SystemAir RETP6, 32293, RETP10, 32294, 303612-42 Operating Instructions Manual

...
RETP6 / RETP10
Multipurpose controller for variable voltage 1 ~ fans
Operating Instructions
Software version: B1061AA from version 1.01
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
english
1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Explanations of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Requirements placed on the personnel / due diligence . . . . . . . . . . . . . . . . . . . . . . . . 5
2.5 Start-up and during operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.6 Work on the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.7 Modications / interventions in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.8 Operators obligation of diligence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.9 Employment of external personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Operational area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.5 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2 Minimum space requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.3 Outdoor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.4 Installation location for agriculture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4.5 Temperature inuences during commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2 EMC-compatible installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.1 Motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.2 Signal cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2.3 Harmonics current for devices 16 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.3 Mains connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4 Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.4.1 Running noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.5 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.6 Signal or sensor connection (E1 = Analog In 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.7 Output voltage 0 - 10 V (A1 = Analog Out 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.8 Voltage supply for external devices (+24V, GND) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.9 Digital input (Digital In 1 = D1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.9.1 Enable, device ON / OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.9.2 Reverse action of control function (only for P-Controller / PI-Controller) . . . . . . . . . . 11
5.10 Relay output (K1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.11 Potential at control voltage connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 Operating and display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
6.1 Main switch and potentiometer with integrated light signal . . . . . . . . . . . . . . . . . . . . . . 12
6.2 Internal Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operating Instructions RETP6 / RETP10
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
2/31
7 Base setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.1 Programming of the desired function (Speed controller / P-Controller, PI-Controller) . . 14
7.2 Select operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.3 Function of dipswitches for operation as Speed controller
1.01 (DIP 1 = |OFF|) . . . . 15
7.4 Function of dipswitches for operation as P-Controller, PI-Controller,
2.01 , 3.01 , 4.01
(DIP 1 = |ON|) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
7.5 Minimum speed cut off DIP 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.5.1 For mode Speed controller
1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7.5.2 For operation as P-Controller, PI-Controller
2.01 , 3.01 , 4.01 . . . . . . . . . . . . . . . . 16
7.6 Hardstart function DIP 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
8.1 Prerequisites for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9 Setting for operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.1 Speed controller
1.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.1.1 Setting for operation as Speed controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9.1.2 Diagram: setting signal and speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
9.1.3 Operation with two variable output voltages (two steps) . . . . . . . . . . . . . . . . . . . . . 18
9.2 Temperaturre control (P-Controller)
2.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9.2.1 Setting for operation as Temperature controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9.2.2 Example Temperature control Cooling function (factory setting) . . . . . . . . . . . . . . 20
9.2.3 Example Temperature control Heating function . . . . . . . . . . . . . . . . . . . . . . . . . . 20
9.3 Pressure control condensers (P-Controller)
3.01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.3.1 Setting for operation as Pressure controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
9.3.2 Example Pressure control condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
9.3.3 Setting with refrigerant medium table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
9.4 Pressure control, Air velocity control (PI-Controller)
4.01 . . . . . . . . . . . . . . . . . . . . . . 24
9.4.1 Setting for operation as Pressure and air velocity controller . . . . . . . . . . . . . . . . . . 24
9.4.2 Example: Pressure control for ventilation systems . . . . . . . . . . . . . . . . . . . . . . . . 24
9.4.3 Example: Air velocity control for clean rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
10 Diagnostics / Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10.1 If controller doesn´t work correctly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
11.1.1 Performance reduction during elevated ambient temperatures . . . . . . . . . . . . . . . . 27
11.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
11.3 Dimensions [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
11.4 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
11.5 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operating Instructions RETP6 / RETP10
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
3/31
1 General notes
1.1 Structure of the operating instructions
Before installation and start-up, read this manual carefully to ensure correct use! We emphasize that these operating instructions apply to specic units only, and are in no way valid for the complete system!
