port.
BACnet/IP configuration (Activation status of BACnet/IP protocol)
Upon delivery, the BACnet/IP protocol is disabled as a default. To enable BACnet communication,
simply change the setting “No” to “Yes”.
BACnet device name
This is the devices name that is shown on the BMS when a device is discovered.
BACnet device ID
The ID of a device, used to identify it on the BACnet network. This number cannot be duplicated
anywhere on the BACnet network and must therefore be unique.
BBMD address and BACnet/IP port number
The BBMD address (BACnet/IP Broadcast Management Device) is used for discovering devices that
are attached to different BACnet/IP subnets and separated by an IP router. The address is entered as
host:port, where “host” can be the host’s name if DNS is configured. If DNS is not configured, the
host address should be entered in the format “xxx.xxx.xxx.xxx”, followed by the port number (default
setting 47808).
Example: mybbmd:47808 (with DNS configured) or 10.100.50.99:47808
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg9.png)
Chapter 2 │System integration 9
DHCP
The Dynamic Host Configuration Protocol (DHCP) is a network protocol used on Internet Protocol
(IP) networks for dynamic distribution of network configuration parameters, such as IP addresses,
DNS servers and other services. The Access controller can be configured to either obtain an IP address
from a DHCP server (dynamic) or the address can be set manually (static).
If static IP address needed for the Access cotroller, simply enter the IP address you wish to use along
with the subnet mask, gateway address and DNS server address via the controller webinterface from
version 4.0-1-04 [Ethernet setting].
Watchdog
Access from software version 4.1-1-00 is capable of supervising communication recieved from a
BMS master. One slave communication protocol can be monitored at a time. If no active
communication from the BMS master is detected before the watchdog timeout elapses, an alarm
message is generated.
BMS watchdog (Activation of protocol)
Upon delivery, the BMS watchdog is disabled as default. Activation and configuration of BMS
watchdog is done via controller web menu Configuration / System settings / Communication / BMS
watchdog
BMS protocol
To enable BMS watchdog, change the setting “None” to the protocol used for BMS communication.
Supported BMS slave protocols are EXOline, Modbus and BACnet.
Watchdog timeout
Configure the watchdog timeout setting between 10 to 3600 seconds (1 hour), default 60 seconds. A
byte counter of received bytes is supposed to change since the last cycle. If counter has not been
changed during the watchdog timeout setting the communication is considered faulty and an alarm
message is generated.
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bga.png)
Chapter 2 │System integration 10
Communication fault BMS master
When a communication fault with BMS is detected, values from BMS should be considered invalid.
The alarm is configured default as Class C with no action.
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bgb.png)
Chapter 2 │System integration 11
Ethernet setting
When NaviPad and Control unit are connected directly to each other via switch module without any
DHCP server they assign themselves with Auto-IP (Link-local) addresses and then randomly pick
from address range 169.254.x.y (255.255.0.0).
The possibility of using a static IP address as alternative to a dynamic IP address (DHCP) is available
from Access software version 4.0-1-04 and NaviPad software version 1.1.0.184. For manually setting
a static IP address, please follow below steps.
1. From NaviPad log in to the AHU web page
2. Select Yes to enable settings AHU to static IP via AHU web interface
3. Edit AHU control unit IP address, subnet mask, gateway and DNS according your IP plan
4. Select Yes for Save IP settings
5. Press home button on NaviPad to log out from AHU web page
The NaviPad will then lose the connection to AHU since it’s probably is assigned to a not valid
IP address anymore
6. In NaviPad system select Advanced HMI setting and select Ethernet (default login password
‘1111’)
7. Activate switch to enable Static IP setting
8. Edit NaviPad IP address, subnet mask and gateway according your IP plan
9. Use NaviPad to search for available devices and select AHU
NOTE The air handling unit and the NaviPad as well as any computer has to be connected on a local
network within the same IP subnet.
NOTE If no gateway is available use either 0.0.0.0 or equal to the IP address set for the device.
Access controller
The below picture illustrates the appearance of Ethernet settings for controller in controller web menu
from Access software version 4.0-1-04:
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bgc.png)
Chapter 2 │System integration 12
NaviPad
The below picture illustrates the appearance of Ethernet settings for the NaviPad from NaviPad
software version 1.1.0.184:
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bgd.png)
Chapter 2 │System integration 13
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bge.png)
Chapter 2 │System integration 14
Type example addresses
Example of useful register addresses in a flow chart for a AHU with rotary exchanger and a cooling
unit.
