SystemAir Topvex SF02-S12 Operation And Maintenance

Page 1
Topvex SF02-S12 Air Handling Unit
Operation and Maintenance Instructions
Document in original language | 130323 · A002
GB
Page 2
© Copyright Systemair AB All rights reserved E&OE
Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
130323 | A002
Page 3
1 Warnings. .. ....... .... ..... .... ..... .... ..... .... ......... .... .1
2 Product description .... ..... .... ......... .... ..... .... ..... ..2
2.1 Internal components .... .... ..... .... ..... .... .... .2
2.2 Description internal components... .... ..... .... 2
2.2.1 Fan ..... ..... .... ..... .... ......... .... .....2
2.2.2 Supply air filter ..... ..... .... ......... ...2
2.2.3 Pressure guard filters ........ .... ..... .2
2.2.4 Temperature sensor. ..... .... ..... .... .2
2.3 Heating battery.. .... ......... .... ..... .... ..... .... .3
2.3.1 Water heating battery . ..... .... .......3
2.3.2 Electrical heater . .... ..... .... ......... ..3
2.4 Electrical connection box,
components. ..... .... ......... .... ..... .... ..... .... .4
3 Interface description .......... .... ..... .... .... . .... .... ....4
3.1 Control panel... .... ..... .... ......... .... ..... .... ...4
3.1.1 Operating the control
panel... .... ......... .... ..... .... .... . .... .5
4 Commissioning .... ......... .... ..... .... ..... .... ......... ...6
4.1 Before starting the system .... ..... .... ..... .... .6
4.2 Initial setup of the unit.... ......... .... ..... .... ...6
4.3 Menu overview ... ..... .... ......... .... ..... .... ...8
4.4 Temperature control possibilities ..... .... ....16
4.5 Free cooling .... . .... .... ..... .... ..... .... ..... .... 17
5 Maintenance.... .... ..... .... ......... .... ..... .... ..... .... 17
5.1 Changing air filters.... .... ..... .... ..... .... ...... 18
5.2 Checking the fan . .... ..... .... ......... .... ..... .. 19
5.3 Cleaning louvers and diffusers.. .... . .... .... .. 19
5.4 Checking the outdoor air intake .... . .... .... .. 19
5.5 Checking the duct system ... .... ..... .... ...... 19
5.6 Changing the internal battery... ..... .... ...... 20
6 Troubleshooting.. ......... .... ..... .... ..... .... ..... .... .. 21
6.1 Alarms... ......... .... ..... .... ..... .... ......... .... 22
7 Service .. ..... .... ..... .... ......... ......... .... ..... .... ....22
Contents
130323 | A002
Page 4
Page 5

1 Warnings

The following admonitions will be presented in the different sections of the document:
Danger
• Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury.
Warning
• Indicates a potentially hazardous situation that may result in minor or moderate injuries.
Caution
• Indicates a risk of damaging the product or prevent optimal operation.
Important
• This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
• Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Warnings
|
1
130323 | A002
Page 6
| Product description
2

2 Product description

2.1 Internal components

1
2
3
4 5
6
7 8
9
Filter, supply air
Fan, supply air
Heater, electrical or water
Electrical connection box Pressure guard filter
Air flow sensor (only EL units)
Outdoor air sensor Duct connection, outdoor air
Duct connection, supply air

2.2 Description internal components

2.2.1 Fan

The fan has external rotor motors of EC type which are steplessly controlled. It is possible to program the speed in 2 steps (normal/reduced) depending on the programming of the week schedule. The motor bearings are life time lubri­cated and maintenance free. It is possible to remove the fan for cleaning

2.2.2 Supply air filter

The filter is of bag filter type with filter quality ePM10 60% (M5). The filter need to be replaced when polluted. New fil­ter can be acquired from your installer or wholesaler.

2.2.3 Pressure guard filters

A pressure guard measures the differential pressure over the supply air filter. When the pressure drop reaches the set value an alarm is triggered in the main regulator. The differential pressure can be set between 40 and 300 Pa. The pres­sure switch is preset from factory to 240 Pa.

2.2.4 Temperature sensor

In Topvex SF the supply air sensor is delivered with the unit and is to be installed in the supply air duct externally from the unit. See Installation instructions for more detailed information.
The outdoor air sensor is mounted and wired inside the unit.
130323 | A002
Page 7
Product description |

2.3 Heating battery

Warning
• Although the mains power supply to the unit has been disconnected there is still risk for injury due to rotating parts that have not come to a complete standstill.
• Beware of sharp edges during maintenance. Use protective clothing.
• Observe that the heating battery can be hot although the power is switched of. Risk of burning.

