SystemAir SYS WSC 86 Installation & Owner's Manual

Page 1
INSTALLATION & OWNER’S
MANUAL
SYS WSC 86
Wired Simplified Controller
Thank you for purchasing the wired controller.
This manual describes the safety precaution requirement of using this controller.
Page 2
Read this manual carefully and be sure you understand the information before attempting to use the controller.
Keep this manual where it is readily accessible after reading it through.
● If another user operates the controller in the future, be
sure to hand over this manual to the new user.
Page 3
Contents
Installation .........................................................................................................1
1. Safety Precautions .......................................................................................... 1
2. Accessories ..................................................................................................... 3
3. Installation Procedure...................................................................................... 4
Operation ........................................................................................................... 9
1. Safety Precautions .......................................................................................... 9
2. Parts of the Wired Controller......................................................................... 11
3. Icons in the Display ....................................................................................... 13
4. Operation Guide ............................................................................................ 13
Field Setting..................................................................................................... 24
1. Restore Factory Default ................................................................................ 24
2. Query and Set the Indoor Unit Address......................................................... 25
3. Commissioning Parameter Settings .............................................................. 26
4. Query Operations .......................................................................................... 33
5. Error Display.................................................................................................. 37
Troubleshooting .............................................................................................. 40
Page 4
Installation
1. Safety Precautions
Please read these Safety Precautions carefully before installing the wired controller.
This manual classifies the precautions into WARNING and CAUTION. They both contain
important information regarding safety. Be sure to follow all the precautions below.
After completing the installation, conduct a trial operation to check for faults and explain to
the customer how to operate the controller with the aid of the operation manual. Ask the customer to store the installation manual along with the operation manual for future reference.
Ask your dealer or qualified personnel to carry out installation work.
Do not attempt to install the wired controller yourself. Improper installation may result in leakage, electric shocks or fire.
Consult your local dealer regarding relocation and reinstallation of the wired controller.
Improper installation work may result in leakage, electric shocks or fire hazards. Install the wired controller in accordance with the instructions in this manual. Improper installation may result in water leakage, electric shocks or fire.
Failure to follow these instructions properly may result in personal injury or loss of life.
Failure to observe these instructions properly may result in property
damage or personal injury, which may be serious depending on the
circumstances.
Identifier
Meaning
Warning
Caution
Warning
1
Important
Indicates a useful hint or additional information.
Page 5
Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in the unit falling down, water leakage, electric
shocks or fire.
Install the wired controller on a foundation strong enough to withstand the weight of the
wired controller.
Insufficient strength may result in the wired controller falling down and causing injury.
Electrical work must be performed in accordance with the relevant local and national regulations and with the instructions in this manual.
Be sure to use a dedicated power supply circuit only. Insufficient power circuit capacity and
improper workmanship may result in electric shocks or fire. Always perform installation work with the power turned off. pressing electric parts may result in electric shock.
Do not disassemble, reconstruct or repair.
This may result in electric shock and/or fire.
Make sure that all wiring is secured, the specified wires are used and that there is no strain
on the terminal connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or fire.
The choice of materials and installations must comply with the available national and international standards.
To avoid leakage and electric shock due to entry of water or insects, fill the wiring through
hole with putty.
To avoid electric shocks, do not operate with wet hands. Do not wash the wired controller with water, as this may result in electric shocks or fire. When the follow me function of the wired controller is used, select the installation location
while considering it should be a place:
1).Where the average temperature in the room can be detected.
2).Which is not exposed to direct sunlight.
3).Which is not near a heat source.
4).Which is not affected by the outside air or air draught due to, for example, opening/closing of doors, the air outlet of the indoor unit or the like.
Caution
2
Page 6
2. Accessories
Please check that you have all the following parts.
Please prepare the following parts on site.
1
2
2
No.
Name
Schematic Qty.
Remarks
No.
Name
Qty.
Remarks
Philips head screw, M4X25mm
2
3
1
2
3
4
5
Plastic support bar
φ5X16mm
Operation and Installation
Manual
86 electrical box
2-core shielded copper wires
Wiring tubes (insulation suite)
Big Phillips screwdriver
Small slotted screwdriver
General specification for electrical box,
which is embedded into the wall.
2*AWG16-AWG20, pre-embedded
into wall.
Longest wiring length is 200 metres.
Pre-embedded into wall.
To install the Philips screws.
To dismantle the bottom lid of the wired controller.
Used to install the wired
controller on the electrical
box
Used to install the wired
controller on the electrical
box
1
1
1
1
1
1
3
/
Table 2.2
Table 2.1
Page 7
Make sure to refer to "1. Safety Precautions" to determine the location.
