Systemair Topvex SX/C, Topvex TX/C, Topvex SC, Topvex FC, Topvex SR User Manual

...
Compact air handling units Topvex SX/C, TX/C, SC, FC, SR, TR, FR
Commissioning Record
Document in original language | 206951 · A011
GB
© Copyright Systemair AB All rights reserved E&OE
Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
206951 | A011
1 Commissioning record .... . .... ..... ..... ..... ..... .... . .... 1
2 Notes and signatures .... ..... ..... ..... .... . .... . .... . .... .1
3 Function settings.... ..... ..... .... . .... . .... . .... . .... . .... . .2
3.1 Airflow... . .... . .... ..... ..... ..... ..... .... . .... . .... . .2
3.2 Temperature . .... . .... . .... . .... . .... . .... ..... ..... .3
3.3 Temperature (Zone control).. . .... ..... ..... ..... 6
3.4 General... ..... ..... .... . .... . .... . .... . .... ..... .... 10
4 Setting the weekly program... ..... .... . .... . .... . .... .. 13
5 I/O Allocation .... ..... ..... .... . .... . .... . .... . .... . .... . ... 14
6 Alarm configuration . ..... ..... . .... ..... .... . .... . .... . ... 15
Contents
206951 | A011

1 Commissioning record

Company:
Responsible:
Customer: Date:
Installation/Project: Installation address:
Object/Unit: Model/Size:
Commissioning record |
1
Item no.:
Access Software version: Operator password: 1111 Service password: 0612
Operator password changed: Service password changed:
Time and date set: Weekly program set:
Installation and service partner information entered into Access’
1
See chapter “System information” in document “Quick guide” available at www.systemair.com
Serial no:
System information page.
External connections (sensors, dampers, external alarm etc.) performed:
1

2 Notes and signatures

Signature:
Printed name:
Location:
Date:
Phone no.:
206951 | A011
Function settings
|
2

3 Function settings

3.1 Airflow

Function
Airflow
Fan levels
Fan control type
Flow preference unit m
Pressure preference unit
Air flow setpoints
Default setting Set value
LowNormalHigh
Flow (CAV)Pressure (VAV)
l/smCFM
Pain wg (x100)
Low Normal High
Flow (CAV) Pressure (VAV)
3
/h
3
/s
3
/h
m l/s
3
m
/s
CFM
Pa in wg (x100)
Supply airflow at low speed
Extract airflow at low speed
Supply airflow at normal speed
Extract airflow at normal speed
Supply airflow at high speed
Airflow readings
Supply airflow at low speed
Extract airflow at low speed
Supply airflow at normal speed
Extract airflow at normal speed
Supply airflow at high speed
Extract airflow at high speed
Output %
Flow
Extract airflow at high speed
Pressure
206951 | A011
Function settings
|
3
Fan compensation curves (configuration)
Fan level All levels
Mode All modes
Fan
Sensor
Fan compensation curves (settings)
Lowest sensor value
Middle sensor value
Highest sensor value
Curve 1 Curve 2 Curve 3
Low speed Normal speed High speed Low + Normal speed Normal + High speed
When defrosting
Supply + Extract Supply Extract
Sensor value
Compensation
All levels Low speed Normal speed High speed Low + Normal speed Normal + High speed
All modes When defrosting
Supply + Extract Supply Extract
Sensor value
Compensation
All levels Low speed Normal speed High speed Low + Normal speed Normal + High speed
All modes When defrosting
Supply + Extract Supply Extract
Sensor value
Compensation