2.3.1 Water heating battery

In units with built in water heating battery the hot water coil is located next to the supply air connection. The hot water coil can be either HWL (hot water coil, low power) or HWH (hot water coil, high power). The coil material is copper pip­ing with a frame of galvanized sheet steel and aluminium fins. The coil is equipped with venting and immersion sensor for frost protection.

2.3.2 Electrical heater

In units with built in electrical heater the heating rods are located after the supply air fan in the airflow direction. The material is stainless steel. The electric heating coil has both automatic and manual overheating protection.
The manual overheat protection is reset by pressing the button, marked RESET figure 1. The power demand of the elec­trical heating coil is controlled by the main regulator.
3
The main regulator controls the heat steplessly by a TTC triac control according to the desired supply/extract or room air temperature that is set in the control panel.
Topvex SF units equipped with Electrical heater performs 3 minutes of re-cooling after the unit have been turned of.
Note:
• If activating the fire alarm when the heater is switched on, the fan stops immediate without re-cooling, this can cause the overheating protection to trip. See figure 1 where to reset.
• Reset of the overheat protection must be done by an authorized electrician.
• An all pole circuit breaker (safety switch) must precede the unit.
130323 | A002
Page 8
| Interface description
4

2.4 Electrical connection box, components

Danger
• Make sure that the mains power supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
Caution
Be careful so the hatch doesn’t fall down if the unit is false ceiling mounted.
Topvex SF is equipped with a built in regulator and internal wiring.
Loosen the 4 screws to remove the hatch to the electrical connection box.
Fig. 1 Connection box
Position Description
1
2
3
4
5
6
7 8
Regulator E283 WEB
Transformer 230/24V AC
Terminals for internal and external components
Terminals for internal wiring
Terminals for mains power supply to the unit
Contactor (K2) On/Off Pump control water (HW units only, not present in EL-units)
Automatic fuse Reset for overheat protection (only EL units)

3 Interface description

3.1 Control panel

The SCP control panel is delivered with a 10 m cable (up to 100 m can be used) that is connected to the panel and with a fast coupling contact, connected to the Topvex unit. The contact is connected to the Corrigo controller in the electrical connection box. The cable can be unscrewed in the back of the control panel (figure 2).
130323 | A002
Page 9

3.1.1 Operating the control panel

Fig. 2 The control panel
Interface description |
5
Position
1 2
3
4
5
6
7
8 9
10
11 12
Explanation
Alarm button: Gives access to the alarm list. Alarm LED: Indicates alarm by flashing red light.
Write LED: Indicates by flashing yellow light that parameters can be set or changed.
OK button: Press this button to be able to change or set parameters whenever possible. Also used to move between changeable parameters in one dialogue window frame.
Cancel button: Used to abort a change and return to the initial setting.
Right/Left & Up/Down buttons: Used to move up, down, left & right in the menu tree. Up/Down buttons are also used to increase or decrease values when setting or changing parameters.
Mounting holes.
Connection block. Connection to brown cable. Connection to yellow cable.
Connection to white cable. Connection to black cable.
130323 | A002
Page 10
Commissioning
|
6

4 Commissioning

4.1 Before starting the system

When the installation is finished, check that:
• The unit is installed in accordance with the installation instructions
• The unit is correctly wired
• Mufflers are installed and that the duct system is correctly connected to the unit
• Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vac­uum system exhaust or similar)
• All external equipment are connected
• The following data is available:
• Intended configuration, for example temperature control functions, fan control, external control functions etc.
• How the unit is supposed to operate according to a weekly schedule (normal and reduced speed)

