SystemAir NaviPad Quick Manual

Page 1
Document in original language | 151671 · A003
Quick Guide NaviPad
Access sw 4.0-1-04
GB
Page 2
151671 | A003
Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Page 3
151671 | A003
Contents
1 General... . . ...... . ...... . ...... . . ..... . . ..... . . ..... . . ..... . . ..1
1.1 Start-up wizard . ..... . . ..... . . ...... . ...... . ...... . . .2
1.2 Key board ..... . . ..... . . ...... . ...... . ...... . . ..... . . ..3
1.3 Symbol description . ...... . ...... . . ..... . . ..... . . ...3
1.4 User levels ..... . . ..... . . ..... . . ..... . . ..... . . ...... . ..4
2 Alarms.... . . ..... . . ..... . . ...... . ...... . ...... . . ..... . . ..... . . ..4
2.1 Alarm list..... . ...... . . ..... . . ..... . . ..... . . ..... . . ....4
3 Controller settings ..... . . ...... . ...... . ...... . . ..... . . ..... . .5
3.1 Data & Settings...... . ...... . . ..... . . ..... . . ..... . . ..5
3.1.1 Operation overview .... . ...... . ...... . .5
3.1.2 In- and output status... . . ..... . . ..... . .5
3.1.3 Temperature control . . . ..... . . ..... . . ..6
3.1.4 Fan control ..... . . ..... . . ..... . . ..... . . ...6
3.1.5 Demand control . . . ..... . . ..... . . ..... . . .6
3.1.6 Fire/Smoke.... . . ..... . . ..... . . ..... . . ....6
3.1.7 Humidity control .... . . ..... . . ..... . . ....7
3.2 Flow chart .. . . ..... . . ..... . . ...... . ...... . ...... . . ....7
3.3 Language ...... . . ..... . . ..... . . ..... . . ..... . . ..... . . ..7
3.4 Time Settings .. ..... . . ..... . . ...... . ...... . ...... . . ..8
3.5 Configuration .. ...... . ...... . ...... . . ..... . . ..... . . ..9
4 Advanced NaviPad Settings.... . . ..... . . ..... . . ..... . . .. 10
5 No communication .. . . ..... . . ...... . ...... . ...... . . ..... . . 11
Page 4
Page 5
General |
1
1 General
NaviPad is Systemair's user interface with a 7” capacitive touch screen. The user interface provides operation informa­tion about the connected air handling units and allows you to control all functions. You navigate by pressing the touchscreen, to activate a function, change setting or by reading values in real time.
After 5 min inactivity the screen activate sleep mode, you return to the screen you left by pressing the touchscreen. After additional 10 min. inactivity you return to the system overview dashboard (figure 3) and have to log in again.
Editable text and values are shown in blue and differs depending on user level.
Since the user interface of the air handling unit consists of a web server with web pages it is possible to use a computer to browse the user interface. Identify the IP address of the air handling unit with NaviPad, see Example 4 and then write it in the address field of an internet browser.
Important
• The air handling unit and the NaviPad as well as any computer has to be connected on a local network with the same IP subnet.
• Chrome browser for computer is supported to navigate the web pages of the air handling unit.
Fig. 1 (1) Home button, (2) USB connection, reboot button, (3) power supply and communication
Fig. 2 Holder for NaviPad, (1) fixing points, (2) cable hook
Attach holder to air handling unit with enclosed screws (wall mounting is also possible, use fastenings suitable to the walls structure).
151671 | A003
Page 6
2
| General
1.1 Start-up wizard
At the first start up of NaviPad you need to calibrate the screen by pressing lightly on the cross marks.
Then you will be requested to fill in following information:
• Language
• Time & Date
Available air handling units will be shown in the device list. Choose the air handling unit you want to pair with your Na­viPad. Use the controller’s serial number in the air handling unit to be sure to pair the correct air handling unit with NaviPad.
If the start-up wizard is cancelled it will start again during next power up of the NaviPad, this will continue until start-up wizard is successfully finished.
Version: PR1.2 (1.1.0.128) and later
Start-up wizard
started
Scan for air handling
units
Show air handling units selection menu
← 0
Numbers of air
handling units
detected
≥1
User input
Select air handling unit
Select language
Set Time & Date
System overview
dashboard
After the start-up wizard is completed the system overview dashboard is shown. Press on the picture of the air han­dling unit to access.
Home > Available devices
20 Dec 2:35 PM
Unit name
Normal operation
Figure 3: System dashboard
151671 | A003
Page 7
General |
3
Unit name 20 Dec 2:35 PM
Running mode
Outdoor
Supply
Normal speed
31.3 °C 16.1 °C
Extended run
Setpoint adjustment
120 min
-2°C +2°C0
Figure 4: The home page shows an overview of the air handling unit operation status.