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bgf.png)
Chapter 3 │Coil Status Register (0x) 15
Chapter 3 Coil Status Register (0x)
EXOL type Modbus address RW
VentSettings.S_AlaAcknowAll
Command to acknowledge all alarms
VentSettings.S_FilterAlarmReset
Command to reset the alarm service interval
counter
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg10.png)
Chapter 4 │Input Register (3x) 16
Chapter 4 Input Register (3x)
EXOL type Modbus address RW Bacnet
AlaData.Ala_MalfunctionSAF1_Status
Malfunction supply air fan 1
AlaData.Ala_MalfunctionSAF2_Status
Malfunction supply air fan 2
AlaData.Ala_MalfunctionSAF3_Status
Malfunction supply air fan 3
AlaData.Ala_MalfunctionSAF4_Status
Malfunction supply air fan 4
AlaData.Ala_MalfunctionSAF5_Status
Malfunction supply air fan 5
AlaData.Ala_MalfunctionEAF1_Status
Malfunction extract air fan 1
AlaData.Ala_MalfunctionEAF2_Status
Malfunction extract air fan 2
AlaData.Ala_MalfunctionEAF3_Status
Malfunction extract air fan 3
AlaData.Ala_MalfunctionEAF4_Status
Malfunction extract air fan 4
AlaData.Ala_MalfunctionEAF5_Status
Malfunction extract air fan 5
AlaData.Ala_AlarmSAF1_Status
AlaData.Ala_AlarmSAF2_Status
AlaData.Ala_AlarmSAF3_Status
AlaData.Ala_AlarmSAF4_Status
AlaData.Ala_AlarmSAF5_Status
AlaData.Ala_AlarmEAF1_Status
AlaData.Ala_AlarmEAF2_Status
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg11.png)
Chapter 4 │Input Register (3x) 17
EXOL type Modbus address RW Bacnet
AlaData.Ala_AlarmEAF3_Status
AlaData.Ala_AlarmEAF4_Status
AlaData.Ala_AlarmEAF5_Status
AlaData.Ala_WarningSAF1_Status
AlaData.Ala_WarningSAF2_Status
AlaData.Ala_WarningSAF3_Status
AlaData.Ala_WarningSAF4_Status
AlaData.Ala_WarningSAF5_Status
AlaData.Ala_WarningEAF1_Status
Warning extract air fan 1
AlaData.Ala_WarningEAF2_Status
Warning extract air fan 2
AlaData.Ala_WarningEAF3_Status
Warning extract air fan 3
AlaData.Ala_WarningEAF4_Status
Warning extract air fan 4
AlaData.Ala_WarningEAF5_Status
Warning extract air fan 5
AlaData.Ala_ExternalRunSAF_Status
External operation supply air fan
AlaData.Ala_ExternalRunEAF_Status
External operation extract air fan
AlaData.Ala_ExternalRunMotor1_Status
Extra fan motor 1 running
AlaData.Ala_ExternalRunMotor2_Status
Extra fan motor 2 running
AlaData.Ala_MalfunctionPumpHeater_Status
AlaData.Ala_MalfunctionPumpCooler_Status
AlaData.Ala_MalfunctionPumpExchanger_Status
Malfunction pump exchanger
AlaData.Ala_MalfunctionFireDamper_Status
AlaData.Ala_MalfunctionDamper_Status
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg12.png)
Chapter 4 │Input Register (3x) 18
EXOL type Modbus address RW Bacnet
AlaData.Ala_MalfunctionMotor1_Status
Malfunction extra fan motor 1
AlaData.Ala_MalfunctionMotor2_Status
Malfunction extra fan motor 2
AlaData.Ala_FireDamperExerciseStop_Status
Malfunction fire damper exercise
AlaData.Ala_MalfunctionPumpSequence1_Status
Malfunction pump sequence-A
AlaData.Ala_MalfunctionPumpSequence2_Status
Malfunction pump sequence-B
AlaData.Ala_MalfunctionPumpSequence3_Status
Malfunction pump sequence-C
AlaData.Ala_MalfunctionPumpSequence4_Status
Malfunction pump sequence-D
AlaData.Ala_MalfunctionPumpSequence5_Status
Malfunction pump sequence-E
AlaData.Ala_MalfunctionPumpSequence6_Status
Malfunction pump sequence-F
AlaData.Ala_MalfunctionPumpSequence7_Status
Malfunction pump sequence-G
AlaData.Ala_MalfunctionPumpSequence8_Status
Malfunction pump sequence-H
