Systemair S-SA2, S-SA2L User Manual

Fire Safety Products
S-SA2 & S-SA2L
Smoke Control Dampers - AAmulti
User Manual
2/40 | User Manual S-SA2 & S-SA2L | 201905
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operating Conditions . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation Methods . . . . . . . . . . . . . . . . . . . . 6
Standard Distances Between Damper Bodies. . . . . . . 10
Wet Installation . . . . . . . . . . . . . . . . . . . . 11
Installation into a Soft Crossing . . . . . . . . . . . . 14
Connecting S-SA2 to “multi” Ductwork Made of Boards . 16
S-SA2L Installation. . . . . . . . . . . . . . . . . . . . . 20
Installation on the Vertical Duct with a Ledge . . . . 22
Installation Directly on the Vertical Duct . . . . . . . 25
Installation on the Horizontal Duct with a Ledge . . . 27
Installation Directly on the Horizontal Duct . . . . . . 30
Electrical Connections . . . . . . . . . . . . . . . . . . . . . 32
Operation Manual . . . . . . . . . . . . . . . . . . . . . . . 36
Smoke Damper Functionality Check . . . . . . . . . . . . . 36
Smoke Damper Inspection . . . . . . . . . . . . . . . . . . 36
Warranty Conditions . . . . . . . . . . . . . . . . . . . . . . 37
Operating Journal . . . . . . . . . . . . . . . . . . . . . . . 38
Warranty Service . . . . . . . . . . . . . . . . . . . . . . . 40
Good to know
Current information on all re safety products is available at
design.systemair.com

Introduction

These are the original installation, inspection and operating instructions for the S-SA2 and S-SA2L smoke control dampers. EVERY S-SA2 AND S-SA2L SMOKE DAMPER NEEDS TO BE INSTALLED IN ACCORDANCE WITH THIS DOCUMENT!
S-SA2
Rectangular smoke control damper without mesh for wall and ceiling installations.
Dimension range (mm): W × H = 200 × 200 up to 1600 × 1000
1396-CPR-0112
Wet Installation
Maximum performance up to EI120S Using concrete lling
Installation into a Soft Crossing
(up to Size 1000 × 800 mm)
S-SA2L
Rectangular smoke control damper with a mesh-tted extension suited for vertical or horizontal duct installations.
Dimension range (mm): W × H = 200 × 200 up to 1600 × 1000
1396-CPR-0147
Installation on the Vertical Duct with a Ledge
Installation Directly on the Vertical Duct
Installation on the Horizontal Duct with a Ledge
Installation Directly on the Horizontal Duct
Maximum performance up to EI90S Using mineral wool lling
4/40 | User Manual S-SA2 & S-SA2L | 201905

Warnings

Some damper parts may have sharp edges; therefore, to protect yourself, please use gloves during damper
installation and manipulation. In order to prevent electric shock, re or any other damage which could result from
incorrect damper usage and operation, it is important to:
1. ensure that installation is performed by a trained person.
2. follow the written and depicted instructions provided within this User Manual closely.
3. perform damper inspection in accordance with this User Manual.
4. check the damper’s functionality as per the install the smoke damper. This procedure prevents the installation of a damper that has been damaged during transportation or handling.
IMPORTANT: Do not install non-functioning dampers!
“Smoke Damper Functionality Check” chapter before you

Operating Conditions

S-SA2 and S-SA2L smoke dampers are intended:
for installation in places which are protected against weather disruptions.
for ducts, distributing air without any mechanical or chemical contamination.
for a maximum air ow velocity 12 m/s.
for a storage temperature range of -20°C to 50°C.
List of Accessories
D1-S-SA2: Duct Extension with Mesh for S-SA2
K1-S-SA2L: Kit for Sheet-Metal Duct Installation

