SystemAir Topvex TR03, Topvex SR03, Topvex SR06, Topvex SR04, Topvex TR06 Installation Instructions Manual

...
Page 1
Document in original language | A003
Topvex SR/TR03, SR/TR04, SR/TR06 Compact Air Handling Unit
Installation instructions
GB
Page 2
© Copyright Systemair AB All rights reserved E&OE
Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Page 3
124454 | A003
Contents
1 Declaration of Conformity . ....... . .... . . .... . .... . ..... . ..1
2 Warnings. . .... . ..... . .... . .... . ..... . .... . ..... . .... . .... . ..... 2
3 Product information ... . . .... . .... . ..... . .... . .... . ..... . .... 2
3.1 General... . .... . ..... ..... . .... . ..... ..... . .... . ..... . .2
3.2 Technical Data .... . ..... ..... . .... . ..... . .... . ..... . .3
3.2.1 Dimensions and weights
Topvex SR 03-06 .... . .... . ..... ..... . ..3
3.2.2 Dimension and weights
Topvex TR 03-06 .... . ..... . .... . ..... . .5
3.2.3 Electrical data Topvex SR/TR
03-06.. . .... . ..... . .... . .... . ..... . .... . ...8
3.3 Transport and Storage . . ..... ..... . .... . ..... . .... . 9
4 Installation.. . .... . .... . ..... . .... . ..... . .... . ..... ..... . .... . ..9
4.1 Unpacking .... ..... . .... . ..... . .... . ..... . .... . .... . ..9
4.2 Where/how to install .... . ..... . .... . ..... . .... . ...9
4.3 Installing the Unit .... . .... . ..... . .... . ..... . .... . . 10
4.3.1 Installation procedure... . .... . .... . .. 11
4.4 Supply air sensor (Topvex SR 03-
06) ..... . .... . .... . . .... . .... . ..... . .... . .... . ..... . .. 11
4.5 Connections ..... . .... . .... . . .... . .... . ..... . .... . .. 13
4.5.1 Ducting ... . ..... ..... . .... . ..... ..... . ... 13
4.5.2 Electric Connections . . .... . .... . ..... . 15
4.6 Installing the Control Panel .... . ..... . .... . ..... 19
4.6.1 Dimensions... . .... . ..... . .... . .... . .... 19
4.6.2 General information . ..... ..... . .... . . 19
4.6.3 Installation.. . .... . .... . . .... . .... . ..... . 19
4.7 Additional Equipment .... . ..... . .... . ..... . .... . . 20
Page 4
Page 5
Declaration of Conformity |
1
1 Declaration of Conformity
MMaannuuffaaccttuurreerr
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99 www.systemair.com
hheerreebbyy ccoonnffiirrmmss tthhaatt tthhee ffoolllloowwiinngg pprroodduuccttss::
Air handling units
EEll
NNoonnee HHWWLL HHWWHH
Topvex SR03-SR06 Topvex SR03-SR06 Topvex SR03-SR06 Topvex SR03-SR06
Topvex SR03-SR06 M0 Topvex SR03-SR06 M0
Topvex SR03-SR06 M0
Topvex TR03-TR06 Topvex TR03-TR06 Topvex TR03-TR06 Topvex TR03-TR06
Topvex TR03-TR06 M0 Topvex TR03-TR06 M0
Topvex TR03-TR06 M0
(The declaration applies only to product in the condition it was delivered in and installed in the facility in accordance with the included installation instructions. The insurance does not cover components that are added or actions carried out subsequently on the product)
CCoommppllyy wwiitthh aallll aapppplliiccaabbllee rreeqquuiirreemmeennttss iinn tthhee ffoolllloowwiinngg ddiirreeccttiivveess aanndd rreegguullaattiioonnss
MMaacchhiinneerryy DDiirreeccttiivvee 22000066//4422//EECC EEccooddeessiiggnn DDiirreeccttiivvee 22000099//112255//EECC
327/2011 Requirements for fans 1253/2014 Requirements for ventilation units
LLooww VVoollttaaggee DDiirreeccttiivvee 22001144//3355//EEUU
EEMMCC DDiirreeccttiivvee 22001144//3300//EEUU
TThhee ffoolllloowwiinngg hhaarrmmoonniizzeedd ssttaannddaarrddss aarree aapppplliieedd iinn aapppplliiccaabbllee ppaarrttss::
EN ISO 12100:2010
Safety of machinery - General principles for design - Risk assessment and risk reduction
EN 13857
Safety of machinery – Safety distances to prevent hazard zones being reached by upper or lower limbs
EN 60204-1
Safety of machinery – Electrical equipment of machines – Part 1: General requirements
EN 60335-1
Household and similar electrical appliances – Safety Part 1: General requirements
EN 60335-2-40
Safety of household and similar electrical appliances - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers
EN 50106:2007
Safety of household and similar appliances – Particular rules for routine tests referring to appliances under the scope of EN 60 335-1 and EN 60967
EN 60529
Degrees of protection provided by enclosures (IP Code)
EN 62233
Measurement methods for electromagnetic fields of household appliances and similar apparatus with regard to human exposure
EN 61000-6-2
Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments
EN 61000-6-3
Electromagnetic compatibility (EMC) – Part 6-3: Generic standards – Emission standards for residential, commercial and light-industrial environments
The complete technical documentation is available.
