SystemAir SR 09 EL, SR 09, SR 09 EL M0, SR 09 M0, SR 11 EL Installation Instructions Manual

...
Page 1
Topvex SR 09, 11, Topvex TR 09-15 Compact Air Handling Units
Installation instructions
Document in original language | 125593 · A003
GB
Page 2
© Copyright Systemair AB All rights reserved E&OE
Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
125593 | A003
Page 3
1 EU Declaration of conformity....... . . . . . ............. . . . . . 1
2 Warnings. . . . . . .............. . . . . . . ............. . . . . . ...........2
3 Product information ....... . . . . . . . ............. . . . . . . ........2
3.1 General....... . . . . . . . ............. . . . . . . ............. . . 2
3.2 Technical data ............ . . . . . . ............. . . . . . . . .3
3.2.1 Dimensions and weights
Topvex SR 09, 11 ..... . . . . . . . ...........3
3.2.2 Dimensions and weight
Topvex TR 09-15 ........... . . . . . . ......4
3.2.3 Electrical data ... . . . . . . . ............ . . . . . .5
3.3 Transport and storage . . . . . . ............. . . . . . . ....6
4 Installation.... . . . . . . ............ . . . . . . . .............. . . . . . . ....6
4.1 Unpacking ........ . . . . . . . ............. . . . . . ...........6
4.2 Where/how to install ........... . . . . . . . ............6
4.3 Dividing the Topvex air handling
units. . . . . ............. . . . . . ............. . . . . . . . .........7
4.3.1 How to split the Topvex SR
unit .. . . . . . . ............. . . . . . . .............. 7
4.3.2 How to split the Topvex TR
unit .. . . . . . . ............. . . . . . . .............. 8
4.4 Installing the unit. . ............. . . . . . . ............. . . 9
4.4.1 Installation procedure........ . . . . . . .. 10
4.4.2 The rotors vertical position
(Topvex SR 09, 11) ........... . . . . . . .. 11
4.5 Supply air sensor (Topvex SR 09,
11) ............ . . . . . . . ............. . . . . . . ............. 12
4.6 Connections . . . ............. . . . . . . . ............. . . . . 13
4.6.1 Ducting ..... . . . . . . . ............. . . . . . . . .. 13
4.6.2 Condensation and heat
insulation ............ . . . . . . ............. 13
4.6.3 Silencers ........ . . . . . . .............. . . . . 14
4.6.4 Electric connections . . . . . . ............ 14
4.6.5 Electrical connection box,
components. . . . . . . .............. . . . . . .. 15
4.6.6 External connections . . . . . . . .......... 16
4.6.7 BMS Connection.. . . . . . . . .............. 16
4.7 Installing the control panel . .............. . . . . . . 18
4.7.1 Dimensions........ . . . . . . ............. . . 18
4.7.2 General information . . . . . . ............ 18
4.7.3 Installation.... . . . . . . ............. . . . . . . . 19
4.8 Additional equipment ... . . . . . ............. . . . . . . . 19
Contents
125593 | A003
Page 4
Page 5

1 EU Declaration of conformity

Manufacturer
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99 www.systemair.com
hereby confirms that the following products:
Air handling units
EU Declaration of conformity |
1
El
Topvex SR09-SR11 Topvex SR09-SR11 Topvex SR09-SR11 Topvex SR09-SR11
Topvex SR09-SR11 M0 Topvex SR09-SR11 M0
Topvex TR09-TR15 Topvex TR09-TR15 Topvex TR09-TR15 Topvex TR09-TR15
Topvex TR09-TR15 M0 Topvex TR09-TR15 M0
(The declaration applies only to product in the condition it was delivered in and installed in the facility in accordance with the included installation instructions. The insurance does not cover components that are added or actions carried out subsequently on the product)
Comply with all applicable requirements in the following directives and regulations
Machinery Directive 2006/42/EC Ecodesign Directive 2009/125/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
The following harmonized standards are applied in applicable parts:
EN ISO 12100:2010
EN 13857
EN 60204-1
EN 60335-1
EN 60335-2-40
EN 50106:2007
EN 60529
EN 62233
EN 61000-6-2
EN 61000-6-3
None HWL HWH
327/2011 Requirements for fans 1253/2014 Requirements for ventilation units
Safety of machinery - General principles for design - Risk assessment and risk reduction
Safety of machinery – Safety distances to prevent hazard zones being reached by upper or lower limbs
Safety of machinery – Electrical equipment of machines – Part 1: General requirements
Household and similar electrical appliances – Safety Part 1: General requirements
Safety of household and similar electrical appliances - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers
Safety of household and similar appliances – Particular rules for routine tests referring to appliances under the scope of EN 60 335-1 and EN 60967
Degrees of protection provided by enclosures (IP Code)
Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments
Electromagnetic compatibility (EMC) – Part 6-3: Generic standards – Emission standards for residential, commercial and light-industrial environments
Topvex SR09-SR11 M0
Topvex TR09-TR15 M0
The complete technical documentation is available.
Skinnskatteberg, 15-03-2016
Mats Sándor Technical Director
125593 | A003
Page 6
Warnings
|
2

