SystemAir SYSVRF WALL 15 Q, SYSVRF WALL 22 Q, SYSVRF WALL 28 Q, SYSVRF WALL 36 Q, SYSVRF WALL 56 Q Installation Manual

...
Page 1
SYSVRF WALL
Wall-mounted VRF indoor unit
INSTALLATION MANUAL
GB
Page 2
When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
Use the attached accessories parts and specified parts for installation.
otherwise, it can cause the unit to fall, water leakage, electrical shock or fire.
Install at a strong and firm location which is able to withstand the set' s weight.
If the strength is not enough or installation is not properly done, the set will drop to cause injury.
The appliance must be installed 2.5m above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in electrical work, it can cause electrical shock or fire.
Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal.
If connection or fixing is not correctt, it can cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly.
If control board cover is not fixed correctly, it can cause heat-up at connection point of terminal, fire or electrical shock.
If the supply cord is damaged, it must be replaced by the manufacturer or its sevice agent or similarly qualifued person in order to avoid a hazard.
An all-pole disconnection switch having a contract separation of at least 3mm in a poles should be connected in fixed wiring.
When carrying out piping connection, take care not to let air substances go into refrigeration cycle.
Otherwise, it can cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances.
Otherwise, it can cause fire or electrical shock.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling and causing accidents.
1
installation manual
Be sure to be in conformity with the local, national and international laws and regulations.
Read "PRECAUTIONS" carefully before installation.
The following precautions include important safty items. Observe and remember.
Keep this manual with the owner's manual in a handy place for future reference.
Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.
1. PRECAUTIONS
WARNING
WARNING
The safty precautions listed here are divided into two categories. In either case, important safty information is listed which must be read carefully.
After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained.Also, inform customers that they should store this installation manual along with the owner's manual for future reference.
Be sure only trained and qualified service personnel to install, repair or service the equipment.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
Install according to this installation instructions strictly.
If installation is defective, it can cause water leakage, electric shock or fire.
Failure to observe a warning may result in death.
CAUTION
Failure to observe a caution may result in injury or damage to the equipment.
CONTENTS PAGE
PRECAUTIONS......................................................................................................1
INSTALLATION INFORMATION........................................................................2
ATTACHED FIT TINGS.........................................................................................3
INSPECTING AND HANDLING THE UNIT......................................................4
INDOOR UNIT INSTALLATION..........................................................................4
REFRIGERANT PIPE INSTALLATION................................................................6
WIRING CHART......................................................................................................7
TEST OPERATION...............................................................................................10
Page 3
2
installation manual
To install properly, please read this "installation manual" at first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow this manual as strictly as possible.
If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
When all the installation work is finished, please turn on the power only after a thorough check.
1.5kW model only can be connected to V4 Plus Series and Inverter Mini VRF outdoor unit.The outdoor unit specific model please contact the local dealer or technical support engineer.
Regret for no further announcement if there is any change of this manual caused by product improvement.
2. INSTALLATION INFORMATION
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation.
CAUTION
Ground the air conditioner.
Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.Incomplete grounding may result in electric shocks.
Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit wires , then connect the indoor unit wires.
You are not allow to connect the air conditioner with the power source until w(including iring and piping the air conditioner is done.
While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires at least 1 meter away from televisions or radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children or infirm persons without supervision.
Young children should be supervised to ensure that they do not play with the appliance.
Don't install the air conditioner in the following locations:
There is petroleum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).
Factories where supply voltage fluctuates greatly.
In buses or cabinets.
Place like kitchen where oil permeates.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
The appliance shall not be installed in the laundry.
Other special conditions.
If the refrigerant leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into the place contacting with fire.
After completing the installation work, check that the refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
Page 4
3. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
QUANTITY
SHAPE
NAME
3. Plastic expanded tube
5.Drain pipe
4. Wrapping tape
6. Wall conduit cover
11. Owner's manual
12. Installation manual
13.
Network matching wire
8. Frame
9. Mounting screw(ST2.9
10-C-H)
10. Alkaline dry batteries (AM4)
1. Remote controller manual
8
1
8
1
1
1
1
1
2
2
1
1
3
installation manual
FUNCTION
2. Screw ST3.9x25 for installation board
Secure the installation board
This manual
1
Hold the remote controller
7. Remote controller (including operation manual)
Insulation Holder for remote controller
Fig.3-1
Never throw or beat the controller.
Before installation, operate the remote controller to determine its location in a reception range.
Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment. (it is necessary to prevent image disturbances or noise interferences.)
Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
Note that the positive and negative poles are right positions when loading batteries.
This manual is subject to changes due to technological improvement without further notices.
