SystemAir Topvex FR03, Topvex FR11, Topvex FR06, Topvex FR08 Operation And Maintenance Instructions

Page 1
TopvexFR03,FR06,FR08,FR11
CompactAirHandlingUnit
OperationandMaintenanceInstructions
Documentinoriginallanguage
129451-EN_GB
24-06-2015A001
Page 2
Contents
1Warnings...................................................................................................................................1
2.1DescriptionofInternalcomponents....................................................................................3
2.1.1SupplyandExtractairFans.....................................................................................3
2.1.2SupplyandExtractairFilters...................................................................................3
2.1.3HeatExchanger......................................................................................................4
2.1.4T emperaturesensors...............................................................................................4
2.1.5Waterheatingbattery..............................................................................................4
2.1.6ElectricalHeater.....................................................................................................4
2.2InternalcomponentsElectricalconnectionbox...................................................................5
3InterfaceDescription..................................................................................................................5
3.1ControlPanel...................................................................................................................5
3.1.1Operatingthecontrolpanel......................................................................................6
4Commissioning..........................................................................................................................7
4.1BeforeStartingtheSystem...............................................................................................7
4.2Initialsetupoftheunit.......................................................................................................7
4.3Menuoverview.................................................................................................................9
4.4Freecoolingdescription....................................................................................................24
5Maintenance..............................................................................................................................25
5.1Important.........................................................................................................................25
5.2Maintenanceintervals.......................................................................................................25
5.3Maintenanceinstructions..................................................................................................26
5.3.1ChangingSupply/Extractairlter.............................................................................26
5.3.2Checkingtheheatexchanger..................................................................................27
5.3.3Checkingthefans...................................................................................................28
5.3.4Cleaningextractlouvresandinletdiffusers...............................................................29
5.3.5Checkingtheoutdoorairintake................................................................................29
5.3.6Checkingtheductsystem........................................................................................29
5.3.7ChangingtheInternalBattery..................................................................................29
5.4Troubleshooting...............................................................................................................30
5.4.1Alarms...................................................................................................................30
6Service......................................................................................................................................31
Page 3

1Warnings

Thefollowingadmonitionswillbepresentedinthedifferentsectionsofthedocument.
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith localrulesandregulations.
Warning
•AlthoughtheMainssupplytotheunithasbeendisconnectedthereisstillriskforinjuryduetorotating partsthathavenotcometoacompletestandstill.
•Bewareofsharpedgesduringmaintenance.Useprotectiveclothing.
•Thisproductisnotintendedtobeusedbychildrenorpeoplewithreducedphysicalormentalability orlackofexperienceandknowledge,ifnoinstructionconcerningtheusehasbeengivenbythe personresponsiblefortheirsafetyorthatthispersonissupervisingtheoperation.Childrenshouldbe supervisedsothattheycannotplaywiththeproduct.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
1
SystemairSverigeAB
Page 4

2ProductDescription

Fig.1ComponentsELunits
Fig.2ComponentsHWunits(incaseofinstalledwaterheatingbattery)
Table1:ComponentdescriptionsELandHWunits
PositionDescription
1Fansupplyair.
2Fanextractair.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
2
SystemairSverigeAB
Page 5
ComponentdescriptionsELandHWunitscont'd
PositionDescription
3Filterextractair.
4Filteroutdoorair.
5
6Rotormotor.
7
8Re-heaterbattery,electricorwatercoil.
9
10
11
12
13Electricalconnectionbox.
14Mountingbrackets.
15
Heatexchanger.
Rotorbelt.
Resetbutton,manualoverheatprotection(onlyunitswithelectricalheater).
Pressureguardforlter.
Pressuretransmitterforfan.
Rotationguardforheatexchanger.
Rotorcontrol(locationdependingonsizeofunit)

2.1DescriptionofInternalcomponents

2.1.1SupplyandExtractairFans

ThefanshaveexternalrotormotorsofECtypewhichcanbesteplesslycontrolledindividually0–100%.It ispossibletoprogramthespeedin2steps(normal/reduced)dependingontheprogrammingoftheweek schedule.Themotorbearingsarelifetimelubricatedandmaintenancefree.Itispossibletoremovethe fansforcleaning(chapter5).
2.1.1.1PressuretransmitterFans
2pressuretransmittersmaintaintheairowataconstantlevelbymeasuringthedifferentialpressureover theinletconeofthefanimpellers(pos.11gure1andgure2)).Thepressuretransmittersareinstalled fromfactoryinallCAVunits.V AVcontrolofthefansisavailableasanaccessory .TheVAVaccessory kitincludestwopressuretransmitters,tubes,electricalcablesandinstructiononhowtoconnecttothe airhandlingunitandset-upthecontroller.See“Installationinstructions”formoreinformationconcerning VAVinstallations.

2.1.2SupplyandExtractairFilters

TheltersareofbagltertypewithlterqualityF7forthesupplyairlterandM5fortheextractairlter. Theltersneedtobereplacedwhenpolluted.Newlterscanbeacquiredfromyourinstallerorwholesaler.
2.1.2.1Pressureguardforlters
Apressureguardmeasuresthedifferentialpressureoverthesupplyandextractairlters(pos.10gure1 andgure2).Whenthepressuredropreachesapresetvalueanalarmistriggeredinthemainregulator. Thealarmvalueissetaccordingtorecommendationsforthefactorymountedlters.Itispossibletoadapt settingstospecicinstallationsandltertypes,seeAlarmsettingsinchapter4.3.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
3
SystemairSverigeAB
Page 6

2.1.3HeatExchanger

TopvexFRmodelsareequippedwithahighlyefcient,beltdriven,rotatingheatexchanger.Required supplyairtemperatureisthereforenormallymaintainedwithoutaddingadditionalheat.Theoperationof theheatexchangerisautomaticanddependsonthesettemperature.
Theheatexchangerisremovableforcleaningandmaintenance(chapter5).
2.1.3.1Rotormotor
Therotormotordrivestheexchangerrotorwithaninnitelyrpmaslongasthereisaheatdemand.The motoriscontrolledbyananalogue0-10Vcontrolsignal(pos.6gure1andgure2).
2.1.3.2Rotationguard
Asensorregisterstherotationoftheheatexchangerrotor.It’sconnectedtothemainregulatorwhich givesanalarmiftherotorstopswhilethereisaheatdemand(pos.12gure1andgure2).

2.1.4Temperaturesensors

4temperaturesensors(PT1000)areincludedintheunitfromfactory.Thesensorsareasfollows:
•Supplyairsensor
•Extractairsensor
•Outdoorairsensor
•Efciencytemperaturesensor
InT opvexFR03–11alltemperaturesensorsaremountedandwiredinsidetheunitexceptforthesupplyair sensor,whichislooselydeliveredwiththeunitandneedstobeinstalledinthesupplyairductexternally fromtheunit.SeeInstallationinstructionsformoreinformation.

