SystemAir Rotovex 2400 EL, Rotovex 2400HW, Rotovex 3800 HW, Rotovex 4800 HW, Rotovex 3800 EL Operating And Maintenance Instruction Manual

...
Air Handling Unit
ROTOVEX
Operating and Maintenance
GB
SE
Instruction
Drift- och skötselanvisning
GB
Contents
Page
3 Declaration of Conformity 4 Electrical connection 5 Check after connection 6 Automatic system/control 7 External connections 8 Description of functions/electrical heating 9 Description of functions/water heating 10 Starting up ROTOVEX 11 Inspection and care of fans 12 Inspection and care of electrical heater 13 Inspection and care of water heater 14 Inspection and care of filter and rotor 15 Measurements and specifications 16 Alarms, damper 17 Configuration of Corrigo
NB. Systemair AB reserve the rights at any time, without prior notice, make changes and improvements to the contents of this manual.
2
GB
Manufacturer
Our products are manufactured in compliance with applicable international standards and regulations.
The manufacturer hereby confirms that the following products:
Air handling units
Rotovex 2400HW Rotovex 2400 EL, Rotovex 3800 HW, 3800 EL, Rotovex 4800 HW, Rotovex 4800 EL.
Comply with the following EC-directives:
Systemair AB Industrivägen 3 SE-739 30 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99
EC Declaration of Conformity
as defined by the EC Machinery Directive 98/37/EEC, Annex II A. Fans for ventilation in air handling systems with air from non-explosion hazardous premises. This machinery must not be
put into operation until prior to reading mounting instructions and safety information.
The following harmonized standards are in use:
EN 60 034-1 Rotating electric machinery; ratings and performances.
EN 60 204-1 Safety of machinery; electrical equipment of machines; general requirements. EN 292-1 Safety of machinery; basic concepts, general principles for design. EN 294 Safety of machinery; safety distances to prevent danger zones reached by the upper limbs. Remark: EN 294 only complies when fitted contact safety device is part of the extent of delivery.
EC Declaration of Conformity
as defined by the EC Low Voltage Directive 73/23/EEC and 93/68/EEC
The following harmonized standards are in use:
EN 60 335-1 Electric domestic products and similar – safety­general requirements.
EN 60 335-2-40 Safety of household and similar electrical appliances - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers.
EN 50 106 Electric domestic products and similar­Safety-Instructions for control of manufacture.
Remark: EN 50 106 complies for internally wired products only.
EC Declaration of Conformity
as defined by EC’s EMC-directive 89/336/EEC, 92/31/EEC and 93/68/EEC
The following harmonized standards are in use:
EN 61000-6-4: Electromagnetic compatibility (EMC)
- Part 6-4: Generic standards - Emission standard for industrial environments
EN 61000-6-2 Electromagnetic compatibility (EMC) – Part 6-2: General requirements – Immunity for appliances in industrial environments.
The complete technical documentation is available.
Skinnskatteberg, 06 Feb 2003
Mats Sándor
Technical Manager
3
GB
Electrical connection
The unit must not be put into operation until all the electrical and mechanical safety precautions have been taken.
The ROTOVEX unit should be perman­ently connected to the mains electric supply through the lockable safety switch on the gable, as shown in the figure.
The unit’s nominal electrical values and manufacturing number are shown on the plate just under the safety switch.
If the unit is equipped with a heater that has separate power supply (see table below). The unit shall bee provided with a working switch, see figure.
Switch for disconnection from the supply, shall have at least 3 mm contact separation in all poles.