4.2 Initial setup of the unit

On the first start-up, the controller will start a special program for setting language, supply air temp set point, Time & date and week schedule for normal speed. Use the “OK” button to move between changeable parameters and the UP/ DOWN arrows to see the displayed alternatives. Confirm by pressing “OK” once more. Move on down in the menu structure by use of the UP/DOWN arrows.
The following will be displayed:
1 Select language by pressing “OK” and then move be-
tween the alternatives with the UP/DOWN buttons. Confirm by pressing “OK”. Move to the next level by pressing the “DOWN” button.
2 Set the supply air set point. Default is 18°C (logon to
service level needed, code 2222, to change default setting)
3 Check and make sure that correct time and date is dis-
played, if not change the settings
4 Set the week schedule for how it’s intended for the
unit to operate at normal speed during Monday to Fri­day. It’s possible to set 2 periods per day.
5 Set the week schedule for how it’s intended for the
unit to operate at normal speed during Saturdays and holidays. It’s possible to set 2 periods per day.
Choose Language English
Supply air temp
Actual:.... ºC
Setp.: 18 ºC
Time: 12.46 Date: 2010–03–12 Weekday: Friday
Normal speed Monday → Friday Per 1: 07:00 – 16:00 Per 2: 00:00 – 00:00
Normal speed Saturday → Holiday Per 1: 07:00 – 16:00 Per 2: 00:00 – 00:00
6 Set the week schedule for how it’s intended for the
unit to operate at reduced speed during Monday to Friday. It’s possible to set 2 periods per day. Normal speed inactivates reduced speed.
7 Set the week schedule for how it’s intended for the
unit to operate at reduced speed during Saturdays and holidays. It’s possible to set 2 periods per day.
Reduced speed Monday → Friday Per 1: 00:00 – 24:00 Per 2: 00:00 – 00:00
Reduced speed Saturday → Holiday Per 1: 00:00 – 24:00 Per 2: 00:00 – 00:00
130323 | A002
Page 11
Commissioning
|
7
8 Select “Yes” or “No”
After finishing the setup the menu system for “Operator level” will be available.
See below menu overviews that display the available menus in the Operator level followed by the “Service level” manual.
To enter Service level use code 2222 in the “Access rights” menu. For operator level use code 1111.
To enter Administrator level use code 3333 in the “Configuration menu”.
End Wizard No
Note:
To perform more advanced settings please see the separate “General Commissioning Record” on www. systemair.com, online catalogue
130323 | A002
Page 12
Commissioning
|
8

