The VAV duct pressure control kit is used for VAV control of Air Handling units. Included in the kit are: 2 pcs of pressure
transmitters PTE (Pressure Transmitter Extract), PTS (Pressure Transmitter Supply), pressure outlet, tubes, electrical cables (4m) and installation instruction.
The pressure transmitters max working range is 0...1250 Pa.
2Warnings
Danger
• Make sure that the mains supply to the unit is disconnected before performing any maintenance or
electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules
and regulations.
• Beware of sharp edges during mounting.
3Mount pressure transmitters
The pressure transmitters need to be mounted in the supply and extract air ducts (figure 1) and connected according to
external connections, chapter 6.7.
Supply duct, connect the tube from the supply duct to +. Extract duct, connect the tube from the extract duct to -.
1
Connect the electrical cables to the electrical connection box.
Note:
For Topvex SF; if an external extract fan is used, mount the pressure transmitter PTE in the extract air duct.
Fig. 1 VAV installation (example show Topvex SR06 and TR06) and pressure sensor
Table 1 Symbol description
SymbolDescription
151785 | A004
Supply air
Exhaust air
Outdoor air
Extract air
Page 6
Wiring
White
Yellow
Brown
Green
White
Yellow
Brown
Green
White
Yellow
Brown
Green
G
G0
41
40
White
Yellow
Brown
Green
G
G0
42
40
1
6
1 2 3 4
1 2 3 4
1
2
3
4
5
6
1
6
2
3
4
|
2
4Wiring
Change the settings of the dip-switches according to table 2.
Table 2 Dip-switch 2, 3 and 4
Dip-switch setting
2 = OFF, 3 = OFF, 4 = OFF0...50
2 = ON, 3 = OFF, 4 = OFF0...100
2 = OFF, 3 = ON, 4 = OFF0...300
2 = ON, 3 = ON, 4 = OFF0...500
2 = OFF, 3 = OFF, 4 = ON0...700
2 = ON, 3 = OFF, 4 = ON0...1000
2 = OFF, 3 = ON, 4 = ON0...1250
Pressure range (Pa)
151785 | A004
Page 7
5Configuration guide Topvex (Access)
5.1Log in
Log in with service mode using password 0612.
Overview:
Service
0612
Login
Step by step:
Configuration guide Topvex (Access)
|
3
1.
2.
3.
4.
Open the log in window
Select service from drop down list
Type in password 0612
Press Login.
5.2Configuration wizard
A configuration wizard is available from software version 4.1. By using the wizard, the following steps in chapter 5.3
and chapter 5.4 can be omitted.
Configuration > Configuration wizard
Set up Pressure control
04 March 12:45
5.3Activation
Activate pressure control.
>
Select Pressure as Fan control type in the Configuration > Function configuration > Function activation menu.
Overview:
Configuration > Function Configuration > Function
activation
Fan control type
Step by step:
1.
2. Select Function configuration
3. Select Function activation
4. Select Pressure as Fan control type.
Select Configuration from the navigation icons
151785 | A004
04 March
12:45
Pressure
Page 8
|
4
Configuration guide Topvex (Access)
5.4Allocation
Setup differential pressure sensors.
Select I/O placement for the differential pressure sensors and set the sensors’ measuring range in the Configura-tion > I/O allocation settings > Analog inputsmenu.
Overview:
Configuration > I/O allocation settings > Analog
inputs
Analogue inputs
Pressure supply airController
Pressure extract air
Configuration > ... > Analog inputs > Pressure supply
air
Sensor value at V
Sensor value at V
min
max
04 March 12:45
DevicePosition
UI2
Controller
UI1
04 March 12:45
0.0
500.0
Step by step:
1.
Select Configuration from the navigation icons
2. Select I/O allocation settings
3. Select Analog inputs
4. Select UI2 as signal for Pressure supply air
5. Select UI1 as signal for Pressure extract air
6. Select Pressure supply air
7. Set Sensor value at V
8. Set Sensor value at V
the same as the start point of the sensor’s selected measuring range
min
the same as the end point of the sensor’s selected measuring range
max
9. Go back to Analog inputs (use the navigation path Configuration > I/O allocation settings > Analog
inputs)
10.Select Pressure extract air and repeat steps 7 and 8.
151785 | A004
Page 9
Configuration guide Topvex (Access)
5.5Operation settings
Adjust the fan pressure set points in the Data & Settings > Fan Control > Fan setpoints.
Overview:
|
5
Data settings > Fan control > Fan setpoints
Setpoint low speed supply air fan
Setpoint low speed extract air fan
Setpoint normal speed supply air fan
Setpoint normal speed extract air fan
Setpoint high speed supply air fan
Setpoint high speed extract air fan
Step by step:
1.
2. Select Fan control
3. Select Fan setpoints
4. Select and adjust set points for the available fan speed levels.
Select Data & settings from the navigation icons
04 March 12:45
100 Pa
100 Pa
200 Pa
200 Pa
200 Pa
200 Pa
5.6Save local settings
When the installation is complete and all functions are tested it is recommended to save a local backup of the current
configuration in the controller.
Select Yes on Commissioning settings in the Configuration > System settings > Save and restore set-tings menu.
Overview:
Configuration > System settings > Save and restore
settings
Save commissioning settings
Step by step:
1.
2. Select System settings
3. Select Save and restore
4. Select Yes on Save commissioning settings.
Select Configuration from the navigation icons
04 March 12:45
Yes
151785 | A004
Page 10
|
6
Configuration guide Topvex SF (Corrigo)
6Configuration guide Topvex SF (Corrigo)
6.1Login
Log on to Administrator level with password 3333.
