SystemAir TCA 150D Operating Instructions Manual

TCA 150D
part. no. 32186
Control module for temperature
Operating Instructions
Software version: D2033A from Version 1.00
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
english
1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . 4
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Operational area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.2 Installation location for agriculture . . . . . . . . . . . . . . . . . . . . . . . 6
4.3 Temperature inuences during commissioning . . . . . . . . . . . . . . 6
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.2 EMC-compatible installation of control lines . . . . . . . . . . . . . . . . 7
5.3 Connection Voltage supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.4 Connection of sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.5 Output voltage 0 - 10 V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.6 Input for switch over Setpoint 1 / Setpoint 2 . . . . . . . . . . . . . . . . 8
6 Device construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.1 Select operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.2 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.3 Menues of operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.4 Characteristic curve temperature sensor 2.00 . . . . . . . . . . . . . . 12
7.5 Temperature controller
2.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
8.1 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operating Instructions TCA 150D
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
2/17
9 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
9.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
9.3 Dimensions [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
9.4 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operating Instructions TCA 150D
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
3/17
1 General notes

1.1 Structure of the operating instructions

Before installation and start-up, read this manual carefully to ensure correct use! We emphasize that these operating instructions apply to specic units only, and are in no way valid for the complete system! Use these operating instructions to work safely with and on the device. They contain safety instructions that must be complied with as well as information that is required for failure-free operation of the device. Keep these operating insturctions together with the device. It must be ensured that all persons that are to work on the device can refer to the operating instructions at any time.

1.2 Target group

The operating instructions address persons entrusted with planning, installation, com­missioning and maintenance and servicing and who have the corresponding qualica­tions and skills for their job.

1.3 Exclusion of liability

To allow for future developments, construction methods and technical data given are subject to alteration. We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. We accept no liability for damage caused by misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modications.

1.4 Copyright

These operating instructions contain copyright protected information. The operating instructions may be neither completely nor partially photocopied, reproduced, translated or put on data medium without previous explicit consent. Infringements are liable for damages. All rights reserved, including those that arise through patent issue or registra­tion on a utility model.
2 Safety instructions
Mounting, electrical connection, and start-up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations (e.g. DIN EN 50110 or DIN EN 60204)!
Persons entrusted with the planning, installation, commissioning and maintenance and servicing in connection with the device must have the corresponding quali­cations and skills for these jobs. In addition, they must be knowledgeable about the safety regulations, EU directives, rules for the prevention of accidents and the corresponding national as well as regional and in-house regulations.
Operating Instructions TCA 150D General notes
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
4/17
The equipment is to be used solely for the purposes specied and conrmed in the order. Other uses which do not coincide with, or which exceed those specied will be deemed unauthorised unless contractually agreed. Damages resulting from such unauthorised uses will not be the liability of the manufacturer. The user will assume sole liability.
It is strictly forbidden for work to be carried out on any components while they are connected to live voltage.
The safe isolation from the supply must be checked using a two-pole voltage detector.
The owner is obliged to ensure that the device are operated in perfect working order only.
Inspect electrical equipment periodically: retighten loose connections – immedi­ately replace damaged lines and cables.
Never clean electrical equipment with water or similar liquids.
A separate fault and performance monitoring-system with an alarm signal function is necessary in order to prevent personal injuries and material damages during malfunctions and in case the device fails. Substitute operation must be taken into consideration!
3 Product overview

3.1 Operational area

Temperature control for e.g.: extraction systems, warm-air heaters, air curtain installa­tions, liquid-cooling, chillers. Controlled output (0 - 10 V) e.g. for activating a speed controller for fans. Fans with integrated controller and input 0 - 10 V can be activated directly.

3.2 Function

The measured actual value at the sensor is compared with the adjusted target value. Output voltage and thus fan speed is controlled automatically depending on the adjusted parameters. Alternatively the device can be operated as temperature sensor. Output 0 - 10 V in this mode proportional to the adjusted measuring range (max. -50...150 °C).

3.3 Storage

The device must be stored in its original packaging in a dry and weather-proof room.
Avoid exposure to extreme heat and cold.
Avoid over-long storage periods (we recommend a maximum of one year).