Electrical data for the unit:
Rotovex Mains Unit (A)
2400HW 230V1~ 5,5 *10,0 ­2400EL 400V3N~ 10,0 3,0 ­2400EL 400V3N~ 5,5 **12,0 **17,5 2400EL 230V3~ 5,5 **12,0 **30 3800HW 400V3N~ 6,0 *15,0 ­3800EL 400V3N~ 12,5 4,5 ­3800EL 400V3N~ 6,0 **15,0 **22 3800EL 230V3~ 6,0 **15,0 **38 4800HW 400V3N~ 8,5 *20,0 ­4800EL 400V3N~ 17,0 6,0 ­4800EL 400V3N~ 8,5 **12,0 **17,5 4800EL 400V3N~ 8,5 **24,0 **35 4800EL 230V3~ 8,5 **12,0 **30 4800EL 230V3~ 8,5 **24,0 **60
*For incoming/outgoing hot water 55/40°C **Electric heater (above 6 KW) has separate incoming power supply. For 230V3~ you need a transformer (230V3~ to 400V3~) for the unit supply.
Heater
[kW]
Heater with separate
power supply [A]
4
GB
To check after connection
• Fans Make sure the fan wheels rotates in correct direction.
• Damper Make sure the damper motors opens and shuts correctly.
• Stop/control valve for hot water Make sure the valve opens and shuts correctly.
• Pressure/Temperatures Make sure the pre-set values for airflow and temperature is correct.
• Closing pressure difference for the filter Make sure the pressure sensors at the filter are set to the correct closing pressure = alarm mode.
Recommended closing pressure approx. 240 Pa.
5
GB
Automatic system/control
All ROTOVEX functions are controlled from the Corrigo panel. For further information refer to the supplied Corrigo user manual.
Regulator vent. sys 05:05:30 15:45 System: Normal run Sp: 18.0 Act: 17.8
A - Control box: Corrigo E28 B - Control box: rotor C - Control box: supply air fan D - Control box: exhaust air fan E - Control box: electric heating F – Control panel. Connects to a fast coupling inside the connection box on the gable of the unit.
6
GB
33/35
36/38
External connections
Terminal block Description Remark
13 G Valve actuator, supply voltage, Heating/cooling 24V AC 14 G0 Valve actuator, supply voltage, Heating/cooling Neutral 43 AO1 Control signal water heating 0-10V DC 57 AO3 Control signal water cooling 0-10V DC
PE Water pump, supply voltage. HW Heating Ground
45 N W ater pump, supply voltage. HW Heating Neutral 46 L1 Water pump, supply voltage. HW Heating 230V AC 39 DO6 Water pump, control voltage (contactor). Cooling 24V AC, 0,5A
G DO ref Water pump, control voltage (contactor). Cooling 33 DO2 Damper, exhaust air 24V AC, 0,5A 34 G0 Damper, exhaust air Neutral 35 G Damper, exhaust air 24V AC 36 DO1 Damper, fresh air 24V AC, 0,5A 37 G0 Damper, fresh air Neutral 38 G Damper, fresh air 24V AC 56 AI3 Extract air temperature sensor PT 1000
Agnd AI ref Extract air temperature sensor
27 UAI1 Fresh air temperature sensor PT 1000
Agnd UI ref Fresh air temperature sensor
31 AI4 Supply air temperature sensor PT 1000 32 AI ref Supply air temperature sensor 55 DO4 DX cooling, step1 24V AC, 0,5A 54 DO5 DX cooling, step2 24V AC, 0,5A 53 DO ref DX cooling, step1 and 2
*64 DI3 Run-indication/alarm circulation pump Cooling
*Ref DI DI ref Run-indication/alarm circulation pump Cooling
*47 DI5 Fire alarm
*Ref DI DI ref Fire alarm
*48 DI6 External stop
*Ref DI DI ref External stop
*49 DI7 Extended operation, Normal *50 DI ref Extended operation, Normal *59 DI8 External alarm
*Ref DI DI ref External alarm
40 DO7 Sum alarm, A- and B-alarm
G DO ref Sum alarm, A- and B-alarm 51 Net + LON 52 Net - LON 60 G Pressure transmitter, supply voltage 24V AC 61 AI1 Pressure transmitter, control signal. Supply air 0-10V DC 62 AI ref Pressure transmitter 63 AI2 Pressure transmitter, control signal. Extract air 0-10V DC 28 UAI2 Free to use
Agnd UI ref Free to use
58 UAI3 Free to use
Agnd UI ref Free to use
*Ref DI DI ref Is used together with UDI
* These inputs may only be wired to voltage free contacts.