AlaData.Ala_MalfunctionPumpSequence9_Status
Malfunction pump sequence-I
AlaData.Ala_MalfunctionPumpSequence10_Status
Malfunction pump sequence-J
AlaData.Ala_FilterGuard1_Status
AlaData.Ala_FilterGuard2_Status
AlaData.Ala_FlowGuard_Status
AlaData.Ala_ExternalFrostGuard_Status
AlaData.Ala_DeicingGuard_Status
Defrosting guard exchanger
AlaData.Ala_FireAlarm_Status
AlaData.Ala_SmokeAlarm_Status
AlaData.Ala_ExternalSwitch_Status
AlaData.Ala_ExternalAlarm_Status
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg13.png)
Chapter 4 │Input Register (3x) 19
EXOL type Modbus address RW Bacnet
AlaData.Ala_ServiceStop_Status
AlaData.Ala_ElectricOverheat_Status
Electric heater is overheated
AlaData.Ala_FrostRisk_Status
Warning freeze protection
AlaData.Ala_LowEfficiency_Status
AlaData.Ala_AnalogueDeicing_Status
AlaData.Ala_RotationguardExchanger_Status
AlaData.Ala_ExtraAlarm1_Status
AlaData.Ala_ExtraAlarm2_Status
AlaData.Ala_ExtraAlarm3_Status
AlaData.Ala_ExtraAlarm4_Status
AlaData.Ala_ExtraAlarm5_Status
AlaData.Ala_ExtraAlarm6_Status
AlaData.Ala_ExtraAlarm7_Status
AlaData.Ala_ExtraAlarm8_Status
AlaData.Ala_ExtraAlarm9_Status
AlaData.Ala_ExtraAlarm10_Status
AlaData.Ala_BatteryFail_Status
AlaData.Ala_Service_Status
AlaData.Ala_RestartBlocked_Status
Restart blocked after power on
AlaData.Ala_ControlErrorSupplyTemp_Status
Deviation alarm supply air temperature
AlaData.Ala_ControlErrorSAF_Status
Deviation alarm supply air fan
AlaData.Ala_ControlErrorEAF_Status
Deviation alarm extract air fan
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg14.png)
Chapter 4 │Input Register (3x) 20
EXOL type Modbus address RW Bacnet
AlaData.Ala_ControlErrorHumidity_Status
Deviation alarm humidity control
AlaData.Ala_ControlErrorExtraController_Status
Deviation alarm extra controller
AlaData.Ala_HighTempSupply_Status
High supply air temperature
AlaData.Ala_LowTempSupply_Status
Low supply air temperature
AlaData.Ala_MaxLimitTempSupply_Status
Supply air temperature max limit
AlaData.Ala_MinLimitTempSupply_Status
Supply air temperature min limit
AlaData.Ala_HighTempRoom_Status
AlaData.Ala_LowTempRoom_Status
AlaData.Ala_HighTempExtract_Status
High extract air temperature
AlaData.Ala_LowTempExtract_Status
Low extract air temperature
AlaData.Ala_HighTempOutdoor_Status
High outdoor air temperature
AlaData.Ala_LowTempOutdoor_Status
Low outdoor air temperature
AlaData.Ala_LowTempFrostGuard1_Status
Freeze protection alarm 1
AlaData.Ala_LowTempFrostGuard2_Status
Freeze protection alarm 2
AlaData.Ala_LowTempFrostGuard3_Status
Freeze protection alarm 3
AlaData.Ala_HighTempExtraSensor1_Status
High temperature extra sensor 1
AlaData.Ala_LowTempExtraSensor1_Status
Low temperature extra sensor 1
AlaData.Ala_HighTempExtraSensor2_Status
High temperature extra sensor 2
AlaData.Ala_LowTempExtraSensor2_Status
Low temperature extra sensor 2
AlaData.Ala_HighTempExtraSensor3_Status
High temperature extra sensor 3
AlaData.Ala_LowTempExtraSensor3_Status
Low temperature extra sensor 3
AlaData.Ala_HighTempExtraSensor4_Status
High temperature extra sensor 4
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg15.png)
Chapter 4 │Input Register (3x) 21
EXOL type Modbus address RW Bacnet
AlaData.Ala_LowTempExtraSensor4_Status
Low temperature extra sensor 4
AlaData.Ala_HighTempExtraSensor5_Status
High temperature extra sensor 5
AlaData.Ala_LowTempExtraSensor5_Status
Low temperature extra sensor 5
AlaData.Ala_HighTempSelectedSensor1_Status
