Page 1
TopvexFR03,FR06,FR08,FR11
CompactAirHandlingUnit
OperationandMaintenanceInstructions
Documentinoriginallanguage
129451-EN_GB
24-06-2015 A001
Page 2
Contents
1Warnings...................................................................................................................................1
2ProductDescription....................................................................................................................2
2.1DescriptionofInternalcomponents....................................................................................3
2.1.1SupplyandExtractairFans.....................................................................................3
2.1.2SupplyandExtractairFilters...................................................................................3
2.1.3HeatExchanger......................................................................................................4
2.1.4T emperaturesensors...............................................................................................4
2.1.5Waterheatingbattery..............................................................................................4
2.1.6ElectricalHeater.....................................................................................................4
2.2InternalcomponentsElectricalconnectionbox...................................................................5
3InterfaceDescription..................................................................................................................5
3.1ControlPanel...................................................................................................................5
3.1.1Operatingthecontrolpanel......................................................................................6
4Commissioning..........................................................................................................................7
4.1BeforeStartingtheSystem...............................................................................................7
4.2Initialsetupoftheunit.......................................................................................................7
4.3Menuoverview.................................................................................................................9
4.4Freecoolingdescription....................................................................................................24
5Maintenance..............................................................................................................................25
5.1Important.........................................................................................................................25
5.2Maintenanceintervals.......................................................................................................25
5.3Maintenanceinstructions..................................................................................................26
5.3.1ChangingSupply/Extractairlter.............................................................................26
5.3.2Checkingtheheatexchanger..................................................................................27
5.3.3Checkingthefans...................................................................................................28
5.3.4Cleaningextractlouvresandinletdiffusers...............................................................29
5.3.5Checkingtheoutdoorairintake................................................................................29
5.3.6Checkingtheductsystem........................................................................................29
5.3.7ChangingtheInternalBattery..................................................................................29
5.4Troubleshooting...............................................................................................................30
5.4.1Alarms...................................................................................................................30
6Service......................................................................................................................................31
Page 3
1Warnings
Thefollowingadmonitionswillbepresentedinthedifferentsectionsofthedocument.
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor
electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith
localrulesandregulations.
Warning
•AlthoughtheMainssupplytotheunithasbeendisconnectedthereisstillriskforinjuryduetorotating
partsthathavenotcometoacompletestandstill.
•Bewareofsharpedgesduringmaintenance.Useprotectiveclothing.
•Thisproductisnotintendedtobeusedbychildrenorpeoplewithreducedphysicalormentalability
orlackofexperienceandknowledge,ifnoinstructionconcerningtheusehasbeengivenbythe
personresponsiblefortheirsafetyorthatthispersonissupervisingtheoperation.Childrenshouldbe
supervisedsothattheycannotplaywiththeproduct.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
1
SystemairSverigeAB
Page 4
2ProductDescription
Fig.1ComponentsELunits
Fig.2ComponentsHWunits(incaseofinstalledwaterheatingbattery)
Table1:ComponentdescriptionsELandHWunits
Position Description
1 Fansupplyair.
2 Fanextractair.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
2
SystemairSverigeAB
Page 5
ComponentdescriptionsELandHWunitscont'd
Position Description
3 Filterextractair.
4 Filteroutdoorair.
5
6 Rotormotor.
7
8 Re-heaterbattery,electricorwatercoil.
9
10
11
12
13 Electricalconnectionbox.
14 Mountingbrackets.
15
Heatexchanger.
Rotorbelt.
Resetbutton,manualoverheatprotection(onlyunitswithelectricalheater).
Pressureguardforlter.
Pressuretransmitterforfan.
Rotationguardforheatexchanger.
Rotorcontrol(locationdependingonsizeofunit)
2.1DescriptionofInternalcomponents
2.1.1SupplyandExtractairFans
ThefanshaveexternalrotormotorsofECtypewhichcanbesteplesslycontrolledindividually0–100%.It
ispossibletoprogramthespeedin2steps(normal/reduced)dependingontheprogrammingoftheweek
schedule.Themotorbearingsarelifetimelubricatedandmaintenancefree.Itispossibletoremovethe
fansforcleaning(chapter5).
2.1.1.1PressuretransmitterFans
2pressuretransmittersmaintaintheairowataconstantlevelbymeasuringthedifferentialpressureover
theinletconeofthefanimpellers(pos.11gure1andgure2)).Thepressuretransmittersareinstalled
fromfactoryinallCAVunits.V AVcontrolofthefansisavailableasanaccessory .TheVAVaccessory
kitincludestwopressuretransmitters,tubes,electricalcablesandinstructiononhowtoconnecttothe
airhandlingunitandset-upthecontroller.See“Installationinstructions”formoreinformationconcerning
VAVinstallations.
2.1.2SupplyandExtractairFilters
TheltersareofbagltertypewithlterqualityF7forthesupplyairlterandM5fortheextractairlter.
Theltersneedtobereplacedwhenpolluted.Newlterscanbeacquiredfromyourinstallerorwholesaler.
2.1.2.1Pressureguardforlters
Apressureguardmeasuresthedifferentialpressureoverthesupplyandextractairlters(pos.10gure1
andgure2).Whenthepressuredropreachesapresetvalueanalarmistriggeredinthemainregulator.
Thealarmvalueissetaccordingtorecommendationsforthefactorymountedlters.Itispossibletoadapt
settingstospecicinstallationsandltertypes,seeAlarmsettingsinchapter4.3.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
3
SystemairSverigeAB
Page 6
2.1.3HeatExchanger
TopvexFRmodelsareequippedwithahighlyefcient,beltdriven,rotatingheatexchanger.Required
supplyairtemperatureisthereforenormallymaintainedwithoutaddingadditionalheat.Theoperationof
theheatexchangerisautomaticanddependsonthesettemperature.
Theheatexchangerisremovableforcleaningandmaintenance(chapter5).
2.1.3.1Rotormotor
Therotormotordrivestheexchangerrotorwithaninnitelyrpmaslongasthereisaheatdemand.The
motoriscontrolledbyananalogue0-10Vcontrolsignal(pos.6gure1andgure2).
2.1.3.2Rotationguard
Asensorregisterstherotationoftheheatexchangerrotor.It’sconnectedtothemainregulatorwhich
givesanalarmiftherotorstopswhilethereisaheatdemand(pos.12gure1andgure2).
2.1.4Temperaturesensors
4temperaturesensors(PT1000)areincludedintheunitfromfactory.Thesensorsareasfollows:
•Supplyairsensor
•Extractairsensor
•Outdoorairsensor
•Efciencytemperaturesensor
InT opvexFR03–11alltemperaturesensorsaremountedandwiredinsidetheunitexceptforthesupplyair
sensor,whichislooselydeliveredwiththeunitandneedstobeinstalledinthesupplyairductexternally
fromtheunit.SeeInstallationinstructionsformoreinformation.