2 Warnings

The following admonitions will be presented in the different sections of the document.
Danger
• Make sure that the mains to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
Warning
• The door handles are only intended to be used during the installation and service. These must be removed before the unit is put into operation to ensure the required level of safety for the unit.
The unit must be duct connected or in some other way provided with protection so that it is not possible to come in contact with the fans through the duct connections
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use protective clothing.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing.
• The units electrical connection to the mains must be preceded by an all pole circuit breaker with a minimum 3 mm gap.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a spanner to tighten the connection.
Important
• This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.

3 Product information

3.1 General

This installation manual concerns air handling unit type Topvex SR 09, 11 and Topvex TR 09-15 manufactured by Sys­temair AB. The units include the following model options:
Model: SR09, SR11, TR09, TR12, TR15
Heating coil: EL (Electric), HWL (Water coil, low power), HWH (Water coil, high power) or None.
Right or left models: R (Right) L (Left). The side where the supply air is located when viewed from the access side.
Airflow control: CAV (Constant Air Volume), VAV – Variable Air Volume = Constant duct pressure control (as an
accessory)
M0: Aluminium fan impeller
This manual consists of basic information and recommendations concerning the design, installation, start-up and opera­tion, to ensure a proper fail-free operation of the unit.
The key to proper and safe operating of the unit is to read this manual thoroughly, use the unit according to given guidelines and follow all safety requirements.
125593 | A003
Page 7

3.2 Technical data

G N N
M
L K
29 29890 890
A
A
F B
100
D C E C
D
810
15R½"

3.2.1 Dimensions and weights Topvex SR 09, 11

Product information |
3
Fig. 1 Dimensions (mm) Topvex SR 09, 11 (Drawn as left hand unit)
Model
A B C D E F
SR09 1120 600 400 108 104 260
SR11 1230 800 400 135 165 215
Model
SR09 840 434 195 145 610 370
G K L M N
Weight, kg
SR11 950 487 195 145 610 440
125593 | A003
Page 8
| Product information
4

3.2.2 Dimensions and weight Topvex TR 09-15

Fig. 2 Dimensions (mm) Topvex TR 09-15 (Drawn as left hand unit)
Model
TR09 1790 1630 1120 810 895 104 129 123 129
TR12 1930 1740 1230 930 965 76 104 141 104
TR15 1930 1980 1470 1180 965 76 104 141 104
Model
TR09 105 210 700 300 165 1030 870 490
TR12 105 215 800 350 185 1140 940 580
TR15 105 236 1000 350 185 1380 940 730
A B C D E F G H I
J K L M N O P
Weight, kg
125593 | A003
Page 9