Cautions on remote controller installation:
Remote controller holder
Mounting screw B ST2.9x10-C-H
Not attach in several unit
The indoor unit which at the terminal of communication system should connect a impedance between port P and port Q.
14.Copper nut
1
Connect piping
Remote
controller
ONOFF
MODE
FAN
SPEED
TURBO
LED DISPLAY
TEMP
SET
TIMER
ECO
DRY E
•A•H
FOLLOW ME
FAN DIRECTION
SYSCONTROL RM 02
AUTO COOL DRY HEAT FAN
TIMER OFF
TIMER ON
FOLLOW ME
TEMP
FAN SPEED
FAN SPEED
FOLLOW ME
FOLLOW ME
SLEEP MODE
Page 5
4
installation manual
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should be reported immediately to the carrier claims agent.
When handling the unit, take into account the following:
5. INDOOR UNIT INSTALLATION
5.1 Installation place
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
Choose on before hand the path along which the unit is to be brought in.
Move this unit in its original package.
When lifting the unit , always use protectors to prevent belt damage and pay attention to the position of the unit’s centre of gravity.
1
2
3
4
Indoor Unit
A place where is no obstacle near the inlet and outlet area.
A place which can bear the weight of the indoor unit.
A place which allows the air filter to be removed.
A place where the reception range is not Exposed to direct sunlight.
A place where the connective pipe and drain hose is easy to lead out.
A place 1m or more to TV, radio instrument, in the center of the room is perfect.
The indoor unit should be installed 2.3 meters or more above the floor.
Installation in the following places may cause trouble.If it is unavoidable, please consult with the local dealer.
A place full of machine oil.
A saline place such as coast.
A place full of sulfide gas such as hot-spring resort.
Places where there are high frequency machines such as wireless equipment, welding
Machine, and medical facility.
A place where there is combustive gases and volatile substances. A place of special environmental conditions.
Installation Board and Its Direction (unit: mm)
1 Fix the installation board.
Install the installation board horizontally on structural parts in the wall with the spaces provided around the plate.
In case of brick, concrete or similar type walls,make 5mmdia, holes in the wall. Insert clip anchors for appropriate mounting screws.
Fix the installation board on the wall.
5.2 Drilling A Hole and Mounting Installation Board
15\22\28\36 type
45\56\71 type
Fig.5-2
Fig.5-1
Correct installation
Fig.5-3
462
57
290
915
712
mounting board of indoor unit
the shape of indoor unit
315
1070
794
730
65
mounting board of indoor unit
the shape of indoor unit
mounting
board
of indoor unit
horizontal line
Page 6
5
installation manual
Fig.5-5
Fig.5-6
Fig.5-7 Fig.5-7
Fig.5-8
5.3 Connective Pipe and Drainage Installation
Do not form a rise
Do not put the hose end into water
Shield pipe
Wall
Drain hose
Extension drainhose
1 Drainage
Run the drain hose sloping downward. Do not install the drain hose as illustrated below.
When connecting extension drain hose,insulate the connecting part of extension drain hose with a shield pipe
Right piping
Left piping
Right back piping
Left back piping
2 Connection pipe
For the left-hand and rear-left-hand piping,install the piping as shown. Bend the connective pipe to be laid at 43mm height or less from the wall.
Connect the indoor unit first then the outdoor unit and bend and arrange the pipe carefully.
Do not allow the piping to let out from the back of the indoor unit.
Be careful not to let the drain hose slack.
Insulate both of the auxiliary piping.
Banding the drain hose under the auxiliary pipe.
Do not allow the piping to let out from the back of the indoor unit.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
43
Indoor unit outline
Connective pipe
Fix the end of the connective pipe.(Refer to Tightening Connection in refrigerant piping connection)
2 Drilling a hole.
Determine the pipe hole position using the installation
board
, and drill the pipehole (N95mm) so it slants slightly
downward.
Always use a wall hole conduit when piercing metal lath, ply wood or metal plate.
Incorrect installation
Fig.5-4
CAUTION
mounting
board
of indoor unit
horizontal line
mounting
board
of indoor unit
horizontal line
Page 7
6. REFRIGERANT PIPE INSTALLATION
Ventilate the air if there was any refrigerant leakage during installation.Leaked refrigerant will generate poisonous gas if in contact with fire.
Make sure there is no refrigerant leakage after installation. Leaked refrigerant will generate poisonous gas if in contact with fire.
6.1 Allowed Length and Drop of Piping
Requirements are different when installing the Outdoor Unit,Please refer to Outdoor Unit Installation Manual for detailed information.