Skinnskatteberg, 15-03-2016
Mats Sándor Technical Director
124454 | A003
Page 6
2
|
Warnings
2 Warnings
The following admonitions will be presented in the different sections of the document.
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
Warning
• The door handles are only intended to be used during the installation and service. These must be removed before the unit is put into operation to ensure the required level of safety for the unit.
The unit must be duct connected or in some other way provided with protection so that it is not possible to come in contact with the fans through the duct connections
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use protective clothing.
• Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing.
• The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a minimum 3 mm gap.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
• Take care not to damage the water battery when connecting water pipes to connectors. Use a spanner to tighten the connection.
3 Product information
3.1 General
This installation manual concerns air handling unit type Topvex SR/TR 03-06 manufactured by Systemair AB. Topvex SR/TR 03-06 include the following model options:
• MMooddeell:: SR03, SR04, SR06, TR03, TR04, TR06
• HHeeaattiinngg ccooiill:: EELL (Electric), HHWWLL (Water coil, low power), HHWWHH (Water coil, high power) or NNoonnee.
• RRiigghhtt oorr lleefftt mmooddeellss:: RR (Right) LL (Left). The side where the supply air is located when viewed from the access side.
• AAiirrffllooww ccoonnttrrooll:: CCAAVV– Constant Air Volume, VVAAVV – Variable Air Volume = Constant duct pressure control (as an accessory)
• MM00:: Aluminium fan impeller
This manual consists of basic information and recommendations concerning the design, installation, start-up and opera­tion, to ensure a proper fail-free operation of the unit.
The key to proper and safe operating of the unit is to read this manual thoroughly, use the unit according to given guidelines and follow all safety requirements.
Page 7
Product information |
3
3.2 Technical Data
3.2.1 Dimensions and weights Topvex SR 03-06
Fig. 1 Dimensions (mm) SR03 (Drawn as a right hand unit)
Fig. 2 Dimensions (mm) SR04, SR06 (Drawn as a right hand unit)
MMooddeell
AA BB CC
DD ((cc//cc)) EE ((cc//cc))
FF
SR04 1600 1041 850 1315 565 175
SR06 1600 1128 1000 1468 868 200
MMooddeell
GG HH II
JJ
KK
SR04 500 171 250 200 355
SR06 600 164 300 200 396
Y: 15R 1/2Inner thread
3.2.1.1 Weights Topvex SR 03-06
MMooddeell
WWeeiigghhtt ((kkgg))
SR03 220
SR04 270
SR06 300
124454 | A003
Page 8
4
| Product information
3.2.1.2 Space required Topvex SR 03-06
Fig. 3 Space required
MMooddeell
MM ((mmmm)) NN ((mmmm))
SR03 650 603
SR04 750 603
SR06 900 603
Page 9
Product information |
5
3.2.2 Dimension and weights Topvex TR 03-06
Fig. 4 Dimensions (mm) TR03, TR04 (Drawn as a left hand unit)
MMooddeell
AA BB CC
DD ((cc//cc)) EE ((cc//cc))
FF
TR03 1180 1230 750 1048 618 193
TR04 1480 1280 850 1348 718 209
MMooddeell
GG HH II
JJ
KK Ø
TR03 265 195 260 295 127 250
TR04 354 315 220 315 163 315
124454 | A003
Page 10
6
| Product information
Fig. 5 Dimensions (mm) TR06
Y: 15R 1/2Inner thread
3.2.2.1 Weights Topvex TR 03-06 (Drawn as a left hand unit)
MMooddeell
WWeeiigghhtt ((kkgg))
TR03 230
TR04 290
TR06 360
Page 11
Product information |
7
3.2.2.2 Space required Topvex TR 03-06
Fig. 6 Space required
MMooddeell
MM ((mmmm)) NN ((mmmm))
TR03 660 570
TR04 760 715
TR06 910 825
124454 | A003
Page 12
8
| Product information
3.2.3 Electrical data Topvex SR/TR 03-06
Table 1 Power Consumption
MMooddeell
FFaannss ((WW ttoott..)) 223300VV 11~~ aanndd 440000 VV 33NN~~
EEll HHeeaattiinngg bbaatttteerryy ((kkWW ttoott..))