3-2 Structural Dimensions
3-3-1 Insert a small slotted-head screwdriver into the bottom slot of the wired controller and
rotate in the direction indicated to remove the rear cover of the wired controller. Pay attention to the direction of rotation to prevent any damage to the rear cover of the wired controller. (see Figure 3.3)
3-3 Rear Cover Installation
3. Installation Procedure
3-1 Determine Where to Install the Wired Controller
Figure 3.1 Figure 3.2
Screwdriver rotation direction
Slotted screwdriver
Figure 3.3
RT1
FOLLOW ME
4
86mm
20mm
86mm
60mm
41.7mm
Page 8
3-3-2 Use a cutting tool to adjust the height of the two plastic support bars (accessory 2) to match the standard length of the screw pillars of the electrical box to the wall surface. Make sure that the support bars are level on the wall when the screw pillars of the electrical box are mounted. (see Figure 3.4)
3-3-3 Once the heights of the plastic support bars are adjusted, fix the bars on the rear cover. (see Figure 3.5)
Screw post of electrical box
Fix the support bars in the
direction of the arrow
Use a cutting tool to adjust the lengths of
the two plastic support bars
Figure 3.4
Figure 3.5
Warning
When using the small slotted screwdriver to open the rear cover of the wired
controller, be careful not to damage the PCB inside.
Do not touch the PCB of the wired controller.
5
h
h
Page 9
Figure 3.6
To X1/X2 of indoor unit
Cross recessed
head screw
Electrical box
Rear cover of
wired controller
3-3-4 Take the shielded wiring that has been pre-embedded in the wall, and thread it through the wire hole of the rear cover. Use the Philips head screws (accessory 1) to fix the rear cover of the wired controller to the electrical box via the support bars. Make sure that the rear cover
is not deformed after being installed (see Figure 3.6).
3-4-1 Wiring specification
• The rear cover may be deformed if the screw is too tight.
• Prepare the electrical box and the 2-core shielded copper wire on site.
• Do not touch the PCB of the wired controller.
Important
Caution
!
3-4 Wiring
6
Type 2-core shielded copper wire
AWG 16-20
Maximum 200m
Diameter
Length
Table 3.1
Page 10
Figure 3.7
1-to-1 1-to-1 1-to-1
One controller to one indoor unit connection method
One controller to one indoor unit connection method
Two controllers to one indoor unit connection method
3-4-2 Communication wiring
• The communication between the indoor unit and wired controller is bi-directional
communication. The parameters displayed on the wired controller are refreshed in real time according to changes in the parameters of the indoor unit.
• X1 and X2 are terminals to connect the indoor unit and wired controller. There is no polarity between X1 and X2.
• The longest wiring length between the wired controller and indoor unit is 200 meters.
P/Q/E
P/Q/E P/Q/E
P/Q/E
X1/X2
○○○
X1/X2
X1/X2
7
Page 11
Figure 3.8
• For the two controllers to one indoor unit connection method, two wired controllers control the same indoor unit, where one controller will be the "Main", and the other be the
"Secondary". Refer to "Field setting". The default setting of the wired controller is set to main controller.
• This method is only available for two WDC-86E/KD wired controllers.
Two controllers to one indoor unit connection method
Not allowed
2-to-1
1-to-1
2-to-1
3.5 Install Main Body of Wired Controller
Take the shielded wiring that has been pre-embedded in the wall and pass it through the wiring hole of the rear cover of the wired controller. Once connected, connect the wiring to the terminal X1/X2 (CN2) of the wired controller, and fix the wired controller to the rear cover. (see
Figure 3.9)
Fix the wired controller correctly and firmly to the rear cover so that the wired controller will not drop. (see Figure 3.10)
P/Q/E
P/Q/E P/Q/E
P/Q/E
X1/X2
○○○
X1/X2
X1/X2
X1/X2
X1/X2
8
Page 12
Figure 3.9
• During installation, reserve a certain length for the connecting shielded wiring to
make it easier to remove the wired controller for maintenance.
The Safety Precautions classifies the precautions into WARNING and CAUTION.
They both contain important information regarding safety. Be sure to follow all the precautions below.
This controller is not intended to be used by persons, including children, with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they are
supervised or have been given instructions on how to use the controller by a person responsible for their safety. Childen should be supervised to ensure that they do not play with the controller.
Figure 3.10
Caution
!
Operation
1. Safety Precautions
Please read the Safety Precautions carefully before operating the wired controller.
9
CN2
X1 X2
Page 13
Failure to follow these instructions properly may result in personal injury or loss of life.
Failure to observe these instructions properly may result in property
damage or personal injury, which may be serious depending on the
circumstances.
Identifier
Meaning
Warning
Caution
Do not install the wired controller by yourself.
Improper installation may result in electric shocks or fire.
Consult your dealer.
Do not modify or repair the wired controller.
This may result in electric shocks or fire. Consult your dealer.
Do not relocate or reinstall the wired controller by yourself.
Improper installation may result in electric shocks or fire.
Consult your dealer.
Do not use flammable materials (e.g., hairspray or insecticide) near the controller.
Do not clean the controller with organic solvents such as paint thinner. The use of organic solvents may cause crack damage to the controller, electric shocks or fire.