High temperature selected sensor 1
AlaData.Ala_LowTempSelectedSensor1_Status
Low temperature selected sensor 1
AlaData.Ala_HighTempSelectedSensor2_Status
High temperature selected sensor 2
AlaData.Ala_LowTempSelectedSensor2_Status
Low temperature selected sensor 2
AlaData.Ala_ManualControlUnit_Status
Manual operation air handling unit
AlaData.Ala_ManualControlSupply_Status
Manual operation supply air
AlaData.Ala_ManualControlSAF_Status
Manual operation supply air fan
AlaData.Ala_ManualControlEAF_Status
Manual operation extract air fan
AlaData.Ala_ManualControlHeater_Status
AlaData.Ala_ManualControlExchanger_Status
Manual operation exchanger
AlaData.Ala_ManualControlCooler_Status
AlaData.Ala_ManualControlDamper_Status
AlaData.Ala_ManualControlPumpHeater_Status
Manual operation pump heater
AlaData.Ala_ManualControlPumpExchanger_Status
Manual operation pump exchanger
AlaData.Ala_ManualControlPumpCooler_Status
Manual operation pump cooler
AlaData.Ala_ManualControlDamperRecirculation_Status
Manual operation damper recirculation
AlaData.Ala_ManualControlDamperOutdoor_Status
Manual operation damper outdoor air
AlaData.Ala_ManualControlDamperExhaust_Status
Manual operation damper exhaust air
AlaData.Ala_ManualControlDamperFire_Status
Manual operation fire damper
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg16.png)
Chapter 4 │Input Register (3x) 22
EXOL type Modbus address RW Bacnet
AlaData.Ala_ManualControlSequence1_Status
Manual control sequence-A
AlaData.Ala_ManualControlSequence2_Status
Manual control sequence-B
AlaData.Ala_ManualControlSequence3_Status
Manual control sequence-C
AlaData.Ala_ManualControlSequence4_Status
Manual control sequence-D
AlaData.Ala_ManualControlSequence5_Status
Manual control sequence-E
AlaData.Ala_ManualControlSequence6_Status
Manual control sequence-F
AlaData.Ala_ManualControlSequence7_Status
Manual control sequence-G
AlaData.Ala_ManualControlSequence8_Status
Manual control sequence-H
AlaData.Ala_ManualControlSequence9_Status
Manual control sequence-I
AlaData.Ala_ManualControlSequence10_Status
Manual control sequence-J
AlaData.Ala_ManualControlOutput_Status
Output in manual operation
AlaData.Ala_ManualControlInput_Status
Input in manual operation
AlaData.Ala_ManualControlExtraController_Status
Manual operation extra controller
AlaData.Ala_ManualControlMotor1_Status
Manual operation external fan motor 1
AlaData.Ala_ManualControlMotor2_Status
Manual operation external fan motor 2
AlaData.Ala_ManualControlPretreatment_Status
Manual operation pretreatment
AlaData.Ala_SensorErrorTempOutdoor_Status
Sensor error outdoor air temperature
AlaData.Ala_SensorErrorTempIntake_Status
Sensor error intake air temperature
AlaData.Ala_SensorErrorTempSupply_Status
Sensor error supply air temperature
AlaData.Ala_SensorErrorTempExhaust_Status
Sensor error exhaust air temperature
AlaData.Ala_SensorErrorTempExtract_Status
Sensor error extract air temperature
AlaData.Ala_SensorErrorTempRoom1_Status
Sensor error room temperature 1
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg17.png)
Chapter 4 │Input Register (3x) 23
EXOL type Modbus address RW Bacnet
AlaData.Ala_SensorErrorTempRoom2_Status
Sensor error room temperature 2
AlaData.Ala_SensorErrorTempRoom3_Status
Sensor error room temperature 3
AlaData.Ala_SensorErrorTempRoom4_Status
Sensor error room temperature 4
AlaData.Ala_SensorErrorPressureSAF_Status