Note:
You can always return to system overview dashboard by pressing the home button, figure 1, (1).
1.2 Key board
When a name, value or password need to be changed/written a key board will appear at the bottom of the touchscreen.
1.3 Symbol description
Home (home page)
Data and settings Shows operating information and settings
Flow diagram A schematic overview of the air handling unit and its components
Language Change language
Time and date Weekly schedule
Configuration Alarm and functions configurations, I/O allocation settings
Alarm symbol, indicates if there are active alarms. One press on the symbol will direct you to the alarm list.
151671 | A003
Page 8
4
| Alarms
1.4 User levels
End user When logged out
Read /write — Home page (Figure 1) Possible actions in end user mode are to stop the air handling unit for maintenance (e.g. filter exchange), change the time for extended run and change the temperature setpoint. Flow diagram and active alarms in alarm list are visible.
Operator mode — log in with 1111 Logged in
Read and write privileges (except Configuration). Acknowledge/block/unblock alarms and view the alarm history.
Service mode — log in with 0612 Logged in
Full read and write privileges.
2 Alarms
A LED-light in the home button, figure 1, (1) indicate the status of the air handling unit.
• Fixed green — Status ok (no active alarms).
• Flashing red — Active/returned alarms in one or several air handling units.
• Fixed red — Acknowledged/blocked alarms in one or several air handling units, alarms not reset.
Different alarm levels
Class A alarm Needs to be acknowledged
Class B alarm Needs to be acknowledged
Class C alarm Returns when the cause of the alarm disappear
2.1 Alarm list
Data & Settings > Alarm list
20 Dec 2:35 PM
Acknowledge all
No
Name:
Level:
Status:
Filter guard 1
Alarmed
Show all alarms
>
Alarm history
>
Alarm status:
• Alarmed
• Acknowledged
• Blocked
• Returned
Accessible when pressing the alarm symbol.
Enter the current alarm and choose action; acknowledge, block or unblock.
151671 | A003
Page 9
Controller settings |
5
3 Controller settings
Menus and functions may differ depending on actual configuration and/or application version running in the air handling unit.
3.1 Data & Settings
Data & Settings
20 Dec 2:35 PM
Operation overview
>
In-/Output status
>
Temperature control
>
Fan control
>
Demand control
>
Fire/Smoke
>
Alarm list
>
3.1.1 Operation overview
Value of active signals I/O signals and operation mode.
• Temperature
• Air flow/pressure
• CO2
• RH
• Heating
• Exchanger
• Cooler
• Recirculation
3.1.2 In- and output status
I/O status Total overview of:
• Sensors
• I/O
• Fan control
• Temperature sequencing
• Running mode
All can be controlled in manual mode.
• Manual setting of temperature sensor
• Locking of fans at adjustment
• Manually I/O testing of external functions
• Raw values
151671 | A003
Page 10
6
| Controller settings
3.1.3 Temperature control
Settings for temperature.
• Limit values
Setpoint for current control type (Example 1)
• Min/max limitation
• Outdoor temperature values
Example 1: Setpoint for current control type
Data & Settings > Temperature control > Supply air controller
20 Dec 2:35 PM
Supply air temperature
10.4 °C
Setpoint adjustment
0 °C
Setpoint adjustment low speed
0 °C
Setpoint adjustment high speed
0 °C
Setpoint Supply air
18 °C
Example show temperature control type set to supply air. To change the setpoint, press on the current value and change to desired setting in the following pop-up menu. Confirm with ok. (Editable text and values are shown in blue on NaviPad.)
3.1.4 Fan control
Settings for fan control.
• Setpoint for different fan speed
• Fan compensation e.g. outdoor compensated fan curves
• Start delay of fans, shut of dampers etc.
• SFP menu
• External fans
3.1.5 Demand control
Settings for:
• CO2
• Recirculation
• Support control
• Free cooling
3.1.6 Fire/Smoke
Settings for:
• Fire dampers
• Smoke detector status
• Fire damper test
151671 | A003
Page 11
Controller settings |
7
3.1.7 Humidity control
Setpoints and settings for dehumidification and humidification
3.2 Flow chart
Flow diagram
20 Dec 2:35 PM
199 Pa
198 Pa
18 000 m³/h
18 000 m³/h
100 %
54 Pa
34 Pa
22,1 °C
22,1 °C
-6,8 °C
-12,2 °C
71 %
74 %
16,7 °C
21,8 °C
19,9 °C
25 % RH71 % RH
32 % RH
84 %
h
Open
Open
0 %
OFF
42 %
ON
Dynamic flow chart of current configured air handling unit. Active sensors and components are visible with values shown in real time. When pressing on values or items marked in blue you will be forwarded to related settings and/or overview page.
3.3 Language
Settings of language.