3.4 Disposal / recycling

Disposal must be carried out professionally and environmentally friendly in accordance with the legal stipulations.
Operating Instructions TCA 150D Product overview
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
5/17
4 Mounting

4.1 General notes

Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental inuences:
Before installation remove the device from the packing and check for any possible shipping damage!
Assemble the device on a clean and stable base. Do not distort during assembly! Use the appropriate mounting devices for proper installation of the unit!
Do not mount equipment on vibrating base!
When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock loads. Any banging shut of doors that are integrated into these lightweight walls, can result in extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
The device should be installed in a location where it will not be disturbed, but at the same time can be easily accessed!
Any cable ducts openings not used must be sealed!
Care must be taken to avoid direct radiation from the sun!
The device is designed for vertical installation (cable inlet down). A horizontal or reclined installation is only permissible after technical release of the manufacturer!

4.2 Installation location for agriculture

In order to avoid damage caused by ammoniac vapours, the controller shall not be installed in the stable, but rather in an outhouse wherever possible.
4.3 Temperature inuences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by storing the controller at room temperature!
Operating Instructions TCA 150D Mounting
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
6/17
5 Electrical installation

5.1 Safety precautions

Danger due to electric current
Work on electric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accord­ance with electrical engineering regulations.
The programming of the equipment takes place with switched on supply voltage by opened cover and voltage for change-over Setpoint 1/2. Use power supplies which guarantee reliable electrical isolation of the operating voltage as per IEC/­DIN EN 60204-1. Consider also the general requirements for PELV circuits in accordance with IEC/DIN EN 60204-1.
Inspect electrical equipment periodically: retighten loose connections – immedi­ately replace damaged lines and cables.
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this manual ( Connection diagram)!
5.2 EMC-compatible installation of control lines
Pay attention to maintain sufcient distance from powerlines and motor wires to prevent interferences. The control cable may not be longer than 30 m. Screened control cables must be used when the cable length is longer than 20 m!

5.3 Connection Voltage supply

Connection Voltage supply at terminals: “+Ub” and “GND”. Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specications ( Technical data and nameplate afxed to the side).

5.4 Connection of sensor

Connection of temperature sensor for measuring actual value (not in scope of delivery) to terminals TF. It is possible to connect sensors of series TF.. (KTY81-210) or PT1000 temperature sensors. It must be paid attention to no polarity. For a high interference immunity a capacitor must be connected directly to the sensor (1 nF parallel). With temperature sensors type TF.. (KTY81-210) a capacitor is integrated.
Attention! Never apply line voltage to analog inputs!
Operating Instructions TCA 150D Electrical installation
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
7/17
5.5 Output voltage 0 - 10 V
Connection to Terminals A - GND (I
max
Technical data).
It is not permissible to connect outputs of several devices to each other!

5.6 Input for switch over Setpoint 1 / Setpoint 2

Via voltage at terminals “1 and 2 (10... 24 V DC) a switchover between Setpoint 1 and Setpoint 2 is possible (note polarity
connection diagram).
20.0 °C
Setpoint 1
None Voltage at terminals 1 and 2 = adjustment for Setpoint1 active.
15.0 °C C
Setpoint 2
Voltage at terminals 1 and 2 = adjustment for Setpoint 2 active.
The active Setpoint is indicated in the menu INFO, an active Setpoint 2 is signalized by the moon symbol.
6 Device construction
Screw off the hinged cover to proceed with electrical connection and programming. Subsequently close carefully!
+Ub
GND A GND
P
05.05.2010
v_ctg_bedien.vsd
!
D
27.5 °C
Actual Value
TF
TF
1
2
D
LC-Display Moon symbol = Adjustment for Setpoint 2
active ! = Exceeding measuring range (sensor in-
terruption / sensor short-circuit)
+Ub / GND Voltage supply
A / GND Output signal 0 - 10 V
TF / TF
Connection temperature sensor (KTY81­210 or PT1000)
1 / 2
Voltage input for switch over Setpoint 1 / Setpoint 2
Multipurpose LC display and internal keyboard
27.5 °C
Actual Value
Text line 1 with 16 gures for display of actual and desired values Text line 2 with 16 gures for display of menu text
P
P Program key and open menu
Menu selection, reduce value Menu selection, increase value
+ ESC-key combination, Escape = leave menu
Operating Instructions TCA 150D Device construction
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
8/17
7 Programming

7.1 Select operation mode

Information
Simple installation is possible through the selection of the preprogrammed mode of operation. This determines the basic function of the device, factory set
2.01 .
Mode Function
2.00
Temperature sensor: output 0...10 V proportional to measuring range
2.01
Temperature controller (P): output 0...10 V depending on adjusted Setpoint an measured actual value (Factory setting)