3.2 Temperature

Function
Temperature °C
Temperature control type and set point Supply 18 °C Supply °
Neutral zone type ½ neutral zone
Neutral zone
Default setting
°F
Extract 22 °C Extract
Room 22 °C Room
Neutral zone to coolingNeutral zone to heating
0 °C
Set value
°C °F
½ neutral zone Neutral zone to cooling Neutral zone to heating
°
°
°
206951 | A011
Function settings
|
4
Function
Summer/Winter mode
Summer mode temperature set point Supply __________°C Supply °
Switch between cascade control during Summer and outdoor compensated supply control during Winter
Type of switch to indicate Summer Calender Calender
If outdoor comp. temp. control
Default setting Set value
NoYes
Extract
Room __________°C Room
NoYes
From Date:
_____
To Date:
_____
Digital input
Outdoor temp.
__________°C
Month:
_____
Month:
_____
> 13 °C
No Yes
Extract
No Yes
From Date:
To Date:
Digital input
Outdoor temp.
Month:
Month:
>
°
°
Outdoor temp/setpoint Curve point 1, 2, 3, 4:
If cascade control:
Min supply air temp. limit 14 °C °
Max supply air temp. limit
Cooling recovery
Mode
Start at temp. difference
Cooling
Type of cooler
If water cooler
Type of feedback, pump
Pump stop delay
-20 / 25 °C °
-10 / 23 °C
0 / 22 °C
10 / 18 °C
30 °C
OnOff
2 °C
WaterDX
NoneAlarmRun indication
5 min
On Off
Water DX
None Alarm Run indication
°
°
°
°
°
min
206951 | A011
Function settings
|
5
Function
If DX cooler
Reduction of min limit supply air temp. when DX cooling
Min setpoint deviation to allow start of DX-cooling
Control function cooling
If step controller
Type of step control Sequential
Number of steps
Freeze protection
Type of freeze protection
Alarm limit when unit is running
P-band when unit is running
Default setting Set value
5 °C °
2 °C
0-10 VStep controller
Binary
1234
NoneTemp. sensorGuard
7 °C
5 °C
°
0-10 V Step controller
Sequential Binary
1 2 3 4
None Temp. sensor Guard
°
°
Set point when unit is stopped
HW pump control
Pump running mode
Type of feedback
Pump stop delay
Pump running when outdoor temp. is below:
Hysteresis to allow pump stop
20 °C
AutoAlways running
NoneAlarmRun indication
5 min
10 °C
1 °C
°
Auto Always running
None Alarm Run indication
min
°
°
206951 | A011
Function settings
|
6

3.3 Temperature (Zone control)

Function
Zone control
Zone control limitation None
Temperature zone 1 ⊠ No
Temperature control type and set point Supply __________°C Supply °
Neutral zone
If cascade control:
Min supply air temp. limit
Max supply air temp. limit
Heating
Type of heater
Type of feedback, heater
If water heater
Pump control
Pump stop delay
Default setting
Interlock heating/cooling
Yes
Extract
Room __________°C Room
__________°C
__________°C
__________°C
NoneWaterElectric
NoneAlarmRun indication
NoneAutoAlways running
5 min
__________°C
Set value
None Interlock heating/cooling
No Yes
Extract
None Water Electric
None Alarm Run indication
None Auto Always running
°
°
°
min
°
°
Pump running when outdoor temp. is below:
Hysteresis to allow pump stop
Freeze protection
Alarm limit when unit is running
P-band when unit is running
Set point when unit is stopped
10 °C
1 °C
NoYes
7 °C
5 °C
20 °C
°
°
No Yes
°
°
°
206951 | A011
Function settings
|
7
Function
Cooling
Type of cooler
Type of feedback, cooler
If water cooler
Pump control
Pump stop delay
If DX cooler
Reduction of min limit supply air temp
Type of step control Sequential
Number of steps
Temperature Zone 2 □ No
Temperature control type and set point Supply __________°C Supply °
Default setting Set value
NoneWaterDX
NoneAlarmRun indication
NoneAutoAlways running
5 min
5 °C
Binary
12
Yes
None Water DX
None Alarm Run indication
None Auto Always running
Sequential Binary
1 2
No Yes
min
°
Neutral zone
If cascade control:
Min supply air temp. limit
Max supply air temp. limit
Heating
Type of heater
Type of feedback, heater
If water heater
Pump control
Pump stop delay
Pump running when outdoor temp. is below:
Hysteresis to allow pump stop
Extract __________°C Extract
Room __________°C Room
__________°C
__________°C
__________°C
NoneWaterElectric
NoneAlarmRun indication
NoneAutoAlways running
5 min
10 °C
1 °C
None Water Electric
None Alarm Run indication
None Auto Always running
°
°
°
°
°
min
°
°
206951 | A011
Function settings
|
8
Function
Freeze protection
Alarm limit when unit is running
P-band when unit is running
Set point when unit is stopped
Cooling
Type of cooler
Type of feedback, cooler
If water cooler
Pump control
Pump stop delay
If DX cooler
Reduction of min limit supply air temp
Default setting Set value
NoYes
7 °C
5 °C
20 °C
NoneWaterDX
NoneAlarmRun indication
NoneAutoAlways running
5 min
5 °C
No Yes
None Water DX
None Alarm Run indication
None Auto Always running
°
°
°
min
°
Type of step control Sequential
Number of steps
Temperature Zone 3
Temperature control type and set point Supply __________°C Supply °
Neutral zone
If cascade control:
Min supply air temp. limit
Max supply air temp. limit
Heating
Type of heater
Type of feedback, heater
Binary
12
NoYes
Extract __________°C Extract
Room __________°C Room
__________°C
__________°C
__________°C
NoneWaterElectric
NoneAlarmRun indication
Sequential Binary
1 2
No Yes
°
°
°
None Water Electric
None Alarm Run indication
°
°
206951 | A011
Function settings
|
9
Function
If water heater
Pump control
Pump stop delay
Pump running when outdoor temp. is below:
Hysteresis to allow pump stop
Freeze protection
Alarm limit when unit is running
P-band when unit is running
Set point when unit is stopped
Cooling
Type of cooler
Type of feedback, cooler
If water cooler
Pump control
Pump stop delay
Default setting Set value
NoneAutoAlways running
5 min
10 °C
1 °C
NoYes
7 °C
5 °C
20 °C
NoneWaterDX
NoneAlarmRun indication
NoneAutoAlways running
5 min
None Auto Always running
No Yes
None Water DX
None Alarm Run indication
None Auto Always running
min
°
°
°
°
°
min
If DX cooler
Reduction of min limit supply air temp
Type of step control Sequential
Number of steps
5 °C
Binary
12
°
Sequential Binary
1 2
206951 | A011
Function settings
|
10