6.2 Material and Size of the Piping
Size(mm)
Pipe Material Copper Pipe for Air Conditioner
Model
Φ12.7
Φ6.4
15/22/28/36/45
(Gas side)
(Liquid side)
Φ15.9
Φ9.5
56/71
6.3 Refrigerant Volume to Be Added
Refrigerant Volume to be added is calculated according to Outdoor Unit Installation Manual .
Add refrigerant and measure with a scale.
If refrigerant volume added is inadequate (too much or insufficient), the compressor can malfunction. Be sure to calculate the refrigerant volume carefully.
The service man should note down the piping length and refrigerant volume added on the nameplate, which is on the Electric Control Box Cover of outdoor unit for to diagnose the compressor when compressor malfunction occurs.
6
installation manual
6.4 Connection of the Refrigerant Pipe
Connection of the refrigerant pipe should be done by professionals. Double-span should be used when connecting pipesof Indoor Unit.
Table 6-1
Fig.5-9
Fig.5-10
Connective cable
Drain hose
Connective pipe
Pipe room
Pond box
Wrapping belt
Indoor unit
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
. .
.
. .
.
3 Piping and bandaging
Wind the connective cable, drain hose and wiring with tape securely, evenly as shown below.
5.4 Indoor Unit Installation
Pass the piping through the hole in the wall.
Put the claw at the back of the indoor unit on the hook of the installation
board
, move the Indoor Unit from side to
side to see that it is securely hooked.
Piping can easily be made by lifting the indoor unit with a cushioning material between the indoor unit and the wall. Get it out after finish piping.
Push the lower part of the Indoor Unit up to the wall,Then move the Indoor Unit from side to side, up and down to check if it is hooked securely.
Because the condensed water from rear of the indoor unit is gathered in a condensation container and is piped out of room. Do not put anything else in this container.
hook
Cushioning material
CAUTION
CAUTION
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
CAUTION
Page 8
7. WIRING CHART
CENTRAL CONTROL MONITOR(CCM)
INDOOR UNIT
OUTDOOR UNIT
COMPUTER
INDOOR UNIT
INDOOR UNIT
Power (220-240V~50/60Hz
the shielded twisted-pair wire
The reserved function is indicated in broken line table,users can select it when necessary.
1 Take out the faceplate,then dismantle the display cover plate.(see
Fig.7-1)
faceplate
display cover plate
NOTE
Please refer to installation instructions for the refrigerant piping conection of the air conditioner that with throttle device inside.
Tightening Torque
Φ6.4
Outer diameter(mm) of connection piping
Φ9.5
Tightening Torque (N.m)
32.7~39.9
Φ15.9
61.8~75.4
Φ19.1
97.2~118.6
14.2~17.2
Table 6-2
Φ12.7
49.5~60.3
7
installation manual
CAUTION
S faceplate
wiring cover plate
Fig.7-1
faceplate
the wire holder of power cord(three-position))
the wire holder of signal line (five-position))
display cover plate
dial switch
2 Individually connect the power cord and signal line,adjust the dial switch.(see
Fig.7-2)
S faceplate
Fig.7-2
the wire holder of power cord(three-position))
the wire holder of signal line (five-position))
wiring cover plate
dial switch
An all-pole disconnection device which has at least 3mm separation distance in all pole and a residual current device(RCD)with the rating of above 10mA shall be incorporated in the fixed wiring according to the nati­onal rule.
CAUTION
Model(W)
1500~7100
15
5A
3x2.5
2x4.0+1x2.5 (Add eletrical auxiliary heat)
8A (Add eletrical auxiliary heat)
Manual switch
(A)
Indoor unit power wiring (mm
2
)
Indoor/outdoor connectingwiring (mm
2
) (
Electric signal
)
Power
Phase
Fuse (A)
1-Phase
220-240V~ 50/60Hz
Frequency and volt
3x0.75(3x0.75)
Page 9
WIRE CONTROLLER
To wire controller
DISPLAY BOARD
The reserved wire control function is indicated in broken line table,users can purchase the wire controller when necessary.
7.2 Horsepower set
Horsepower code
Code
Capacity(Horsepower)
0
1
2
3
4
2200W(0.8HP)
5600W(2.0HP)
4500W(1.5HP)
3600W(1.2HP)
2800W(1.0HP)
5
7100W(2.5HP)
Note: The horsepower has been set before leaving the factory , no one should modify it except the maintenance person.
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
ENC1
POWER_S
For set horsepower
Toggle switch ENC1
7.1 Terminal Board Diagram
Please refer to the indoor unit wiring diagram for the wiring.
NOTE
The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wire correctly and set system address and network address of indoor units.