2.1.5Waterheatingbattery
Inunitswithbuiltinwaterheatingbatterythehotwatercoilislocatednexttothesupplyairconnection.
ThehotwatercoilcanbeeitherHWL(hotwatercoil,lowpower)orHWH(hotwatercoil,highpower).
Thecoilmaterialiscopperpipingwithaframeofgalvanizedsheetsteelandaluminiumns.Thecoilis
equippedwithventingandimmersionsensorforfrostprotection.
2.1.6ElectricalHeater
Inunitswithbuiltinelectricalheatertheheatingrodsarelocatedafterthesupplyairfanintheairow
direction.Thematerialisstainlesssteel.Theelectricalheatingbatteryhasbothautomaticandmanual
overheatingprotection.Themanualoverheatprotectionisresetbypushingtheredbuttonontopofthe
electricalheaterframe(pos.9gure1).Thepowerdemandoftheelectricheatingcoiliscontrolledby
themainregulator,whichcontrolstheheatsteplesslybyaTTCtriaccontrolaccordingtothedesired
supply/extractorroomairtemperaturethatissetinthecontrolpanel.
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor
electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith
localrulesandregulations.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
4
SystemairSverigeAB
Page 7
2.2InternalcomponentsElectricalconnectionbox
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor
electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith
localrulesandregulations.
TopvexFR03–11areequippedwithabuiltinregulatorandinternalwiring(gure3).
Fig.3Electriccomponents
3InterfaceDescription
Position description
1 RegulatorE-28WEB.
2
3
4
5
6
7
8
9
10
Transformer230/24VAC.
Terminalsforinternalandexternal
components.
Terminalsforinternalwiring.
Terminalsformainssupplytotheunit.
Contactor(K2)Pumpcontrolwater(HW
unitsonly,notpresentinEL-units).
Automaticfuse.
Automaticfuseforheater.
Contactor(K3)ELheater.
TTCElheatercontrol.
3.1ControlPanel
TheSCPcontrolpanelisdeliveredwitha10mcable(upto100mcanbeused)thatisconnectedto
thepanelandwithafastcouplingcontact,connectedtotheT opvexunit.Thecontactisconnectedto
theCorrigocontrollerintheelectricalconnectionbox.Thecablecanbeunscrewedinthebackofthe
controlpanel(gure4).
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
5
SystemairSverigeAB
Page 8
3.1.1Operatingthecontrolpanel
Fig.4Thecontrolpanel
Posi-
tion
1
2
3
4
5
6
7
8
9
10
11
12
Explanation
Alarmbutton:Givesaccesstothealarmlist.
AlarmLED:Indicatesalarmbyashingredlight.
WriteLED:Indicatesbyashingyellowlightthatparameterscanbesetorchanged.
OKbutton:Pressthisbuttontobeabletochangeorsetparameterswheneverpossible.Also
usedtomovebetweenchangeableparametersinonedialoguewindowframe.
Cancelbutton:Usedtoabortachangeandreturntotheinitialsetting.
Right/Left&Up/Downbuttons:Usedtomoveup,down,left&rightinthemenutree.Up/Down
buttonsarealsousedtoincreaseordecreasevalueswhensettingorchangingparameters.
Mountingholes.
Connectionblock.
Connectiontobrowncable.
Connectiontoyellowcable.
Connectiontowhitecable.
Connectiontoblackcable.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
6
SystemairSverigeAB
Page 9
3.1.1.1Navigatingthemenus
Thestartdisplay(thedisplaynormallyshown)isattherootofthemenutree.PressingDOWNwillmove
youthroughthemenuoptions.UPwillmoveyoubackthroughtheoptions.Toenterahighermenulevel,
useUPorDOWNtoplacethecursoratthemenuyouwishtoaccessandpressRIGHT.Ifyouhave
sufcientlogonprivilegesthedisplaywillchangetothemenuyouhavechosen.
AteachleveltheremaybeseveralnewmenuswhichyoumovethroughusingUP/DOWN.Sometimes
therearefurthersubmenuslinkedtoamenuormenuitem.Thisisindicatedbyanarrowsymbolatthe
right-handsideofthedisplay.T oenteramenu,pressRIGHTagain.T ostepbacktopreviousmenu
level,useLEFT .
4Commissioning
4.1BeforeStartingtheSystem
Whentheinstallationiscompleted,checkthat:
•Theunitisinstalledinaccordancewiththeinstallationinstructions.
•Theunitiscorrectlywired.
•Soundattenuatorsareinstalledandthattheductsystemiscorrectlyconnectedtotheunit.
•Outdoorairintakeispositionedwithsufcientdistancetopollutionsources(kitchenventilatorexhaust,
centralvacuumsystemexhaustorsimilar).
•Allexternalequipmentareconnected.
•Thefollowingdataisavailable:
•Intendedconguration,forexampletemperaturecontrolfunctions,fancontrol,externalcontrol
functionsetc.
•Howtheunitissupposedtooperateaccordingtoaweeklyschedule(normalandreducedspeed).
4.2Initialsetupoftheunit
Ontherststart-up,thecontrollerwillstartaspecialprogramforsettinglanguage,supplyairtemp
setpoint,Time&dateandweekschedulefornormalspeed.Usethe“OK”buttontomovebetween
changeableparametersandtheUP/DOWNarrowstoseethedisplayedalternatives.Conrmbypressing
“OK”oncemore.MoveondowninthemenustructurebyuseoftheUP/DOWNarrows.
Thefollowingwillbedisplayed:
1
Selectlanguagebypressing“OK”andthenmove
betweenthealternativeswiththeUP/DOWN
buttons.Conrmbypressing“OK”.Movetothe
nextlevelbypressingthe“DOWN”button.
2
Showstheactualextractairtemperature
Setthesupplyairsetpoint.Defaultis18°C(logon
toservicelevelneeded,code2222,tochange
defaultsetting)
ChooseLanguage
English
Extractairtemp
Actual:.... ºC
Setp.: 18ºC
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
7
SystemairSverigeAB
Page 10
3
Checkandmakesurethatcorrecttimeanddateis
displayed,ifnotchangethesettings
Time: 12.46
Date: 2010–03–12
Weekday: Friday
4
Settheweekscheduleforhowit’sintendedforthe
unittooperateatnormalspeedduringMondayto
Friday.It’spossibletoset2periodsperday .
5
Settheweekscheduleforhowit’sintendedforthe
unittooperateatnormalspeedduringSaturdays
andholidays.It’spossibletoset2periodsperday.
6
Settheweekscheduleforhowit’sintendedforthe
unittooperateatreducedspeedduringMonday
toFriday.It’spossibletoset2periodsperday.
Normalspeedinactivatesreducedspeed.
7
Settheweekscheduleforhowit’sintendedforthe
unittooperateatreducedspeedduringSaturdays
andholidays.It’spossibletoset2periodsperday.