Menu level 1Menu level 2Menu level 3
Temperature
Air control
Time settings
→ Access rights
→ Log on
Log off
Change password
→ Log on
Enter password:3333
Actual level:Admin
Note:
The grey-marked instructions is only for when Topvex SF have an external extract air fan installed.
6.2Fan control
Set the fan control type in menu Configuration > Fan control.
Change the fan control to Pressure control.
Menu level 1Menu level 2Menu level 3
Manual/Auto
Settings
→ Configuration
Access rights
Sensor settings
Control function
→ Fan control
Extra sequence Y4
Fan control
Pressure control
6.3Sensor setting
Set the adjusted working range for the added VAV pressure transmitters in menu Configuration/Sensor
setting.
Adjust SAF (supply air fan) and EAF (extract air fan) actual pressure range at 10,0 V.
Example: If pressure transmitter is set to 0...500 Pa set: 0,0 V: 0,0 Pa and 10,0 V : 500,0 Pa. Filter factor is not to be
changed.
Menu level 1Menu level 2Menu level 3
Manual/Auto
Settings
→ Configuration
Access rights
Inputs/Outputs
→ Sensor settings
Control functions
Fan control
SAF pressure at 0,0V:0,0 Pa
10,0V:XXX,X Pa
Filter factor ↓
EAF pressure at 0,0V:0,0 Pa
10,0V:XXX,X Pa
Filter factor
6.4Air control setpoint
Adjust the new Pressure ctrl SAF and Pressure ctrl EAF set points.
Menu level 1Menu level 2Menu level 3
Running mode
Temperature
→ Air control
Time settings
Pressure ctrl SAF
Actual:0 Pa
Setp:0 Pa →
↓
Pressure ctrl EAF
Actual:0 Pa
Setp:0 Pa →
↓
Pressure ctrl SAF
Setp 1/1: 200 Pa
Setp 1/2: 100 Pa
←
Pressure ctrl EAF
Setp 1/1: 200 Pa
Setp 1/2: 100 Pa
←
151785 | A004
Page 11
Configuration guide Topvex SF (Corrigo)
6.5Alarm limit
Deviation from pressure setpoint value
Menu level 1Menu level 2Menu level 3
Manual/Auto
→ Settings
Configuration
Access rights
Control temp
Control pressure
→ Alarm settings
→Alarm limits
Alarm delays
Restore alarm
Control dev SAF
25.0 Pa
Control dev EAF
25.0 Pa
6.6Allocation
Menu level 1Menu level 2Menu level 3
Manual auto
Settings
→ Configuration
Access rights
→ Inputs/Outputs
Sensor settings
Control function
Fan control
AI
→ UI
DI
UI
|
7
Menu level 4Menu level 5
UI1:→
Choose AI or DI sign
AI sign:Not used
DI sign:Not used
↓
UI2:→
Choose AI or DI sign
AI sign:Not used
DI sign:Not used
UAI1:
Sign:EAF pressure
Raw value: NaN
Compansation:0.0°C
←
UAI2:
Sign:SAF pressure
Raw value: NaN
Compensation: 0.0°C
151785 | A004
Page 12
|
8
Configuration guide Topvex SF (Corrigo)
6.7External connections
Table 3 Connections to external functions
Terminal block
PE
NN
L1L1
L2L2
L3L3
1G
2G0
10
1
12
WPL1
1
14
1
15
1
16
1
17
30
31AI 1
40
2
41
2
42
44
3
4
P1:50/P2:60
P:151/P2:61
P1:52/P2:62
3
74
3
75
76
3
90
93AO 3
94AO 4
1
Maximum current load for all DO combined: 8A
2
Connection to external pressure sensor in case of pressure controlled unit (VAV)
3
These inputs may only be wired to voltage free contacts
DO refDO reference
DO 2
DO 4
DO 5
DO 6
DO 7
AI RefSupply air temperature sensor referenceneutral
AgndUI referenceneutral
UAI 1/(UDI 1)
UAI 2/(UDI 2)
UAI 3/(UDI 3)
DI refExtended running/Fire alarm reference
B
A
N
DI 4
DI 5
DI 6
AgndAO Referenceneutral
Description
Remark
Ground
Earthed neutral (mains power supply)
Used for phase 230V 1~ and
400V 3~
Phase (mains power supply)
Used for phase 230V 1~ if the
unit has this mains
400V 3~/230V 3~
Phase (mains power supply)400V 3~/230V 3~
Phase (mains power supply)400V 3~/230V 3~
Auxiliary supply (Pressure transmitter. Water
24V AC
valve actuators)
Reference (Water valve actuator mains)
24V AC
G (24V AC)
Outdoor/Exhaust air damper
24V AC
Max. 2,0 A continuous load
Circulation pump hot water system
Cooling pump
DX Cooling step 1
DX Cooling step 2
Alarm output for DO signals
230V AC
24V AC
24V AC
24V AC
24V AC
Temperature sensor, supply air
Pressure transmitter extract air
Pressure transmitter supply air
Frost protection sensor water heating
Use terminal 40 as reference
battery
+ 24V DC
Exo-line BModbus, Exo-line connection
Exo-line AModbus, Exo-line connection
Exo-line NModbus, Exo-line connection
Extended runningNormally open contact
Use terminal 4 as reference
Fire alarmNormally open contact
Use terminal 4 as reference
External stopNormally open contact
Use terminal 4 as reference
Control signal valve actuator, Water Heating
Control signal valve actuator, Cooling
0–10V DC
0–10V DC