3.2.3 Electrical data

Product information |
5
Model
SR09 EL 5062 12 3x32 3x50
SR09 (None, HWL/HWH)
SR09 EL M0 3754 12 3x35 3x50
SR09 (None,/HWH) M0
SR11 EL 4902 15 3x35 3x63
SR11 (None, HWL/HWH)
SR11 EL M0 6130 15 3x35 3x63
SR11 (None, HWH) M0
Model
TR09 EL 5052 9 3x25 3x40
TR09 (None, HWL/HWH)
TR09 EL M0 3780 9 3x25 3x40
TR09 (None, HWH) M0
TR12 EL 4756 12 3x32 3x50
TR12 (None, HWL/HWH)
TR12 EL M0 3574 12 3x35 3x50
TR12 (None, HWH) M0
TR15 EL 4998 15 3x35 3x63
TR15 (None, HWL/HWH)
TR15 EL M0 6760 15 3x35 3x63
TR15 (None, HWH) M0
Fans (W tot) 400 V 3N~
5062
3754
4902
6130
Fans (W tot) 400 V 3N~
5052
3780
4756
3574
4998
6760
El Heating battery (kW tot.)
El Heating battery (kW tot.)
Fuse (mains) (A) for 400 V 3N~
3x10 3x16
3x10 3x16
3x10 3x16
3x16 3x20
Fuse (mains) (A) for 400 V 3N~
3x10 3x16
3x10 3x10
3x10 3x16
3x10 3x16
3x10 3x16
3x16 3x20
Fuse (mains) (A) for 230 V 3~
Fuse (mains) (A) for 230 V 3~
125593 | A003
Page 10
| Installation
6

3.3 Transport and storage

The Topvex SR/TR should be stored and transported in such a way that it is protected against physical damage that can harm panels, handles, display etc. It should be covered so that dust, rain and snow cannot enter and damage the unit and its components. The appliance is delivered in one piece containing all necessary components, wrapped in plastic on a pallet for easy transportation.
When transporting the Topvex SR/TR units use a forklift placed on the gable of the unit.
Warning
The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use protective clothing.

4 Installation

4.1 Unpacking

Verify that all ordered equipment are delivered before starting the installation. Any deviation from the ordered equip­ment must be reported to the supplier of Systemair products.

4.2 Where/how to install

Place the unit on a horizontal flat surface. It’s important that the unit is completely levelled before it is put into operation.
Place the unit preferably in a separate room (e.g. storage, laundry room, attic or similar).
Topvex SR 09, 11 can be installed outside if weather protected. An outdoor air section, ODS is available as accessory.
If the unit is installed in a cold place it is important that the unit is not shut-off by the main switch. As long as the main voltage is on the electrical cabinet will be kept warm also in cold climates.
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspec­tion doors should be easily accessible. Leave free space for opening the doors and for taking out the main components (figure 1 and figure 2).
Avoid placing the appliance against a wall, as low frequency noise can cause vibrations in the wall even if the fan noise-level is acceptable. If this is not possible it is recommended to carefully insulate the wall.
The outdoor air intake of the building should if possible be put in the northern or eastern side of the building and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets.
125593 | A003
Page 11
Installation |

4.3 Dividing the Topvex air handling units

On delivery the two halves of the Topvex appliance are mounted together. If necessary they can be divided for easy transport to the site of installation figure 3 and figure 4.

4.3.1 How to split the Topvex SR unit

Remove the heat exchanger, supply air fan and the extract air filter
A. Loosen the cable connectors in the wall
B. The two halves of the unit are joined using 4 M10 screws, one in each corner
C. It is possible dismount the gables by removing 6 MRX M6 screws with PH2 bits tool
Reassemble in the reverse order.
7
Fig. 3 Left hand version
Note:
When reassembling the pieces make sure they are connected correctly – see cable markings on the side of the cables.
125593 | A003
Page 12
| Installation
8

4.3.2 How to split the Topvex TR unit

Remove the heat exchanger, extract fan and the extract air filter
A. Remove the plate
B. Loose the cable connectors
C. Remove the 7 M10 screws that join the two halves of the appliance
Fig. 4 Left hand version
125593 | A003
Page 13

4.4 Installing the unit

The unit must be installed in the following position (figure 5 and figure 6).
Fig. 5 Installation position (left hand unit)
Installation |
9
Fig. 6 Installation position (right hand)
Table 1 Symbol description
Symbol Description
Supply air
Exhaust air
Outdoor air
Extract air
125593 | A003
Page 14
| Installation
10