Normalspeed
Monday→Friday
Per1: 07:00–16:00
Per2: 00:00–00:00
Normalspeed
Saturday→Holiday
Per1: 07:00–16:00
Per2: 00:00–00:00
Reducedspeed
Monday→Friday
Per1: 00:00–24:00
Per2: 00:00–00:00
Reducedspeed
Saturday→Holiday
Per1: 00:00–24:00
Per2: 00:00–00:00
8
Select“Yes”or“No”
EndWizard
No
Afternishingthesetupthemenusystemfor“Operatorlevel”willbeavailable.
SeebelowmenuoverviewsthatdisplaytheavailablemenusintheOperatorlevelfollowedbythe
“Servicelevel”manual.
ToenterServicelevelusecode2222inthe“Accessrights”menu.Foroperatorlevelusecode1 111.
ToenterAdministratorlevelusecode3333inthe“Congurationmenu”.
Note:
Toperformmoreadvancedsettingspleaseseetheseparate“GeneralCommissioningRecord”on
www.systemair.com,onlinecatalogue
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
8
SystemairSverigeAB
Page 11
4.3Menuoverview
BelowmenuoverviewshowsboththeOperator,ServiceandAdministratorlevel.Theoverviewoftheparts
uniquetothelevelsinbelowtablearemarkedwithdifferentbackgroundcolor.
TologontoOperator
levelusecode
1111underAccess
rights .
Mainmenuitem
FR03EL
2015–03–1509:00
System:Normalrun
Sp:22.0Act: ºC
→Runningmode →Runningmode Runningmode
TologontoService
levelusecode
2222underAccess
rights .
Sub-menuitem1 Sub-menuitem2
Auto
Optime
SAF:0.0h
EAF:0.0h
→ Selected
functions
Controlfunction
Cascadeextract
ctrl
Fancontrol
Flow/Pressure/
Manualcontrol
Heating: Water
Tologonto
Administratorlevel
usecode3333
underAccess
rights .
Explanations
Startscreenheadline
Canbesetto5differentlayouts
(Changeableat“Administrator
level”underthe
Configuration menu).
SetrunningmodetoAuto,
Manualreducedrun,
ManualnormalrunorOff.
Thetimeinhoursthatthe
motorshavebeenoperating
SAF=Supplyairfan
EAF=Extractairfan
Typeofairtemperaturecontrol
theunitisconguredfor.
Typeoffanspeedcontrolthe
unitisconguredfor.
Typeofheatingselected.
Exchanger:
Plate/Rot.exc
Cooling: Not
connect
Freecool
active:No
Supportcontrol
Active: No
CO2/VOCactive
Never
Firedamper
function
Notactive
Operationwhen
alarm
Stopped
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
9
Typeofexchangerselected.
Typeofcoolingselected.
Statusofthefreecooling
function.
Statusofthesupportcontrol
function.
Statusofthedemandventilation
(CO2/VOC)function.
Statusoftheredamper
functionwhenrealarmis
active.
SystemairSverigeAB
Page 12
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Frostprotection
Active
Explanations
Statusofthefrostprotection
function.
→Alarmevents
→ Input/Output
Coolingrecovery
Yes
Externalset
point
Notactive
→AI
→AIexp3
→DI
→UI
→UIexp3
Statusofthecoolingrecovery
function.
Statusoftheexternalsetpoint.
Alarmloglistalongwiththetime
anddatetheyoccurred.
Movedownandupinthelistby
pressing↑↓.
StatusoftheAnalogueinputs.
StatusoftheAnalogueinputs
forexpansionunit.
Onlyvisiblefor
counter-/crossowunits
withaconnectedpressure
module
StatusoftheDigitalinputs.
StatusofUniversalAnalogue
inputsorUniversalDigital
inputs.
StatusoftheUniversalAnalogue
inputsforexpansionunit.
Onlyvisiblefor
counter-/crossowunits
withaconnectedpressure
module
→AO
→DO
→Temperature
Extractair
temp
Actual: ºC
Setp: 22.0ºC
StatusoftheAnalogueoutputs.
StatusoftheDigitaloutputs.
Conguredtemperaturecontrol
(defaultisExtractair
temp ).
Actualtemperatureinthe
chosencontrolmode.
Set-pointtemperatureforthe
chosencontrolmode.
Ifcascade
control
Max/minsupply
setp.
Max: 30ºC
Setthemaximumandminimum
allowedsupplyairtemperature
incaseofcascadecontrol.
Logontoservicelevelneeded
tochangesettings.
Min: 14.0ºC
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
10
SystemairSverigeAB
Page 13
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Outdoortemp:
ºC
Neutralzone0.0
°C
Supplyairtemp
Act.: ºC
Setp: 18ºC
Explanations
Actualoutdoorairtemperature.
Actualsupplyairtemperature.
Calculatedsupplyairsetpoint.
Theextractaircontrolleroutput
signalgeneratesthesupplyair
controller’ssetpointvalue.
Aneutralzonecanbeset
aroundthesetpointvalue.
Note:
SeeCorrigomanual-Ventilation
applicationformoreinformation.
Frost
protection
Actual: ºC
Efficiency
exch.
Actual: %
Output
exchanger
Actualwatertemperatureinthe
waterheatingbattery.(Only
visibleforHWunits).
Actualheatrecoveryefciency .
Thefunctioncalculatesthe
heatexchangerstemperature
efciencyin%whentheoutput
signaltotheexchangeris
higherthan5%andtheoutdoor
temperatureislowerthan10°C.
Efciencycalculatedfromthe
Actual: 100%
Outdoor,ExtractandEfciency
airtemperature.
Whenthecontrolsignalis
lowerthan5%ortheoutdoor
temperatureishigherthan10°
Cthedisplaywillshow0%.
Statusoftheexchangeroutput.
Tempfor
calculation
Presentedtemperaturefor
supplyairefciencycalculation.
efficiency
Act: NaNC
→ AirControl
Thismenuoptionbecomes
visibleiftheunitiscongured
for“Flowcontrol”,“Manual
frequency”or“Pressure
control”.
Frequency
Frequencycontrolmanual.
controlmanual
SAF
Fanscontrolledbysettingxed
outputsignal.
Output: %
Thismenuoptionbecomes
visibleiftheunitiscongured
for"Manualfrequency”.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
11
SystemairSverigeAB
Page 14
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Frequency
controlmanual
SAF
Output1/1: 75%
Output1/2: 50%
Outdoor
comp.output.
–20°C=0m³/h
0°C=0m³/h
Act. Comp: 0
m³/h
Frequency
controlmanual
EAF
Output: %
Frequency
controlmanual
EAF
Output1/1: 75%
Explanations
Flowcontrol
SAF
Actual: m³/h
Setp.: m³/h
Output1/2: 50%
Outdoor
comp.output.