4.3 Menu overview

Below menu overview shows both the Operator, Service and Administrator level. The overview of the parts unique to the levels in below table are marked with different background color.
Note:
See Corrigo manual-Ventilation application for more information and additional configuration alternatives.
To logon to Operator level use code 1111 under Access rights.
Main menu item
Topvex SF03 HW 2015–03–15 09:00 System:Normal run Sp:22.0 Act: ºC
→ Running mode → Running mode Running mode
To logon to Service level use code 2222 under Access rights.
Sub-menu item 1 Sub-menu item 2 Explanations
Auto
Op time SAF: 0.0 h
Selected functions
Alarm events
Input/Output
Control function Supply air control Fan control Frequency manual control
Heating: Water Exchanger: Not conne Cooling: Water
Free cool active:No
Support control Active: No CO2/VOC active Never
Fire damper function Not active Operation when alarm Stopped
Frost protection Active Cooling recovery No
External set point Not active
AI
To logon to Administrator level use code 3333 under Access rights.
Start screen headline Can be set to 5 different layouts (Changeable at “Administrator level” under the Configuration menu).
Set running mode to Auto,
Manual reduced run, Manual normal run or Off.
The time in hours that the motors have been operating SAF = Supply air fan
Type of air temperature control the unit is configured for.
Type of fan speed control the unit is configured for.
Type of heating selected.
Type of exchanger selected.
Type of cooling selected.
Status of the free cooling function.
Status of the support control function.
Status of the demand ventilation (CO2/VOC) function.
Status of the fire damper function when fire alarm is active.
Status of the frost protection function.
Status of the cooling recovery function.
Status of the external set point.
Alarm log list along with the time and date they occurred. Move down and up in the list by pressing ↑↓.
Status of the Analogue inputs.
130323 | A002
Page 13
Commissioning
|
9
Main menu item
Temperature
Air Control
Sub-menu item 1 Sub-menu item 2 Explanations
Outd temp: ºC Supply air temp Act.: ºC Setp: 18ºC
DI
UI
AO
DO
Supply air temp. 18° C
Neutral zone 0.0 °C
Status of the Digital inputs.
Status of Universal Analogue inputs or Universal Digital inputs.
Status of the Analogue outputs.
Status of the Digital outputs.
Actual outdoor air temperature. Actual supply air temperature.
Choose setpoint value.
A neutral zone can be set around the setpoint value.
Note:
See Corrigo manual­Ventilation application for more information.
Frost protection Actual: ºC
Frequency control manual SAF Output: %
Frequency control manual SAF Output 1/1: 75% Output 1/2: 50%
Outdoor comp. output. –20°C = 0 % 0°C = 0 % Act. Comp: 0 %
Pressure control SAF Actual: Pa Setp.: Pa
Pressure control SAF Setp 1/1: 500 Pa Setp 1/2: 250 Pa
Outdoor comp.Setp. 1 —20°C = 0 Pa 10°C = 0 Pa Act. Comp: 0 Pa
Actual water temperature in the water heating battery. (Only visible
for HW units).
Frequency control manual. Fans controlled by setting fixed output signal.
This menu option becomes visible if the unit is configured for "Manual frequency”.
The actual external pressure and set point for the supply air fan.
Only visible if the unit is configured for "Pressure control" (VAV accessory).
Set the external pressure set point for normal speed (1/1) and reduced speed (1/2) for the supply air fan.
Set the SAF pressure compensation for the settable outdoor temperature. The outdoor compensation is linear and is set using two parameter pairs which give the value of the compensation at two different outdoor temperatures. The compensation can be positive or negative. Shows the actual pressure compensation.
130323 | A002
Page 14
10
Commissioning
|
Main menu item
Time settings
Sub-menu item 1 Sub-menu item 2 Explanations
Time/Date
Timer Normal
Speed
Timer Reduced Speed
Extended running
Holidays Holidays (mm:dd)
Normal Speed Monday Per 1: 07:00–16:00 Per 2: 00:00–00:00 Normal Speed Monday-Friday Per 1: 07:00–16:00 Per 2: 00:00–00:00
Reduced speed Monday Per 1: 00:00–24:00 Per 2: 00:00–00:00 Reduced Speed Monday-Friday Per 1: 00:00–24:00 Per 2: 00:00–00:00
Extended running 60 min Time in ext. running 0 min
1:01–01 — 01–02 2:01–01 — 01–01 3:01–01 — 01–01
Set correct time and date. Set 00:00 - 24:00 for continuous running. Setting 00:00 - 00:00 inactivates the period (stops the unit). Normal speed overrides Reduced speed i.e. Normal speed 07:00 - 16:00 and Reduced speed 00:00 - 24:00 runs the unit on Normal speed 07:00 - 16:00 and Reduced speed the rest of the day.
Set week schedule Monday to Sunday, Monday-Friday+ Holiday for normal speed. Possible to set 2 periods per day. Note the settings in the commissioning record.
Set week schedule Monday to Sunday, Monday-Friday + Holiday for reduced speed. Possible to set 2 periods per day. Note the settings in the commissioning record.
Set the time for extended running. Use digital input to force the unit to start or increase to normal running even if the actual mode is Off or Reduced. If the running time is set to 0 the unit only runs as long as the digital input is closed. The time the extended running is active is monitored in "Time in ext. Running". It's also possible to set a time here as well in order to shorten the initial set period.
