SystemAir Topvex SX/C Series, Topvex SX/C03, Topvex TX/C Series, Topvex SX/C04, Topvex SX/C06 Installation Instructions Manual

...
Page 1
Topvex SX/C, Topvex TX/C Air Handling Unit
Installation instructions
Document in original language | 131677 · A004
GB
Page 2
131677 | A004
Page 3
3.1 General................................................2
3.2 Technical data .......................................3
3.2.1 Dimensions and weight
Topvex SX/C ........... ... ... . .. . .. . . . . . .3
3.2.2 Dimensions and weight
Topvex TX/C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2.3 Electrical data ............................6
3.3 Transport and storage ... . .. . .. . . . . . . . . . . . . . . . . . . . .7
4.1 Unpacking ... .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . 8
4.2 Where/how to install .. . . . . . . . . . . . . . . . . . . . . . . . . .. . . 8
4.3 Condensation drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.4 Installing the unit.................................. 10
4.4.1 Installation procedure................ 10
4.5 Supply air sensor (Topvex SX/C) .............. 11
4.6 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.6.1 Ducting .................................. 12
4.6.2 Condensation and Heat
Insulation ............................... 13
4.6.3 Silencers ... . .. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.6.4 Electrical connection,
components. . . . . .. . . . . . . . . . . . . . . . . . . . . . 14
4.6.5 Topvex External
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.6.6 BMS Connection....................... 16
4.7 Installing the Control Panel .. . . . . . . . . . . . . . . . . . . . 17
4.7.1 Dimensions............................. 17
4.7.2 General information . . .. . . . . . . . . . . . . . . 17
4.7.3 Installation.............................. 17
4.8 Additional Equipment .......................... .. 18
Contents
131677 | A004
Page 4
Page 5
EU Declaration of Conformity |

1 EU Declaration of Conformity

Manufacturer
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99 www.systemair.com
hereby confirms that the following products:
Air handling units Topvex SX/C and Topvex TX/C
EL None HWL HWH
Topvex SX/C03-06 Topvex SX/C03-06 Topvex SX/C03-06 Topvex SX/C03-06
Topvex SX/C03-06 M0 Topvex SX/C03-06 M0
Topvex TX/C03-06 Topvex TX/C03-06 Topvex TX/C03-06 Topvex TX/C03-06
Topvex TX/C03-06 M0 Topvex TX/C03-06 M0
(The declaration applies only to product in the condition it was delivered in and installed in the facility in accordance with the included installation instructions. The insurance does not cover components that are added or actions carried out subsequently on the product)
Comply with all applicable requirements in the following directives and regulations
Topvex SX/C03-06 M0
Topvex TX/C03-06 M0
1
Machinery Directive 2006/42/EC Ecodesign Directive 2009/125/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
The following harmonized standards are applied in applicable parts:
EN ISO 12100:2010
EN 13857
EN 60204-1
EN 60335-1
EN 60335-2-40
EN 50106:2007
EN 60529
EN 62233
EN 61000-6-2
EN 61000-6-3
Safety of machinery - General principles for design - Risk assessment and risk reduction
Safety of machinery – Safety distances to prevent hazard zones being reached by upper or lower limbs
Safety of machinery – Electrical equipment of machines – Part 1: General requirements
Household and similar electrical appliances – Safety Part 1: General requirements
Safety of household and similar electrical appliances - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers
Safety of household and similar appliances – Particular rules for routine tests referring to appliances under the scope of EN 60 335-1 and EN 60967
Degrees of protection provided by enclosures (IP Code)
Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments
Electromagnetic compatibility (EMC) – Part 6-3: Generic standards – Emission standards for residential, commercial and light-industrial environments
327/2011 Requirements for fans 1253/2014 Requirements for ventilation units
The complete technical documentation is available.
Skinnskatteberg, 2016-05-18
Mats Sándor Technical Director
131677 | A004
Page 6
Warnings
|
2

2 Warnings

The following admonitions will be presented in the different sections of the document.
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
Warning
• Keep the doors locked during operation to ensure required level of safety for the unit.
• The unit must be duct connected or in some other way provided with protection so that it is not possible to come in contact with the fans through the duct connections
• Beware of hot surface on the heating battery during maintenance and service.
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use protective clothing.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing.
• The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a minimum 3 mm gap.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a spanner to tighten the connection.