2.1.5Waterheatingbattery

Inunitswithbuiltinwaterheatingbatterythehotwatercoilislocatednexttothesupplyairconnection. ThehotwatercoilcanbeeitherHWL(hotwatercoil,lowpower)orHWH(hotwatercoil,highpower). Thecoilmaterialiscopperpipingwithaframeofgalvanizedsheetsteelandaluminiumns.Thecoilis equippedwithventingandimmersionsensorforfrostprotection.

2.1.6ElectricalHeater

Inunitswithbuiltinelectricalheatertheheatingrodsarelocatedafterthesupplyairfanintheairow direction.Thematerialisstainlesssteel.Theelectricalheatingbatteryhasbothautomaticandmanual overheatingprotection.Themanualoverheatprotectionisresetbypushingtheredbuttonontopofthe electricalheaterframe(pos.9gure1).Thepowerdemandoftheelectricheatingcoiliscontrolledby themainregulator,whichcontrolstheheatsteplesslybyaTTCtriaccontrolaccordingtothedesired supply/extractorroomairtemperaturethatissetinthecontrolpanel.
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith localrulesandregulations.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
4
SystemairSverigeAB
Page 7

2.2InternalcomponentsElectricalconnectionbox

Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith localrulesandregulations.
TopvexFR03–11areequippedwithabuiltinregulatorandinternalwiring(gure3).
Fig.3Electriccomponents

3InterfaceDescription

Positiondescription
1RegulatorE-28WEB.
2
3
4
5
6
7
8
9
10
Transformer230/24VAC.
Terminalsforinternalandexternal components.
Terminalsforinternalwiring.
Terminalsformainssupplytotheunit.
Contactor(K2)Pumpcontrolwater(HW unitsonly,notpresentinEL-units).
Automaticfuse.
Automaticfuseforheater.
Contactor(K3)ELheater.
TTCElheatercontrol.

3.1ControlPanel

TheSCPcontrolpanelisdeliveredwitha10mcable(upto100mcanbeused)thatisconnectedto thepanelandwithafastcouplingcontact,connectedtotheT opvexunit.Thecontactisconnectedto theCorrigocontrollerintheelectricalconnectionbox.Thecablecanbeunscrewedinthebackofthe controlpanel(gure4).
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
5
SystemairSverigeAB
Page 8

3.1.1Operatingthecontrolpanel

Fig.4Thecontrolpanel
Posi-
tion
1
2
3
4
5
6
7
8
9
10
11
12
Explanation
Alarmbutton:Givesaccesstothealarmlist.
AlarmLED:Indicatesalarmbyashingredlight.
WriteLED:Indicatesbyashingyellowlightthatparameterscanbesetorchanged.
OKbutton:Pressthisbuttontobeabletochangeorsetparameterswheneverpossible.Also usedtomovebetweenchangeableparametersinonedialoguewindowframe.
Cancelbutton:Usedtoabortachangeandreturntotheinitialsetting.
Right/Left&Up/Downbuttons:Usedtomoveup,down,left&rightinthemenutree.Up/Down buttonsarealsousedtoincreaseordecreasevalueswhensettingorchangingparameters.
Mountingholes.
Connectionblock.
Connectiontobrowncable.
Connectiontoyellowcable.
Connectiontowhitecable.
Connectiontoblackcable.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
6
SystemairSverigeAB
Page 9
3.1.1.1Navigatingthemenus
Thestartdisplay(thedisplaynormallyshown)isattherootofthemenutree.PressingDOWNwillmove youthroughthemenuoptions.UPwillmoveyoubackthroughtheoptions.Toenterahighermenulevel, useUPorDOWNtoplacethecursoratthemenuyouwishtoaccessandpressRIGHT.Ifyouhave sufcientlogonprivilegesthedisplaywillchangetothemenuyouhavechosen.
AteachleveltheremaybeseveralnewmenuswhichyoumovethroughusingUP/DOWN.Sometimes therearefurthersubmenuslinkedtoamenuormenuitem.Thisisindicatedbyanarrowsymbolatthe right-handsideofthedisplay.T oenteramenu,pressRIGHTagain.T ostepbacktopreviousmenu level,useLEFT .

4Commissioning

4.1BeforeStartingtheSystem

Whentheinstallationiscompleted,checkthat:
•Theunitisinstalledinaccordancewiththeinstallationinstructions.
•Theunitiscorrectlywired.
•Soundattenuatorsareinstalledandthattheductsystemiscorrectlyconnectedtotheunit.
•Outdoorairintakeispositionedwithsufcientdistancetopollutionsources(kitchenventilatorexhaust, centralvacuumsystemexhaustorsimilar).
•Allexternalequipmentareconnected.
•Thefollowingdataisavailable:
•Intendedconguration,forexampletemperaturecontrolfunctions,fancontrol,externalcontrol
functionsetc.
•Howtheunitissupposedtooperateaccordingtoaweeklyschedule(normalandreducedspeed).

4.2Initialsetupoftheunit

Ontherststart-up,thecontrollerwillstartaspecialprogramforsettinglanguage,supplyairtemp setpoint,Time&dateandweekschedulefornormalspeed.Usethe“OK”buttontomovebetween changeableparametersandtheUP/DOWNarrowstoseethedisplayedalternatives.Conrmbypressing “OK”oncemore.MoveondowninthemenustructurebyuseoftheUP/DOWNarrows.
Thefollowingwillbedisplayed:
1
Selectlanguagebypressing“OK”andthenmove betweenthealternativeswiththeUP/DOWN buttons.Conrmbypressing“OK”.Movetothe nextlevelbypressingthe“DOWN”button.
2
Showstheactualextractairtemperature
Setthesupplyairsetpoint.Defaultis18°C(logon toservicelevelneeded,code2222,tochange defaultsetting)
ChooseLanguage
English
Extractairtemp
Actual:....ºC
Setp.:18ºC
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
7
SystemairSverigeAB
Page 10
3
Checkandmakesurethatcorrecttimeanddateis displayed,ifnotchangethesettings
Time:12.46
Date:2010–03–12
Weekday:Friday
4
Settheweekscheduleforhowit’sintendedforthe unittooperateatnormalspeedduringMondayto Friday.It’spossibletoset2periodsperday .
5
Settheweekscheduleforhowit’sintendedforthe unittooperateatnormalspeedduringSaturdays andholidays.It’spossibletoset2periodsperday.
6
Settheweekscheduleforhowit’sintendedforthe unittooperateatreducedspeedduringMonday toFriday.It’spossibletoset2periodsperday. Normalspeedinactivatesreducedspeed.
7
Settheweekscheduleforhowit’sintendedforthe unittooperateatreducedspeedduringSaturdays andholidays.It’spossibletoset2periodsperday.
Normalspeed
Monday→Friday
Per1:07:00–16:00
Per2:00:00–00:00
Normalspeed
Saturday→Holiday
Per1:07:00–16:00
Per2:00:00–00:00
Reducedspeed
Monday→Friday
Per1:00:00–24:00
Per2:00:00–00:00
Reducedspeed
Saturday→Holiday
Per1:00:00–24:00
Per2:00:00–00:00
8
Select“Yes”or“No”
EndWizard
No
Afternishingthesetupthemenusystemfor“Operatorlevel”willbeavailable.
SeebelowmenuoverviewsthatdisplaytheavailablemenusintheOperatorlevelfollowedbythe “Servicelevel”manual.
ToenterServicelevelusecode2222inthe“Accessrights”menu.Foroperatorlevelusecode1 111.
ToenterAdministratorlevelusecode3333inthe“Congurationmenu”.
Note:
Toperformmoreadvancedsettingspleaseseetheseparate“GeneralCommissioningRecord”on www.systemair.com,onlinecatalogue
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
8
SystemairSverigeAB
Page 11