Set up to 24 separate possible holiday periods for a full year. A holiday period can be any number of consecutive days from one and upwards. The dates are in the format: MM: DD. When the current date falls within a holiday period, the scheduler will use the settings for the weekday “Holiday”.
130323 | A002
Page 15
Commissioning
|
11
Main menu item
Manual/Auto
Sub-menu item 1 Sub-menu item 2 Explanations
In this menu the running mode of all the configured output signals and a number of control functions can be manually controlled. The supply air controller's output signal can be manually set (Manual/Auto) to any value between 0 and 100%. The temperature output signals will change accordingly if they are in Auto mode. It is also possible to manually control each of the temperature output signals individually.
Since leaving any of the outputs in manual control will disrupt the normal control, an alarm will be generated as soon as any output is set to a manual mode.
Supply temp. contr. Auto Manual set: 0.0
SAF: Auto Manual set: 0.0
Heating Auto Manual set: 100.0
Cooling Auto Manual set: 0.0
Set the supply air temperature controller to Auto, Manual or Off. Set the output signal between 0­100%. The outputs Y1, Y2 and Y3, if in Auto-mode, will follow the signal according to the set split values.
Set the output signal for SAF (supply air fan) to:Auto,
Manual,1/2–speed or 1/1– speed.
Set the heating to Auto, Manual or Off.
Set the manual output 0-100%.
Set the cooling to Auto, Manual or
Off
Set the manual output 0-100%
P1–Heating Auto
P1–Cooling Auto
Fire damper Auto
Outdoor air damper Auto
Exhaust air damper Auto
Note:
Needs to be activated in order to be visible here
Set the pump control for the heating coil to Auto, On or Off
Set the pump control for the cooling coil to Auto, On or Off
Set the Fire damper to Auto, Open or Close
Note:
Needs to be activated in order to be visible here Configuration of fire damper functions are made at
Administrator level
Set the Outdoor air damper to
Auto, Open or Close
Set the Exhaust air damper to Auto, Open or Close
130323 | A002
Page 16
12
Commissioning
|
Main menu item
Settings
Sub-menu item 1 Sub-menu item 2 Explanations
Extra sequence Y5 Auto Manual set: 0.0
Motor control1 Auto Motor control2 Auto
Control temp
Supply air control P-band: 33.0°C I-time: 100.0 sec
Set the Extra sequence to Auto, Manual or Off
Not used in default setting.
Motor control
Note:
See Corrigo manual­Ventilation application for more information.
In this menu group the settings for the activated functions are available. Depending on which choices have been made in the configuration menu some of the possible alternatives may not be displayed.
Set P-band and I-time for the Supply air control function
Note:
See Corrigo manual­Ventilation application for more information.
Control
pressure
Shutdown mode P-band: 100.0°C I-time: 100.0 sec
Frost protection Active Setp shutdown:
25.0°C P-band active: 5.0° C
Fast stop at frost protection alarm Yes
Sequency with frost protection Y1–Heating
Pressure control SAF P-band: 500.0 m³/h I-time: 60.0 sec Min. output: 0%
Set P-band and I-time for the Shutdown function
Note:
See Corrigo manual­Ventilation application for more information.
Status for frost protection. When running mode switched to "Off". Shutdown controller will control the heating output to maintain a constant settable temperature at the frost protection sensor for the hot water coil. If frost protection temperature falls below Frost protection Alarm level + settable P-Band for frost protection, it will rise the internal signal and force the heating valve to open to avoid freeze-up of hot water coil.
Set the fast stop of the unit in case of frost protection alarm to Yes or No.
Frost protection control. Is available for Y1 heating, Y4 extra sequenceor on both Y1 and Y4.
Set P-band, I-time and Min. output for the supply air.
Only shown if VAV accessory is used.
130323 | A002
Page 17
Commissioning
|
13
Main menu item
Darker gray area, log in to “Administrator level” code 3333
Configuration
Sub-menu item 1 Sub-menu item 2 Explanations
Alarm settings Alarm limits
Alarm delays
Restore alarm
Restore factory settings: No Restore user settings: No
Save user settings No
Inputs/Outputs
Sensor settings
Control function
Fan control Frequency manual
Extra sequency Y4
Extra sequency Y5
Heating
Cooling
Pump control
Control function Mode: Supply air control
Mode extra sequence Y4 Active w cool recov
P1–Heating P1–Cooling
Set the alarm limits and allowed deviations for the different functions
Set the alarm delays and allowed deviation delays for the different functions
Reset the service alarm (filter alarm).
In this menu, it is possible to restore all parameters to their factory settings or to the user settings they were saved as earlier. Select Yes or No
The current configuration can be saved in a separate memory area and can later be restored using the previous menu, Restore user settings. Select Yes or No
Setup for inputs and outputs.
Setup of sensor types and control range.
Set type of temperature control function you want the unit to operate under. Choose between
Supply air control, Outdoor comp. supply
More information in chapter 4.4
*Set type of fan control function you want the unit to operate under. Choose between Pressure
control (option accessory), Frequency manual.
Can be configured to one of the following alternatives:
Active, Active with cooling recovery, Active with enthalpy control and Active with both cooling recovery and enthalpy control.