Use these operating instructions to work safely with and on the device. They contain safety instruc­tions that must be complied with as well as information that is required for failure-free operation of the device. Keep these operating insturctions together with the device. It must be ensured that all persons that are to work on the device can refer to the operating instructions at any time. Keep the operating instructions for continued use. They must be passed-on to all successive owners, users and nal customers.
1.2 Target group
The operating instructions address persons entrusted with planning, installation, commissioning and maintenance and servicing and who have the corresponding qualications and skills for their job.
1.3 Exclusion of liability
Concurrence between the contents of these operating instructions and the described hardware and software in the device has been examined. It is still possible that non-compliances exist; no guarantee is assumed for complete conformity. To allow for future developments, construction methods and technical data given are subject to alteration. We do not accept any liability for possible errors or omissions in the information contained in data, illustrations or drawings provided. We accept no liability for damage caused by misuse, incorrect use, improper use or as a consequence of unauthorized repairs or modications.
1.4 Copyright
These operating instructions contain copyright protected information. The operating instructions may be neither completely nor partially photocopied, reproduced, translated or put on data medium without previous explicit consent. Infringements are liable for damages. All rights reserved, including those that arise through patent issue or registration on a utility model.
2 Safety instructions
This chapter contains instructions to prevent personal injury and property damage. These instructions do not lay claim to completeness. In case of questions and problems, please consult our company technicians.
2.1 Intended use
The equipment is to be used solely for the purposes specied and conrmed in the order. Other uses which do not coincide with, or which exceed those specied will be deemed unauthorised unless contractually agreed. Damages resulting from such unauthorised uses will not be the liability of the manufacturer. The user will assume sole liability. Reading these operating instructions and complying with all contained instructions - especially the safety notications contained therein - are considered part of intended use. To consider is also the manual of attached components. Not the manufacturer, rather the operator of the device is liable for any personal harm or material damage arising from non-intended use!
2.2 Explanations of symbols
Safety instructions are highlighted with warning triangles and are depicted according to the degree of hazard as follows.
Attention!
General hazardous area. Death or severe injury or signicant property damage can occur if the corresponding precautions are not taken!
Operating Instructions RETP6 / RETP10 General notes
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
4/31
Danger due to electric current
Warning of dangerous voltage or dangerous current.
Information
Important additional information and advice for user.
2.3 Product safety
The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable. The device and its accessories must only be used in a flawless condition and installed and operated in compliance with the assembly instructions and/or operating instructions. Operating out­side the device's technical specications (
rating plate and attachment / technical data) can lead to
a defect in the device and additional damage!
In the case of a malfunction or a failure of the equipment check all functions with alarms in order to prevent injury to persons or property. Note possibility of back-up operation. If used in intensive animal environments, any malfunctions in the air supply must be detected as soon as possible to prevent the development of a life-threatening situation for the animals. The design and installation of the system must comply with local regulations and directives. In Germany these include DIN VDE 0100, the animal protection and the keeping of working animals ordinance and the pig-keeping ordinance etc. Also note the instructions of AEL, DLG, VdS.
2.4 Requirements placed on the personnel / due diligence
Persons entrusted with the planning, installation, commissioning and maintenance and servicing in connection with the frequency inverter must have the corresponding qualications and skills for these jobs. In addition, they must be knowledgeable about the safety regulations, EU directives, rules for the prevention of accidents and the corresponding national as well as regional and in-house regulations. Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supervision of an experienced person. This also applies to personnel undergoing general training. Comply with the legal minimum age. This device is not intended to be used by people (including children) who have restricted mental, sensory or intellectual abilities or who have a lack of experience and/or knowledge.
2.5 Start-up and during operation
Attention!
During commissioning, unexpected and hazardous conditions can arise in the entire installation due to defective adjustments, defective components or incorrect electrical connections. Remove all persons and objects from the hazardous area.
During operation, the device must be closed or installed in a control cabinet. Fuses may only be replaced by new ones and must not be repaired or bypassed. The data for the maximum line fuse are to be considered absolutely (
Technical data). Use only fuses specied in schematic
diagrams.
Any faults detected in the electric system/modules/operating equipment must be corrected immediately. If these faults are not corrected, the device/system is potentially very dangerous. The device/system must therefore not be operated when it is faulty.