4.3Menuoverview

BelowmenuoverviewshowsboththeOperator,ServiceandAdministratorlevel.Theoverviewoftheparts uniquetothelevelsinbelowtablearemarkedwithdifferentbackgroundcolor.
TologontoOperator levelusecode 1111underAccess rights.
Mainmenuitem
FR03EL
2015–03–1509:00
System:Normalrun
Sp:22.0Act:ºC
→Runningmode→RunningmodeRunningmode
TologontoService levelusecode 2222underAccess rights.
Sub-menuitem1Sub-menuitem2
Auto
Optime
SAF:0.0h
EAF:0.0h
Selected functions
Controlfunction
Cascadeextract ctrl
Fancontrol
Flow/Pressure/ Manualcontrol
Heating:Water
Tologonto Administratorlevel usecode3333 underAccess rights.
Explanations
Startscreenheadline
Canbesetto5differentlayouts
(Changeableat“Administrator level”underthe Configurationmenu).
SetrunningmodetoAuto,
Manualreducedrun, ManualnormalrunorOff.
Thetimeinhoursthatthe motorshavebeenoperating
SAF=Supplyairfan
EAF=Extractairfan
Typeofairtemperaturecontrol theunitisconguredfor.
Typeoffanspeedcontrolthe unitisconguredfor.
Typeofheatingselected.
Exchanger: Plate/Rot.exc
Cooling:Not connect
Freecool active:No
Supportcontrol
Active:No
CO2/VOCactive
Never
Firedamper function
Notactive
Operationwhen alarm
Stopped
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
9
Typeofexchangerselected.
Typeofcoolingselected.
Statusofthefreecooling function.
Statusofthesupportcontrol function.
Statusofthedemandventilation (CO2/VOC)function.
Statusoftheredamper functionwhenrealarmis active.
SystemairSverigeAB
Page 12
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Frostprotection
Active
Explanations
Statusofthefrostprotection function.
Alarmevents
Input/Output
Coolingrecovery
Yes
Externalset point
Notactive
AI
AIexp3
DI
UI
UIexp3
Statusofthecoolingrecovery function.
Statusoftheexternalsetpoint.
Alarmloglistalongwiththetime anddatetheyoccurred.
Movedownandupinthelistby pressing↑↓.
StatusoftheAnalogueinputs.
StatusoftheAnalogueinputs forexpansionunit.
Onlyvisiblefor counter-/crossowunits withaconnectedpressure module
StatusoftheDigitalinputs.
StatusofUniversalAnalogue inputsorUniversalDigital inputs.
StatusoftheUniversalAnalogue inputsforexpansionunit.
Onlyvisiblefor counter-/crossowunits withaconnectedpressure module
AO
DO
Temperature
Extractair temp
Actual:ºC
Setp:22.0ºC
StatusoftheAnalogueoutputs.
StatusoftheDigitaloutputs.
Conguredtemperaturecontrol (defaultisExtractair temp).
Actualtemperatureinthe chosencontrolmode.
Set-pointtemperatureforthe chosencontrolmode.
Ifcascade control
Max/minsupply setp.
Max:30ºC
Setthemaximumandminimum allowedsupplyairtemperature incaseofcascadecontrol.
Logontoservicelevelneeded tochangesettings.
Min:14.0ºC
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
10
SystemairSverigeAB
Page 13
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Outdoortemp: ºC
Neutralzone0.0 °C
Supplyairtemp
Act.:ºC
Setp:18ºC
Explanations
Actualoutdoorairtemperature.
Actualsupplyairtemperature.
Calculatedsupplyairsetpoint. Theextractaircontrolleroutput signalgeneratesthesupplyair controller’ssetpointvalue.
Aneutralzonecanbeset aroundthesetpointvalue.
Note:
SeeCorrigomanual-Ventilation applicationformoreinformation.
Frost protection
Actual:ºC
Efficiency
exch.
Actual:%
Output exchanger
Actualwatertemperatureinthe waterheatingbattery.(Only visibleforHWunits).
Actualheatrecoveryefciency .
Thefunctioncalculatesthe heatexchangerstemperature efciencyin%whentheoutput signaltotheexchangeris higherthan5%andtheoutdoor temperatureislowerthan10°C.
Efciencycalculatedfromthe
Actual:100%
Outdoor,ExtractandEfciency airtemperature.
Whenthecontrolsignalis lowerthan5%ortheoutdoor temperatureishigherthan10° Cthedisplaywillshow0%.
Statusoftheexchangeroutput.
Tempfor calculation
Presentedtemperaturefor supplyairefciencycalculation.
efficiency Act:NaNC
AirControl
Thismenuoptionbecomes visibleiftheunitiscongured for“Flowcontrol”,“Manual frequency”or“Pressure control”.
Frequency
Frequencycontrolmanual.
controlmanual SAF
Fanscontrolledbysettingxed outputsignal.
Output:%
Thismenuoptionbecomes visibleiftheunitiscongured for"Manualfrequency”.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
11
SystemairSverigeAB
Page 14
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Frequency controlmanual SAF
Output1/1:75%
Output1/2:50%
Outdoor comp.output.
–20°C=0m³/h
0°C=0m³/h
Act.Comp:0 m³/h
Frequency controlmanual EAF
Output:%
Frequency controlmanual EAF
Output1/1:75%
Explanations
Flowcontrol SAF
Actual:m³/h
Setp.:m³/h
Output1/2:50%
Outdoor comp.output.
–20°C=0m³/h
0°C=0m³/h
Act.Comp:0 m³/h
FlowcontrolSAF
Setp1/1:1100 m³/h
Setp1/2:550 m³/h
Outdoor comp.Setp.
–20°C=0m³/h
0°C=0m³/h
Act.Comp:0 m³/h
Airowforthesupplyairfan (constantairowcontrol).
Onlyvisibleiftheunitis conguredfor“Flowcontrol” (CAV).
Setthenormal(1/1)and reduced(1/2)airowforthe supplyairfan.
SettheSAFairow compensationforthesettable outdoortemperature.The outdoorcompensationislinear andissetusingtwoparameter pairswhichgivethevalueofthe compensationattwodifferent outdoortemperatures.The compensationcanbepositive ornegative.
Showstheactualairow compensation.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
12
SystemairSverigeAB
Page 15
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Flowcontrol EAF
Explanations
Airowfortheextractairfan (constantairowcontrol).