Extra sequence Y5 can be configured to Active or Not active.
Type of heater
Type of cooler
Set parameters for pump control. If, for any of the control circuits, no output is configured for pump control these settings will be ignored.
130323 | A002
Page 18
14
Commissioning
|
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
Free cooling Free cool active: No
Outd. temp activation 22°C
Outd. temp night High: 18.0°C Low: 10.0°C Room temp min. 18°C
Hour for start/stop Free cooling Start: 0 Stop: 7
Time to block heat output after Free cooling 60 min
Fan output when free cooling SAF: 0 % EAF: 0 %
Outdoor sensor placed in intake channel (intake duct) No
Support control Support control
Active: No EAF running during Support contr.: Yes
Min. run time for support ctrl: 60 min
Set free cooling active toYes or No. Set the lower outdoor day
temperature limit for the activation of the free cooling function. The temperature of the previous day needs to be over the set temperature in order activate the free cooling function.
Set the upper outdoor night temperature limit for the activation of the free cooling function. Set the lower outdoor night temperature limit for the activation of the free cooling function. Set the lower room temperature limit. The temperature needs to be above this value for the free cooling function to stay active. If no room sensor are connected extract air is valid.
Set the start and stop time for the free cooling function For example Start: 0 and
Stop: 6
means that the free cooling sequence is active between 00.00 and 06.00 h.
Set the delay in minutes from the time where the free cooling sequence has stopped until a possible heating sequence is initiated, i.e. how long a cooler room temperature than set temperature can be accepted
Set the fan speed in percentage of the normal speed for each fan individually during the free cooling sequence
Set if the outdoor sensor is placed in the intake duct or not. Choose between No and Yes Preset is No.
When using the control function room control or extract air temperature control, it is possible to utilize support-heating and/or support-cooling. Minimum running time is settable 0…720 minutes (factory setting 60 minutes). Choose between “Active: Yes or No”. (For start and stop temperatures see the "Temperature" menu)
Set the minimum running time in minutes for support control
130323 | A002
Page 19
Commissioning
|
15
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
CO2/VOC Control CO2/VOC active
Never Type: Fan Min. time: 20 min
Activation level 1/2–speed: 800 ppm 1/1–speed: 1000 ppm diff: 160 ppm
Sequency with CO2 comtrol Y2 exchanger
Fire Function
External setpoint
Type of actuator
Motor control Motor control1
Fire damper function Not active Operation when alarm Stopped
Fire alarm input Normally open Damper exercise
No
External setpoint Not active Min setp.: 12.0°C Max setp.: 30.0°C
Run mode when unit run (/DI) Stop delay 120s
Motor control2 Run mode when unit run (/DI) Stop delay 0s
In applications with varying occupancy the fan speeds can be controlled by the air quality as measured by a CO2/VOC-sensor. See Corrigo manual for further explanation
Set active to Never, Always or If time channel off.
Set what should be regulated. Select type Fan Set the min. time the unit is activated by the CO2/VOC demand function
Set the activation level at 1/2 speed Set the activation level at 1/1 speed Set allowed diff. value
CO2/VOC control can be used with mixing dampers. Select for use on Y2, Y4 or on both outputs.
The fire alarm input can be configured as Not active,
Normally closed or Normally open.
Choose operation when alarm is active Stopped, Continuous
run, Normal run, Only SAF, or Only EAF
Fire alarm input can be configured to normally open or normally closed. Fire alarm input is also available to be configure from digital inputs. Note the risk of a twice changed signal can create an undesired function. Activate the fire damper exercising, choose between No, Yes unit running or Yes unit stopped. Set the parameters for damper exercise in the submenu.
An external setpoint device can be connected. The setpoint device must follow the PT1000 resistance curve. The setting range can be restricted.
Type of control signal for actuators. Choose between 0-10V, 2-10V, 10­2V, 10-0V.
Settings running conditions external fan.
130323 | A002
Page 20
16
Commissioning
|
Main menu item
Access rights
Sub-menu item 1 Sub-menu item 2 Explanations
Alarm settings
Communication
Log on Log on
Log off Log off?
Change password Change password for
Alarm no(1–115): 1 Run Error Supply Air
Function Port1 Slave
→ Function Port2 Slave
TCP/IP
Enter password xxxx Actual level: None
No Actual level:None
level:None New password xxxx
Set functionality and adjust communication settings Slave,
Expansion unit, Freq conv/ Press tran, External display, Exp and freq conv or Exp and ext display.
Log on to service level by entering a 4-digit code. After reaching the desired level go back with “LEFT” arrow (press 2 times) on the control panel. Standard code from factory to enter service level is 2222. Back to operator level: 1111. To enter Admin level code: 3333.
Log off from Administrator level by changing Noto Yes with the "OK" and "UP/DOWN" buttons Automatic logoff after 6 minutes of inactivity.
Set a new password for the level of your choice. Can only be done once logged on to the service level.