3 Product information

3.1 General

This installation manual concerns air handling unit type Topvex SX/C, TX/C manufactured by Systemair Sverige AB. The units include the following model options:
Model: Topvex SX/C03, Topvex SX/C04, Topvex SX/C06, Topvex TX/C03, Topvex TX/C04 and Topvex TX/C06.
Heating coil: EL (Electric), HWL (Water coil, low power), HWH (Water coil, high power) or None.
Right or left models: R (Right) L (Left). The side where the supply air is located when viewed from the access side.
Airflow control: CAV (Constant Air Volume). VAV, Variable Air Volume (constant duct pressure control) is available as
an accessory.
M0: Aluminium fan impeller
This manual consists of basic information and recommendations concerning the design, installation, start-up and opera­tion, to ensure a proper fail-free operation of the unit.
The key to proper and safe operating of the unit is to read this manual thoroughly, use the unit according to given guidelines and follow all safety requirements.
131677 | A004
Page 7

3.2 Technical data

30 30
1063
F F
B
A
V
XY
Z
102
L
DCECD
G
K
M
1063
61
H
1

3.2.1 Dimensions and weight Topvex SX/C

Product information |
3
Model
Topvex SX/C03
Topvex SX/C04
Topvex SX/C06
1
SX/C06 has 4 extra feet
Model
Topvex SX/C03
Topvex SX/C04
Topvex SX/C06
A B C D E F G H K
877 500 250 170 200 188 1041 1772 1926
877 600 300 163 200 138 1127 1905 2060
877 600 300 235 342 138 1412 2187
L M V X Y Z
720 765 664 335 213 87 272
720 833 664 417 203 106 283
720 1120 664 560 203 106 395
1
2344
Weight, kg
131677 | A004
Page 8
| Product information
A
D
102 B 58
45
E
C
F G H I J
K
KLK
O
120N
KL
ØM
87
4

3.2.2 Dimensions and weight Topvex TX/C

Fig. 1 Dimensions (mm) Topvex SX/C03 (drawn as left hand unit)
Model
Topvex TX/C03
Model
Topvex TX/C03
A B C D E F G H
1587 1210 880 1435 725 240 348 410
I J K L
358 230 335 210 315 181 785 286
ØM
N O
Weight, kg
131677 | A004
Page 9
Product information |
30B102
968
A
62
E C 45
K 120
II J
L FGLHLGLF
M
87
968
D
1
5
Fig. 2 Dimensions (mm) Topvex TX/C04-06 drawn as left hand unit
Model
Topvex TX/C04
Topvex TX/C06
1
Model
Topvex TX/C04
Topvex TX/C06
TX/C has 4 extra feet
A B C D E F G
1860 1279 880 1708 725 104 136
2150 1630 880 1998
1
725 116 196
H I J K L M
180 190 500 195 300 920 296
324 140 600 197 300 1065 405
Weight, kg
131677 | A004
Page 10
| Product information
6