7.2 Menu structure

27.5 °C
Actual Value
Display after turning on the voltage supply.
Switch over between actual value display and INFO with the key shortcut for Escape (ESC = + ).
INFO
Example for Mode
2.01 (Factory setting)
INFO
▼ ▲
SETTING
▼ ▲
BASE SETUP
P ESC P ESC P ESC
20.0 °C
Actual Value
20 °C
Setpoint 1
2.01
Mode
▲ ▼ ▲ ▼ ▲ ▼
20 °C
Setpoint 1
15 °C
Setpoint 2
KTY81-210
Sensortype
▲ ▼ ▲ ▼ ▲ ▼
0.0 V
Uout
5.0 K
Pband
0.0 K
Offset
▲ ▼ ▲ ▼ ▲ ▼
2058
Resistor
0.0 V
Min. Uout
OFF
MSCO
▲ ▼ ▲ ▼ ▲ ▼
0.08
UNIcon
10.0 V
Max. Uout
ON
Value>Set = n+
Selection of the menu group (e.g. BASE SETUP) to the right through the -key, to the left through the -key.
Operating Instructions TCA 150D Programming
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
9/17
You can go to the menu items in the menu groups (e.g. mode) by using the P key. Use the arrow keys to move up and down within the menu group. To make adjustments, press the P key after selecting the menu item. If the previously set value starts to ash, it can be adjusted with the + keys and then saved with the P key. To exit the menu without making any changes, use the Esc short-key, i.e., the originally set values remain.
Reprogramming Mode
2.01 to 2.00 in “BASE SETUP”
1 2 3
4
5 6 7
2.01
Mode
P
«2.01»
Mode
«2.00»
Mode
P
2.00
Mode

7.3 Menues of operating modes

Parameter Factory setting User Set-
ting
Function
Mode
2.00 2.01 Mode
INFO
Actual Value 27.1 °C 27.1 °C Display actual temperature
Setpoint 1 - 20.0 °C Display active Setpoint
Uout 5.0 V 5.0 V Magnitude of the output voltage 0...10 V
Resistor 2049 2049
current resistance value of the temperature sensor
UNIcon 1.00 1.00 software version
SETTING
Setpoint 1 - 20.0 °C
Setpoint1 Setting range: -50.0...+150.0 °C Factory setting: 20.0 °C
Setpoint 2 - 15.0 °C
Setpoint 2 active, if voltage at terminals 1, 2 Setting range: -50.0...+150.0 °C Factory setting: 15.0 °C
Pband -
5.0 K
Pband Setting range: 1.0...50.0 K Factory setting: 5.0 K
Min. Uout 0.0 V 0.0 V Setting minimal output voltage
Max. Uout 10.0 V 10.0 V Setting maximal output voltage
Operating Instructions TCA 150D Programming
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
10/17
Parameter Factory setting User Set-
ting
Function
BASE SETUP
Mode
2.00 2.01 Mode selection
Sensortype KTY81-210 KTY81-210
Setting type of sensor: KTY81-210 or PT1000
Range min. Tem­perature
-50 °C -
Setting measuring range, minimum temper­ature value
Setting range: -50...150 °C Factory setting: -50 °C
Range max. Temperature
150 °C -
Setting measuring range, maximum tem­perature value
Setting range: 150...-50 °C Factory setting: 150 °C
Offset 0.0 K 0.0 K Sensor offset
MSCO - OFF
Minimum speed cut off
|
MSCO|: |OFF| (factory setting)
If Min. Uout is adjusted (e.g. 2.0 V), than no diconnection of the output takes place (does not go under Min. Uout).
|
MSCO|: |-2.0 K| (example)
It takes place a disconnection from Setting Min. Uout to 0, if the given difference is reached related to the Setpoint.
At a plus value (+) before reaching the de­sired value
At a minus value (-) after falling below the desired value.
Hysteresis
|H|
ON /OFFs: approx. 1 K
Setting range: -10.0 K...+10.0 K
Value>Set = n+ - ON
Controller function
|
Value>Set = n+|: |ON| Cooling = increas­ing modulation for increasing actual value over Setpoint.
|
Value>Set = n+|: |OFF| Heating = increas­ing modulation for decreasing actual value below Setpoint.
- Parameter for selected mode not available
Operating Instructions TCA 150D Programming
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
11/17