–20°C=0m³/h
0°C=0m³/h
Act. Comp: 0
m³/h
FlowcontrolSAF
Setp1/1: 1100
m³/h
Setp1/2: 550
m³/h
Outdoor
comp.Setp.
–20°C=0m³/h
0°C=0m³/h
Act. Comp: 0
m³/h
Airowforthesupplyairfan
(constantairowcontrol).
Onlyvisibleiftheunitis
conguredfor“Flowcontrol”
(CAV).
Setthenormal(1/1)and
reduced(1/2)airowforthe
supplyairfan.
SettheSAFairow
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Showstheactualairow
compensation.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
12
SystemairSverigeAB
Page 15
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Flowcontrol
EAF
Explanations
Airowfortheextractairfan
(constantairowcontrol).
Actual: xxx
m³/h
Setp.:xxxm³/h
Pressure
controlSAF
Actual: Pa
Setp.: Pa
FlowcontrolEAF
Setp1/1: 1100
m³/h
Setp1/2: 550
m³/h↓
Outdoor
comp.Setp.
–20°C=0m³/h
0°C=0m³/h
Act. Comp: 0
m³/h
Pressurecontrol
SAF
Setp1/1: 200
Pa
Onlyvisibleiftheunitis
conguredfor“Flowcontrol”
(CAV).
Setthenormal(1/1)and
reduced(1/2)airowforthe
extractairfan.
SettheEAFairow
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Showstheactualairow
compensation.
Theactualexternalpressure
andsetpointforthesupplyair
fan.
Onlyvisibleiftheunitis
conguredfor"Pressure
control"(VAV)
Settheexternalpressureset
pointfornormalspeed(1/1)
andreducedspeed(1/2)forthe
supplyairfan.
Setp1/2: 100
Pa
Outdoor
comp.Setp. 1
—20°C=0Pa
10°C=0Pa
Act. Comp: 0
Pa
SettheSAFpressure
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Showstheactualpressure
compensation.
Pressure
controlEAF
Actual: Pa
Setp.: Pa
Theactualexternalpressure
andsetpointfortheextractair
fan.
Onlyvisibleiftheunitis
conguredfor"Pressure
control"(VAV).
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
13
SystemairSverigeAB
Page 16
Mainmenuitem
→Timesettings
Sub-menuitem1 Sub-menuitem2
Pressurecontrol
EAF
Setp1/1: 200
Pa
Setp1/2: 100
Pa
Outdoor
comp.Setp. 1
—20°C=0Pa
10°C=0Pa
Act. Comp: 0
Pa
ExtraflowEAF
Actual: m³/h
→ Time/Date
Explanations
Settheexternalpressureset
pointfornormalspeed(1/1)
andreducedspeed(1/2)forthe
supplyairfan.
SettheEAFpressure
compensationforthesettable
outdoortemperature.The
outdoorcompensationislinear
andissetusingtwoparameter
pairswhichgivethevalueofthe
compensationattwodifferent
outdoortemperatures.The
compensationcanbepositive
ornegative.
Showstheactualpressure
compensation.
Showstheextractairow
Setcorrecttimeanddate.
→TimerNormal
Speed
→ TimerReduced
Speed
NormalSpeed
Monday
Per1:
07:00–16:00
Per2:
00:00–00:00→
NormalSpeed
Monday-Friday
Per1:
07:00–16:00
Per2:
00:00–00:00
Reducedspeed
Monday
Per1:
00:00–24:00
Per2:
00:00–00:00→
ReducedSpeed
Monday-Friday
Per1:
00:00–24:00
Per2:
00:00–00:00
Set00:00-24:00forcontinuous
running.Setting00:00-00:00
inactivatestheperiod(stopsthe
unit).Normalspeedoverrides
Reducedspeedi.e.Normal
speed07:00-16:00and
Reducedspeed00:00-24:00
runstheunitonNormalspeed
07:00-16:00andReduced
speedtherestoftheday.
SetweekscheduleMonday
toSunday,Monday-Friday+
Holidayfornormalspeed.
Possibletoset2periodsper
day.
Notethesettingsinthe
commissioningrecord.
SetweekscheduleMonday
toSunday ,Monday-Friday+
Holidayforreducedspeed.
Possibletoset2periodsper
day.
Notethesettingsinthe
commissioningrecord.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
14
SystemairSverigeAB
Page 17
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
→ Extended
Extendedrunning
running
60min
Timeinext.
running
0min
→ HolidaysHolidays(mm:dd)
1:01–01—01–02
2:01–01—01–01
3:01–01—01–01
Explanations
Setthetimeforextended
running.Usedigitalinputto
forcetheunittostartorincrease
tonormalrunningevenifthe
actualmodeisOfforReduced.
Iftherunningtimeissetto0
theunitonlyrunsaslongasthe
digitalinputisclosed.
Thetimetheextendedrunning
isactiveismonitoredin"Timein
ext.Running".
It'salsopossibletosetatime
hereaswellinordertoshorten
theinitialsetperiod.
Setupto24separatepossible
holidayperiodsforafullyear.
Aholidayperiodcanbeany
numberofconsecutivedays
fromoneandupwards.
Thedatesareintheformat:
MM:DD.
Whenthecurrentdatefalls
withinaholidayperiod,the
schedulerwillusethesettings
fortheweekday“Holiday”.
→Manual/Auto
Inthismenutherunningmode
ofalltheconguredoutput
signalsandanumberofcontrol
functionscanbemanually
controlled.
Thesupplyaircontroller'soutput
signalcanbemanuallyset
(Manual/Auto )toanyvalue
between0and100%.The
temperatureoutputsignalswill
changeaccordinglyiftheyare
inAutomode.Itisalsopossible
tomanuallycontroleachof
thetemperatureoutputsignals
individually.
Sinceleavinganyofthe
outputsinmanualcontrolwill
disruptthenormalcontrol,
analarmwillbegeneratedas
soonasanyoutputissettoa
manualmode.
Supplytemp.
contr.
Auto
Manualset:
0.0
Setthesupplyairtemperature
controllertoAuto,Manualor
Off .
Settheoutputsignalbetween
0-100%.
TheoutputsY1,Y2andY3,ifin
Auto-mode,willfollowthesignal
accordingtothesetsplitvalues.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
15
SystemairSverigeAB
Page 18
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
SAF:Auto
Manualset:
0.0
EAF:Auto
Manualset:
0.0
Heating
Auto
Manualset:
100.0
Exchanger
Auto
Manualset:
0.0
Cooling
Auto
Manualset:
0.0
Explanations
SettheoutputsignalforSAF
(supplyairfan)to:Auto ,
Manual,1/2–speedor
1/1–speed.
SettheoutputsignalforEAF
(extractairfan)to:Auto ,
Manual,1/2–speedor
1/1–speed.