Installation

The duct connected to the smoke damper must be supported or hung in such a way that the damper does not
carry its weight. The damper must not support any part of the surrounding construction or wall which could cause damage and consequent damper failure.
The damper driving mechanism can be placed on either side of the wall, however, it needs to be situated to ensure
easy access during inspection.
According to the EN 1366-2 standard, the distance between the smoke damper bodies must be at least 200 mm.
According to the EN 1366-2 standard, the distance between smoke damper and the adjacent wall/ceiling
and the smoke damper must be at least 75 mm.
The S-SA2 smoke damper must be installed into a smoke and re partition structure in such a way that the damper
blade is located inside this structure in its closed position. To help you nd the suspension plane, a bendable hinge
is provided on the damper body. This condition does not apply for S-SA2L.
The gap in the installation opening between the smoke damper and the wall/ceiling can be increased by up to 50%
of the gap area, or decreased to the smallest amount possible that still provides sufcient space for the installation
of the seal.
The gap between the damper blade in the open position and the self-standing grill (when installed) must be at least
200 mm according to EN 1366-10. Otherwise, the damper must be tested together with the grill.
The smoke damper must be earthed after being installed into or onto the duct.
Lists of all permitted installation methods are provided on the following pages. Every method only applies to those
damper types that are listed in the corresponding paragraph’s heading.
6/40 | User Manual S-SA2 & S-SA2L | 201905

Installation Methods

All S-SA2 and S-SA2L smoke dampers are CE certied according to EN 12101-8:2011, tested according to EN 1366–10 :2011+A1:2017, and classied according to EN 13501-4:2016. The smoke damper, together with its installation, form an inseparable part of the re resistivity rating.
Tab. 1: S-SA2 re resistivity
Dimension
Range
Certicate
(mm)
200 × 200
up to
1000 × 800
200 × 200
1396 - CPR - 0112
up to
1600 × 1000
Tab. 2: S-SA2L re resistivity
Product
No.
Type
EI90 (v
S-SA2
EI120 (v
EI120 (h
Allowed Blade Axis Orientation
Classication
i ↔ o) S1500
ew
AAmulti
C
mod
i ↔ o) S1500
ew
AAmulti
C
mod
i ↔ o) S1500
ow
AAmulti
C
mod
Construction Type/Minimal Thickness (mm)
Supporting
Construction
ve
Wet Soft
Rigid/150
Rigid/150
Flexible/150
Flexible/150
ve -
ho Rigid/150 -
Applicable Duct Tested per Standard
Dimension
Range
(mm)
200 × 200
up to
1600 × 1000
Certicate
No.
Product
Type
S-SA2L
1396 - CPR - 0147
Allowed Blade Axis Orientation
Classication
EI120 (v
EI120 (h
i ↔ o) S1500
ed
AAmulti
C
mod
i ↔ o) S1500
od
AAmulti
C
mod
Supporting
ve
Construction
On the Duct/
Bottom Mounted
EN 1366-9,
EN 1366-8
On the Duct/ Top Mounted
EN 1366-9,
EN 1366-8
ho - -
On the Duct/
Side Mounted
EN 1366-9,
EN 1366-8
EN 1366-9,
EN 1366-8
In the Duct/
Horizontal
Axis
-
-
Legend
ve Vertical supporting construction (wall, horizontal duct)
ho Horizontal supporting construction (oor/ceiling, vertical duct)
Wet Installation
Installation into a soft crossing
Damper placed on duct surface, bottom side of the duct
Damper placed on duct surface, top side of the duct
Damper placed on duct surface, left and right side of the duct
Damper placed within the duct canal, outside of supporting construction
Installation of S-SA2L on the vertical duct with a ledge
Installation of S-SA2L directly on the vertical duct
Installation of S-SA2L on the horizontal duct with a ledge
Installation of S-SA2L directly on the horizontal duct
Damper‘s horizontal blade axis orientation
- mechanism can be placed on either side
Damper‘s vertical blade axis orientation
- mechanism can be placed on top and bottom.
S-SA2
8/40 | User Manual S-SA2 & S-SA2L | 201905

Opening Preparation for S-SA2 Installation

The S-SA2 smoke damper can be installed in a wall or ceiling between zones classied as “multi-multi”, “multi-single” and “single-multi”.
Opening Preparation for a Rigid Wall
1
W
H
1
s
Fig. 1: Rigid wall/ceiling with a rectangular opening
NOTE: Dimensions W
and H1 are dened in every installation
1
Legend
1 Concrete/Masonry/Cellular Concrete
Tab. 3: Thickness of tested wall
Fire Resistivity
90
120
1
Minimum s (mm)
Wall Ceiling
Concrete/Masonry/Cellular Concrete
150 ± 10
S-SA2
Opening Preparation for a Flexible Wall
25
6
.
x
ma
3 4
H
1
2 1
4
1
3
W
1
× W H
1
1
s
Fig. 2: Flexible (plasterboard) wall with a rectangular opening and vertical cross-section (right)
Legend
1 On each side - 2 layers of plasterboard reproof plate type F, EN 520 (thickness see Tab. 4)
2 Vertical CW-proles (proles with s
3 Horizontal CW-proles (prole with s
4 Mineral wool; thickness/cubic density see Tab. 4)
based on re resistivity, see Tab. 4)
CW
based on re resistivity, see Tab. 4)
CW
s
CW
s
Tab. 4: Thickness of tested wall
Fire Resistivity
90
120 85 ... 115
Minimum s Minimum s
(mm) (mm) (kg/m
150 100 C 12,5 60 ... 70
CW
Allowed Metal
Stud Group
Thickness
of Plasterboards
Thickness Cubic Density
Insulation
80 ... 115
3
)
10/40 | User Manual S-SA2 & S-SA2L | 201905
S-SA2
10/40 | User Manual S-SA2 & S-SA2L | 201905