4.4 Temperature control possibilities

Type of Control Temperature sensor placement
Supply air temperature control: The supply air temperature sensor is
placed in the supply air duct approximately 3m after the unit.
Supply air temperature control with outdoor air temperature compensation:
Extract air temperature control: 2 temperature sensors are needed.
2 temperature sensors are needed. The outdoor air sensor is mounted and wired inside the unit. The supply air temp sensor is placed in the supply air duct approximately 3m after the unit.
The extract air temp sensor is placed in the extract air duct or in the room if the building lacks extract air ducting. The supply air temp sensor is placed in the supply air duct approximately 3m after the unit.
Description/function
Controls the temperature of the supply air
Compensates for low outdoor temperatures by increasing the supply air temperature with an optional value to avoid sudden temperature drops in the interior of the building. Preset is + 20K temperature increase at -20°C outdoor temperature and +15K increase at 0°C outdoor temperature.
Set the extract air temperature (preset is +18°C). To ensure that the supply air temperature produced by the unit is not too low or too high, a minimum and maximum supply air temperature value can be set by the installer/operator. Preset minimum temperature is +12°C and maximum temperature is +30°C.
130323 | A002
Page 21
Maintenance
|

4.5 Free cooling

This function is used during the warm period to save energy by using cold outdoor air, e.g. during night time, to cool down the building.
Note:
The following is only valid if the free cooling function is set to Active in the program menu. In order for the free cooling function to work, a total of 3 temperature sensors (outdoor, supply and extract/ room) are required.
Free cooling is only activated when the following starting conditions are met.
Starting conditions:
• Less than 4 days have passed since the unit was last in running mode
• The outdoor temperature during the previous running period exceeded a set limit (+22°C)
• It is between 00:00 and 07:00:00 in the day (settable)
• The timer outputs for normal speed, Extended running normal and External stop are Off
• A time channel will be On sometime during the recently started 24 hours. The unit checks the night temperature (indoor and outdoor temperature) during 3 minutes at the set starting hour when
the fans are started so that the sensors can perform a temperature measurement.
If above conditions are met the free cooling function is started, if not the unit goes back to OFF position.
17
If the outdoor sensor is not located in the outdoor air inlet duct and a room sensor has been selected, the unit will not start free cooling as long as all the temperatures are not within the start and stop temperature intervals.
Stop conditions:
• Outdoor temp above the set max value (+18°C) or below the set min value (condensation risk, +10°C)
• The room temp/extract air temp is below the set stop value (+18°C)
• One of the timer outputs for normal speed, External stop or Extended running normal is On
• The time has past 07:00:00. When free cooling is active, the fans run at normal speed or the set value for pressure/flow control and the digital out-
put Free cooling is active. The outputs Y1-Heating and Y3-Cooling are shut down. After free cooling has been activated, the heating output is blocked for 60 minutes (configurable).

5 Maintenance

Danger
• Make sure that the mains power supply to the unit is disconnected before performing any maintenance or electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations.
Warning
In order to avoid electrical shock, fire or other damage that might occur in connection with faulty use and operation of the unit, it is important to consider the following:
• The system must be installed according to the installation instructions.
• Insulate mains power supply before service or cleaning of the heat recovery unit.
• Make sure the filter is mounted in its place before running the system.
• Maintenance must be performed according to the instructions.
130323 | A002
Caution
Make sure that loosened parts during maintenance doesn’t fall down and causing injury.
Page 22
Maintenance
|
18

5.1 Changing air filters

The bag filter cannot be cleaned and must be changed when necessary. New filters can be ordered from Systemair. Op­eration time between filter changes depends on the air pollution at the installation site. A differential pressure switch indicates when it’s time to change the filters. This will trigger an alarm in the control panel.
Re-set the alarm after filter change, see Alarm settings, Alarm limits, Service alarm in the Control panel.
Initial pressure drop for Topvex SF02 to Topvex SF03 is approx. 50 Pa and 60 Pa for Topvex SF04 to Topvex SF12.
130323 | A002
Page 23
Maintenance
|

5.2 Checking the fan

Even if the required maintenance, such as changing of filters is carried out, dust and grease may slowly build up inside the fan. This will reduce the efficiency.
The fan may be cleaned with a cloth or a soft brush. Do not use water. White spirit can be used to remove accumula­tions which are otherwise difficult to remove. Allow drying properly before use.
The fan can easily be taken out, by removing 4 screws (pos 1) shown in figure 3 and disconnecting the fast couplings to the electric wires.
19
Fig. 3

5.3 Cleaning louvers and diffusers

Check the louvers and diffusers at least twice a year, and clean if necessary.
The system supplies fresh air to the building via the duct system and diffusers/louvers. Diffusers and louvers are mounted in ceilings/walls.
Remove diffusers and louvers and wash in hot soapy water as required. (Diffusers/louvers must be put back with their original settings and positions in order not to unbalance the system).