SettheheatingtoAuto,
ManualorOff.
Setthemanualoutput0-100%.
Settheexchangerrotorcontrol
toAuto,ManualorOff
Setthemanualoutput0-100%
SetthecoolingtoAuto,Manual
orOff
Setthemanualoutput0-100%
Note:
P1–Heating
Auto
P1–Cooling
Auto
Firedamper
Auto
Outdoorair
damper
Auto
Exhaustair
damper
Needstobeactivatedinorder
tobevisiblehere
Setthepumpcontrolforthe
heatingcoiltoAuto,OnorOff
Setthepumpcontrolforthe
coolingcoiltoAuto,OnorOff
SettheFiredampertoAuto,
Open orClose
Note:
Needstobeactivatedinorder
tobevisiblehere
Congurationofredamper
functionsaremadeat
Administratorlevel
SettheOutdoorairdamperto
Auto,OpenorClose
SettheExhaustairdamperto
Auto,OpenorClose
Auto
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
16
SystemairSverigeAB
Page 19
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Extrasequence
Y4
Explanations
SettheExtrasequencetoAuto,
ManualorOff
Auto
Manualset:
0.0
Extrasequence
Y5
Auto
Manualset:
0.0
→Settings
→Controltemp
Supplyair
control
P-band: 33.0°C
I-time: 100.0
sec
OnlyvisibleforTopvexSC
units
SettheExtrasequencetoAuto,
Manual orOff
Notusedindefaultsetting.
Inthismenugroupthesettings
fortheactivatedfunctionsare
available.Dependingonwhich
choiceshavebeenmadeinthe
congurationmenusomeofthe
possiblealternativesmaynotbe
displayed.
Set P-bandandI-timeforthe
Supplyaircontrolfunction
Note:
SeeCorrigomanual-Ventilation
applicationformoreinformation.
Extractair
control
P-band: 100.0°C
I-time: 300.0
sec
Shutdownmode
P-band: 100.0°C
I-time: 100.0
sec
Set P-bandandI-timeforthe
Extractaircontrolfunction
Note:
SeeCorrigomanual-Ventilation
applicationformoreinformation.
Set P-bandandI-timeforthe
Shutdownfunction
Note:
SeeCorrigomanual-Ventilation
applicationformoreinformation.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
17
SystemairSverigeAB
Page 20
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
→ Frost
protection
Active
Explanations
Statusforfrostprotection.
Whenrunningmodeswitchedto
"Off".
→Controlflow
orControl
pressure
→ Alarm
settings
Setpshutdown:
25.0°C
P-bandactive:
5.0°C
Faststopat
frostprotection
alarm
Yes
Sequencywith
frostprotection
Y1–Heating
FlowcontrolSAF
P-band: 2160.0
m³/h
I-time: 40.0
sec
Min. output:
0%
FlowcontrolEAF
P-band: 2160.0
m³/h
I-time: 40.0
sec
Min. output:
0%
→Alarmlimits
→Alarmdelays
→Restorealarm
Shutdowncontrollerwillcontrol
theheatingoutputtomaintaina
constantsettabletemperature
atthefrostprotectionsensorfor
thehotwatercoil.
Iffrostprotectiontemperature
fallsbelowFrost
protectionAlarmlevel
+settableP-Bandforfrost
protection,itwillrisetheinternal
signalandforcetheheating
valvetoopentoavoidfreeze-up
ofhotwatercoil.
Set thefaststopoftheunitin
caseoffrostprotectionalarmto
Yes orNo.
Frostprotectioncontrol.
IsavailableforY1heating,
Y4extrasequence oron
bothY1andY4.
OnlyshownifFancontrol
selectedtothesealternatives.
Set P-band,I-timeandMin.
outputforthesupplyairfan
whentheunitcomescongured
asFlowcontrolfrom
factory.AlternativelyPressure
control ifthatcongurationis
chosen
Set P-band,I-timeandMin.
outputfortheExtractairfan
whentheunitcomescongured
asFlowcontrolfrom
factory.AlternativelyPressure
control ifthatcongurationis
chosen
Set thealarmlimitsandallowed
deviationsforthedifferent
functions
Set thealarmdelaysand
alloweddeviationdelaysforthe
differentfunctions
Resettheservicealarm(lter
alarm).
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
18
SystemairSverigeAB
Page 21
Mainmenuitem
Darkergrayarea,login
to“Administratorlevel”
code3333
→Configuration
Sub-menuitem1 Sub-menuitem2
Restorefactory
settings: No
Restoreuser
settings: No
Saveuser
settings
No
→
Inputs/Outputs
→
Sensorsettings
→
Control
Controlfunction
Mode:
function
Cascadeextract
ctrl
Explanations
Inthismenu,itispossibleto
restoreallparameterstotheir
factorysettingsortotheuser
settingstheyweresavedas
earlier.
SelectYesorNo
Thecurrentcongurationcan
besavedinaseparatememory
areaandcanlaterberestored
usingthepreviousmenu,
Restoreusersettings.Select
Yes orNo
Setupforinputsandoutputs.
Setupofsensortypesand
controlrange.
Set typeoftemperaturecontrol
functionyouwanttheunitto
operateunder.Choosebetween
Roomcontrol,Cascade
extractctrl,Outd
comproom,Outdcomp
extrair,Supplyair
control,Outdoorcomp.
supply
Extract/supplyair
→(possibletoswitchbetween
thetwodependingonoutdoor
temp.),
Room/supplyair →(possible
toswitchbetweenthetwo
dependingonoutdoortemp.),
Fancontrol
→
Extrasequency
Y4
TopvexSC:
Modeextra
sequenceY4
Activewcool
recov
OnlyactiveforTopvexSC
Canbeconguredtoone
ofthefollowingalternatives:
Active,Activewith
coolingrecovery,
Activewithenthalpy
controlandActivewith
bothcoolingrecovery
andenthalpycontrol.
→
Extrasequency
Y5
ExtrasequenceY5canbe
conguredto ActiveorNot
active.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
19
SystemairSverigeAB
Page 22
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
→
Pumpcontrol
→ Freecooling
P1–Heating
P1–Cooling
Freecool
active: No
Explanations
Setparametersforpump
control.
If,foranyofthecontrolcircuits,
nooutputisconguredforpump
controlthesesettingswillbe
ignored.
Set freecoolingactivetoYesor
No.
Outd. temp
activation
22°C
Outd. temp
night
High: 15.0°C
Low: 5.0°C
Roomtempmin.
18°C
Hourfor
start/stop
Set theloweroutdoorday
temperaturelimitforthe
activationofthefreecooling
function.Thetemperatureof
thepreviousdayneedstobe
overthesettemperaturein
orderactivatethefreecooling
function.
Set theupperoutdoornight
temperaturelimitforthe
activationofthefreecooling
function.
Set theloweroutdoornight
temperaturelimitforthe
activationofthefreecooling
function.