Actual:xxx m³/h
Setp.:xxxm³/h
Pressure controlSAF
Actual:Pa
Setp.:Pa
FlowcontrolEAF
Setp1/1:1100 m³/h
Setp1/2:550 m³/h
Outdoor comp.Setp.
–20°C=0m³/h
0°C=0m³/h
Act.Comp:0 m³/h
Pressurecontrol SAF
Setp1/1:200 Pa
Onlyvisibleiftheunitis conguredfor“Flowcontrol” (CAV).
Setthenormal(1/1)and reduced(1/2)airowforthe extractairfan.
SettheEAFairow compensationforthesettable outdoortemperature.The outdoorcompensationislinear andissetusingtwoparameter pairswhichgivethevalueofthe compensationattwodifferent outdoortemperatures.The compensationcanbepositive ornegative.
Showstheactualairow compensation.
Theactualexternalpressure andsetpointforthesupplyair fan.
Onlyvisibleiftheunitis conguredfor"Pressure control"(VAV)
Settheexternalpressureset pointfornormalspeed(1/1) andreducedspeed(1/2)forthe supplyairfan.
Setp1/2:100 Pa
Outdoor comp.Setp.1
—20°C=0Pa
10°C=0Pa
Act.Comp:0 Pa
SettheSAFpressure compensationforthesettable outdoortemperature.The outdoorcompensationislinear andissetusingtwoparameter pairswhichgivethevalueofthe compensationattwodifferent outdoortemperatures.The compensationcanbepositive ornegative.
Showstheactualpressure compensation.
Pressure controlEAF
Actual:Pa
Setp.:Pa
Theactualexternalpressure andsetpointfortheextractair fan.
Onlyvisibleiftheunitis conguredfor"Pressure control"(VAV).
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
13
SystemairSverigeAB
Page 16
Mainmenuitem
Timesettings
Sub-menuitem1Sub-menuitem2
Pressurecontrol EAF
Setp1/1:200 Pa
Setp1/2:100 Pa
Outdoor comp.Setp.1
—20°C=0Pa
10°C=0Pa
Act.Comp:0 Pa
ExtraflowEAF Actual:m³/h
Time/Date
Explanations
Settheexternalpressureset pointfornormalspeed(1/1) andreducedspeed(1/2)forthe supplyairfan.
SettheEAFpressure compensationforthesettable outdoortemperature.The outdoorcompensationislinear andissetusingtwoparameter pairswhichgivethevalueofthe compensationattwodifferent outdoortemperatures.The compensationcanbepositive ornegative.
Showstheactualpressure compensation.
Showstheextractairow
Setcorrecttimeanddate.
TimerNormal
Speed
TimerReduced Speed
NormalSpeed Monday Per1: 07:00–16:00 Per2: 00:00–00:00
NormalSpeed Monday-Friday Per1: 07:00–16:00 Per2: 00:00–00:00
Reducedspeed Monday Per1: 00:00–24:00 Per2: 00:00–00:00
ReducedSpeed Monday-Friday Per1: 00:00–24:00 Per2: 00:00–00:00
Set00:00-24:00forcontinuous running.Setting00:00-00:00 inactivatestheperiod(stopsthe unit).Normalspeedoverrides Reducedspeedi.e.Normal speed07:00-16:00and Reducedspeed00:00-24:00 runstheunitonNormalspeed 07:00-16:00andReduced speedtherestoftheday.
SetweekscheduleMonday toSunday,Monday-Friday+ Holidayfornormalspeed. Possibletoset2periodsper day.
Notethesettingsinthe commissioningrecord.
SetweekscheduleMonday toSunday ,Monday-Friday+ Holidayforreducedspeed. Possibletoset2periodsper day.
Notethesettingsinthe commissioningrecord.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
14
SystemairSverigeAB
Page 17
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Extended
Extendedrunning
running
60min
Timeinext. running
0min
HolidaysHolidays(mm:dd)
1:01–01—01–02
2:01–01—01–01
3:01–01—01–01
Explanations
Setthetimeforextended running.Usedigitalinputto forcetheunittostartorincrease tonormalrunningevenifthe actualmodeisOfforReduced.
Iftherunningtimeissetto0 theunitonlyrunsaslongasthe digitalinputisclosed.
Thetimetheextendedrunning isactiveismonitoredin"Timein ext.Running".
It'salsopossibletosetatime hereaswellinordertoshorten theinitialsetperiod.
Setupto24separatepossible holidayperiodsforafullyear.
Aholidayperiodcanbeany numberofconsecutivedays fromoneandupwards.
Thedatesareintheformat: MM:DD.
Whenthecurrentdatefalls withinaholidayperiod,the schedulerwillusethesettings fortheweekday“Holiday”.
Manual/Auto
Inthismenutherunningmode ofalltheconguredoutput signalsandanumberofcontrol functionscanbemanually controlled.
Thesupplyaircontroller'soutput signalcanbemanuallyset (Manual/Auto)toanyvalue between0and100%.The temperatureoutputsignalswill changeaccordinglyiftheyare inAutomode.Itisalsopossible tomanuallycontroleachof thetemperatureoutputsignals individually.
Sinceleavinganyofthe outputsinmanualcontrolwill disruptthenormalcontrol, analarmwillbegeneratedas soonasanyoutputissettoa manualmode.
Supplytemp. contr.
Auto
Manualset:
0.0
Setthesupplyairtemperature controllertoAuto,Manualor Off.
Settheoutputsignalbetween 0-100%.
TheoutputsY1,Y2andY3,ifin Auto-mode,willfollowthesignal accordingtothesetsplitvalues.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
15
SystemairSverigeAB
Page 18
Mainmenuitem
Sub-menuitem1Sub-menuitem2
SAF:Auto
Manualset:
0.0
EAF:Auto
Manualset:
0.0
Heating
Auto
Manualset:
100.0
Exchanger
Auto
Manualset:
0.0
Cooling
Auto
Manualset:
0.0
Explanations
SettheoutputsignalforSAF (supplyairfan)to:Auto,
Manual,1/2–speedor 1/1–speed.
SettheoutputsignalforEAF (extractairfan)to:Auto,
Manual,1/2–speedor 1/1–speed.
SettheheatingtoAuto, ManualorOff.
Setthemanualoutput0-100%.
Settheexchangerrotorcontrol toAuto,ManualorOff
Setthemanualoutput0-100%
SetthecoolingtoAuto,Manual orOff
Setthemanualoutput0-100%
Note:
P1–Heating
Auto
P1–Cooling
Auto
Firedamper
Auto
Outdoorair damper
Auto
Exhaustair damper
Needstobeactivatedinorder tobevisiblehere
Setthepumpcontrolforthe heatingcoiltoAuto,OnorOff