• To synchronize NaviPad with all connected air handling units, go to system dashboard by pressing the
home button figure 1, (1). Press
and , choose language.
• Using
in selected air handling units homepage via NaviPad or computer will only change language
in the selected air handling unit.
151671 | A003
Page 12
8
| Controller settings
3.4 Time Settings
In this menu date and time can be changed as well as other system settings. Settings for:
• Date and time
Schedule for operating time (Example 2 & 3)
• Schedule for holiday
• Schedule for extra time groups
Each day has up to two individual running periods, set desired start and stop time. For holidays, set the dates in Time settings > Schedule > Holiday calendar and the time in Time settings > Schedule > Fan Low Speed/Fan Normal Speed/High Speed.
Example 2: Schedule for normal fan speed
Time settings > Schedule > Fan Normal Speed
20 Dec 2:35 PM
Start
Stop
Start
Stop
Monday (12–hour clock system)
5:00 AM 6:00 PM 12:00 AM 12:00 AM
Monday (24–hour clock system)
05:00 18:00 00:00 00:00
In above example, the air handling unit starts at a normal fan speed at 5:00 AM (05:00) and stops at 6:00 PM (18:00). The second running period is deactivated.
Example 3: Schedule for low fan speed
Time settings > Schedule > Fan Low Speed
20 Dec 2:35 PM
Start
Stop
Start
Stop
Monday (12–hour clock system)
6:00 PM 24:00 AM 12:00 AM 5:00 AM
Monday (24–hour clock system)
18:00 24:00 00:00 05:00
In above example, the air handling unit starts at a low fan speed at 6:00 AM (18:00) and stops at 24:00 AM (24:00). The second running period on low fan speed is between 12:00 AM (00:00) and 5:00 AM (05:00).
151671 | A003
Page 13
Controller settings |
9
3.5 Configuration
• System settings
Function (Example 4)
• I/O allocation settings
Alarm configuration (Example 5)
• PID controllers
Example 4: Function configuration
Configuration > Functions > Function activation
20 Dec 2:35 PM
Fan compensation curves
Yes
Support control
No
CO2 Control
No
To activate a function go to Function activation. Choose function to activate and set Yes in the following pop-up menu. Values for the activated function are now visible and can be adjusted in Data Settings.
If required, allocate in- and outputs in I/O allocation settings.
Example 5: Alarm configuration
Configuration > Alarms
20 Dec 2:35 PM
Filter alarm supply air
53
Filter alarm extract air
54
Alarm low air flow
55
Freeze protection guard
56
Defrosting guard exchanger
57
Fire alarm
58
Smoke alarm
59
151671 | A003
Page 14
10
| Advanced NaviPad Settings
Configuration > ... > Filter alarm supply air
20 Dec 2:35 PM
Action: No action
Level: Class B
Delay:
300 s
Limit X1: 0 m
3
/h
Limit Y1: 10 Pa
No: 53
Limit X2: 2000 m
3
/h
Limit Y2: 150 Pa
Name:
Filter alarm supply air
Original text: Filter alarm supply air
4 Advanced NaviPad Settings
Return to system overview dashboard by pressing on the home button, figure 1, (1). Go to
and choose
Advanced NaviPad settings. Login required — 1111
NaviPad settings
20 Dec 2:35 PM
Home
Unit name
Normal operation
Language
Time & Date setting
Advanced HMI settings
Restart NaviPad
Available devices (air handling units) (Example 6)
• Change Password
• Ethernet
1
Restore NaviPad Factory Settings (Example 7)
• Software Update
1
1
Further information in document Access 4x Modbus_BACnet manual
151671 | A003
Page 15
No communication
|
11
Example 6: Available devices (air handling units)
Home > Advanced HMI settings > Available decives
20 Dec 2:35 PM
192.168.41.38
Select device
Serial number: 012345678910
IP Address:
192.168.41.116
Name: Unit name
Serial number: 058345678919
IP Address:
192.168.41.49
Name: Unit name
The air handling unit will appear, press the button to select the air handling unit to pair it with the NaviPad. If there are several air handling units at the same IP subnet, a list of available air handling units will be presented.
The IP address of NaviPad itself is presented above the Select device header
Example 7: Restore NaviPad factory settings
You will be requested to confirm your action.
All settings including password will be reset and Start-Up wizard will run again.
5 No communication
Home > Available devices
20 Dec 2:35 PM
Unit name
No Communication
If the above symbol are shown the communication to the selected air handling unit is lost. One reason could be that the IP number has changed. Go back to available devices (air handling units), figur 4, and first deactivate all the air handling units and then activate them again.
151671 | A003
Page 16
Quick Guide NaviPadAccess sw 4.0-1-04 · · 151671 · en_GB · 2019-02-22 · A003
Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg, Sweden
Phone +46 222 440 00 Fax +46 222 440 99
www.systemair.com
Loading...