Set thelowerroomtemperature
limit.Thetemperatureneedsto
beabovethisvalueforthefree
coolingfunctiontostayactive.
Ifnoroomsensorareconnected
extractairisvalid.
Set thestartandstoptimefor
thefreecoolingfunction
Freecooling
Start: 0
Stop: 7
Timetoblock
heatoutput
afterFree
cooling
60min
Fanoutputwhen
freecooling
SAF:0%
EAF:0%
Forexample Start:0 and
Stop: 6
meansthatthefreecooling
sequenceisactivebetween
00.00and06.00h.
Set thedelayinminutesfrom
thetimewherethefreecooling
sequencehasstoppeduntila
possibleheatingsequenceis
initiated,i.e.howlongacooler
roomtemperaturethanset
temperaturecanbeaccepted
Set thefanspeedinpercentage
ofthenormalspeedforeach
fanindividuallyduringthefree
coolingsequence
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
20
SystemairSverigeAB
Page 23
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Outdoorsensor
placedinintake
channel(intakeduct)
No
→ Support
Supportcontrol
control
Active: No
EAFrunning
duringSupport
contr.: Yes
Min. runtime
forsupport
ctrl: 60min
→ CO2/VOC
Control
CO2/VOCactive
Never
Type: Fan
Min. time: 60
min
Explanations
Setiftheoutdoorsensoris
placedintheintakeductornot.
ChoosebetweenNoandYes
PresetisNo.
Whenusingthecontrol
functionroomcontrolor
extractairtemperature
control,itispossibleto
utilizesupport-heatingand/or
support-cooling.Minimum
runningtimeissettable0…720
minutes(factorysetting60
minutes).Choosebetween
“Active:Y esorNo”.
(Forstartandstoptemperatures
seethe"Temperature"menu)
Set theminimumrunningtime
inminutesforsupportcontrol
Inapplicationswithvarying
occupancythefanspeeds
canbecontrolledbytheair
qualityasmeasuredbya
CO2/VOC-sensor.SeeCorrigo
manualforfurtherexplanation
Set activetoNever,Alwaysor
Iftimechanneloff.
Setwhatshouldberegulated.
SelecttypeFan
Set themin.timetheunitis
activatedbytheCO2/VOC
demandfunction
Activationlevel
1/2–speed: 800
ppm
1/1–speed: 1000
ppm
diff: 160ppm
Set theactivationlevelat1/2
speed
Set theactivationlevelat1/1
speed
Set alloweddiff.value
Sequencywith
CO2comtrol
CO2/VOCcontrolcanbeused
withmixingdampers.
Y2exchanger
SelectforuseonY2,Y4oron
bothoutputs.
→
FireFunction
Firedamper
function
Notactive
Operationwhen
alarm
Stopped
Therealarminputcanbe
conguredasNotactive,
Normallyclosedor
Normallyopen.
Chooseoperationwhenalarmis
activeStopped,Continuous
run,Normalrun,Only
SAF,orOnlyEAF
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
21
SystemairSverigeAB
Page 24
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Firealarminput
Normallyopen
Damperexercise
Explanations
Firealarminputcanbe
conguredtonormallyopenor
normallyclosed.
Firealarminputisalsoavailable
tobecongurefromdigital
inputs.
Notetheriskofatwicechanged
signalcancreateanundesired
function.
No
Activatetheredamper
exercising,choosebetween
No,Yesunitrunningor
Yesunitstopped.
Settheparametersfordamper
exerciseinthesubmenu.
→Exchanger
deicing
Exchanger
deicing
Thissectionsisforunitswith
counterowandcrossow
exchangers.
Yes
Setifexchangerdeicingwillbe
used,Yes/No
Thissectionsisforunitswith
counterowandcrossow
exchangers.
Bypass: On
Exchangerdeicingallowedwith
bypass,On/Off.
Stopdeicing:
On
Activationtemp:
0,0°C
Exchangerdeicingallowedwith
stopofthesupplyairfan(SAF),
On/Off
Outdoortemperaturelimitto
allowdeicingfunction.
StoptempSAF:
-8,0°C
Outdoortemperaturelimitfor
forcedstopdeicing,interlockof
bypassdeicing.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
22
SystemairSverigeAB
Page 25
Mainmenuitem
Sub-menuitem1 Sub-menuitem2
Explanations
Thissectionsisforunitswith
counterowandcrossow
exchangers.
SetpPressdev:
50%
Setpointinpercentofthe
pressuredeviationtostart
deicing.
Stophyst: 60%
Reductionofthepressure
deviationinpercenttocancel
deicing.
Actualsetp:
xxxPa
Actualsetpointfordeicing
presented.
Note! Thevaluecanvary,
dependingonairow.
Manualcalib:
Off
ManualcalibrationON/Off
tomakeanewcalibration
manually.
Note! Recommendedto
performthisoperationwithadry
exchangerandnormalairow.
→Cooling
recovery
Coolingrecovery
Yes
Coolinglimit:
2.0°C
Set thecoolingrecoverytoYes
orNo.
Set thecoolinglimit(the
differenceintemperature
betweenextractairandoutdoor
airthatactivatesthecooling
recovery).
→
External
setpoint
External
setpoint
Notactive
Minsetp.:
Anexternalsetpointdevicecan
beconnected.Thesetpoint
devicemustfollowthePT1000
resistancecurve.Thesetting
rangecanberestricted.
12.0°C
Maxsetp.:
30.0°C
→
Alarmsettings
Alarmno(1–100):
1
RunErrorSupply
Air
→
Communication
FunctionPort1
Slave
Function
Expansionunit
Slave
Choosebetweendifferent
communicationsSlave,
Expansionunit,Freq
conv/Presstran,
Externaldisplay,Exp
andfreqconvorExpand
extdisplay.
→FunctionPort2
Expandext
display
PDTxxC-2
Pressuredualtransmitter
module.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
23
SystemairSverigeAB
Page 26
Mainmenuitem
→Accessrights
Sub-menuitem1 Sub-menuitem2
Expansionunit1
None
Expansionunit2
None
Expansionunit3
PDTxxC-2
Expansionunit4
PDTxxC-2
→ LogonLogon
Enterpassword
xxxx
Actuallevel:
None
→ LogoffLogoff?
No
Actual
level:None
→ Change
password
Changepassword
for
Explanations
Logontoservicelevelby
enteringa4-digitcode.After
reachingthedesiredlevelgo
backwith“LEFT”arrow(press2
times)onthecontrolpanel.
Standardcodefromfactoryto
enterservicelevelis2222.Back
tooperatorlevel:111 1.T oenter
Adminlevelcode:3333.
Logoff fromAdministratorlevel
bychangingNotoYeswiththe
"OK"and"UP/DOWN"buttons
Automaticlogoffafter6minutes
ofinactivity.