Warning
10
Page 14
Figure 4.1
Do not play with the wired controller.
Accidental operation by a child may result in impairment of bodily functions and harm health.
Never disassemble the wired controller.
Pressing the interior parts may result in electric shocks or fire.
Consult your dealer or authorized contractor for internal inspections and adjustments.
To avoid electric shocks, do not operate with wet hands. Do not wash the wired controller.
Doing so may cause electric leakage and result in electric shocks or fire.
Do not leave the wired controller wherever there is a risk of wetting.
If water gets into the wired controller there is a risk of electrical leakage and damage to
electronic components.
Caution
2. Parts of the Wired Controller
Adjust
Adjust
ON/OFF button
Operating indicator
CancelConfirm
Infrared signal
receiving window
Display area of
wired controller
Mode
Fan speed
Swing
Function
11
Page 15
Table 4.1
Note 1: Auxiliary heater function is reserved.
To turn on/off the unit
To set the operating mode: Auto → Cool→ Heat→ Dry→ Fan
To adjust temperature setting and timing (for timer) upwards.
To adjust temperature setting and timing (for timer) downwards.
To switch to functions that can be set in the current mode.
To set the fan speed.
To set the swing function.
To turn off the timer/IDU LED display/silent/ECO/auxiliary
heater function
1
; to cancel the timer.
To turn on the timer/IDU LED display/silent/ECO/auxiliary
heater function
1
; to confirm the timer.
To indicate the ON/OFF state of the indoor unit.
Button
Functions
12
10. Confirm
8. Operating indicator
7. ON/OFF
1. Mode
5. Adjust upwards
6. Adjust downwards
4. Function
2. Fan speed
3. Swing
9. Cancel
Page 16
Figure 5.1
3. Icons in the Display
4. Operation Guide
Clean filter reminder indicator
Indoor unit ON/OFF
1
Operating mode
Lock indicator
Timer ON/OFF
Fan speed
Swing
Function
Signal transmission indicator
Temperature
13
4-1 ON/OFF Setting
Note1: When the indoor unit is on, the icon " " spins; when the indoor unit is off, the icon " "
does not spin.
Page 17
Figure 6.1
Figure 6.2
1) Press (ON/OFF) button, and the Operating Indicator " " on the wired controller will
light up, while the ON/OFF icon " " of the indoor unit on the display will spin to indicate
that the indoor unit has started running. (see Figure 6.1)
2) Press (ON/OFF) button again, and the Operating Indicator " " on the wired controller will
turn off, and the display icon " " will stop spinning as the indoor unit stops running.
4-2 Mode Setting
Press (Mode) button. Each time press this button, the operating mode will change in turn as shown in Figure 6.3.
14
Page 18
4-3 Fan Speed Setting
Figure 6.3
• The "Auto" mode is not available for all air conditioner models.
• Temperature setting is not available in the "Fan" mode.
"Dry" mode and "Auto" mode is not available for FAPU .
Figure 6.4
Figure 6.5
15
In the "Auto", "Cool", "Dry", or "Heat" mode, press ▲ and ▼ buttons to adjust to the setting temperature. (see Figure 6.4)
Note:
AutoCoolHeatDryFan
Page 19
4-4 Swing Setting
In the "Cool", "Heat" or "Fan" mode, press (Fan speed) button to set the operating fan speed (see Figure 6.5). If the wired controller is configured with seven fan speeds, press (Fan speed) button to set
the fan speed in turn as shown in Figure 6.6.
If the wired controller is configured with three fan speeds, press (Fan speed) button to set the fan speed in turn as shown in Figure 6.7.
• In the "Auto" and "Dry" modes, the fan speed is set to "Auto", and will not change even
press (Fan speed) button.
• The default fan speed is 7 fan speeds, please refer to "Field Setting" to adjust the default fan speed.
Auto Speed 1 Speed 2 Speed 3 Speed 4 Speed 5 Speed 6 Speed 7
Figure 6.6
Figure 6.7
Figure 6.8
→ → → → → → →
16
Auto Low Mid High
→ → →
Note:
Page 20
• The swing function is only available for indoor units configured with vertical louver.
• When the unit is off, the (Swing) button is invalid, and the wired controller automatically turns off the swing function, and the display icon will no longer show the swing angle.
This wired controller is unable to control horizontal swing in indoor unit.
Press (Swing) button to control the swing of the vertical louver of indoor unit (see Figure 6.8).
When the unit is on, the display icon shows the swing angle of the current louver.
Press (Swing) button, and the louver switches from the current angle to the angles in turn as shown in Figure 6.9.
When the louver is in "Auto" state, Press (Swing) button again, and the louver will stop at
the current operating angle, and the display icon will show the current angle of the louver after 10 seconds.