Standard Distances Between Damper Bodies

According to the EN 1366-2 standard, the minimum distance from the wall or ceiling to the damper body is 75 mm.
For multiple crossings through a re resistive wall, the minimum distance between two damper bodies is 200 mm. This applies for distances between the damper body and a nearby foreign object crossing the re resistive wall.
Damper clearances vary from the type of mechanism and their rotation (please see Fig. 3 and see Tab. 5).
75
210
75A
Fig. 3: Installation distances between damper bodies
Tab. 5: Installation distances for minimal clearance to the actuator in Fig. 3
Clearance
200
250
300
350
400
450
500
200
250
300
350
400
450
H
(mm)
500 -
600 -
700 - -
800 - - -
900 - - - -
1000 - - - - -
B230, G230, B24, G24; A = 240 mm B230-ST, G24-ST; A = 380 mm
-
-
-
-
A = 240 mm
-
-
210
200 A
W (mm)
600
700
800
900
1000
-
- - - - - - - -
-
- - - - - - -
-
A = 270 mm
210
1100
1200
1300
1400
1500
- - - - - -
- -
- - - -
-
- - -
-
A = 430 mm
- -
-
1600
-
-
S-SA2
Wet Installation
Using Concrete Filling
Wet
1. The supporting construction opening must be prepared in a way depicted in the “Opening preparation” section
(as per Fig. 1 – Fig. 2). Opening surfaces must be even and cleaned. The exible wall opening must be reinforced
as per the standards for plasterboard walls. The opening dimensions are driven by the nominal dimensions of the damper with added clearance. The opening will be made with dimensions W
and H1 ( Fig. 4 ).
1
2. Insert the closed damper into the middle of the opening so that the damper blade is in the wall. Use the bendable hanger to secure the damper against the wall by using a suitable screw (3; recommended screw diameter 5,5; e.g. DIN7981).
For damper widths greater than 600 mm, it is recommended to use a duct support inside the damper during
installation to avoid any damage to the damper housing from the weight of the lling.
3. Fill in the area between the wall and the damper with gypsum plaster, or mortar or concrete lling (2), while paying attention to prevent the fouling of the damper’s functional parts, which could limit its correct functionality.
The best way is to cover the functional parts during installation. To prevent seepage of the lling material, the use
of boards is recommended.
First let the plaster, mortar or concrete lling harden and then perform the next steps.
4. After the lling hardens, remove the duct support from inside of the damper.
5. If needed, uncover and clean the damper after installation.
6. Check the damper’s functionality.
Product Type Dimension Range (mm) Classication Supporting Construction
S-SA2 200 × 200 up to 1600 × 1000
EI120 (v
EI120 (h
i ↔ o) S1500 C
ew
i ↔ o) S1500 C
ow
AAmulti Wall
mod
AAmulti Ceiling/Floor
mod
S-SA2
12/40 | User Manual S-SA2 & S-SA2L | 201905
Wet
Legend for Figures of Wet Instalation
1 Smoke damper S-SA2 (actuator side)
2 Accessory LEAS/Connected ductwork tested according to EN 1366-9
3 Screw 5,5 DIN 7981 xing the Damper through bendable hangers
4 Gypsum plaster; Mortar; Concrete lling - minimal category M2.5, EN 998-2
Damper‘s horizontal blade axis orientation
Damper‘s vertical blade axis orientation
3
)
0
4
±
(
0
= W + 12
1
2
4
W
1
7
5
1
H
= H + 120 (±40)
1
H
W
Fig. 4: Wet installation of the S-SA2 smoke damper
Loading...
+ 28 hidden pages