FFuussee ((mmaaiinnss)) ((AA)) ffoorr 223300VV 11~~ aanndd 440000 VV 33NN~~
FFuussee ((mmaaiinnss)) ((AA)) ffoorr 223300VV 11~~ aanndd 223300VV 33~~
SR/TR03 EL
1412 3 3x13 3x16
SR/TR03 (None, HWL/HWH)
1412
10 10
SR/TR03 El M0
1014 3 3x13 3x16
SR/TR03 (None, HWH M0)
1016
13 13
SR/TR04 EL
1460 4 3x16 3x20
SR/TR04 (None, HWL/HWH)
1460
10 10
SR/TR04 El M0
1560 4 3x16 3x20
SR/TR04 (None, HWH) M0
1560
10 13
SR/TR06 EL
1794 6.3 3x16 3x25
SR/TR06 (None, HWL/HWH)
1794
3x10 3x10
SR/TR06 El M0
2066 6.3 3x16 3x25
SR/TR06 (None, HWH) M0
2066
3x10 3x13
Page 13
Installation |
9
3.3 Transport and Storage
The Topvex SR/TR 03-06 should be stored and transported in such a way that it is protected against physical damage that can harm panels, handles, display etc. It should be covered so that dust, rain and snow cannot enter and damage the unit and its components. The appliance is delivered in one piece containing all necessary components, wrapped in plastic on a pallet for easy transportation.
When transporting the Topvex SR/TR 03-06 units use a forklift. placed on the gable of the unit (figure 7.)
Warning
The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use protective clothing.
Fig. 7 Transporting the unit
4 Installation
4.1 Unpacking
Verify that all ordered equipment are delivered before starting the installation. Any discrepancies from the ordered equipment must be reported to the supplier of Systemair products.
4.2 Where/how to install
Topvex SR/TR 03-06 are meant for indoor installation. Topvex SR03,SR04 and SR06 can be installed outside if weather protected. Use accessory ODS to size 04 and 06. Place the unit on a hhoorriizzoonnttaall ffllaatt ssuurrffaaccee. It’s important that the unit is completely levelled before it is put into operation.
Place the unit preferably in a separate room (e.g. storage, laundry room, attic or similar). The electronic components should not be exposed to lower temperature than 0°C and higher than +50°C.
If the unit is installed in a cold place it is important that the unit is not shut-off by the main switch. As long as the main voltage is on the electrical cabinet will be kept warm also in cold climates.
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspec­tion doors should be easily accessible. Leave free space for opening the doors and for taking out the main components (figure 3 and figure 6).
Avoid placing the appliance against a wall, as low frequency noise can cause vibrations in the wall even if the fan noise-level is acceptable. If this is not possible it is recommended to carefully insulate the wall.
The outdoor air intake of the building should if possible be put in the northern or eastern side of the building and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets.
124454 | A003
Page 14
10
| Installation
4.3 Installing the Unit
The unit must be installed in the following position (figure 8).
Fig. 8 Installation position (left hand unit)
Fig. 9 Installation position (right hand unit)
Table 2 Symbol description
SSyymmbbooll
DDeessccrriippttiioonn
Supply air
Exhaust air
Outdoor air
Extract air
Page 15
Installation |
11
4.3.1 Installation procedure
11 Prepare the surface where the unit is to be mounted.
Make sure that the surface is flat, levelled and that it sup­ports the weight of the unit. Perform the installation in accordance with local rules and regulations.