Angle 1 Angle 2 Angle 3 Angle 4 Angle 5 Auto Stop
Figure 6.9
Figure 6.10
4-5 Function Setting
17
Note:
Page 21
Press (Function) button to go to the function settings. Press (Function) button each
time to select the function, and the icon for the selected function will blink. Press (Confirm) button to confirm the function, or (Cancel) button to cancel the function.
Press (Function) button to go to the function setting, and the display on the wired
controller will show in turns: " ", " ", " ", " ", " " (reserved). Alternatively, you can press ▲ and ▼ buttons to switch to the selected function. (see Figure 6.11)
Press (Function) button to switch to the function that can be set in the current mode (see
Figure 6.10).
Press (Function) button to go to the function setting page. Press (Function) button again to select " ", and the IDU LED Display icon " " will blink. Then press (Confirm)
button to confirm, and " " will light up, or press (Cancel) button to cancel, and the "IDU LED Display" function will turn off. (see Figure 6.12)
Figure 6.11
Figure 6.12
→ → → →
Auxiliary
Heater
Start
Off
Steady on
Off
Blink
18
The "IDU LED Display" function is used to control the on/off state of display in the indoor unit.
4-5-1 IDU LED Display
Page 22
The "Silent" function is used to send the "Silent" control signal to the indoor unit. The indoor unit automatically optimizes the noise it generates when it is in the "Silent" state.
The "ECO" function is used to send the "ECO" control signal to the indoor unit. The indoor unit will run in the energy saving mode when it is in the "ECO" state.
Figure 6.13
4-5-2 Silent
4-5- 3 ECO
• Turn on/off the "Silent" function: press (Function) button to switch to the "Silent"
function (" " blinks), and press (Confirm) button to turn on the function or (Cancel) button to turn off the function (see Figure 6.13).
• The "Silent" function will be cancelled and needed to be reset when the unit is manually turned off.
• Once it has been running for 8 hours, the Silent icon " " will no longer light up, and the unit will exit the "Silent" operating state.
• The "Silent" and "ECO" functions cannot be set at the same time.
19
Note:
Blink
Start
Off
Off
Page 23
Figure 6.14
4-5-4 Auxiliary Heater (Reserved)
4-5-5 Follow Me
• Turn on/off the "ECO" function: press (Function) button to switch to the "ECO" function (" " blinks), and press (Confirm) button to turn on the function or (Cancel) button to
turn off the function (see Figure 6.14).
• When switching modes or turning off the unit, the unit will exit the "ECO" function.
• Once it has been running for 8 hours, the ECO icon " " will no longer light up, and the
unit will exit the "ECO" operating state.
• The "Silent" and "ECO" functions cannot be set at the same time.
20
Note:
Blink
Start
Off
Off
Page 24
Figure 6.15
"Timer" is used to set the timed on/off state of indoor unit.
• press (Function) button to switch to the "Timer" function. When the indoor unit is on, first
complete the "Timer Off" settings, and then the "Timer On" settings. When the indoor unit
is off, first complete the "Timer On" settings, then the "Timer Off" settings.
• When the indoor unit is off:
1) "Timer On" setting: press (Function) button to go to the "Timer On" setting, the display will show "0.0h Time On", and the words "Time On" will blink, then press (Confirm) button to go to the timer setting. Press ▲ and ▼ buttons to adjust the time, and press (Confirm) button to complete the timer setting (see Figure 6.16).
4-5-6 Timer
• When the "Follow Me" functions of wired and remote controllers are turned on at the same time, the "Follow Me" function priority is assigned to the wired controller.
21
Note:
The "Follow Me" function of the wired controller is on by default, and its icon lights up when the function is on.
1) Turn off "Follow Me": Press (Swing) and (Confirm) buttons at the same time, and
hold for 5 seconds to turn off the "Follow Me" function, and its icon disappear.
2) Turn on "Follow Me": When the "Follow Me" function is off, Press (Swing) and
(Confirm) buttons at the same time, and hold for 5 seconds to start the "Follow Me" function again, and display its icon " " (see Figure 6.15).
Press at the same
time and hold for 5 seconds
Page 25
Figure 6.16
2) "Timer Off" setting: Once the "Timer On" setting is completed, press (Function) button
to go to the "Timer Off" setting, the display will show "0.0h Time Off", and the words
"Time Of" will blink. press (Confirm) button to go to the timer setting, and press ▲ and ▼ buttons to adjust the time, then press (Confirm) button to complete the timer setting.
• When the indoor unit is on: Refer to the above operations to configure the "Timer On" and
"Timer Off" settings.
• When adjusting the timing steps, press and hold ▲ and ▼ buttons for more than 1 second
to adjust the timing step values quickly.
"Cancel Timer" Function: press (Function) button to go to the timer setting, press (Cancel) or (ON/OFF) button or set the time value to zero to cancel the timer settings. Go
back to the main page.
• When the unit is on, the wired controller can be used to set the timer information for "Timer Off" and "Timer On", and when "Timer Off" is cancelled, "Timer On" will be cancelled
as well. When the unit is off, timer information for both "Timer On" and "Timer Off" can be set, and when "Timer On" is cancelled, "Timer Off" will be cancelled as well.