Setthepumpcontrolforthe coolingcoiltoAuto,OnorOff
SettheFiredampertoAuto, OpenorClose
Note:
Needstobeactivatedinorder tobevisiblehere
Congurationofredamper functionsaremadeat
Administratorlevel
SettheOutdoorairdamperto
Auto,OpenorClose
SettheExhaustairdamperto
Auto,OpenorClose
Auto
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
16
SystemairSverigeAB
Page 19
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Extrasequence Y4
Explanations
SettheExtrasequencetoAuto,
ManualorOff
Auto
Manualset:
0.0
Extrasequence Y5
Auto
Manualset:
0.0
Settings
Controltemp
Supplyair control
P-band:33.0°C
I-time:100.0 sec
OnlyvisibleforTopvexSC units
SettheExtrasequencetoAuto,
ManualorOff
Notusedindefaultsetting.
Inthismenugroupthesettings fortheactivatedfunctionsare available.Dependingonwhich choiceshavebeenmadeinthe congurationmenusomeofthe possiblealternativesmaynotbe displayed.
SetP-bandandI-timeforthe Supplyaircontrolfunction
Note:
SeeCorrigomanual-Ventilation applicationformoreinformation.
Extractair control
P-band:100.0°C
I-time:300.0 sec
Shutdownmode
P-band:100.0°C
I-time:100.0 sec
SetP-bandandI-timeforthe Extractaircontrolfunction
Note:
SeeCorrigomanual-Ventilation applicationformoreinformation.
SetP-bandandI-timeforthe Shutdownfunction
Note:
SeeCorrigomanual-Ventilation applicationformoreinformation.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
17
SystemairSverigeAB
Page 20
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Frost protection
Active
Explanations
Statusforfrostprotection.
Whenrunningmodeswitchedto "Off".
Controlflow
orControl pressure
Alarm settings
Setpshutdown:
25.0°C
P-bandactive:
5.0°C
Faststopat frostprotection alarm
Yes
Sequencywith frostprotection
Y1–Heating
FlowcontrolSAF
P-band:2160.0 m³/h
I-time:40.0 sec
Min.output: 0%
FlowcontrolEAF
P-band:2160.0 m³/h
I-time:40.0 sec
Min.output: 0%
Alarmlimits
Alarmdelays
Restorealarm
Shutdowncontrollerwillcontrol theheatingoutputtomaintaina constantsettabletemperature atthefrostprotectionsensorfor thehotwatercoil.
Iffrostprotectiontemperature fallsbelowFrost
protectionAlarmlevel
+settableP-Bandforfrost protection,itwillrisetheinternal signalandforcetheheating valvetoopentoavoidfreeze-up ofhotwatercoil.
Setthefaststopoftheunitin caseoffrostprotectionalarmto YesorNo.
Frostprotectioncontrol.
IsavailableforY1heating, Y4extrasequenceoron bothY1andY4.
OnlyshownifFancontrol selectedtothesealternatives.
SetP-band,I-timeandMin. outputforthesupplyairfan whentheunitcomescongured asFlowcontrolfrom factory.AlternativelyPressure controlifthatcongurationis chosen
SetP-band,I-timeandMin. outputfortheExtractairfan whentheunitcomescongured asFlowcontrolfrom factory.AlternativelyPressure controlifthatcongurationis chosen
Setthealarmlimitsandallowed deviationsforthedifferent functions
Setthealarmdelaysand alloweddeviationdelaysforthe differentfunctions
Resettheservicealarm(lter alarm).
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
18
SystemairSverigeAB
Page 21
Mainmenuitem
Darkergrayarea,login to“Administratorlevel” code3333
Configuration
Sub-menuitem1Sub-menuitem2
Restorefactory
settings:No
Restoreuser
settings:No
Saveuser settings
No
Inputs/Outputs
Sensorsettings
Control
Controlfunction
Mode:
function
Cascadeextract ctrl
Explanations
Inthismenu,itispossibleto restoreallparameterstotheir factorysettingsortotheuser settingstheyweresavedas
earlier.
SelectYesorNo
Thecurrentcongurationcan besavedinaseparatememory areaandcanlaterberestored usingthepreviousmenu, Restoreusersettings.Select YesorNo
Setupforinputsandoutputs.
Setupofsensortypesand controlrange.
Settypeoftemperaturecontrol functionyouwanttheunitto operateunder.Choosebetween
Roomcontrol,Cascade extractctrl,Outd comproom,Outdcomp extrair,Supplyair control,Outdoorcomp. supply
Extract/supplyair
→(possibletoswitchbetween thetwodependingonoutdoor temp.),
Room/supplyair→(possible toswitchbetweenthetwo dependingonoutdoortemp.),
Fancontrol
Extrasequency Y4
TopvexSC:
Modeextra sequenceY4
Activewcool recov
OnlyactiveforTopvexSC
Canbeconguredtoone ofthefollowingalternatives:
Active,Activewith coolingrecovery, Activewithenthalpy controlandActivewith bothcoolingrecovery andenthalpycontrol.
Extrasequency Y5
ExtrasequenceY5canbe conguredtoActiveorNot active.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
19
SystemairSverigeAB
Page 22
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Pumpcontrol
Freecooling
P1–Heating
P1–Cooling
Freecool active:No
Explanations
Setparametersforpump
control.
If,foranyofthecontrolcircuits, nooutputisconguredforpump controlthesesettingswillbe ignored.
SetfreecoolingactivetoYesor No.
Outd.temp activation
22°C
Outd.temp night
High:15.0°C
Low:5.0°C
Roomtempmin. 18°C
Hourfor start/stop
Settheloweroutdoorday temperaturelimitforthe activationofthefreecooling function.Thetemperatureof thepreviousdayneedstobe overthesettemperaturein orderactivatethefreecooling function.
Settheupperoutdoornight temperaturelimitforthe activationofthefreecooling function.
Settheloweroutdoornight temperaturelimitforthe activationofthefreecooling function.
Setthelowerroomtemperature limit.Thetemperatureneedsto beabovethisvalueforthefree coolingfunctiontostayactive.
Ifnoroomsensorareconnected extractairisvalid.
Setthestartandstoptimefor thefreecoolingfunction