Sensor error pressure supply air
AlaData.Ala_SensorErrorPressureEAF_Status
Sensor error pressure extract air
AlaData.Ala_SensorErrorFlowSAF_Status
Sensor error flow supply air
AlaData.Ala_SensorErrorFlowEAF_Status
Sensor error flow extract air
AlaData.Ala_SensorPressureExchangerSAF_Status
Sensor error flow exchanger supply air
AlaData.Ala_SensorPressureExchangerEAF_Status
Sensor error pressure exchanger extract air
AlaData.Ala_SensorErrorTempDeicing_Status
Sensor error defrosting temperature
AlaData.Ala_SensorErrorTempFrost1_Status
Sensor error freeze protection temperature 1
AlaData.Ala_SensorErrorTempFrost2_Status
Sensor error freeze protection temperature 2
AlaData.Ala_SensorErrorTempFrost3_Status
Sensor error freeze protection temperature 3
AlaData.Ala_SensorErrorCO2_Status
Sensor error CO2 room/extract air
AlaData.Ala_SensorErrorHumidityRoom_Status
Sensor error humidity room/extract air
AlaData.Ala_SensorErrorHumidityDuct_Status
Sensor error humidity supply air
AlaData.Ala_SensorErrorTempExtraController_Status
Sensor error extra controller
AlaData.Ala_SensorErrorExtCtrlSAF_Status
Signal error external control supply air fan
AlaData.Ala_SensorErrorExtCtrlEAF_Status
Signal error external control extract air fan
AlaData.Ala_SensorErrorHumidityOutdoor_Status
Sensor error humidity outdoor
AlaData.Ala_SensorErrorTempExtraSensor1_Status
Sensor error extra sensor 1
AlaData.Ala_SensorErrorTempExtraSensor2_Status
Sensor error extra sensor 2
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg18.png)
Chapter 4 │Input Register (3x) 24
EXOL type Modbus address RW Bacnet
AlaData.Ala_SensorErrorTempExtraSensor3_Status
Sensor error extra sensor 3
AlaData.Ala_SensorErrorTempExtraSensor4_Status
Sensor error extra sensor 4
AlaData.Ala_SensorErrorTempExtraSensor5_Status
Sensor error extra sensor 5
AlaData.Ala_SensorErrorExtSupplySetp_Status
Sensor error external temperature setpoint
AlaData.Ala_SensorErrorExtFlowSetpoint_Status
Signal error external flow setpoint
AlaData.Ala_SensorErrorFilterGuard1_Status
Sensor error pressure filter supply air
AlaData.Ala_SensorErrorFilterGuard2_Status
Sensor error pressure filter extract air
AlaData.Ala_SensorErrorTempEfficiency_Status
Sensor error efficiency temp
AlaData.Ala_CommErrorDevice_Status
Fault communication device
AlaData.Ala_MalfunctionExtraController_Status
Malfunction Extra Controller
AlaData.Ala_InternalError_Status
AlaData.Ala_SmokeDetectorService_Status
AlaData.Ala_SmokeDetectorError_Status
Smoke detector connection error
AlaData.Ala_MalfunctionPreheater_Status
AlaData.Ala_CommunicationFaultBMS_Status
Communication fault BMS master
AlaData.Ala_LeakageHeaterValve_Status
AlaData.Ala_SensorErrorTempPreheat_Status
Sensor error preheater temp
AlaData.Ala_MalfunctionSAF6_Status
Malfunction supply air fan 6
AlaData.Ala_MalfunctionSAF7_Status
Malfunction supply air fan 7
AlaData.Ala_MalfunctionSAF8_Status
Malfunction supply air fan 8
AlaData.Ala_MalfunctionEAF6_Status
Malfunction extract air fan 6
AlaData.Ala_MalfunctionEAF7_Status
Malfunction extract air fan 7
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg19.png)
Chapter 4 │Input Register (3x) 25
EXOL type Modbus address RW Bacnet
AlaData.Ala_MalfunctionEAF8_Status
Malfunction extract air fan 8
AlaData.Ala_AlarmSAF6_Status
AlaData.Ala_AlarmSAF7_Status
AlaData.Ala_AlarmSAF8_Status
AlaData.Ala_AlarmEAF6_Status
AlaData.Ala_AlarmEAF7_Status
AlaData.Ala_AlarmEAF8_Status