• Once the wired controller has set the timer information, the Timer icon in the display of
the indoor unit will not light up until the preset timing when the wired controller sends the
ON/OFF signal to the indoor unit.
• Secondary wired controller has no timer function.
22
Note:
Page 26
• When the system contains both the centralized controller and wired controller at the same time, the centralized controller can lock the indoor unit so that some of its functions become unavailable. If the indoor unit is locked by the centralized controller, and the display icon of the wired controller " " is on, and some operations fail to respond, please check the corresponding setting of the centralized controller.
• When the wired controller locks the temperature range by itself, the icon " " will light up, but the outer frame " " will be off. When the temperature range is locked by the centralized controller, the lock icon " " and the outer frame " " will both light up at the same time. When two locks exist, the interval for the alternating display is 5 seconds.
4-6 Clean Filer Reminder
Figure 6.17
Figure 6.18
• When the operating time reaches the preset time, the Filter icon " " lights up to remind
users to clean the filter.
• Press and hold (Swing) button for 5 seconds to remove the Filter icon " ".
• Go to "Field Setting" to turn on/off this function or preset time of this function.
• The secondary wired controller has no clean filer reminder function.
4-7 Locking Function
23
Page 27
24
• One or more of the following functions of the indoor unit are locked when the icon " " lights
up on the display: wireless remote controller, on/off state, lowest cooling set temperature, highest set temperature, mode, fan speed, wired controller lock.
• When the centralized controller and wired controller execute the lock function on the wired controller at the same time, priority is assigned to the centralized controller.
• When two wired controllers control one indoor unit at the same time, one controller will be the "Main", and the other will be the "Secondary".
• Go to "Field Setting" to configure the "Main" and "Secondary" controllers. The default
setting is set to main wired controller.
Note:
• The main wired controller can set the "Timer", "Filter" and "Indoor unit commissioning parameter" , but not the secondary remoter controller.
• The "Follow Me" function of the main wired controller is effective but the secondary wired controller does not have this function.
• If either controller is used to change the operating state of the indoor unit, the change will be
4.8 Main/Secondary Wired Controller
• At any time, press and hold (Mode), (Function), ▲ and ▼ buttons at the same time for
5 seconds, and the wired controller will reset.
Field Setting
1. Restore Factory Default
Page 28
• If the indoor unit has no address, the display will show "FE", and the wired controller will
display an E9 error.
• Press and hold ▲ and ▼ buttons for 8 seconds to go to the page to set the indoor unit address. press (Cancel) button to exit the settings page.
• Query and set up the address of the indoor unit is allowed in the address setting page.
• In the address setting page, the wired controller displays the current address if the indoor unit has an address. If the indoor unit has no address, press ▲ and ▼ buttons to
2. Query and Set the Indoor Unit Address
Figure 7.1
Figure 7.2
25
Page 29
• Go to the commissioning parameter setting page. Check that "C0" is displayed in the temperature display area. Press ▲ and ▼ buttons to change the "commissioning parameter Code".
• Once the "commissioning parameter Code" is selected, press (Confirm) button to go to the specific commissioning parameter settings, and then press ▲ and ▼ buttons to adjust the value.
Press (Confirm) button to save the value and complete the commissioning parameter setting.
• Press (Cancel) button to return to the previous page until you exit commissioning parameter settings. Alternatively, system will exit the commissioning parameter settings page if there is no operation for 60 seconds.
• When it is in the commissioning parameter settings page, the wired controller does not
respond to any remote control signals.
• In the commissioning parameter setting page, the (Mode), (Fan speed), (Swing), (Function) and (ON/OFF) buttons are not available.
• Commissioning parameter can be set when the unit is on or off.
• Press and hold (Function) and (Mode) buttons for 5 seconds to go to the page for
commissioning parameter settings.
3. Commissioning Parameter Settings
Figure 7.3
26
adjust the address to the required value (address range is 0-63). press (Confirm) button
to send the current address value to the indoor unit. In 60 seconds, the wired controller will exit the address setting page, or press (Cancel) button to exit the address setting page.
• In the address setting page, the wired controller will not respond to any remote control signals.
Page 30
C7
Table 5.1
27
Parameter Code
Parameter Content
Select Parameters
Address Setting
F0: Main wired controller
F0
If two wired controllers control one indoor unit,
the address must be different
F1: Secondary wired controller
Cooling
Only/Cooling and Heating
Setting
00: Cooling and Heating
00
Heating mode is not available in cooling only
setting.
01: Cooling Only
Reserved
/
/
/
Set time to remind users to clean the filter
00/01/02/03/04 02
00: No reminder to clean filter
01: 1250h
02: 2500h
03: 5000h
04: 10000h
Settings for
infrared receiver of wired
controller
00: Disable
01
When "Disable" is selected, the wired controller cannot receive remote control signal,
01: Enable
Fan speed setting in wired controller
00: 3 fan speeds
02
Default is 7 fan speeds.