3.4 General

Function
General
Extended operation stop delay 0 min min
Warm start when outdoor temp. is below:
CO
control
2
Supply air fan set point when CO control
Extract air fan set point when CO control
Start limit
Stop hysteresis
Min time for CO
Free cooling
control
2
2
2
Default setting
3 °C
NoFan start/stop
LowNormalHigh
LowNormalHigh
800 ppm
160 ppm
20 min
NoYes
Set value
°
No Fan start/stop
Low Normal High
Low Normal High
ppm
ppm
min
No Yes
Running when day outdoor temp. is above:
Stop when night outdoor temp. is above:
Stop when night outdoor temp. is below:
Stop when room temp. is below:
Free cooling start/stop hour
Time to block heat output after free cooling:
Offset from normal speed when free cooling:
22 °C °
18 °C
10 °C
18 °C
Start: 00:00
Stop: 07:00
60 min
SAF: 0
EAF: 0
Start:
Stop:
SAF:
EAF:
°
°
°
min
206951 | A011
Function settings
|
11
Function
Support control
Start heating room temperature 15 °C °
Stop heating room temperature
Start cooling room temperature
Stop cooling room temperature
Preheater
Start/Stop function
Preheater setpoint:
Exchanger defrosting mode (only applied for SC, SX/C, TX/C, FC units)
Bypass On
Stop defrosting
Outdoor temp. to allow defrosting
Default setting
NoYes
21 °C
30 °C
28 °C
NoYes
Unit runningWhen defrosting
-15 °C
Pressure monitoring Pressure monitoring
Off
OnOff
18 °C
Set value
No Yes
No Yes
Unit running When defrosting
On Off
On Off
°
°
°
°
°
Outdoor temp. for stop of supply air fan
Max deviation exchanger pressure to start defrosting
Pressure hysteresis to end defrosting
Exchanger defrosting mode (only applied units with section defrosting)
Allow fan stop defrosting if exchanger pressure > max limit
Max allowed deviation exchanger pressure when defrosting
Max deviation exchanger pressure to start defrosting
Pressure hysteresis to end defrosting
Setpoint temperature min limit
Temperature hysteresis to end defrosting
Calibration extract air flow
Calibration exchanger pressure
18 °C
50 %
60 %
Section defrosting Section defrosting
YesNo
150%
25%
60%
4 °C
4 °C
_____________
_____________
°
%
%
Yes No
%
%
%
°
°
206951 | A011
12
Function settings
|
Function
Fire function
Operation mode when fire alarm
Supply air fan setpoint type
Extract air fan setpoint type
Outdoor air damper function
Default setting Set value
StoppedContinuous runOnly supply air fanOnly extract air fanRunning via normal start/stop conditions
AutoLowNormalHigh
Manual output
Manual setpoint
AutoLowNormalHigh
Manual output
Manual setpoint
NormalOpenClosed
__________ %
__________
__________ %
__________
Stopped Continuous run Only supply air fan Only extract air fan Running via normal start/stop conditions
Auto Low Normal High
Manual output
Manual setpoint
Auto Low Normal High
Manual output
Manual setpoint
Normal Open Closed
%
%
Exhaust air damper function
NormalOpenClosed
Normal Open Closed
206951 | A011
Setting the weekly program |