Freecooling
Start:0
Stop:7
Timetoblock heatoutput afterFree cooling
60min
Fanoutputwhen freecooling
SAF:0%
EAF:0%
ForexampleStart:0and
Stop:6
meansthatthefreecooling sequenceisactivebetween
00.00and06.00h.
Setthedelayinminutesfrom thetimewherethefreecooling sequencehasstoppeduntila possibleheatingsequenceis initiated,i.e.howlongacooler roomtemperaturethanset temperaturecanbeaccepted
Setthefanspeedinpercentage ofthenormalspeedforeach fanindividuallyduringthefree coolingsequence
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
20
SystemairSverigeAB
Page 23
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Outdoorsensor placedinintake channel(intakeduct)
No
Support
Supportcontrol
control
Active:No
EAFrunning duringSupport contr.:Yes
Min.runtime forsupport ctrl:60min
CO2/VOC Control
CO2/VOCactive
Never
Type:Fan
Min.time:60 min
Explanations
Setiftheoutdoorsensoris
placedintheintakeductornot.
ChoosebetweenNoandYes
PresetisNo.
Whenusingthecontrol functionroomcontrolor extractairtemperature control,itispossibleto utilizesupport-heatingand/or support-cooling.Minimum runningtimeissettable0…720 minutes(factorysetting60 minutes).Choosebetween “Active:Y esorNo”.
(Forstartandstoptemperatures seethe"Temperature"menu)
Settheminimumrunningtime inminutesforsupportcontrol
Inapplicationswithvarying occupancythefanspeeds canbecontrolledbytheair qualityasmeasuredbya CO2/VOC-sensor.SeeCorrigo manualforfurtherexplanation
SetactivetoNever,Alwaysor Iftimechanneloff.
Setwhatshouldberegulated. SelecttypeFan
Setthemin.timetheunitis activatedbytheCO2/VOC demandfunction
Activationlevel
1/2–speed:800 ppm
1/1–speed:1000 ppm
diff:160ppm
Settheactivationlevelat1/2 speed
Settheactivationlevelat1/1 speed
Setalloweddiff.value
Sequencywith CO2comtrol
CO2/VOCcontrolcanbeused withmixingdampers.
Y2exchanger
SelectforuseonY2,Y4oron bothoutputs.
FireFunction
Firedamper function
Notactive
Operationwhen alarm
Stopped
Therealarminputcanbe conguredasNotactive,
Normallyclosedor Normallyopen.
Chooseoperationwhenalarmis activeStopped,Continuous
run,Normalrun,Only SAF,orOnlyEAF
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
21
SystemairSverigeAB
Page 24
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Firealarminput
Normallyopen
Damperexercise
Explanations
Firealarminputcanbe conguredtonormallyopenor normallyclosed.
Firealarminputisalsoavailable tobecongurefromdigital inputs.
Notetheriskofatwicechanged signalcancreateanundesired function.
No
Activatetheredamper exercising,choosebetween
No,Yesunitrunningor Yesunitstopped.
Settheparametersfordamper exerciseinthesubmenu.
Exchanger
deicing
Exchanger deicing
Thissectionsisforunitswith counterowandcrossow exchangers.
Yes
Setifexchangerdeicingwillbe used,Yes/No
Thissectionsisforunitswith counterowandcrossow exchangers.
Bypass:On
Exchangerdeicingallowedwith bypass,On/Off.
Stopdeicing: On
Activationtemp: 0,0°C
Exchangerdeicingallowedwith stopofthesupplyairfan(SAF),
On/Off
Outdoortemperaturelimitto allowdeicingfunction.
StoptempSAF:
-8,0°C
Outdoortemperaturelimitfor forcedstopdeicing,interlockof bypassdeicing.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
22
SystemairSverigeAB
Page 25
Mainmenuitem
Sub-menuitem1Sub-menuitem2
Explanations
Thissectionsisforunitswith counterowandcrossow exchangers.
SetpPressdev: 50%
Setpointinpercentofthe pressuredeviationtostart deicing.
Stophyst:60%
Reductionofthepressure deviationinpercenttocancel deicing.
Actualsetp: xxxPa
Actualsetpointfordeicing presented.
Note!Thevaluecanvary, dependingonairow.
Manualcalib: Off
ManualcalibrationON/Off tomakeanewcalibration manually.
Note!Recommendedto performthisoperationwithadry exchangerandnormalairow.
Cooling
recovery
Coolingrecovery
Yes
Coolinglimit:
2.0°C
SetthecoolingrecoverytoYes orNo.
Setthecoolinglimit(the differenceintemperature betweenextractairandoutdoor airthatactivatesthecooling recovery).
External setpoint
External setpoint
Notactive
Minsetp.:
Anexternalsetpointdevicecan beconnected.Thesetpoint devicemustfollowthePT1000 resistancecurve.Thesetting rangecanberestricted.
12.0°C
Maxsetp.:
30.0°C
Alarmsettings
Alarmno(1–100): 1 RunErrorSupply Air
Communication
FunctionPort1
Slave
Function Expansionunit
Slave
Choosebetweendifferent communicationsSlave,
Expansionunit,Freq conv/Presstran, Externaldisplay,Exp andfreqconvorExpand extdisplay.
→FunctionPort2
Expandext display
PDTxxC-2
Pressuredualtransmitter module.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
23
SystemairSverigeAB
Page 26
Mainmenuitem
Accessrights
Sub-menuitem1Sub-menuitem2
Expansionunit1 None
Expansionunit2 None
Expansionunit3 PDTxxC-2
Expansionunit4 PDTxxC-2
LogonLogon
Enterpassword xxxx
Actuallevel: None
LogoffLogoff?
No
Actual level:None
Change password
Changepassword for
Explanations
Logontoservicelevelby
enteringa4-digitcode.After reachingthedesiredlevelgo backwith“LEFT”arrow(press2 times)onthecontrolpanel.
Standardcodefromfactoryto enterservicelevelis2222.Back tooperatorlevel:111 1.T oenter Adminlevelcode:3333.
LogofffromAdministratorlevel bychangingNotoYeswiththe "OK"and"UP/DOWN"buttons
Automaticlogoffafter6minutes ofinactivity.
Setanewpasswordforthe levelofyourchoice.
level:None
Newpassword xxxx
Canonlybedoneoncelogged ontotheservicelevel.