01: 4 fan
speeds
02: 7 fan speeds
Reserved
/
/
/
Display indoor room temperature
00: No
00
If "00" is selected, the wired controller will
01: Yes
Default
Value
Remarks
C0
C1
C2
C3
C4
C5
C6
C7
The bi-directional communication automatically identifies 3 fan speeds or 7 fan speeds.
display the setting temperature when the backlight is off. If "01" is selected, the wired controller will display the room temperature when the backlight is off.
1
Page 31
28
Settings to turn on/off operating indicator
01
Select "On" and the operating indicator will show the
ON/OFF state of the indoor unit. Select "Off" and the operating indicator will always be off regardless if the indoor unit is on or off.
C91
Static pressure setting of indoor unit
A52:00/01/02/
03/04/05/06/07 /08/09/FF H-DUCT
3
4
, FAPU : 00/01/~/19/
FF
01
The indoor unit sets the selected corresponding static pressure. Refer to the indoor unit for specific static pressure values. FF: initial value is based on the indoor unit data read by the wired controller.
C101
Set the time delay to stop the fan of the indoor unit.
00/01/02/03 /FF
00
Parameter
00
01
02
03
FF
Value Represents
4 Min
8 Min
12 Min
16 Min
Based on
the dial switches in the main PCB of the
indoor unit
C111
Indoor unit
-
cold draft prevention temperature settings
00/01/02/03 /FF
00
Parameter
00
01
02
03
FF
Common Indoor Unit
15°C/ 59°F
20°C/ 68°F
24°C/ 75°F
26°C/ 79°F
Based on
the dial switches in the main PCB of the
indoor unit
FAPU
14°C/ 57°F
12°C/ 54°F
16°C/
61°F
18°C/ 64°F
Based on
the dial switches in the main PCB of the indoor unit
01: On
00: Off
Remarks
Default Value
Select Parameters
Parameter Content
Parameter Code
C8
Page 32
29
C12
1 and 5
Indoor unit heating temperature compensation setting
00/01/02/ 03/04/FF
00
Parameter 00 01 02 03 04 FF
Value Represents
6°C/ 43°F
2°C/ 36°
F
4°C/ 39°F
6°C/
43°F
0°C/
32° F
Based on the dial switches in the main PC
B
of the indoor unit
C13
1 and 5
Indoor unit
cooling ­Temperature compensation setting
00/01/FF 00
Parameter 00 01 FF
Value Represents
0°C/32°F 2°C/36°F
Based on the
dial switches in the main PCB of
the indoor unit
C145
Indoor unit auxiliary heater setting
00: None
Common
Indoor Unit: 01
FAPU: 00
01:
Available
C151
Indoor unit
auto-restart
setting
00: None
01
01:
Available
C165
Indoor unit vertical swing setting
00: None
Common
Indoor Unit: 01
FAPU: 00
01:
Available
Remarks
Value
Default Select
Parameters
Parameter Content
Parameter Code
Page 33
30
C175
Indoor unit horizontal swing
setting
00: None
Common
Indoor Unit: 01
FAPU: 00
01: Available
C18
Display of
indoor unit to receive the remote control
signals
00: No
01
01: Yes
C19
Buzzer of the indoor unit rings
00: No
01
01: Yes
C20
Follow Me in
wired controller temperature
correction
Celsius:
-5.0~5.0°C Fahrenheit:
-9.0~9.0°F
Celsius:
-3.0°C Fahrenheit:
-6.0°F
Accuracy is 0.5°C/1°F.
C21
Set outdoor ambient temperature value when auxiliary heater is on
Celsius:
-5~20°C Fahrenheit: 23-68°F
Accuracy is 1°C/1°F.
C22
Mode switch interval in Auto mode
00/01/02/03 00
Parameter 00 01 02 03
Value Represents
15 Min 30 Min 60 Min 90 Min
Remarks
Default Value
Select Parameters
Parameter Content
Parameter Code
Celsius:
15 °C
Fahrenheit:
59 °F
Page 34
31
C23
Select opening of electronic expansion valve in Heating or Standby mode
00/01/FF 01
Parameter FF
Value Represents
Based on the dial switches in the main PCB of the indoor unit
C24
Temperature
Unit
00/01 00
00: Celsius 01: Fahrenheit
C25
Set lowest cooling temperature limit
Celsius: 30°C - 17°C (default is 17°C) Fahrenheit: 86°F - 62°F (default is 62°F)
Only available for the wired controller itself.
C26
Set highest heating temperature limit
Celsius: 30°C - 17°C (default is 17°C) Fahrenheit: 86°F - 62°F (default is 62°F)
Only available for the wired controller itself.