4 Setting the weekly program

Factory setting of the normal and low fan speed are:
• High fan speed 00:00 to 00:00 Monday to Sunday.
• Normal fan speed 07:00 to 16:00 Monday to Sunday.
• Low fan speed 00:00 to 24:00 Monday to Sunday.
• Settings of 00:00 to 00:00 stops the unit. E.g. changing low fan speed setting from 00:00-24:00 to 00:00-00:00 will stop the unit outside the time of normal fan speed.
Note:
High fan speed has priority over normal fan speed which has priority over low fan speed.
Weekday Period Low fan speed Normal fan speed High fan speed
13
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
1
2
1
2
1
2
1
2
1
2
1
2
1
2
Holiday (month. day) Holiday (month. day) Holiday (month. day)
1.
2.
3.
4.
5.
6.
7.
8.
206951 | A011
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
| I/O Allocation
14

5 I/O Allocation

Note any changes from the factory default input and output allocation configuration. Fill in any related information in the comment field. E.g. a pressure sensors measuring range, a contact’s polarity or similar.
Note:
Make notes of any additional connected accessories or external signals in the air handling unit’s wiring diagram!
Digital outputs
DO1
DO2
DO3
DO4
DO5
DO6
DO7
Analog outputs
AO1
AO2
AO3
AO4
AO5
Function
Function
Comment
Comment
Digital inputs
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
Analog inputs
AI1
AI2
AI3
AI4
Function
Function
Comment
Comment
206951 | A011
Alarm configuration |
15
Universal inputs
UI1
UI2
UI3
UI4
Function