By spring-loaded damper, co nnect
By spring-loaded damper, connect
or
or
All external connections are done in the connection boxes found on each end plate of the unit. There is a sign on the inside illustrating the various functions and how they are to be connected.
7
GB
Description of functions
Electrical heating, extract air temperature control with cascade function.
Function
Start and stop times are set in the Control panel. To maintain constant room temperature the RC receives a signal from GT3 and regulates the VVX and the electrical heater in sequence. The GT1 sensor is used to limit the max and min supply air temperature. Maximum temperature in the electrical re-heater is controlled by GTM. GTO disconnects the heater, gives an alarm signal and stops the appliance in case of overheating.
ST1 closes the fresh air damper when the appliance is stopped. In case of an unintended stop on the rotor, the RCR gives an alarm, which is displayed on the Control panel as an alarm.
Also displayed in the Control panel are date and time, operating status, desired and actual room temperature.
GP1 and GP2 give alarm signals when the actual value exceeds the pre-set desired value for pressure drop over the filter.
Designation Name
FF Exhaust air fan TF Supply air fan GT1 Sensor, supply air GT2 Sensor, fresh air GT3 Sensor, extract air GTM Sensor, max temperature
in the electrical re-heater.
GTO Sensor overheating in
heater
GP1 Pressure guard, extract
air filter
GP2 Pressure guard, supply
air filter RC Regulator Corrigo E28 RCF Control box: exhaust air RCT Control box: supply air RCR Control box for rotor DR Motor, rotor VVX Heat exchanger rotor ST1 Damper, fresh air ST2 Damper, exhaust air
8
GB
Description of functions
Water heating, extract air temperature control with cascade function.
Function
Start and stop times are set in the Control panel. To maintain constant room temperature the RC receives a signal from GT3 and regulates the VVX and SV in sequence. The GT1 sensor is used to limit the max and min supply air temperature.
If there is a risk of frost in the water heater SV opens completely. If the temperature drops further, an alarm is set off and the appliance stops. GTF maintains constant water temperature even when the fans have stopped.
ST1 closes the fresh air damper when the appliance stops. In case of an unintended stop on the rotor, the RCR gives an alarm, which is displayed on the Control panel as an alarm.
Also displayed in the Control panel are date and time, operating status, desired and actual room temperature.
GP1 and GP2 give alarm signals when the actual value exceeds the pre-set desired value for pressure drop over the filter.
Designation Name
FF Exhaust air fan TF Supply air fan GT1 Sensor, supply air GT2 Sensor, fresh air GT3 Sensor, extract air GTF Sensor for frost protection GP1 Pressure guard, extract
air filter GP2 Pressure guard, supply
air filter RCF Control box: exhaust air RCT Control box: supply air RC Regulator Corrigo E28 RCR Control box for rotor DR Motor, rotor VVX Heat exchanger rotor SV Valve regulator, water
valve ST1 Damper, fresh air ST2 Damper, exhaust air
9
GB
Starting up ROTOVEX
Instructions
In order to start up and run all the functions the sensors and other external attachments must be fitted.
Start the Rotovex by using the control panel. Follow the instructions in the Corrigo E – User Manual. Start with chapter 6. Display, LEDs and buttons.
Set the menu language
Press the OK button while switching on the mains supply. Press the OK button. Choose language with the UP / DOWN buttons. Confirm the choice with the OK button.
Configuration/Settings
Refer to the Corrigo E – User Manual. The unit is pre-set to constant airflow and Extract air temperature control with cascade function. Week schedule is pre-set to Normal fan speed between 07:00–16:00 Monday to Sunday and stopped the rest of the time. For more detailed information see the
Commissioning record in the Operating and Maintenance Instruction.
Important!
Do not forget to set the current time and date.
10
GB
Inspection and care of the fans
For inspection and care of the fans open the front covers of the unit.
Important!