22 Lift the unit in place.
Warning
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is used. Use protective clothing.
33 Level the unit with help of the enclosed mounting feet
44 Connect the unit electrically to the mains through the all
pole circuit breaker (safety switch), which is enclosed in­side the unit on delivery. The wiring is led through the ga­ble of the unit (Topvex SR 03-06) or through the top of the unit casing (Topvex TR 03-06) directly to the electrical connection box. See enclosed wiring diagram, and below table (table 3) for more information.
Warning
The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a minimum 3 mm gap.
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
4.4 Supply air sensor (Topvex SR 03-06)
The supply air sensor is fitted in the duct after the unit in the supply air duct (figure 10). See table 3 to which terminals the sensor needs to be connected in the electrical connection box. Other temperature sensors are built in to the unit from factory. The supply air sensor is enclosed in the unit package on delivery.
124454 | A003
Page 16
12
| Installation
Fig. 10 Installed supply air sensor (right hand connected unit)
Page 17
Installation |
13
4.5 Connections
4.5.1 Ducting
4.5.1.1 Air connections principles
Fig. 11 Connections and basic components in left hand connected units
PPoossiittiioonn DDeessccrriippttiioonn
SSyymmbbooll
A
Connection supply air
B
Connection exhaust air
C
Connection outdoor air
D Connection extract air
1
Fan supply air
2 Fan extract air
3
Filter supply air
4
Filter extract air
5
Heat exchanger
6 Rotor motor
7
Electric compartment
8
Re-heater battery
4.5.1.2 Condensation and Heat Insulation
Outdoor air duct and discharge ducts must always be well insulated against condensation. Correct insulation installation on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas must be well insulated. Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion barrier. In areas with extremely low out­door temperatures during the winter, additional insulation must be installed. Total insulation thickness must be at least 150 mm.
Caution
• If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
• Duct connections/duct ends should be covered during storage and installation
• Do not connect tumble dryers to the ventilation system
124454 | A003
Page 18
14
| Installation
4.5.1.3 Silencers
To avoid fan noise being transferred via the duct system, silencers should be installed both on supply and extract air.
To avoid noise being transferred between rooms via the duct system and also to reduce noise from the duct system it­self, installation of silencers before every inlet diffuser is recommended.
Page 19
Installation |
15
4.5.2 Electric Connections
All electric connections are made in the electrical connection box which can be found in the front of the unit (figure 12). The hatch is removed by unscrewing four screws (figure 12).
The unit must not be put into operation before all the electrical safety precautions have been read and understood. See the enclosed wiring diagram for internal and external wiring.
All external connections to possible accessories are made to terminals inside the electrical connection box (table 3).
Fig. 12 Opening the electrical connection box
Danger
• Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
124454 | A003
Page 20
16
| Installation
4.5.2.1 Electrical connection box, Components
Topvex SR/TR 03-06 are equipped with a built in regulator and internal wiring (figure 13).
The figure shows the electrical connection box for the Topvex TR 03-06 units. The connection box for the Topvex SR 03-06 has the same layout and components with the difference that the electrical heater is situated in a separate compartment.