6 Alarm configuration

Alarm settings Def. settings
Alarm number 1
Alarm name Malfunction supply air fan
Action:
Level:
Delay:
Alarm number 5
Normal stop
A
300 s
Comment
Set value
Alarm name Malfunction extract air fan
Action:
Level:
Delay:
Alarm number 43
Alarm name
Action: No action
Level:
Delay:
Alarm number 45
Alarm name
Action: No action
Level:
Delay:
Normal stop
A
300 s
Malfunction pump heating (SEQ-A)
B
5 s
Malfunction pump cooling (SEQ-C)
B
5 s
206951 | A011
| Alarm configuration
16
Alarm settings Def. settings
Alarm number 49
Alarm name
Action: No action
Level:
Delay:
Alarm number 50
Alarm name
Action: No action
Level:
Delay:
Alarm number 52
Alarm name Malfunction pump external heating/cooling cap.
Action: No action
Malfunction pump heating 2 (SEQ-G)
B
5 s
Malfunction pump cooling 2 (SEQ-H)
B
5 s
Set value
Level:
Delay:
Alarm number 53
Alarm name Filter alarm supply air
Action: No action
Level:
Delay:
Alarm number 54
Alarm name Filter alarm extract air
Action: No action
Level:
Delay:
B
5 s
B
300 s
B
300 s
206951 | A011
Alarm configuration |
17
Alarm settings Def. settings
Alarm number 56
Alarm name Freeze protection guard
Action:
Level: Disabled
Delay:
Alarm number 58
Alarm name Fire alarm
Action:
Level:
Delay:
Alarm number 59
Alarm name Smoke alarm
Action:
Fast stop
0 s
Fast stop
A
0 s
Fast stop
Set value
Level:
Delay:
Alarm number 60
Alarm name External stop
Action:
Level:
Delay:
Alarm number 61
Alarm name External alarm
Action: No action
Level:
Delay:
A
0 s
Normal stop
C
0 s
B
0 s
206951 | A011
| Alarm configuration
18
Alarm settings Def. settings
Alarm number 63
Alarm name Electric heater is overheated
Action:
Level:
Delay:
Alarm number 65
Alarm name Low efficiency exchanger
Action: No action
Level: Disabled
Delay:
Limit: 50 %
Alarm number 66
Alarm name Defrosting alarm
Normal stop
A
0 s
30 s
Set value
Action: No action
Level: Disabled
Delay:
Alarm number 67
Alarm name Rotary exchanger alarm
Action:
Level:
Delay:
Alarm number 79
Alarm name Alarm service interval
Action: No action
Level:
Delay:
0 s
Normal stop
A
10 s
C
0 s
206951 | A011
Alarm configuration |
19
Alarm settings Def. settings
Alarm number 80
Alarm name Restart blocked after power on
Action:
Level:
Delay:
Alarm number 81
Alarm name Deviation alarm supply air temperature
Action: No action
Level: Disabled
Delay:
Limit: 5 °
Alarm number 82
Alarm name Deviation alarm supply air fan
Fast stop
B
0 s
4 min
Set value
Action: No action
Level:
Delay:
Limit: 250
Alarm number 83
Alarm name Deviation alarm extract air fan
Action: No action
Level:
Delay:
Limit: 250
B
4 min
B
4 min
206951 | A011
| Alarm configuration
20
Alarm settings Def. settings
Alarm number 85
Alarm name Deviation alarm extra controller
Action: No action
Level: Disabled
Delay:
Limit: 10 °
Alarm number 86
Alarm name High supply air temperature
Action: No action
Level:
Delay:
Limit: 35 °
Alarm number 87
30 min
B
300 s
Set value
Alarm name Low supply air temperature
Action: No action
Level:
Delay:
Limit: 10 °
Alarm number 90
Alarm name High room temperature
Action: No action
Level: Disabled
Delay:
Limit: 30 °
B
300 s
30 min
206951 | A011
Alarm configuration |
21
Alarm settings Def. settings
Alarm number 91
Alarm name
Action: No action
Level: Disabled
Delay:
Limit: 10 °
Alarm number 92
Alarm name High extract air temperature
Action: No action
Level:
Delay:
Limit: 30 °
Alarm number 93
Low room temperature
30 min
B
30 min
Set value
Alarm name
Action: No action
Level:
Delay:
Limit: 10 °
Alarm number 94
Alarm name High outdoor air temperature
Action: No action
Level: Disabled
Delay:
Limit: 40°
Low extract air temperature
B
30 min
0 min
206951 | A011
| Alarm configuration
22
Alarm settings Def. settings
Alarm number 95
Alarm name Low outdoor air temperature
Action: No action
Level: Disabled
Delay:
Limit: -30 °
Alarm number 96
Alarm name Freeze protection alarm 1
Action:
Level:
Delay:
Alarm number 97
Alarm name Freeze protection alarm 2
0 min
Fast stop
A
0 s
Set value
Action:
Level:
Delay:
Alarm number 98
Alarm name Freeze protection alarm 3
Action:
Level:
Delay:
Alarm number 113
Alarm name Manual operation air handling unit
Action: No action
Level:
Delay:
Fast stop
A
0 s
Fast stop
A
0 s
C
0 s
206951 | A011
Alarm configuration |