Pay attention to smooth, low vibration running of the motor/fan, the appropriate instructions in the drive documentation must be observed!
2.6 Work on the device
Information Mounting, electrical connection, and start-up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)!
Operating Instructions RETP6 / RETP10 Safety instructions
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
5/31
Danger due to electric current It is generally forbidden to carry out work on electrical live parts. Protection class of the device when open is IP 00! It is possible to touch hazardous voltages directly! The safe isolation from the supply must be checked using a two-pole voltage detector.
Attention! Automatically restart after a power failure or mains disconnection!
2.7 Modications / interventions in the device
Attention!
For reasons of safety, no unauthorized interventions or modications may be made on the device. All planned modications must be authorized by the manufacturer in writing.
Only use the manufacturers original spare parts / wearing parts / accessories. These parts are specially designed for this device. If parts from other sources are used, there is no guarantee that they are designed and produced for the proper loads and with the required level of safety. Parts and special equipment not supplied by the manufacturer are not approved for use.
2.8 Operators obligation of diligence
The contractor or owner must also ensure that the electric systems and equipment are operated and maintained in accordance with electro-technical regulations.
The owner is obliged to ensure that the device are operated in perfect working order only.
The device may only be used as intended (
Application).
You must periodically examine the safety equipment for their properly functioning condition.
The assembly instructions and/or operating instructions are always readily available at the location where the device is being used, are complete and are in legible condition.
These persons are regularly instructed in all applicable questions regarding occupational safety and environmental protection and are knowledgeable regarding the assembly instructions and/or operating instructions and, especially, are familiar with the safety instructions contained therein.
All safety and warning notices attached to the device are never removed and remain legible.
2.9 Employment of external personnel
Maintenance and service work are frequently carried out by external employees who often do not recognize the specic situations and the thus resulting dangers.These persons must be comprehen­sively informed about the hazards in their area of activity. You must monitor their working methods in order to intervene in good time if necessary.
3 Product overview
3.1 Operational area
The controller described is used for continuous speed adjustment on variable voltage 1~ motors used to drive ventilators or pumps.
3.2 Maintenance
The device must be checked for soiling and, if necessary, cleaned in periodic intervals.
3.3 Transport
The device is packed ex factory to suit the transport method previously agreed.
Always use the original packaging materials when transporting the device.
Avoid shocks and impacts to the device during the transport.
During manual handling the human lifting and carrying restrictions must be observed and adhered to.
Operating Instructions RETP6 / RETP10 Product overview
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
6/31
3.4 Storage
The device must be stored in its original packaging in a dry and weather-proof room.
Avoid exposure to extreme heat and cold.
Avoid over-long storage periods (we recommend a maximum of one year).
3.5 Disposal / recycling
Disposal must be carried out professionally and environmentally friendly in accordance with the legal stipulations.
4 Mounting
4.1 General notes
Attention!
The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental inuences:
Before installation remove the device from the packing and check for any possible shipping damage!
Assemble the device on a clean and stable base. Do not distort during assembly! Use the appropriate mounting devices for proper installation of the unit!
Do not mount equipment on vibrating base!
When mounted onto lightweight walls, there must be no impermissibly high vibrations or shock loads. Any banging shut of doors that are integrated into these lightweight walls, can result in extremely high shock loads. Therefore, we advise you to decouple the devices from the wall.
Do not allow drilling chips, screws and other foreign bodies to reach the device interior!
The device should be installed in a location where it will not be disturbed, but at the same time can be easily accessed!
Depending on the housing model use supplied stoppers for cable inlets, cut off necessary cable inlets respectively to the cable diameter. Or alternative use cable inlet for cable glands. Any cable ducts openings not used must be sealed!
Care must be taken to avoid direct radiation from the sun!
The device is designed for vertical installation (cable inlet down). A horizontal or reclined installation is only permissible after technical release of the manufacturer!
Be sure to observe proper heat dissipation (
Technical data, heat dissipation).