7.4 Characteristic curve temperature sensor 2.00

Uout
[V]
10
Actual Value
[°C]
Range min. value -50 °C Range max. value 150 °C
5
0
50 100
150-50
Range min. value 0 °C Range max. value 100 °C
05.05.2010
v_kennnl_ctg_temp_sens.vsd

7.5 Temperature controller 2.01

Functional diagrams temperature control
Cooling:
|
Value>Set = n+|: |ON
|
20 °C
Setpoint
05.05.2010
v_temp_cool_ctg.vsd
24 °C
Uout
[V]
5
10
Actual Value
[°C]
Min. Uout = 3.5 V Max. Uout = 8.5 V
Min. Uout = 0.0 V Max. Uout = 10.0 V
4 K
Pband
Heating: |Value>Set = n+|: |OFF
|
20 °C
Setpoint
4 K
Pband
05.05.2010
v_temp_heat_ctg.vsd
16 °C
Max. Uout = 10.0 V Min. Uout = 0.0 V
Max. Uout = 8.5 V Min. Uout = 3.5 V
Uout
[V]
Actual Value
[°C]
10
5
Operating Instructions TCA 150D Programming
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
12/17
Minimum speed cut off
10
Min. Uout = 3.5 V Max. Uout = 10.0 V
20 °C
Setpoint
7 K
Pband
27 °C
06.05.2010
v_min_luft_abschalt_ctg.vsd
Uout
[V]
Actual Value
[°C]
5
H
Msco. = OFF
Msco. = -2.0 K
8 Start-up

8.1 Procedure

1. You must mount and connect the device in accordance with the operating instruc­tions.
2. Double check that all connections are correct.
3. The supply voltage must match the information on the rating plate.
4. Set the operating Mode in the BASE SETUP (factory settings
2.01 ).
5. When saving the Operating Mode, the factory settings are stored. Therefore the settings you have made, e.g. in SETTING are lost.
Attention, electrostatic sensitive devices!
Be sure to ground the board at a suitable point in order to prevent damage to the electronic components being caused by electrostatic discharges. Such damage could occur, e.g., if a metal water pipe or heating line are briey touched.
Operating Instructions TCA 150D Start-up
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
13/17
9 Enclosure

9.1 Technical data

Type TCA 150 D
Part-No. 32168 (320048-42)
Measuring range -50...150 °C (external sensor KTY81-210 or
PT1000)
Voltage supply U
B
10 V...24 V DC Protected against reverse polarity
@ U
B
10 V DC @ UB 13...24 V DC
Max. load output 0 - 10 V (short-circuit-proof)
0,3 mA 10 mA
Max. current consumption ca. 6 mA 14 mA
LC-Display double-row (max. 16 digits each)
Housing Cover ABS, bottom Polyamid PA 6.6
Fire protection classication UL 94 HB
Protection class IP54 according EN 60529
Weight approx. 200 g
Permissible ambient temperature -10 °C...50 °C
Permissible rel. humidity 85 % no condensation
Interference emission according EN 61000-6-3 (domestic household
applications)
Interference immunity according 61000-6-2 (industrial applications)
Operating Instructions TCA 150D Enclosure
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
14/17

9.2 Connection diagram

GND A GND
1
2+Ub
MCTE03K1
05.10.2010
TCA 150D
Eingang
Input
10...24 V DC (I
max
= 6 mA)
+
1
Ausgang
Output
0...10 V
(I
max
= 0.3 mA)
+
2
10...24 V DC
+
4
Ri = 4 kΩ
0 1
0 = Setpoint 1 1 = Setpoint 2
q
TF..
TF TF
KTY 81-210 PT 1000
3
+
-
1 Voltage supply 10...24 V DC 2 Output 0...10 V 3 Temperature sensor KTY 81-210 or PT 1000 4 Voltage input for switch over Setpoint 1 / Setpoint 2
Operating Instructions TCA 150D Enclosure
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
15/17
9.3 Dimensions [mm]
GM00009A
12.05.2010
104
70
95
4,5
114
108
56
Operating Instructions TCA 150D Enclosure
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
16/17

9.4 Manufacturer reference

Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact:
Systemair Industrievägen 3 73930 Skinnskatteberg Telefon:+46 (0) 222 440 00 Telefax:+46 (0) 222 440 99 mailbox@systemair.se www.systemair.se
Operating Instructions TCA 150D Enclosure
L-BAL-E119-GB 1318 Index 002 Part.-No. 00163357-GB
17/17
Loading...