Fig. 13 Electric components
PPoossiittiioonn
ddeessccrriippttiioonn
1
Regulator E-28 WEB
2
Transformer 230/24V AC
3
Terminals for internal and external components
4
Terminals for internal wiring
5
Terminals for mains supply to the unit
6
Contactor (K2) Pump control water (HW units only, not present in EL-units)
7
Automatic fuse
8
Electric heater frame
9
Automatic fuse for heater
10
Contactor (K3) for control of EL heater
11
Thermostat (EL units)
12
Manual over heat protection reset (EL units)
4.5.2.2 Topvex External Connections
Table 3 Connections to external functions
TTeerrmmiinnaall bblloocckk
DDeessccrriippttiioonn
RReemmaarrkk
PE
Ground
N N
Earthed neutral (supply voltage)
Used for phase 230V 1~ and 400V 3~
Page 21
Installation |
17
Connections to external functions cont'd
TTeerrmmiinnaall bblloocckk
DDeessccrriippttiioonn
RReemmaarrkk
L1 L1
Phase (Main supply voltage)
Used for phase 230V 1~ if the unit has this mains supply 400V 3~/230V 3~
L2 L2
Phase (Main supply voltage) 400V 3~/230V 3~
L3 L3
Phase (Main supply voltage) 400V 3~/230V 3~
1 G
Auxiliary supply (Pressure transmitter. Water valve actuators)
24V AC
2 G0
Reference (Water valve actuator mains supply)
24V AC
10
DO ref DO reference
G (24V AC)
12
1
DO 2
Outdoor/Exhaust air damper
24V AC Max. 2,0 A continuous load
WP L1
Circulation pump hot water system
230V AC
14
1
DO 4
Cooling pump
24V AC
15
1
DO 5
DX Cooling step 1
24V AC
16
1
DO 6
DX Cooling step 2
24V AC
17
1
DO 7
Alarm output for DO signals
24V AC
30
AI Ref Supply air temperature sensor reference neutral
31 AI 1
Temperature sensor, supply air
40
Agnd UI reference neutral
41
2
UAI 1/(UDI 1)
Pressure transmitter extract air
42
2
UAI 2/(UDI 2)
Pressure transmitter supply air
44
UAI 3/(UDI 3)
Frost protection sensor water heating battery
Use terminal 40 as reference
4
3
DI ref Extended running/Fire alarm reference
+ 24V DC
P1:50/P2:60
B
Exo-line B Modbus, Exo-line connection
P:151/P2:61
A
Exo-line A Modbus, Exo-line connection
P1:52/P2:62
N
Exo-line N Modbus, Exo-line connection
74
3
DI 4
Extended running Normally open contact
Use terminal 4 as reference
75
3
DI 5
Fire alarm Normally open contact
Use terminal 4 as reference
76
3
DI 6
External stop Normally open contact
Use terminal 4 as reference
90
Agnd AO Reference neutral
93 AO 3
Control signal valve actuator, Water Heating
0–10V DC
94 AO 4
Control signal valve actuator, Cooling
0–10V DC
1. Maximum current load for all DO combined: 8A
2. Connection to external pressure sensor in case of pressure controlled unit (VAV)
3. These inputs may only be wired to voltage free contacts
124454 | A003
Page 22
18
| Installation
4.5.2.3 BMS Connection
BMS Connection
Communication possibilities for controller E283 WEB.
• RS485(Modbus): 50-51-52 or 60-61-62
• RS485(Exoline): 50-51-52-53 or 60-61-62-63
• TCP/IP Exoline
• TCP/IP Modbus
• TCP/IP WEB
• BACnet/IP
Fig. 14 BMS connection on the controller
Page 23
Installation |
19
4.6 Installing the Control Panel
4.6.1 Dimensions
Fig. 15 Control panel dimensions
PPoossiittiioonn
DDiimmeennssiioonnss ((mmmm))
A 115.0
B 94.0
C 26.0
D
c/c 60.0
E 50.5
4.6.2 General information
The control panel is delivered connected to the Corrigo control unit situated in the electrical connection box. Cable length is 10 m. In case the control panel needs to be detached from the signal cable it is possible to loosen the wires on the back of the control panel (figure 16).
A set of self-adhesive magnet strips are included in the package to facilitate installation on a metal surface.
4.6.3 Installation
11 Find an appropriate place to install the control panel. Max-
imum length between control panel and unit is 100 m.
22 If needed, drill two holes in the wall to hang the control
panel (center to center: 60 mm) (pos.1, figure 16).
124454 | A003
Page 24
20
| Installation
Fig. 16 Control panel wire connections
PPoossiittiioonn
DDeessccrriippttiioonn
1
Mounting holes
2
Connection block
3
Connection to brown cable
4
Connection to yellow cable
5
Connection to white cable
6
Connection to black cable
4.7 Additional Equipment
For information concerning additional external equipment such as valve actuators, motorized dampers, E-tool, roof units, wall grilles etc. see technical catalogue and their enclosed instructions.
For electrical connections of external components see enclosed wiring chart.
Page 25
Page 26
Page 27
Page 28
· Installation instructions · 124454 · en_GB · 15-03-2016 · A003
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden
Phone +46 222 440 00 Fax +46 222 440 99
www.systemair.com
Loading...