C27
Set to display
0.5°C
00/01 00
00: Show 1
°
C
01: Show 0.5°C
Remarks
Default Value
Select Parameters
Parameter Content
Parameter Code
Celsius:
17 °C
Fahrenheit:
62 °F
Celsius:
30 °C
Fahrenheit:
86 °F
00
72
01
96
Page 35
1 Once the indoor unit and wired controller communicate successfully, the default parameters
of the above table will synchronize to the indoor unit settings.
2 Only for medium static duct unit
4 Only for FAPU models
5 This parameter is not available for the FAPU models.
• The secondary wired controller can only perform the parameter settings for C0-C8 and C24-C27.
Capacity
00 01
02 03 04 05 06
07
08 09
1.8 - 7.1kW
0Pa
10Pa
20Pa
30Pa
40Pa
50Pa
50Pa
50Pa
50Pa
50Pa
8.0
-
12.5kW
10Pa
20Pa
30Pa
40Pa
50Pa
60Pa
70Pa
80Pa
90Pa
100Pa
14.0kW
30Pa
40Pa
50Pa
60Pa
70Pa
80Pa
90Pa
100Pa
125Pa
150Pa
32
Note:
Capacity 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19
1
4.0 kW
100
Pa
110
Pa
120
Pa
130
Pa
140
Pa
150
Pa
160
Pa
170
Pa
180
Pa
190
Pa
200
Pa
210
Pa
220
Pa
230
Pa
240
Pa
250
Pa
250
Pa
250
Pa
250
Pa
250
Pa
20.0- 28.0 kW
100
Pa
120
Pa
140
Pa
160
Pa
180
Pa
200
Pa
220
Pa
240
Pa
260
Pa
270
Pa
280
Pa
290
Pa
300
Pa
310
Pa
320
Pa
330
Pa
340
Pa
360
Pa
380
Pa
400
Pa
45.0-56.0 kW
100
Pa
120
Pa
140
Pa
160
Pa
180
Pa
200
Pa
220
Pa
240
Pa
260
Pa
270
Pa
280
Pa
290
Pa
300
Pa
310
Pa
320
Pa
330
Pa
340
Pa
360
Pa
380
Pa
400
Pa
3 Only for high static duct unit
Capacity 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19
7.1 - 1
6.0
kW
30
Pa
50
Pa
60 Pa
70 Pa
80 Pa
90 Pa
100
Pa
110
Pa
120
Pa
130
Pa
140
Pa
150
Pa
160
Pa
170
Pa
180
Pa
190
Pa
200
Pa
200
Pa
200
Pa
200
Pa
20.0- 28.0
kW
30
Pa
50
Pa
60 Pa
70 Pa
80 Pa
90 Pa
100
Pa
110
Pa
120
Pa
130
Pa
140
Pa
150
Pa
160
Pa
170
Pa
180
Pa
190
Pa
200
Pa
210
Pa
230
Pa
250
Pa
40.0-56.0
kW
100
Pa
120
Pa
140
Pa
160
Pa
180
Pa
200
Pa
220
Pa
240
Pa
260
Pa
270
Pa
280
Pa
290
Pa
300
Pa
310
Pa
320
Pa
330
Pa
340
Pa
360
Pa
380
Pa
400
Pa
Page 36
In the main page, press and hold (Fan speed) and (Confirm) buttons at the same time for 5 seconds to go to the query page. You can query the check operation parameters of the
outdoor and indoor units as well as the program version of the wired controller.
Press ▲ and ▼ buttons to select the indoor or outdoor unit: o00-o03 for outdoor unit; n00-n63
for indoor unit.
• press (Confirm) button to query the parameter, or (Cancel) button to quit the query
function.
• In the query page, press ▲ and ▼ buttons to query the parameters. Parameters can be
queried in turn.
• The "Check No." is displayed in the timer area at the top of the query page, and the
contents of the checked parameter is displayed in the temperature area.
4. Query Operations
Figure 7.4
33
Page 37
1
ODU address
2 Outdoor ambient(T4) temperature (°C)
3
T2/T2B average Temp. (corrected) (°C)
Main heat exchanger pipe(T3) temperature (°C)
5
Discharge Temp. of compressor A(°C)
6 Discharge Temp. of compressor A(°C)
7
Inverter compressor A current (A)
8 Inverter compressor B current (A)
9
Reserved
10 Fan speed
11
EXVA position/4
12 EXVB position/4
13
EXVC position/4
14 Operating mode
15
Priority mode
16 Total capacity requirement correction of indoor unit
17
Number of outdoor units
18 Total capacity of outdoor unit
Parameter displayed on the wired controller during ODU spot check No.