Single phase indoor unit
INDOOR UNIT POWER 220-240V
50/60Hz
(Conventional)
XT1
Y/G
L N
RED
BLUE
WHITE
BLUE
BLACK
BLACK
YELLOW
To central control Monitor (CCM) COMM. BUS
To outdoor COMM. BUS
Please adopt the shielded twisted-pair wire, and connect the shielded layed to (E)
X
P Q (E)
Y
(E)
GRAY
XT1
Y/G
L1 L2
RED
BLUE
INDOOR UNIT POWER 220-240V
50/60Hz
(Special for UL)
POWER IN
POWER IN
F
1500W(0.6HP)
MAIN BOARD
8
installation manual
7.3 Network address set
1) Network address is set by communication of indoor and outdoor unit; the address is the same as indoor address, there is no need to set separately.
2) The central control of indoor units can be done on outdoor unit, there is no need to control indoor unit separately, for details please refer to V4+ outdoor unit manual.
3) For previous control of indoor units, the network can be set by connecting (X,Y,E) terminals, there is no need to set network address. The network can also be set by outer network module and main board (CN20).
The system together have 64units(0-63), each one has a unique system addresscode. If two addresses are the same in one system, operation will be abnormal.
Please switch off the power before setting, otherwise unexpected errors will occur.
CAUTION
Page 10
9
installation manual
7.4 Main board Code designation
1 means factory test mode
0 means auto addressing mode
(default setting)
1 means DC fan Is chosen
0 means AC fan Is chosen
00 means DC fan static pressure is 0
(reserved)
01 means DC fan static pressure is 1 (reserved)
10 means DC fan static pressure is 2
(reserved)
11 means DC fan static pressure is 3
(reserved)
1234
SW1
ON
1234
SW1
ON
1234
SW1
ON
1234
SW1
ON
1234
SW1
ON
1234
SW1
ON
SW1 definition
00 means shutting down the
unit to"stop cold air" at 15 degrees
01 means shutting down the
unit to"stop cold air" at 20 degrees
10 means shutting down the
unit to"stop cold air" at 24 degrees
11 means shutting down the
unit to"stop cold air" at 26 degrees
00 means the time of stopping
TERMAL fan is 4 minutes
01 means the time of stopping
TERMAL fan is 8 minutes
10 means the time of stopping
TERMAL fan is 12 minutes
11 means the time of stopping
TERMAL fan is 16 minutes
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW2
ON
SW2 definition
00 means temp.compensation
value is 6 degrees under heat mode
10 means temp.compensation
value is 4 degrees under heat mode
11 means temp.compensation
value is 8 degrees under heat mode
01 means temp.compensation
value is 2 degrees under heat mode
1 2
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
SW5 definition
1 means old display panel
0 means new display panel
1 means auto air blow under auto mode
0 means auto air blow under non-auto mode
reserved
1 2 3
SW6
ON
1 2 3
SW6
ON
1 2 3
SW6
ON
SW6 definition
without jumper "J1" for auto restart function
with jumper "J1" for non-auto restart function
reserved
J1,J2 definition
J1
J1
J2
Page 11
10
installation manual
According to the user’s requirement, install the remote controller frame where the remote controller’s signal can reach the indoor unit smoothly.
Test operation Set the air conditioner under the mode of “COOLING”with the remote controller, and check the following points per the “Owner’s Manual”. If there is any malfunction, please resolve it through chapter “Troubles And Causes ”.
The indoor unit
Whether the switch on the remote controller works well.
Whether the buttons on the remote controller works well.
Whether the air flow louver moves normally.
Whether the room temperature is adjusted well.
Whether the indicator lights normally.
Whether the temporary buttons works well.
Whether the drainage is normal.
Whether there is vibration or abnormal noise during operation.
Whether the air conditioner heats well in the case of the HEATING/COOLING type.
The outdoor unit
Whether there is vibration or abnormal noise during operation.
Whether the generated wind, noise, or condensed water by the air conditioner have influenced your neighborhood.
Whether any of the refrigerant is leaked.
8 TEST OPERATION
Protection function will delay the startup of compressor for 3 minutes in case the unit is turned on immediately after power on or re­started after shutdown.
CAUTION
ON
ON
Means 0
Means 1
0/1 definition
The test operation must be carried out after the entire installation has been completed.
Please confirm the following points before the test operation:
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of the refrigerant have been recorded.
The power voltage fits the rated voltage of the air conditioner.
There is no obstacle at the outlet and inlet of the outdoor and indoor and indoor units.
The gas-side and liquid-side stop values are both opened.
The air conditioner is pre-heated by turning on the power.
Page 12
SYSVRF WALL_IM EN  April 2014
202000172227(MD13I-012CW)