4.2 Minimum space requirement
In order to ensure sufcient ventilation of the device, clearance on all sides of at least 50 mm has to be maintained to the housing walls, switch cabinet doors, wiring ducts, etc. The same clearance applies to the installation of several devices next to each other. When installing several devices on top of each other, the danger of reciprocal heating exists. This layout is only then permissible when the air suctioned from the upper unit does not become warmer than the permissible ambient temperature (
Technical data). I.e., a correspondingly larger clearance
or thermal shielding is required.
4.3 Outdoor installation
Outdoor installation is possible up to -20 °C when the controller supply is not switched off. Installation must be protected from the effects of weather as much as possible, including protection from direct sunlight!
Operating Instructions RETP6 / RETP10 Mounting
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
7/31
4.4 Installation location for agriculture
In order to avoid damage caused by ammoniac vapours, the controller shall not be installed in the stable, but rather in an outhouse wherever possible.
4.5 Temperature inuences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by storing the controller at room temperature!
5 Electrical installation
5.1 Safety precautions
Danger due to electric current
Work on electric components may only be carried out by trained electricians or by persons instructed in electricity under the supervision of an electrician in accordance with electrical engineering regulations.
It is forbidden to carry out work on electrically live parts.
A second person must always be present when working on energized parts or lines who disconnects in case of emergency.
Inspect electrical equipment periodically: retighten loose connections – immediately re­place damaged lines and cables.
Always keep switch cabinets and all electrical supply facilities locked. Access is only allowed for authorized persons using a key or special tool.
Operating the device with the housing cover removed is prohibited because energized, exposed parts are present inside the device. Disregarding this regulation can lead to severe personal injury.
The required protective earth connection is established using screws between the hous­ing parts in metal terminal space covers and housing casings. Commissioning is only permissible after these screws have been properly attached!
Metal screwed-connections are not permitted in plastic housing parts because there is no potential equalization.
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this manual (
Connection diagram)!
5.2 EMC-compatible installation
5.2.1 Motor cable
The applicable standard for interference emissions is EN 61000-6-3. Compliance with this standard is achieved through the use of an unscreened motor feed cable.
5.2.2 Signal cable
Pay attention to sufcient distance from powerlines and motor wires to prevent interferences. The control cable may not be longer than 30 m. Screened control cables must be used when the cable length is longer than 20 m. When using a shielded cable connect the shielding to one side only, i.e. only to the control unit with the protective ground (keep cable short and with as little inductance as possible!).
5.2.3 Harmonics current for devices 16 A
According to EN 61000-3-2 the devices are to be classied as professional devices. The application is therefore limited to use by trade, certain vocations or industries. Connection to a low voltage supply (public networks) is allowed insofar as this has been claried with the respective energy supply company responsible. Note: up to a maximum current of approx. 4 A, the limits are adhered to with no restrictions. Exception for Germany: An energy provider follows the technical connection conditions of the TAB2007, in which case the use of phase angle controlled devices up to a rating of 3.4 kVA per phase is allowed.
Operating Instructions RETP6 / RETP10 Electrical installation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
8/31
5.3 Mains connection
Power from the mains is connected to terminals: PE, L1 and N. Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specications (
Technical data and nameplate
afxed to the side).
Danger due to electric current The mains voltage must comply with the DIN EN 50160 quality characteristics and the dened standard voltages in IEC 60038!
5.4 Motor connection
The motor is connected at terminals U1 and U2. Several motors can be connected to the device.
Attention The maximum total control current (specied for electronic voltage regulation) for all motors may not exceed the devices rated current. If the maximum control current for electronic voltage regulation is not known, a supplementary 20% of the rated motor current must be allowed for. When controlling motors from other manufacturers, the controllability and the maximum current for electronic voltage regulation should be requested from the manufacturer.
Information
It is recommended that a separate motor protection unit be foreseen for each fan.
5.4.1 Running noise
When controlling ventilators using electronic voltage regulators, motor noise can occur (due to the system), which can be troublesome. On fast running ventilators with a high level of air noise, this noise is relatively low. On slow running ventilators with a low level of air noise, this noise may be dominant in the lower speed range due to the occurrence of resonance.