23
Alarm settings Def. settings
Alarm number 114
Alarm name Manual operation supply air
Action: No action
Level:
Delay:
Alarm number 115
Alarm name Manual operation supply air fan
Action: No action
Level:
Delay:
Alarm number 116
Alarm name Manual operation extract air fan
Action: No action
C
0 s
C
0 s
Set value
Level:
Delay:
Alarm number 117
Alarm name Manual operation heater
Action: No action
Level:
Delay:
Alarm number 118
Alarm name Manual operation exchanger
Action: No action
Level:
Delay:
C
0 s
C
0 s
C
0 s
206951 | A011
| Alarm configuration
24
Alarm settings Def. settings
Alarm number 119
Alarm name Manual operation cooler
Action: No action
Level:
Delay:
Alarm number 120
Alarm name Manual operation damper
Action: No action
Level:
Delay:
Alarm number 121
Alarm name Manual operation pump heater
Action: No action
C
0 s
C
0 s
Set value
Level:
Delay:
Alarm number 122
Alarm name Manual operation pump exchanger
Action: No action
Level:
Delay:
Alarm number 123
Alarm name Manual operation pump cooler
Action: No action
Level:
Delay:
C
0 s
C
0 s
C
0 s
206951 | A011
Alarm configuration |
25
Alarm settings Def. settings
Alarm number 124
Alarm name Manual operation damper recirculation
Action: No action
Level:
Delay:
Alarm number 125
Alarm name Manual operation damper outdoor air
Action:
Level:
Delay:
Alarm number 126
Alarm name Manual operation damper exhaust air
Action: No action
C
0 s
Fast stop
A
0 s
Set value
Level:
Delay:
Alarm number 127
Alarm name Manual operation fire damper
Action: No action
Level:
Delay:
Alarm number 138
Alarm name Output in manual operation
Action: No action
Level:
Delay:
C
0 s
C
0 s
C
0 s
206951 | A011
| Alarm configuration
26
Alarm settings Def. settings
Alarm number 139
Alarm name Input in manual operation
Action: No action
Level:
Delay:
Alarm number 144
Alarm name Sensor error outdoor air temperature
Action: No action
Level:
Delay:
Alarm number 145
Alarm name Sensor error intake air temperature
Action: No action
C
0 s
B
5 s
Set value
Level:
Delay:
Alarm number 146
Alarm name Sensor error supply air temperature
Action: No action
Level:
Delay:
Alarm number 147
Alarm name Sensor error exhaust air temperature
Action: No action
Level:
Delay:
B
5 s
B
5 s
B
5 s
206951 | A011
Alarm configuration |
27
Alarm settings Def. settings
Alarm number 148
Alarm name
Action: No action
Level:
Delay:
Alarm number 149
Alarm name
Action: No action
Level:
Delay:
Alarm number 150
Alarm name
Action: No action
Sensor error extract air temperature
B
5 s
Sensor error room temperature 1
B
5 s
Sensor error room temperature 2
Set value
Level:
Delay:
Alarm number 151
Alarm name
Action: No action
Level:
Delay:
Alarm number 152
Alarm name
Action: No action
Level:
Delay:
B
5 s
Sensor error room temperature 3
B
5 s
Sensor error room temperature 4
B
5 s
206951 | A011
| Alarm configuration
28
Alarm settings Def. settings
Alarm number 153
Alarm name Sensor error pressure supply air
Action: No action
Level:
Delay:
Alarm number 154
Alarm name
Action: No action
Level:
Delay:
Alarm number 155
Alarm name Sensor error flow supply air
Action: No action
B
5 s
Sensor error pressure extract air
B
5 s
Set value
Level:
Delay:
Alarm number 156
Alarm name Sensor error flow extract air
Action: No action
Level:
Delay:
Alarm number 158
Alarm name Sensor error pressure exchanger extract
Action: No action
Level:
Delay:
B
5 s
B
5 s
B
5 s
206951 | A011
Alarm configuration |
29
Alarm settings Def. settings
Alarm number 159
Alarm name Sensor error defrosting temperature
Action: No action
Level:
Delay:
Alarm number 160
Alarm name Sensor error freeze protection temperature 1
Action:
Level:
Delay:
Alarm number 161
Alarm name Sensor error freeze protection temperature 2
Action:
B
5 s
Normal stop
A
5 s
Normal stop
Set value
Level:
Delay:
Alarm number 162
Alarm name Sensor error freeze protection temperature 3
Action:
Level:
Delay:
Alarm number 163
Alarm name Sensor error CO2 room/extract air
Action: No action
Level:
Delay:
A
5 s
Normal stop
A
5 s
B
5 s
206951 | A011
| Alarm configuration
30
Alarm settings Def. settings
Alarm number 177
Alarm name Sensor error pressure filter supply air
Action: No action
Level:
Delay:
Alarm number 178
Alarm name Sensor error pressure filter extract air