3.2.3 Electrical data

Model
Topvex SX/C03 EL
Topvex SX/C03 None, HWL, HWH
Topvex SX/C03 EL M0
Topvex SX/C03 None, HWL, HWH M0
Topvex SX/C04 EL
Topvex SX/C04 None, HWL, HWH
Topvex SX/C04 EL M0
Topvex SX/C04 None, HWL, HWH M0
Topvex SX/C06 EL
Topvex SX/C06 None, HWL, HWH
Topvex SX/C06 EL M0
Topvex SX/C06 None, HWL, HWH M0
Model
Topvex TX/C03 EL
Topvex TX/C03 None, HWL, HWH
Topvex TX/C03 EL M0
Topvex TX/C03 None, HWL, HWH M0
Topvex TX/C04 EL
Topvex TX/C04 None, HWL, HWH
Topvex TX/C04 EL M0
Topvex TX/C04 None, HWL, HWH M0
Topvex TX/C06 EL
Topvex TX/C06 None, HWL, HWH
Topvex TX/C06 EL M0
Topvex TX/C06 None, HWL, HWH M0
Fans (W tot.) 230V 1~ and 400 V 3N~
1480 8 3x25
1480
1088 8 3x25
1088
1478 12 3x32
1478
1530 12 3x32
1530
1780 16 3x32
1780
2124 16 3x32
2124
Fans (W tot.) 230V 1~ and 400 V 3N~
1474 8 3x25
1474
1068 8 3x20
1068
1480 12 3x32
1480
1652 12 3x32
1652
1790 16 3x32
1790
2146 16 3x32
2146
El Heating battery (kW tot.) Fuse (mains) (A) for
-
-
-
-
-
El Heating battery (kW tot.) Fuse (mains) (A) for
-
-
-
-
-
-
230 V 1~ and 400 V 3~
10
10
10
10
3x10
3x10
230 V 1~ and 400 V 3~
10
10
10
10
3x10
3x10
131677 | A004
Page 11
Product information |

3.3 Transport and storage

The unit is delivered in one piece standing on a pallet for easy transportation using a forklift. The unit should be stored and transported in such a way that it is protected against physical damage that can harm panels, handles, display etc. It should be covered so that dust, rain and snow cannot enter and damage the unit and its components. The appliance is delivered complete with all necessary components, wrapped in plastic on a pallet for easy transportation.
When transporting the Topvex SX/C, TX/C units use a forklift placed on the gable of the unit.
Note:
Necessary parts like control panel, supply air sensor (only Topvex SX/C), mounting feet, drainage pipe with drain trap and electrical safety switch are enclosed at delivery.
Warning
• The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use protective clothing.
• The unit must not be put into operation before the enclosed parts are removed and installed properly.
7
131677 | A004
Page 12
| Installation
8

4 Installation

4.1 Unpacking

Verify that all ordered equipment are delivered before starting the installation. Any deviation from the ordered equip­ment must be reported to the supplier of Systemair products.

4.2 Where/how to install

The unit is meant for indoor installation. The electronic components should not be exposed to lower temperature than 0° C and higher than +50° C.
If the unit is installed in a cold place it is important that the unit is not shut-off by the main switch. As long as the main voltage is on the electrical cabinet will be kept warm also in cold climates.
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspec­tion doors should be easily accessible. Leave free space for opening the doors and for taking out the main components (chapter 3.2.1.)
The outdoor air intake of the building should if possible be put in the northern or eastern side of the building and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets.
Warning
• The unit should only be put into operation with the doors closed.
• The unit must be duct connected or in some other way provided with protection so that it is not possible to come in contact with the fans through the duct connections.
131677 | A004
Page 13
Installation |

4.3 Condensation drain

The unit must be connected to the condensation drain, which is enclosed upon delivery. The drainage needs to be con­nected on the exhaust air side of the heat exchanger at the bottom of the unit, figure 3. If the unit is to be used for cool recovery the normally plugged drainage outlet needs to be connected as well to a separate tube and water lock (accessories).
Use the enclosed connection tube, which needs to be cut down to the appropriate height. See table 1 how the height “H” corresponds to different maximum negative pressures. See figure 4 for dimensions and assembly.
Note:
When installed in a non heated place the drain pipe and trap needs to be insulated well to prevent the water from freezing.
9
Fig. 3 Drainage connection
Fig. 4 Dimension and assembly
Table 1
H (mm) Max. Negative pressure (Pa)
65 300
1
95
600
135 1000
1
Normal conditions
131677 | A004
Page 14
| Installation
10

4.4 Installing the unit

The unit is designed for floor installation. Left and right connections are possible. The unit can be installed in the follow­ing positions.
Fig. 5 Installing position (left hand units)
Fig. 6 Installing position (right hand units)
Table 2 Symbol description
Symbol Description
Supply air
Exhaust air
Outdoor air
Extract air