Set anewpasswordforthe
levelofyourchoice.
level:None
Newpassword
xxxx
Canonlybedoneoncelogged
ontotheservicelevel.
4.4Freecoolingdescription
Thisfunctionisusedduringthewarmperiodtosaveenergybyusingcoldoutdoorair,e.g.duringnight
time,tocooldownthebuildingandtherebyreducingtheneedforcoolingduringthedaytime.
Note:
ThefollowingisonlyvalidifthefreecoolingfunctionissettoActiveintheprogrammenu.
Freecoolingisonlyactivatedwhenthefollowingstartingconditionsaremet.
Startingconditions:
•Lessthan4dayshavepassedsincetheunitwaslastinrunningmode
•Theoutdoortemperatureduringthepreviousrunningperiodexceededasetlimit(+22°C)
•Itisbetween00:00and07:00:00intheday(settable)
•Thetimeroutputsfornormalspeed,ExtendedrunningnormalandExternalstopareOff
•AtimechannelwillbeOnsometimeduringtherecentlystarted24hours.
Theunitchecksthenighttemperature(indoorandoutdoortemperature)during3minutesattheset
startinghourwhenthefansarestartedsothatthesensorscanperformatemperaturemeasurement.If
aboveconditionsaremetthefreecoolingfunctionisstarted,ifnottheunitgoesbacktoOFFposition.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
24
SystemairSverigeAB
Page 27
Iftheoutdoorsensorisnotlocatedintheoutdoorairinletductandaroomsensorhasbeenselected,
theunitwillnotstartfreecoolingaslongasallthetemperaturesarenotwithinthestartandstop
temperatureintervals.
Stopconditions:
•Outdoortempabovethesetmaxvalue(+18°C)orbelowthesetminvalue(condensationrisk,+10°C)
•Theroomtemp/extractairtempisbelowthesetstopvalue(+18°C)
•Oneofthetimeroutputsfornormalspeed,ExternalstoporExtendedrunningnormalisOn
•Thetimehaspast07:00:00.
Ifanystopconditionsisfullledafterthreeminutes,theunitwillstopagain.Otherwise,operationwill
continueuntilastopconditionisfullled.
Whenfreecoolingisactive,thefansrunatnormalspeedorthesetvalueforpressure/owcontroland
thedigitaloutputFreecoolingisactive.TheoutputsY1-Heating,Y2-Heatexchangerand
Y3-Cooling areshutdown.Afterfreecoolinghasbeenactivated,theheatingoutputisblockedfor60
minutes(congurabletime).Whenusingfreecooling,anoffsettonormalfancontrolsetpointisadjustable.
5Maintenance
5.1Important
Danger
•MakesurethattheMainssupplytotheunitisdisconnectedbeforeperforminganymaintenanceor
electricalwork!
•Allelectricalconnectionsmustbecarriedoutbyanauthorizedinstallerandinaccordancewith
localrulesandregulations.
Warning
•AlthoughtheMainssupplytotheunithasbeendisconnectedthereisstillriskforinjuryduetorotating
partsthathavenotcometoacompletestandstill.
•Bewareofsharpedgesduringmountingandmaintenance.Useprotectiveclothing.
5.2Maintenanceintervals
Thetablebelowshowsrecommendedmaintenanceintervalsfortheunitandtheinstallation.T o
ensurealongoperationlifetimefortheunititisimportanttoperformmaintenanceaccordingtobelow
recommendationsandthattheyareperformedaccordingtotheoperationandmaintenanceinstructions.A
thoroughandrecurrentmaintenanceisamustforavalidguarantee.
Typeofmaintenance Onceayear
Whennecessary
Cleaningtheheatexchanger.
Cleaningthefans.
Cleaningextractlouvresand
supplyairdiffusers.
Cleaningtheoutdoorairintake.
Cleaningtheductsystem.
1.Orinaccordancewithlocalrulesandregulations
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
X
X
X
25
X
1
X
SystemairSverigeAB
Page 28
5.3Maintenanceinstructions
5.3.1ChangingSupply/Extractairlter
Thebagltercannotbecleanedandmustbechangedwhennecessary .Newlterscanbeorderedfrom
Systemair.Operationtimebetweenlterchangesdependsontheairpollutionattheinstallationsite.A
differentialpressureswitchindicateswhenit’stimetochangethelters.Thiswilltriggeranalarmin
thecontrolpanel.
Whenthisoccursdothefollowing:
1.Replacethelterswithnewonesasdescribedbelow.
2.Acknowledgethealarmbypressingtheredbuttononthecontrolpanel(pos.1gure4)followedbyOK
(pos.4gure4).
3.Choose→AcknowledgebypressingOK.
Theltersaretakenoutaccordingtobelowprocedure:
1
Releasethelterframebypullingtheltersupport
bars.
2
Tiltthesupportbarstotheback.
3
Itisnowpossibletofoldthelterandframe
backwards.Thisisespeciallyimportantifthereis
lackofspaceinfrontoftheunitandthesliding
doorkitisused.
Theltercannowbetakenoutoftheunit.
4
Insertthenewlterandfastenitagainsttheinletsealwiththeltersupportbars.
Makesurethelteristtedtightallaroundtheframe.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
26
SystemairSverigeAB
Page 29
5.3.2Checkingtheheatexchanger
Afteralongtimeofusedustmaybuildupintheexchanger(pos.5,gure1)andblocktheairow.Itis
importanttocleantheexchangerregularlytomaintainhighefciency.TheheatexchangerintheT opvex
FR03–11canbetakenoutoftheunit.Washinhotsoapywaterorusepressureair.Donotusedetergent
containingammonia.
Note:
Makesurethattherotormotorisnotexposedtomoisture.
5.3.2.1Dismountingtheheatexchangerblockonceilingmountedunits
1
Removetheexchangercoverplateinthecentreof
theunitbyunscrewingthe4screwsinthecorners
oftheplate.
Removingtheplateisonlypossibleafteropening
bothinspectiondoors.
2
Thereare4screws(2oneachside)holdingthe
heatexchangerblock(ModelsFR08andFR11
have8screws,4oneachside).Whenremoving
theheatexchangerstartwithcheckingthatthe
screwmarked“A”istightenedproperly.Remove
thescrewmarked“B”completelyasshowninthe
gureafterwhichthescrewmarked“A”isloosened
carefully,justenoughtoallowtheexchangerframe
toslideinthetracks.
3
Slideouttheexchangerblockuntiltheendofthe
tracks.
Warning
Theheatexchangerblockisheavy.Use
propersupportdevicewhentakingouttheheat
exchangerblockformaintenance!
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
27
SystemairSverigeAB
Page 30
4
Afternishedcleaning/maintenance,pushbacktheheatexchangerblockandfastenallscrewstightly.
5.3.2.2Dismountingtheheatexchangerblockonoormountedunits
1
Loosenallscrewscompletelyholdingtheheatexchangerblock.