Action: No action
Level:
Delay:
Alarm number 179
Alarm name Sensor error efficiency temperature exchanger
Action: No action
B
5 s
B
5 s
Set value
Level:
Delay:
Alarm number 180
Alarm name Communication fault device
Action: No action
Level:
Delay:
Alarm number 181
Alarm name Malfunction extra controller
Action: No action
Level:
Delay:
B
5 s
C
0 s
B
5 s
206951 | A011
Alarm configuration |
31
Alarm settings Def. settings
Alarm number 185
Alarm name Malfunction preheater
Action: No action
Level:
Delay:
Alarm number 186
Alarm name Communication fault BMS master
Action: No action
Level:
Delay:
Alarm number 187
Alarm name Leakage heater valve
Action: No action
B
5 s
C
1 s
Set value
Level:
Delay:
Alarm number 188
Alarm name Sensor error preheater temperature
Action: No action
Level:
Delay:
Alarm number 207
Alarm name Malfunction heating zone 1
Action: No action
Level: Class B
Delay:
B
5 min
B
5 s
5 s
206951 | A011
| Alarm configuration
32
Alarm settings Def. settings
Alarm number 208
Alarm name Malfunction heating zone 2
Action: No action
Level: Class B
Delay:
Alarm number 209
Alarm name Malfunction heating zone 3
Action: No action
Level: Class B
Delay:
Alarm number 210
Alarm name Malfunction cooling zone 1
Action: No action
5 s
5 s
Set value
Level: Class B
Delay:
Alarm number 211
Alarm name Malfunction cooling zone 2
Action: No action
Level: Class B
Delay:
Alarm number 212
Alarm name Malfunction cooling zone 3
Action: No action
Level: Class B
Delay:
5 s
5 s
5 s
206951 | A011
Alarm configuration |
33
Alarm settings Def. settings
Alarm number 213
Alarm name Deviation alarm supply temp zone 1
Action: No action
Level: Class B
Delay:
Limit: 10 °C
Alarm number 214
Alarm name Deviation alarm supply temp zone 2
Action: No action
Level: Class B
Delay:
Limit: 10 °C
Alarm number 215
30 min
30 min
Set value
Alarm name Deviation alarm supply temp zone 3
Action: No action
Level: Class B
Delay:
Limit: 10 °C
Alarm number 216
Alarm name Freeze protection alarm zone 1
Action
Level Class A
Delay
Alarm number 217
Alarm name Freeze protection alarm zone 2
Action
Level Class A
30 min
Fast stop
0 s
Fast stop
Delay
206951 | A011
0 s
| Alarm configuration
34
Alarm settings Def. settings
Alarm number 218
Alarm name Freeze protection alarm zone 3
Action
Level Class A
Delay
Alarm number 219
Alarm name Electric heater is overheated zone 1
Action
Level Class A
Delay
Alarm number 220
Alarm name Electric heater is overheated zone 2
Action
Fast stop
0 s
Normal stop
0 s
Normal stop
Set value
Level Class A
Delay
Alarm number 221
Alarm name Electric heater is overheated zone 3
Action
Level Class A
Delay
Alarm number 222
Alarm name Sensor error supply air temp zone 1
Action No action
Level Class B
Delay
0 s
Normal stop
0 s
5 s
206951 | A011
Alarm configuration |
35
Alarm settings Def. settings
Alarm number 223
Alarm name Sensor error supply air temp zone 2
Action No action
Level Class B
Delay
Alarm number 224
Alarm name Sensor error supply air temp zone 3
Action No action
Level Class B
Delay
Alarm number 225
Alarm name
Action No action
5 s
5 s
Sensor error room temp zone 1
Set value
Level Class B
Delay
Alarm number 226
Alarm name
Action No action
Level Class B
Delay
Alarm number 227
Alarm name
Action No action
Level Class B
Delay
Alarm number 228
Alarm name
5 s
Sensor error room temp zone 2
5 s
Sensor error room temp zone 3
5 s
Sensor error extract temp zone 1
Action No action
Level Class B
Delay
206951 | A011
5 s
| Alarm configuration
36
Alarm settings Def. settings
Alarm number 229
Alarm name
Action No action
Level Class B
Delay
Alarm number 230
Alarm name
Action No action
Level Class B
Delay
Alarm number 231
Alarm name Sensor error freeze protection zone 1
Action No action
Sensor error extract temp zone 2
5 s
Sensor error extract temp zone 3
5 s
Set value
Level Class B
Delay
Alarm number 231
Alarm name Sensor error freeze protection zone 2
Action No action
Level Class B
Delay
Alarm number 233
Alarm name Sensor error freeze protection zone 3
Action No action
Level Class B
Delay
5 s
5 s
5 s
206951 | A011
206951 | A011
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden
Phone +46 222 440 00
www.systemair.com
Compact air handling units · Commissioning Record · 206951 · en_GB · 2020-08-14 · A011