5.4 Checking the outdoor air intake

Leaves and pollution could plug up the air intake grille and reduce the capacity.
Check the air intake grille at least twice a year, and clean if necessary.

5.5 Checking the duct system

Dust and grease settlements may build up in the duct system even if filters are changed regularly. This will reduce the efficiency of the installation. The duct runs should therefore be cleaned/changed when necessary.
Steel ducts can be cleaned by pulling a brush soaked in hot soapy water through the duct via diffuser/louver openings or special inspection hatches in the duct system (if fitted).
Note:
In addition the roof cowl must be checked once a year and cleaned as necessary.
130323 | A002
Page 24
Maintenance
|
20

5.6 Changing the internal battery

Note:
This procedure requires knowledge of proper ESD protection; i.e. an earthed wristband must be used!
When the alarm ”Internal Battery” is activated and the battery LED lights up red, the battery for backup of program memory and real-time clock has become too weak. The battery is replaced as described below. A backup capacitor saves the memory and keeps the clock running for at least 10 minutes after the power supply is removed. Therefore, if the battery replacement takes less than 10 minutes, there will be no need to reload the program, and the clock will continue to run normally.
The replacement battery must be of the type CR2032.
1 Remove the cover by pressing down the locking tor-
ques at the edge of the cover using a small screw­driver, and at the same time pulling the edges outwards.
2 Grip the battery firmly with your fingers and lift it up-
wards until it rises from its holder. Press the new battery firmly down into place. Note that to preserve correct polarity, the battery can only be inserted the “right way round”.
130323 | A002
Page 25
Troubleshooting |

6 Troubleshooting

Should problems occur, please check or correct the following before contacting your service representative.
Always check if there are any alarms active in the control panel.
1. The fan do not start
• Check that the fuses are not defect.
• Check the settings in the control panel (time, week schedule, auto, manual operating etc.).
• Check if there are any alarm messages.
2. Reduced airflow
• Check the settings of Normal and reduced fan speed.
• Check that the outdoor air damper, if used, opens.
• Change of filter required?
• Cleaning of diffusers/louvers required?
• Cleaning of fan required?
• Is roof unit/air intake clogged?
• Duct system. Check visible duct runs for damage and/or build-up of dust/pollution.
• Check diffuser/louver openings.
3. Cold supply air
• Check set supply air temperature on the control panel.
• Check if overheating thermostat is still alert. If necessary, reset by pressing the button, marked RESET, figure 1).
• Check if the fan thermo switch has tripped, shows as Fan alarm in the control panel. If necessary, reset it.
4. Fluctuating supply air temperature
• Check that the supply air temperature sensor is assembled approximately 3 meters from the heater.
5. Noise/vibrations
• Clean fan impeller.
21
130323 | A002
Page 26
Service
230/400V 25 A 50Hz
Systemair Sverige AB Industrivägen 3 SE-73930 Skinnskatteberg Sweden
4016 W IP23 225kg
Ver. A
Serial. no: 1234/567891-0001/140214
Topvex XXXX
16kW 16kW
www.systemair.com
2 3 4
5
|
22

6.1 Alarms

The alarm button (pos.1, figure 2) opens the alarm queue. When pressing this button active and non-acknowledged alarms will be displayed in the menu window. The alarm-LED (pos.2, figure 2) is flashing if there are non-acknowledged alarms and steady if the alarms are still active but have been acknowledged.
If there are multiple alarms, use UP/DOWN to move between them. An alarm can be acknowledged or blocked by using OK and UP/DOWN. To abort and go back to start menu press cancel and then press LEFT.

7 Service

Before calling your service representative, make a note of the specification and production number from the data plate on the unit.
1. Item number
2. Production order number
3. Consecutive number
4. Production date
5. Product code (product specification)
130323 | A002
Page 27
130323 | A002
Page 28
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden
Phone +46 222 440 00 Fax +46 222 440 99
www.systemair.com
Topvex SF02-S12 · Operation and Maintenance Instructions · 130323 · en_GB · 02-10-2018 · A002
Loading...