2
Removetheheatexchangerblockcompletelyby
liftingitstraightup.
Caution
Theexchangerblockisheavy,makesureto
useproperliftingdeviceorsufcientnumberof
personstolifttheheatexchangeroutoftheunit
Table2:Weightofheatexchangerblock
Model
FR03 31
FR06 43
FR08
FR11 71
Weightofheatexchanger
block(kg)
55
5.3.3Checkingthefans
5.3.3.1Checkingthefans
Eveniftherequiredmaintenance,suchaschangeoflters,iscarriedoutdustandgreasemayslowly
buildupinsidethefans(pos.1and2,gure1).Thiswillreducetheefciency.
Thefanscanbedismountedbylooseningthe4screwsonthefancasing(gure5).TopvexFR06–1 1have
afansupportbracketthatneedstoberemovedbyloosening4screws.Thefansmaybecleanedwith
aclothorasoftbrush.Donotusewater.Whitespiritcanbeusedtoremoveaccumulationswhichare
otherwisedifculttoremove.Allowdryingproperlybeforeremounting.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
28
SystemairSverigeAB
Page 31
Fig.5Dismountingthefans
5.3.4Cleaningextractlouvresandinletdiffusers
Thesystemsuppliestreatedoutdoorairtothebuildingandextractstheusedindoorairviatheductsystem
anddiffusers/louvres.Diffusersandlouvresaremountedinceilings/wallsinbedroom,livingroom,wet
rooms,WCetc.Removediffusersandlouvresandwashinhotsoapywaterifrequired.Diffusers/louvres
mustbeputbackwiththeiroriginalsettingsandpositionsinordernottounbalancethesystem.
5.3.5Checkingtheoutdoorairintake
Leavesandpollutioncouldpluguptheairintakegrilleandreducetheunit’scapacity.Checktheairintake
grilleatleasttwiceayearandcleanifnecessary .
5.3.6Checkingtheductsystem
Dustandgreasesettlementsmaybuildupintheductsystemevenifltersarechangedregularly.This
willreducetheefciencyoftheinstallation.Theductsshouldthereforebecleaned/changedwhen
necessary.Steelductscanbecleanedbypullingabrush,soakedinhotsoapywaterthroughtheductvia
diffuser/louvreopeningsorspecialinspectionhatchesintheductsystem(iftted).
5.3.7ChangingtheInternalBattery
Note:
ThisprocedurerequiresknowledgeofproperESDprotection;i.e.anearthedwristbandmustbeused!
Whenthealarm”InternalBattery”isactivatedandthebatteryLEDlightsupred,thebatteryforbackupof
programmemoryandreal-timeclockhasbecometooweak.Thebatteryisreplacedasdescribedbelow.
Abackupcapacitorsavesthememoryandkeepstheclockrunningforatleast10minutesafterthepower
supplyisremoved.Therefore,ifthebatteryreplacementtakeslessthan10minutes,therewillbenoneed
toreloadtheprogram,andtheclockwillcontinuetorunnormally .
ThereplacementbatterymustbeofthetypeCR2032.
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
29
SystemairSverigeAB
Page 32
1
Removethecoverbypressingdownthelocking
torquesattheedgeofthecoverusingasmall
screwdriver,andatthesametimepullingthe
edgesoutwards.
2
Gripthebatteryrmlywithyourngersandliftit
upwardsuntilitrisesfromitsholder.
Pressthenewbatteryrmlydownintoplace.Note
thattopreservecorrectpolarity ,thebatterycan
onlybeinsertedthe“rightwayround”.
5.4Troubleshooting
Shouldproblemsoccur,pleasecheckorcorrectthefollowingbeforecontactingyourservicerepresentative.
Alwayscheckifthereareanyalarmsactiveinthecontrolpanel.
1.Fan(s)donotstart
•Checkifthereareanyalarmmessages.
•Checkthatthefusesarenotdefect(pos.8gure3).
•Checkthesettingsinthecontrolpanel(times,weekschedule,auto/manualoperationetc.).
2.Reducedairow
•Checkthesettingsformediumandlowfanspeed.
•Checkthattheoutdoor/exhaustairdamper(ifused)opens.
•Checkifltersneedchanging.
•Checkifdiffusersandlouvresneedcleaning.
•Checkdiffuser/louvreopenings.
•Checkiffansandexchangerblockneedcleaning.
•Checkiftheroofunitorairintakeisclogged.
•Checkductsforvisibledamageand/orbuildupofdust/pollution.
3.Coldsupplyair
•Checkthecontroltemperatureonthecontrolpanel.
•Checkiftheemergencythermostathastripped.Ifnecessarypresstheredbutton,ontheelectrical
heater(pos.9,gure1)withapointedtool.
•Checkiftheextractltermustbechanged.
•Checkifthefanshavestoppedduetooverheating.Ifsothethermalcontactmighthavetripped
(showsasFanalarminthecontrolpanel).
4.Noise/vibrations
•Checkthattheunitiscompletelyleveled.
•Cleanthefanimpellers.
•Checkthatthescrewsholdingthefansaretightenedproperly.
5.4.1Alarms
Thealarmbutton(pos.1,gure4)opensthealarmqueue.Whenpressingthisbuttonactiveand
non-acknowledgedalarmswillbedisplayedinthemenuwindow.Thealarm-LED(pos.2,gure4)is
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
30
SystemairSverigeAB
Page 33
ashingiftherearenon-acknowledgedalarmsandsteadyifthealarmsarestillactivebuthavebeen
230 / 4 0 0 V 2 5 A 5 0 H z
Syst e m a i r S v e r i g e A B
I n d u s t r i v ä g e n 3
SE-7 3 9 3 0 S k i n n s k a t t e b e r g
S w e d e n
4016 W I P 2 3 2 2 5 k g
V e r . A
e r i a l . n o : 1 2 3 4 / 5 6 7 8 9 1 - 0 0 0 1 / 1 4 0 2 1 4
T o p v e x X X X X
16kW 1 6 k W
www .systemair .com
2
3 4
5
acknowledged.Iftherearemultiplealarms,useUP/DOWNtomovebetweenthem.Analarmcanbe
acknowledgedorblockedbyusingOKandUP/DOWN.T oabortandgobacktostartmenupresscancel
andthenpressLEFT .
Seecommissioningrecordforanoverviewofpossiblealarms.
6Service
Beforecallingyourservicerepresentative,makeanoteofthespecicationandproductionnumberfrom
thetypelabel(gure6)
Fig.6Typelabel
Position Description
1 Itemnumber
2 Productionordernumber
3
4 Productiondate
5
Consecutivenumber
Productcode(productspecication)
TopvexFR03,FR06,FR08,FR11 OperationandMaintenanceInstructions
129451
31
SystemairSverigeAB
Page 34
lastpage