4.4.1 Installation procedure

1 Prepare the surface where the unit is to be mounted.
Make sure that the surface is flat, levelled and that it carries the weight of the unit. Perform the installation in accordance with local rules and regulations.
2 Lift the unit in place.
Warning
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing.
131677 | A004
Page 15
Installation |
3 Connect the unit electrically to the mains through the
all pole circuit breaker (safety switch), which is en­closed inside the unit on delivery. The wiring is led di­rectly to the electrical connection box. See enclosed wiring diagram, and chapter 4.6.5 for more information.
Warning
The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a minimum 3 mm gap.
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.

4.5 Supply air sensor (Topvex SX/C)

The supply air sensor should be mounted in the duct approximately 3 m after the unit in the supply air duct. See table 3 to which terminals the sensor needs to be connected in the electrical connection box. All other temperature sensors are built in to the unit from factory. The supply air sensor is enclosed in the unit package on delivery.
11
Fig. 7 Installed supply air sensor, Topvex SX/C, left hand unit
131677 | A004
Page 16
| Installation
12

4.6 Connections

4.6.1 Ducting

Position Description
A
B
C
D Connection extract air
1
2 Fan extract air
3
4
5
6
7
8
9
10
11
12
Connection supply air
Connection exhaust air
Connection outdoor air
Fan supply air
Filter supply air
Filter extract air
Heat exchanger
Electrical connection box
Damper by-pass outdoor air
Pressure transmitter fans (accessory)
Pressure guard filter
Re-heater battery
Airflow guard (only EL units)
Differential pressure sensor – deicing
Symbol
131677 | A004
Page 17
Installation |

4.6.2 Condensation and Heat Insulation

Outdoor air duct and exhaust ducts must always be well insulated against condensation. Correct insulation installation on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas must be well insulated. Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion barrier. In areas with extremely low out­door temperatures during the winter, additional insulation must be installed. Total insulation thickness must be at least 150 mm.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system

4.6.3 Silencers

To avoid fan noise being transferred via the duct system, silencers should be installed both on supply and extract air.
To avoid noise being transferred between rooms via the duct system and also to reduce noise from the duct system it­self, installation of silencers before every inlet diffuser is recommended.
13
131677 | A004
Page 18
| Installation
14

4.6.4 Electrical connection, components

Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
All electric connections are made in the electrical connection box which can be found in the front of the unit. The hatch is removed by unscrewing four screws.
Reset the manual overheat protection for Topvex TX/C by pushing the red button on top of the electrical heater frame, reachable by opening the units door. For Topvex SX/C it is reachable by unscrewing the lower hatch (to the re-heater battery).
The unit must not be put into operation before all the electrical safety precautions have been read and understood. See the enclosed wiring diagram for internal and external wiring.
All external connections to possible accessories are made to terminals inside the electrical connection box.
Position
1
2
3
4
5
6
7
8
9
10
11
Description
Regulator E-283 WEB
Transformer 230/24V AC
Terminals for internal and external components
Terminals for internal wiring
Terminals for mains supply to the unit
Contactor (K2) On/Off Pump control water (HW units only, not present in EL-units)
Automatic fuse
Automatic fuse for heater (EL units only)
Contactor (K3) EL heater (EL units only)
Manual over heat protection reset (EL units only)
TTC El heater control (EL units only)
131677 | A004
Page 19