AlaData.Ala_WarningSAF6_Status
AlaData.Ala_WarningSAF7_Status
AlaData.Ala_WarningSAF8_Status
AlaData.Ala_WarningEAF6_Status
Warning extract air fan 6
AlaData.Ala_WarningEAF7_Status
Warning extract air fan 7
AlaData.Ala_WarningEAF8_Status
Warning extract air fan 8
AlaData.Ala_MalfunctionHeatingZone1_Status
Malfunction heating zone 1
AlaData.Ala_MalfunctionHeatingZone2_Status
Malfunction heating zone 2
AlaData.Ala_MalfunctionHeatingZone3_Status
Malfunction heating zone 3
AlaData.Ala_MalfunctionCoolingZone1_Status
Malfunction cooling zone 1
AlaData.Ala_MalfunctionCoolingZone2_Status
Malfunction cooling zone 2
AlaData.Ala_MalfunctionCoolingZone3_Status
Malfunction cooling zone 3
AlaData.Ala_ControlErrorSupplyTempZone1_Status
Deviation alarm supply air temperature zone 1
AlaData.Ala_ControlErrorSupplyTempZone2_Status
Deviation alarm supply air temperature zone 2
AlaData.Ala_ControlErrorSupplyTempZone3_Status
Deviation alarm supply air temperature zone 3
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg1a.png)
Chapter 4 │Input Register (3x) 26
EXOL type Modbus address RW Bacnet
AlaData.Ala_LowTempFrostGuardZone1_Status
Freeze protection alarm zone 1
AlaData.Ala_LowTempFrostGuardZone2_Status
Freeze protection alarm zone 2
AlaData.Ala_LowTempFrostGuardZone3_Status
Freeze protection alarm zone 3
AlaData.Ala_ElectricOverheatZone1_Status
Electric heater is overheated zone 1
AlaData.Ala_ElectricOverheatZone2_Status
Electric heater is overheated zone 2
AlaData.Ala_ElectricOverheatZone3_Status
Electric heater is overheated zone 3
AlaData.Ala_SensorErrorTempSupplyZone1_Status
Sensor error supply air temperature zone 1
AlaData.Ala_SensorErrorTempSupplyZone2_Status
Sensor error supply air temperature zone 2
AlaData.Ala_SensorErrorTempSupplyZone3_Status
Sensor error supply air temperature zone 3
AlaData.Ala_SensorErrorTempRoomZone1_Status
Sensor error room temperature zone 1
AlaData.Ala_SensorErrorTempRoomZone2_Status
Sensor error room temperature zone 2
AlaData.Ala_SensorErrorTempRoomZone3_Status
Sensor error room temperature zone 3
AlaData.Ala_SensorErrorTempExtractZone1_Status
Sensor error extract temperature zone 1
AlaData.Ala_SensorErrorTempExtractZone2_Status
Sensor error extract temperature zone 2
AlaData.Ala_SensorErrorTempExtractZone3_Status
Sensor error extract temperature zone 3
AlaData.Ala_SensorErrorTempFrostZone1_Status
Sensor error freeze protection temperature zone 1
AlaData.Ala_SensorErrorTempFrostZone2_Status
Sensor error freeze protection temperature zone 2
AlaData.Ala_SensorErrorTempFrostZone3_Status
Sensor error freeze protection temperature zone 3
VentActual.A_AnalogInput(1)
VentActual.A_AnalogInput(2)
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg1b.png)
Chapter 4 │Input Register (3x) 27
EXOL type Modbus address RW Bacnet
VentActual.A_AnalogInput(3)
VentActual.A_AnalogInput(4)
VentActual.A_AnalogInput(5)
VentActual.A_AnalogInput(6)
VentActual.A_AnalogInput(7)
VentActual.A_AnalogInput(8)
VentActual.A_AnalogInputExp1(1)
Actual value exp.unit 1 AI1
VentActual.A_AnalogInputExp1(2)
Actual value exp.unit 1 AI2
VentActual.A_AnalogInputExp1(3)
Actual value exp.unit 1 AI3
VentActual.A_AnalogInputExp1(4)
Actual value exp.unit 1 AI4
VentActual.A_AnalogInputExp1(5)
Actual value exp.unit 1 analog UI1
VentActual.A_AnalogInputExp1(6)
Actual value exp.unit 1 analog UI2
VentActual.A_AnalogInputExp1(7)
Actual value exp.unit 1 analog UI3