Disconnect the power supply before opening the covers.
Fans
When cleaning or carrying out other maintenance work where the fans need to be removed, proceed as follows:
1. Loosen all cable connectors and pressure hoses
2. Loosen the lock nut at the foot
3. Pull out the fan cartridge
Proceed in the reverse order when replacing the fan.
Push the fan cartridge in and make sure that the lock nut is in place (fig 2).
Important!
DO NOT use water when cleaning the inside of the unit.
11
GB
Inspection and care of the electrical heater
The heater is positioned in the same section of the appliance as the rotor. It is easy to remove for servicing or cleaning. The connecting cables are provided with quick connectors for easy disconnection.
Regulating the heater
The power requirement for the heater is adjusted according to the extract air temperature, as set on the control panel. The temperature is indicated using a sensor in the extract air.
A Pulser regulates the power requirements for the heaters.
ROTOVEX 2400 3000W 12000W ROTOVEX 3800 4500W 15000W ROTOVEX 4800 6000W 12000W
24000W
If the manual overheating protection for the heater trips, it can be reset as follows after the appliance has cooled down:
1. Loosen the cable connectors
2. Pull out the heater until the
reset button is visible
3. Press the reset button
4. Push in the heater
5. Reconnect the cables
Position of the heater
12
GB
Inspection and care of the water heater
The heater is positioned in the same section of the appliance as the rotor. It is easy to access for installation of hot water pipes.
When starting, the battery should be bled using the air nipple on the collec­tor to prevent air bubbles disturbing the water flow. See figure below (A).
Regulating the heater
The power requirements for the heater are adjusted according to the extract air temperature, as set on the control panel. The temperature is indicated using a sensor in the extract air.
Position of the heater
Service and maintenance
The heater does not normally require any service or maintenance. Check the supply air side a couple of times a year and clean if necessary.
Brush or vacuum the radiator. Take great care when in contact with the surface of the radiator, which must not be deformed.
Heater power ROTOVEX 2400 10000W ROTOVEX 3800 15000W ROTOVEX 4800 20000W
A – Venting device B – Frost protection sensor
13
GB
Inspection and care of filter
ROTOVEX is supplied with a class F7 supply air filter and class F5 exhaust air filter. The filter is divided into 2 cassettes for ease of handling. The filters are stretched with extensible­rails against sealing strips to minimise leakage.
The filters are disposable and should be replaced when the pressure drop exceeds the given limit.
The filter can be ordered from ROTOVEX suppliers or from Systemair.
Inspection and care of rotating heat exchanger
ROTOVEX is fitted with a rotating heat exchanger. The rotor is made of aluminium.
Service and maintenance
Clean the surface of the exchanger using a vacuum cleaner with a brush fitting. Take great care not to damage the surface. Inspect and clean the heat exchanger surface when changing the filter, at least twice a year.
Clean using the exhaust air filter space, turning the rotor by hand to access the whole surface. If necessary, compressed air may be used to remove dirt.
If the transmission belt is worn or slack it should be replaced. Contact Systemair Service for help.
14
GB
Measurements and specifications
Illustrations below are of a right-mounted version. The left-mounted version has the inspection hatch on the opposite side. Duct connectors are rectangular, with connection frame for joining guides. For connection directed upward on exhaust air, see view below.
Systemair
Exhaust air connection upwards (Option)
N - Electrical connection through safety switch O - Pipe connection for water heating, internal dimension 15 R (1/2”) P - Appliance separates here Q - Minimum space to enable rotor replacement = A-150 R - Minimum space for door 670 mm
Dimensions, heater connection
K L M ROTOVEX 2400 337 210 145 ROTOVEX 3800 434 190 145 ROTOVEX 4800 487 190 145
Table of measurements
A
B
C
D
E
F
G
Weights
[kg] ROTOVEX 2400 1000 600 300 125 150 200 795 300 ROTOVEX 3800 1120 600 400 108 104 260 915 340 ROTOVEX 4800 1230 800 400 135 165 215 1025 375
15