4.4Freecoolingdescription

Thisfunctionisusedduringthewarmperiodtosaveenergybyusingcoldoutdoorair,e.g.duringnight time,tocooldownthebuildingandtherebyreducingtheneedforcoolingduringthedaytime.
Note:
ThefollowingisonlyvalidifthefreecoolingfunctionissettoActiveintheprogrammenu.
Freecoolingisonlyactivatedwhenthefollowingstartingconditionsaremet.
Startingconditions:
•Lessthan4dayshavepassedsincetheunitwaslastinrunningmode
•Theoutdoortemperatureduringthepreviousrunningperiodexceededasetlimit(+22°C)
•Itisbetween00:00and07:00:00intheday(settable)
•Thetimeroutputsfornormalspeed,ExtendedrunningnormalandExternalstopareOff
•AtimechannelwillbeOnsometimeduringtherecentlystarted24hours.
Theunitchecksthenighttemperature(indoorandoutdoortemperature)during3minutesattheset startinghourwhenthefansarestartedsothatthesensorscanperformatemperaturemeasurement.If aboveconditionsaremetthefreecoolingfunctionisstarted,ifnottheunitgoesbacktoOFFposition.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
24
SystemairSverigeAB
Page 27
Iftheoutdoorsensorisnotlocatedintheoutdoorairinletductandaroomsensorhasbeenselected, theunitwillnotstartfreecoolingaslongasallthetemperaturesarenotwithinthestartandstop temperatureintervals.
Stopconditions:
•Outdoortempabovethesetmaxvalue(+18°C)orbelowthesetminvalue(condensationrisk,+10°C)
•Theroomtemp/extractairtempisbelowthesetstopvalue(+18°C)
•Oneofthetimeroutputsfornormalspeed,ExternalstoporExtendedrunningnormalisOn
•Thetimehaspast07:00:00.
Ifanystopconditionsisfullledafterthreeminutes,theunitwillstopagain.Otherwise,operationwill continueuntilastopconditionisfullled.
Whenfreecoolingisactive,thefansrunatnormalspeedorthesetvalueforpressure/owcontroland thedigitaloutputFreecoolingisactive.TheoutputsY1-Heating,Y2-Heatexchangerand Y3-Coolingareshutdown.Afterfreecoolinghasbeenactivated,theheatingoutputisblockedfor60 minutes(congurabletime).Whenusingfreecooling,anoffsettonormalfancontrolsetpointisadjustable.

5Maintenance

5.1Important

Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith localrulesandregulations.
Warning
•AlthoughtheMainssupplytotheunithasbeendisconnectedthereisstillriskforinjuryduetorotating partsthathavenotcometoacompletestandstill.
•Bewareofsharpedgesduringmountingandmaintenance.Useprotectiveclothing.

5.2Maintenanceintervals

Thetablebelowshowsrecommendedmaintenanceintervalsfortheunitandtheinstallation.T o ensurealongoperationlifetimefortheunititisimportanttoperformmaintenanceaccordingtobelow recommendationsandthattheyareperformedaccordingtotheoperationandmaintenanceinstructions.A thoroughandrecurrentmaintenanceisamustforavalidguarantee.
TypeofmaintenanceOnceayear
Whennecessary
Cleaningtheheatexchanger.
Cleaningthefans.
Cleaningextractlouvresand supplyairdiffusers.
Cleaningtheoutdoorairintake.
Cleaningtheductsystem.
1.Orinaccordancewithlocalrulesandregulations
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
X
X
X
25
X
1
X
SystemairSverigeAB
Page 28

5.3Maintenanceinstructions

5.3.1ChangingSupply/Extractairlter
Thebagltercannotbecleanedandmustbechangedwhennecessary .Newlterscanbeorderedfrom Systemair.Operationtimebetweenlterchangesdependsontheairpollutionattheinstallationsite.A differentialpressureswitchindicateswhenit’stimetochangethelters.Thiswilltriggeranalarmin thecontrolpanel.
Whenthisoccursdothefollowing:
1.Replacethelterswithnewonesasdescribedbelow.
2.Acknowledgethealarmbypressingtheredbuttononthecontrolpanel(pos.1gure4)followedbyOK (pos.4gure4).
3.Choose→AcknowledgebypressingOK.
Theltersaretakenoutaccordingtobelowprocedure:
1
Releasethelterframebypullingtheltersupport bars.
2
Tiltthesupportbarstotheback.
3
Itisnowpossibletofoldthelterandframe backwards.Thisisespeciallyimportantifthereis lackofspaceinfrontoftheunitandthesliding doorkitisused.
Theltercannowbetakenoutoftheunit.
4
Insertthenewlterandfastenitagainsttheinletsealwiththeltersupportbars.
Makesurethelteristtedtightallaroundtheframe.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
26
SystemairSverigeAB
Page 29

5.3.2Checkingtheheatexchanger

Afteralongtimeofusedustmaybuildupintheexchanger(pos.5,gure1)andblocktheairow.Itis importanttocleantheexchangerregularlytomaintainhighefciency.TheheatexchangerintheT opvex FR03–11canbetakenoutoftheunit.Washinhotsoapywaterorusepressureair.Donotusedetergent containingammonia.
Note:
Makesurethattherotormotorisnotexposedtomoisture.
5.3.2.1Dismountingtheheatexchangerblockonceilingmountedunits
1
Removetheexchangercoverplateinthecentreof theunitbyunscrewingthe4screwsinthecorners oftheplate.
Removingtheplateisonlypossibleafteropening bothinspectiondoors.
2
Thereare4screws(2oneachside)holdingthe heatexchangerblock(ModelsFR08andFR11 have8screws,4oneachside).Whenremoving theheatexchangerstartwithcheckingthatthe screwmarked“A”istightenedproperly.Remove thescrewmarked“B”completelyasshowninthe gureafterwhichthescrewmarked“A”isloosened carefully,justenoughtoallowtheexchangerframe toslideinthetracks.
3
Slideouttheexchangerblockuntiltheendofthe tracks.
Warning
Theheatexchangerblockisheavy.Use propersupportdevicewhentakingouttheheat exchangerblockformaintenance!
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
27
SystemairSverigeAB
Page 30
4
Afternishedcleaning/maintenance,pushbacktheheatexchangerblockandfastenallscrewstightly.
5.3.2.2Dismountingtheheatexchangerblockonoormountedunits
1
Loosenallscrewscompletelyholdingtheheatexchangerblock.
2
Removetheheatexchangerblockcompletelyby liftingitstraightup.
Caution
Theexchangerblockisheavy,makesureto useproperliftingdeviceorsufcientnumberof personstolifttheheatexchangeroutoftheunit
Table2:Weightofheatexchangerblock
Model
FR0331
FR0643
FR08
FR1171
Weightofheatexchanger block(kg)
55