5.5 Motor protection
The motor can be protected by connecting thermostats TB. When multiple motors are connected, it is essential to ensure that thermostats TB are always connected in series. If a connected thermostat is tripped (break between the two terminals “TB”), the device is switched off and is not switched back on. Relais K1 is de-energized, terminals 11 - 12 bridged. The signal lamp ashes in code
|2|
(
Diagnostics / faults).
Possibilities for re-starting after the drive has cooled down (terminals TB bridged) by:
By switching the mains voltage off and then on again.
Via a digital input for remote control (ON / OFF enable).
Attention!
An outside voltage may never be connected to the terminals TB”!
If a bypass circuit is installed, or in the “100 %” position on devices with a main switch, the motor protection inside the controller has no function. In this case, additional motor monitoring may be required.
5.6 Signal or sensor connection (E1 = Analog In 1)
The unit has one-analog input: terminals E1 / “GND” (Analog In 1). The connection is independent of the programmed operating mode and from the sensor signal employed. The internal jumpers must be placed in correct position depending on input signal. Factory setting 0 ­10 V.
When connecting passive temperature sensors TF.. (KTY81-210) must be paid attention to no polarity.
When connecting active sensors attention must be paid to correct polarity, a 24 V DC power supply is integrated.
Operating Instructions RETP6 / RETP10 Electrical installation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
9/31
For sensors in two-wire-technology (4 - 20 mA signal), the connection is made on the +24 V and E1 (GND terminal is omitted).
Over DIP 4 an inverting of the input is possible for mode
1.01 speed controller.
DIP 4 =
|
OFF| (factory setting) for signals: 0 - 10 V, 2 - 10 V, 0 - 20 mA, 4 - 20 mA
DIP 4 =
|ON|
for signals: 10 - 0 V, 10 - 2 V, 20 - 0 mA, 20 - 4 mA
Attention! Never apply line voltage to analog inputs!
5.7 Output voltage 0 - 10 V (A1 = Analog Out 1)
Connection to terminals A1 - GND = “Analog Out 1” (I
max
10 mA).
It is not permissible to connect outputs of several devices to each other!
For mode speed controller
1.01 function of signal output A1 (Analog Out 1) can be determined
by DIP 8.
DIP 8 =
|
OFF|Constant voltage + 10 V for external potentiometer (factory setting)
DIP 8 =
|ON|
0 - 10 V modulation 0 - 100 %
Proportional the internal control of modulation with consideration “n-min” and “n-max” setting.
For enable “OFF” it goes not back to0 V.
For motor fault the output signal remains for a slave controller (“Master-Slave” combination).
For mode as P-Controller or PI-Controller
2.01 , 3.01, 4.01 the function is rmly adjusted.
0 - 10 V
modulation 0 - 100 %
Proportional the internal control of modulation with consideration “n-min” and “n-max” setting.
For enable “OFF” it goes back to 0 V.
For motor fault the output signal remains for a slave controller (“Master-Slave” combination).
Information
For operation as P-Controller or PI-Controller function constant voltage cannot be selected! For operation as P-Controller or PI-Controller function for
|D1|
can be selected with DIP 8!
5.8 Voltage supply for external devices (+24V, GND)
There is an integrated power supply for external devices, e.g. a sensor. Terminal +24 V, output voltage tolerance +/- 20%. max. load current
Technical data.
In case of overload or short circuit (24 V – GND), the external power supply is shut down (multi-fuse). The device performs a Reset and continues operation. It is not permissible to connect outputs of several devices to each other!
5.9 Digital input (Digital In 1 = D1)
Activation via oating contacts, a low voltage of approx. 24 V DC is connected.
Attention! No disconnection when turned off (no isolation in accordance with VBG4 §6)!
Never apply line voltage to the digital input! It is not permissible to connect inputs of several devices to each other!
Operating Instructions RETP6 / RETP10 Electrical installation
L-BAL-E082-GB 1237 Index 002 Part.-No. 00163339-GB
10/31