4
34
Table 6.1
Page 38
Address of VIP indoor unit
No. Parameter displayed on the wired controller during ODU spot check
19
Inverter-module heatsink Temp. A(°C)
20 Inverter-module heatsink Temp. B(°C) (reserved)
21
Reserved
22 --
23
Plate heat exchanger outlet (T6B) temperature (°C)
24 Plate heat exchanger inlet (T6A) temperature (°C)
25
System discharge superheat degree
26 --
27 Number of operating indoor units
(in case of virtual addresses, this is
the number of units with the virtual addresses included)
28 --
29
High pressure of system
30 Low pressure of the system (reserved)
31
Most recent error or protection code
32 Inverter compressor A frequency
33
Inverter compressor B frequency
34 Unit capacity
35
Program version No.
35
36
Page 39
No.
Parameter displayed on the wired controller during ODU spot check
37 Reserved 2
38
Reserved 2
No. Parameter displayed on the wired controller during IDU spot check
1
IDU communication address
2 Capacity (HP) of IDU
3
IDU network address (the same as the communication address)
4 Set temperature Ts
5
Room temperature T1
6 Actual T2 indoor temperature
7
Actual T2A indoor temperature
8 Actual T2B indoor temperature
9
Ta temperature (FAPU)
11
Target superheat degree (reserved)
12 EXV position/8
13
Software version No.
14 Error Code
Compressor discharge temperature (show high discharge temperature)
10
36
Table 6.2
Page 40
• When there is a communication error between the wired controller and the indoor unit, the
wired controller will show the error code "E9", an indication of a communication failure in wired controller.
• When the indoor or outdoor unit fails, the display of the wired controller shows the address of faulty unit(s) in the timer area, and the error code in the temperature area.
Table 7.1
5. Error Display
List of IDU error codes:
Error Code
Error Definition and Description
FE Indoor unit has no address
E0 Mode conflict error
E1 Communication error between indoor and outdoor units
E2 T1 sensor error
T2 sensor error
E4 T2B sensor error
E5 T2A sensor error (Reserved)
E6
Fan error in indoor unit
E7 EEPROM error fault
Ed
Outdoor unit error
EE Water level alarm error
Eb Electronic expansion valve of indoor unit has error
E3
37
Page 41
Table 7.2
List of ODU error codes:
Error Code
E0
ODU communication fault
XF1
PTC error
E1
Three-phase power supply phase protection
F3
Error in temperature sensor at T6B plate heat exchanger outlet
E2
Communication error between
indoor and outdoor units
F5
Error in temperature sensor at T6A
plate heat exchanger inlet
E4
Error in condenser
temperature sensor (T3) or ambient temperature sensor
(T4)
P0
Inverter compressor top temperature protection
E5
Voltage protection
P1
High pressure protection
E7
Discharge temperature sensor fault
P2 Low pressure protection
E8
ODU address error fault
XP3
Compressor overcurrent protection
XE9 Drive mismatching fault P4
Protection against excessive discharge temperature of compressor
EL Reserved P5
High temperature protection of
condenser
XH0
Communication error between IR341 and master chip
P9 DC Fan Error
H1
Communication chip and master chip communication
fault
PF Reserved
H2 ODU qty decrease fault PL
Protection against excessive temperature of the inverter module
H3 ODU qty increase fault PP
Protection against excessively low
discharge superheat
Code
Error
Error Definition and Description
Error Definition and Description
38
Page 42
List of ODU error codes:
Error Code
Error Definition and Description
Error Code
Error Definition and Description
XH4
Inverter module protection
fault
XL0 Inverter module fault
H5
3X P2 protection fault in 60 minutes
XL1 DC bus low voltage protection
H6
3X P4 protection fault in 100
minutes
XL2 DC bus high voltage protection
H7
IDU qty decrease fault
XL3
Reserved
H8
High-pressure sensor fault
XL4
MCE fault/synchronization/closed loop
H9
3X P9 protection in 60 minutes
XL5 Zero speed protection
Hb
Low pressure sensor fault
XL7
Phase sequence error protection
C7
3X PL protection in 100 minutes
XL8
Protection against sudden speed change in compressor > 15Hz
F0
3X PP protection in 100 minutes
XL9
Protection to prevent the difference between the speed setting and actual operating speed of the compressor >
15Hz
39
Page 43
40
Troubleshooting
Error code and
description
Possible Causes Possible Solutions
No display on the wired controller
IDU is not powered on Power on the IDU.
Wired controller connection error
First power off the IDU, and then check if the wired controller connection is correct. See Section 3.4 on the wiring requirements.
Wired controller damaged Replace the wired controller.
Power supply failure of the IDU main PCB Replace the IDU main PCB.
E9
Wired controller and IDU communi cation fault
IDU has no address or IDU address duplicated
Set an address for the IDU; duplicated IDU
addresses are not allowed in the same
system.
Wired controller damaged Replace the wired controller.
IDU main PCB fault Replace the IDU main PCB.
Some functions of
the indoor unit cannot be controlled, such as ON/OFF, temperature, mode, fan speed and
wired
controller lock.
The
" "
icon in the wired controller is
always on.
Check if the indoor unit has been locked by the centralized controller.
Table 8.1
Page 44
16117100001523
MD18U-003DW
Loading...