5.3.3Checkingthefans

5.3.3.1Checkingthefans
Eveniftherequiredmaintenance,suchaschangeoflters,iscarriedoutdustandgreasemayslowly buildupinsidethefans(pos.1and2,gure1).Thiswillreducetheefciency.
Thefanscanbedismountedbylooseningthe4screwsonthefancasing(gure5).TopvexFR06–1 1have afansupportbracketthatneedstoberemovedbyloosening4screws.Thefansmaybecleanedwith aclothorasoftbrush.Donotusewater.Whitespiritcanbeusedtoremoveaccumulationswhichare otherwisedifculttoremove.Allowdryingproperlybeforeremounting.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
28
SystemairSverigeAB
Page 31
Fig.5Dismountingthefans

5.3.4Cleaningextractlouvresandinletdiffusers

Thesystemsuppliestreatedoutdoorairtothebuildingandextractstheusedindoorairviatheductsystem anddiffusers/louvres.Diffusersandlouvresaremountedinceilings/wallsinbedroom,livingroom,wet rooms,WCetc.Removediffusersandlouvresandwashinhotsoapywaterifrequired.Diffusers/louvres mustbeputbackwiththeiroriginalsettingsandpositionsinordernottounbalancethesystem.

5.3.5Checkingtheoutdoorairintake

Leavesandpollutioncouldpluguptheairintakegrilleandreducetheunit’scapacity.Checktheairintake grilleatleasttwiceayearandcleanifnecessary .

5.3.6Checkingtheductsystem

Dustandgreasesettlementsmaybuildupintheductsystemevenifltersarechangedregularly.This willreducetheefciencyoftheinstallation.Theductsshouldthereforebecleaned/changedwhen necessary.Steelductscanbecleanedbypullingabrush,soakedinhotsoapywaterthroughtheductvia diffuser/louvreopeningsorspecialinspectionhatchesintheductsystem(iftted).

5.3.7ChangingtheInternalBattery

Note:
ThisprocedurerequiresknowledgeofproperESDprotection;i.e.anearthedwristbandmustbeused!
Whenthealarm”InternalBattery”isactivatedandthebatteryLEDlightsupred,thebatteryforbackupof programmemoryandreal-timeclockhasbecometooweak.Thebatteryisreplacedasdescribedbelow. Abackupcapacitorsavesthememoryandkeepstheclockrunningforatleast10minutesafterthepower supplyisremoved.Therefore,ifthebatteryreplacementtakeslessthan10minutes,therewillbenoneed toreloadtheprogram,andtheclockwillcontinuetorunnormally .
ThereplacementbatterymustbeofthetypeCR2032.
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
29
SystemairSverigeAB
Page 32
1
Removethecoverbypressingdownthelocking torquesattheedgeofthecoverusingasmall screwdriver,andatthesametimepullingthe edgesoutwards.
2
Gripthebatteryrmlywithyourngersandliftit upwardsuntilitrisesfromitsholder.
Pressthenewbatteryrmlydownintoplace.Note thattopreservecorrectpolarity ,thebatterycan onlybeinsertedthe“rightwayround”.

5.4Troubleshooting

Shouldproblemsoccur,pleasecheckorcorrectthefollowingbeforecontactingyourservicerepresentative. Alwayscheckifthereareanyalarmsactiveinthecontrolpanel.
1.Fan(s)donotstart
•Checkifthereareanyalarmmessages.
•Checkthatthefusesarenotdefect(pos.8gure3).
•Checkthesettingsinthecontrolpanel(times,weekschedule,auto/manualoperationetc.).
2.Reducedairow
•Checkthesettingsformediumandlowfanspeed.
•Checkthattheoutdoor/exhaustairdamper(ifused)opens.
•Checkifltersneedchanging.
•Checkifdiffusersandlouvresneedcleaning.
•Checkdiffuser/louvreopenings.
•Checkiffansandexchangerblockneedcleaning.
•Checkiftheroofunitorairintakeisclogged.
•Checkductsforvisibledamageand/orbuildupofdust/pollution.
3.Coldsupplyair
•Checkthecontroltemperatureonthecontrolpanel.
•Checkiftheemergencythermostathastripped.Ifnecessarypresstheredbutton,ontheelectrical
heater(pos.9,gure1)withapointedtool.
•Checkiftheextractltermustbechanged.
•Checkifthefanshavestoppedduetooverheating.Ifsothethermalcontactmighthavetripped
(showsasFanalarminthecontrolpanel).
4.Noise/vibrations
•Checkthattheunitiscompletelyleveled.
•Cleanthefanimpellers.
•Checkthatthescrewsholdingthefansaretightenedproperly.

5.4.1Alarms

Thealarmbutton(pos.1,gure4)opensthealarmqueue.Whenpressingthisbuttonactiveand non-acknowledgedalarmswillbedisplayedinthemenuwindow.Thealarm-LED(pos.2,gure4)is
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
30
SystemairSverigeAB
Page 33
ashingiftherearenon-acknowledgedalarmsandsteadyifthealarmsarestillactivebuthavebeen
230 /400V 25 A 5 0Hz
Syst ema ir Sve rige AB Indus triväge n 3 SE-7 3930 Skinns katte berg Swe den
4016 W IP23 225kg
Ve r. A
eria l. n o: 123 4/5678 91-000 1/1402 14
To p vex XXXX
16kW 16kW
www .systemair .com
2
3 4
5
acknowledged.Iftherearemultiplealarms,useUP/DOWNtomovebetweenthem.Analarmcanbe acknowledgedorblockedbyusingOKandUP/DOWN.T oabortandgobacktostartmenupresscancel andthenpressLEFT .
Seecommissioningrecordforanoverviewofpossiblealarms.

6Service

Beforecallingyourservicerepresentative,makeanoteofthespecicationandproductionnumberfrom thetypelabel(gure6)
Fig.6Typelabel
PositionDescription
1Itemnumber
2Productionordernumber
3
4Productiondate
5
Consecutivenumber
Productcode(productspecication)
TopvexFR03,FR06,FR08,FR11OperationandMaintenanceInstructions
129451
31
SystemairSverigeAB
Page 34
lastpage
SystemairABreservestherighttomakechangesandimprovementstothecontents
ofthismanualwithoutpriornotice.