VentActual.A_AnalogInputExp1(8)
Actual value exp.unit 1 analog UI4
VentActual.A_AnalogInputExp2(1)
Actual value exp.unit 2 AI1
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg1c.png)
Chapter 4 │Input Register (3x) 28
EXOL type Modbus address RW Bacnet
VentActual.A_AnalogInputExp2(2)
Actual value exp.unit 2 AI2
VentActual.A_AnalogInputExp2(3)
Actual value exp.unit 2 AI3
VentActual.A_AnalogInputExp2(4)
Actual value exp.unit 2 AI4
VentActual.A_AnalogInputExp2(5)
Actual value exp.unit 2 analog UI1
VentActual.A_AnalogInputExp2(6)
Actual value exp.unit 2 analog UI2
VentActual.A_AnalogInputExp2(7)
Actual value exp.unit 2 analog UI3
VentActual.A_AnalogInputExp2(8)
Actual value exp.unit 2 analog UI4
VentActual.A_AI_OutDoorTemp
Actual value outdoor temperature
VentActual.A_AI_IntakeAirTemp
Actual value intake air temperature
VentActual.A_AI_SupplyAirTemp
Actual value supply air temperature
VentActual.A_AI_ExhaustAirTemp
Actual value exhaust air temperature
VentActual.A_AI_ExtractAirTemp
Actual value extract air temperature
VentActual.A_AI_RoomTemp1(0)
Actual value room temperature 1
VentActual.A_AI_RoomTemp2
Actual value room temperature 2
VentActual.A_AI_RoomTemp3
Actual value room temperature 3
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg1d.png)
Chapter 4 │Input Register (3x) 29
EXOL type Modbus address RW Bacnet
VentActual.A_AI_RoomTemp4
Actual value room temperature 4
VentActual.A_AI_SAFPressure
Actual value supply air pressure
VentActual.A_AI_EAFPressure
Actual value extract air pressure
Actual value supply air flow
Actual value extract air flow
VentActual.A_ExchPressureSAF
Actual value exchanger supply flow
VentActual.A_AI_ExchPressureEAF
Actual value exchanger extract pressure
VentActual.A_AI_DeIcingTemp
Actual value defrosting temperature
VentActual.A_AI_FrostprotTemp1(0)
Actual value freeze protection temperature 1
VentActual.A_AI_FrostprotTemp2
Actual value freeze protection temperature 2
VentActual.A_AI_FrostprotTemp3
Actual value freeze protection temperature 3
Actual value CO₂ room/extract air
VentActual.A_AI_HumidityRoom
Actual value humidity room/extract air
VentActual.A_AI_HumidityDuct
Actual value humidity duct
VentActual.A_AI_HumidityOutDoor
Actual value humidity outdoor
![](/html/a1/a178/a1783922e1785fdec6e1b7113b155f2eb8d154ec8090863bf47e6091fe0fec24/bg1e.png)
Chapter 4 │Input Register (3x) 30
EXOL type Modbus address RW Bacnet
VentActual.A_AI_ExtraControllerTemp
Actual value extra controller temperature
VentActual.A_AI_ExtSAFControl
Actual value external control supply air fan
VentActual.A_AI_ExtEAFControl
Actual value external control exract air fan
VentActual.A_AI_ExtraSensor1(0)
Actual value extra sensor 1
VentActual.A_AI_ExtraSensor2
Actual value extra sensor 2
VentActual.A_AI_ExtraSensor3
Actual value extra sensor 3
VentActual.A_AI_ExtraSensor4
Actual value extra sensor 4
VentActual.A_AI_ExtraSensor5
Actual value extra sensor 5
VentActual.A_AI_ExternalSupplySetP
Actual value external temperature setpoint
VentActual.A_AI_ExternalFlowSetP
Actual value external supply air flow setpoint
VentActual.A_AI_FilterGuard1(0)
Actual value supply air filter pressure
VentActual.A_AI_FilterGuard2
Actual value extract air filter pressure
VentActual.A_AI_EfficiencyTemp
Actual value efficiency temperature
VentActual.A_AI_PreHeatTemp
Actual value preheater temperature
VentActual.A_AI_Zone1SupplyTemp(0)
Actual value supply air temperature zone 1