4.6.5 Topvex External Connections

Table 3 Connections to external functions
Terminal block
PE
N N
L1 L1
L2 L2
L3 L3
1 G
2 G0
10
12
1
DO ref DO reference
DO 2
WP L1
1
14
15
16
17
30
1
1
1
DO 4
DO 5
DO 6
DO 7
AI Ref Supply air temperature sensor reference neutral
31 AI 1
40
2
41
2
42
44
3
4
P1:50/P2:60
P:151/P2:61
P1:52/P2:62
3
74
3
75
3
76
90
Agnd UI reference neutral
UAI 1/(UDI 1)
UAI 2/(UDI 2)
UAI 3/(UDI 3)
DI ref Extended running/Fire alarm reference
B
A
N
DI 4
DI 5
DI 6
Agnd AO Reference neutral
93 AO 3
94 AO 4
1
Maximum current load for all DO combined: 8A
2
Connection to external pressure sensor in case of pressure controlled unit (VAV)
3
These inputs may only be wired to voltage free contacts
Description
Ground
Earthed neutral (supply voltage)
Phase (Main supply voltage)
Phase (Main supply voltage) 400V 3~/230V 3~
Phase (Main supply voltage) 400V 3~/230V 3~
Auxiliary supply (Pressure transmitter. Water valve actuators)
Reference (Water valve actuator mains supply)
Outdoor/Exhaust air damper
Circulation pump hot water system
Cooling pump
DX Cooling step 1
DX Cooling step 2
Alarm output for DO signals
Temperature sensor, supply air
Pressure transmitter extract air
Pressure transmitter supply air
Frost protection sensor water heating battery
Exo-line B Modbus, Exo-line connection
Exo-line A Modbus, Exo-line connection
Exo-line N Modbus, Exo-line connection
Extended running Normally open contact
Fire alarm Normally open contact
External stop Normally open contact
Control signal valve actuator, Water Heating
Control signal valve actuator, Cooling
Installation |
Remark
Used for phase 230V 1~ and 400V 3~
Used for phase 230V 1~ if the unit has this mains supply 400V 3~/230V 3~
24V AC
24V AC
G (24V AC)
24V AC Max. 2,0 A continuous load
230V AC
24V AC
24V AC
24V AC
24V AC
Use terminal 40 as reference
+ 24V DC
Use terminal 4 as reference
Use terminal 4 as reference
Use terminal 4 as reference
0–10V DC
0–10V DC
15
131677 | A004
Page 20
| Installation
16

4.6.6 BMS Connection

BMS Connection
Communication possibilities for controller E283 WEB.
RS485(Modbus): 50-51-52 or 60-61-62
RS485(BACnet): 50-51-52 or 60-61-62
RS485(Exoline): 50-51-52-53 or 60-61-62-63
• TCP/IP Exoline
• TCP/IP Modbus
TCP/IP WEB
TCP/IP BACnet
Fig. 8 BMS connection on the controller
131677 | A004
Page 21

4.7 Installing the Control Panel

4.7.1 Dimensions

Installation |
17
Fig. 9 Control panel dimensions
Position
A 115.0
B 94.0
C 26.0
D
E 50.5
Dimensions (mm)
c/c 60.0

4.7.2 General information

The control panel is delivered connected to the Corrigo control unit situated in the electrical connection box. Cable length is 10 m. In case the control panel needs to be detached from the signal cable it is possible to loosen the wires on the back of the control panel (figure 10).
A set of self-adhesive magnet strips are included in the package to facilitate installation on a metal surface.

4.7.3 Installation

1 Find an appropriate place to install the control panel.
Maximum length between control panel and unit is 100 m.
2 If needed, drill two holes in the wall to hang the con-
trol panel (center to center: 60 mm) (pos.1, figure
10).
131677 | A004
Page 22
| Installation
18
Fig. 10 Control panel wire connections
Position
1
2
3
4
5
6
Description
Mounting holes
Connection block
Connection to brown cable
Connection to yellow cable
Connection to white cable
Connection to black cable

4.8 Additional Equipment

For information concerning additional external equipment such as valve actuators, motorized dampers, E-tool, roof units, wall grilles etc. see technical catalogue and their enclosed instructions.
For electrical connections of external components see enclosed wiring chart.
131677 | A004
Page 23
131677 | A004
Page 24
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden
Phone +46 222 440 00 Fax +46 222 440 99
www.systemair.com
Topvex SX/C, Topvex TX/C · Installation instructions · 131677 · en_GB · 2017-04-28 · A004
Loading...