4.4.1 Installation procedure

1 Prepare the surface where the unit is to be mounted.
Make sure that the surface is flat, levelled and that it supports the weight of the unit. Perform the installa­tion in accordance with local rules and regulations.
2 Lift the unit in place.
Warning
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing.
3 Level the unit with help of the enclosed mounting
feet
4 Connect the unit electrically to the mains through the
all pole circuit breaker (safety switch), which is en­closed inside the unit on delivery. The wiring is led through the gable of the unit (Topvex SR 09, 11) or through the top of the unit casing (Topvex TR 09-15) directly to the electrical connection box. See enclosed wiring diagram, and chapter 4.6.6, for more information.
Warning
The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a minimum 3 mm gap.
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
125593 | A003
Page 15
Installation |

4.4.2 The rotors vertical position (Topvex SR 09, 11)

To achieve optimal sealing against the rotor's brush strip and the chassits frame, check and if necessary adjust the ro­tors vertical position when the unit is installed. Remove the filter for easy access.
11
Fig. 7 Rotor position (left hand unit)
Adjustment:
1. Loosen the two screws
2. Remove the cover
3. Adjust the rotors height by loosening the locking screw to the axel of the rotor
4. Adjust the rotor vertical position by adjusting the two screws on the rotor bracket
5. After adjustment, tighten the locking screw to the rotor axel (3), mount the cover (2) and fasten the screws (1).
125593 | A003
Page 16
| Installation
12

4.5 Supply air sensor (Topvex SR 09, 11)

The supply air sensor is fitted in the duct ca. 3 m after the unit in the supply air duct (figure 8). See chapter 4.6.6 to which terminals the sensor needs to be connected in the electrical connection box. Other temperature sensors are built in to the unit from factory. The supply air sensor is enclosed in the unit package on delivery.
Fig. 8 Installed supply air sensor (left hand connected unit)
125593 | A003
Page 17

4.6 Connections

4.6.1 Ducting

Fig. 9 Connections and basic components in left hand connected units
Installation |
13
Position
A
B Connection exhaust air
C Connection outdoor air
D Connection extract air
1
2 Fan extract air
3
4 Filter extract air
5
6 Rotor motor
7 Electrical connection box
8
Description Symbol
Connection supply air
Fan supply air
Filter supply air
Heat exchanger
Re-heater battery

4.6.2 Condensation and heat insulation

Outdoor air duct and exhaust ducts must always be well insulated against condensation. Correct insulation installation on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas must be well insulated. Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion barrier. In areas with extremely low out­door temperatures during the winter, additional insulation must be installed. Total insulation thickness must be at least 150 mm.
125593 | A003
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
Page 18
| Installation
14

4.6.3 Silencers

To avoid fan noise being transferred via the duct system, silencers should be installed both on supply and extract air.
To avoid noise being transferred between rooms via the duct system and also to reduce noise from the duct system it­self, installation of silencers before every inlet diffuser is recommended.

4.6.4 Electric connections

All electric connections are made in the electrical connection box which can be found in the front of the unit (figure 10). The hatch is removed by unscrewing four screws (figure 10).
The unit must not be put into operation before all the electrical safety precautions have been read and understood. See the enclosed wiring diagram for internal and external wiring.
All external connections to possible accessories are made to terminals inside the electrical connection box (chapter
4.6.6).
Fig. 10 Opening the electrical connection box
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
125593 | A003
Page 19
Installation |

4.6.5 Electrical connection box, components

Topvex SR/TR are equipped with a built in regulator and internal wiring (figure 11).
The figure shows the electrical connection box for the Topvex TR 09-15 units. The connection box for the Topvex SR 09, 11 has the same layout and components with the difference that the electrical heater is situated in a separate compartment.
15
Fig. 11 Electric components
Position
1
2
3
4
5
6
7
8
9
10
11
12
description
Regulator E-28
Transformer 230/24V AC
Terminals for internal and external components
Terminals for internal wiring
Terminals for mains supply to the unit
Contactor (K2) Pump control water (HW units only, not used in EL-units)
Automatic fuse
Automatic fuse for EL heater
Contactor (K3) EL heater
Automatic over heat protection (EL units)
Manual over heat protection reset (EL units)
TTC EL heater control (EL units)
125593 | A003
Page 20
| Installation
16

4.6.6 External connections

Table 2 Connections to external functions
Terminal block
PE
N N
L1 L1
L2 L2
L3 L3
1 G
2 G0
10
1
12
WP L1
1
14
1
15
1
16
1
17
30
31 AI 1
40
2
41
2
42
44
3
4
P1:50/P2:60
P:151/P2:61
P1:52/P2:62
3
74
3
75
76
3
90
93 AO 3
94 AO 4
1
Maximum current load for all DO combined: 8A
2
Connection to external pressure sensor in case of pressure controlled unit (VAV)
3
These inputs may only be wired to voltage free contacts
DO ref DO reference
DO 2
DO 4
DO 5
DO 6
DO 7
AI Ref Supply air temperature sensor reference neutral
Agnd UI reference neutral
UAI 1/(UDI 1)
UAI 2/(UDI 2)
UAI 3/(UDI 3)
DI ref Extended running/Fire alarm reference
B
A
N
DI 4
DI 5
DI 6
Agnd AO Reference neutral
Description
Remark
Ground
Earthed neutral (supply voltage)
Used for phase 230V 1~ and 400V 3~
Phase (Main supply voltage)
Used for phase 230V 1~ if the unit has this mains 400V 3~/230V 3~
Phase (Main supply voltage) 400V 3~/230V 3~
Phase (Main supply voltage) 400V 3~/230V 3~
Auxiliary supply (Pressure transmitter. Water
24V AC
valve actuators)
Reference (Water valve actuator mains)
24V AC
G (24V AC)
Outdoor/Exhaust air damper
24V AC Max. 2,0 A continuous load
Circulation pump hot water system
Cooling pump
DX Cooling step 1
DX Cooling step 2
Alarm output for DO signals
230V AC
24V AC
24V AC
24V AC
24V AC
Temperature sensor, supply air
Pressure transmitter extract air
Pressure transmitter supply air
Frost protection sensor water heating
Use terminal 40 as reference
battery
+ 24V DC
Exo-line B Modbus, Exo-line connection
Exo-line A Modbus, Exo-line connection
Exo-line N Modbus, Exo-line connection
Extended running Normally open contact
Use terminal 4 as reference
Fire alarm Normally open contact
Use terminal 4 as reference
External stop Normally open contact
Use terminal 4 as reference
Control signal valve actuator, Water Heating
Control signal valve actuator, Cooling
0–10V DC
0–10V DC

4.6.7 BMS Connection

BMS Connection
125593 | A003
Page 21
Communication possibilities for controller E283 WEB.
RS485(Modbus): 50-51-52 or 60-61-62
RS485(BACnet): 50-51-52 or 60-61-62
RS485(Exoline): 50-51-52-53 or 60-61-62-63
• TCP/IP Exoline
• TCP/IP Modbus
TCP/IP WEB
TCP/IP BACnet
Installation |
17
Fig. 12 BMS connection on the controller
125593 | A003
Page 22
| Installation
18

4.7 Installing the control panel

4.7.1 Dimensions

Fig. 13 Control panel dimensions
Position
A 115.0
B 94.0
C 26.0
D
E 50.5
Dimensions (mm)
c/c 60.0

4.7.2 General information

The control panel is delivered connected to the Corrigo control unit situated in the electrical connection box. Cable length is 10 m. In case the control panel needs to be detached from the signal cable it is possible to loosen the wires on the back of the control panel (figure 14).
A set of self-adhesive magnet strips are included in the package to facilitate installation on a metal surface.
125593 | A003
Page 23
Installation |

4.7.3 Installation

1. Find an appropriate place to install the control panel. Maximum length between control panel and unit is 100 m.
2. If needed, drill two holes in the wall to hang the control panel (center to center: 60 mm) (pos.1, figure 14).
19
Fig. 14 Control panel wire connections
Position
1
2
3
4
5
6
Description
Mounting holes
Connection block
Connection to brown cable
Connection to yellow cable
Connection to white cable
Connection to black cable

4.8 Additional equipment

For information concerning additional external equipment such as valve actuators, motorized dampers, E-tool, roof units, wall grilles etc. see technical catalogue and their enclosed instructions.
For electrical connections of external components see enclosed wiring chart.
125593 | A003
Page 24
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden
Phone +46 222 440 00 Fax +46 222 440 99
www.systemair.com
Topvex SR 09, 11, Topvex TR 09-15 · Installation instructions · 125593 · en_GB · 2017-06-08 · A003
Loading...